Design Specification
Design Specification
PROJECT:
LOCATION:
OWNER:
TO: ______________________________________ DATE: ____________________
ARCHITECTURAL DESIGN PARAMETERS
A. CODES AND STANDARDS
The Architectural Works shall be in accordance with the following Laws, Codes and Standards.
1.00 LAWS AND CODES
1.1 PD 1096 or National Building Code of the Philippines and its Latest and Amended IRR
1.2 RA 9266 or The Architecture Act of 2004 and its Latest and Amended IRR
1.3 BP 344 or Accessibility Law and its Latest and Amended IRR
1.4 RA 9514 or Fire Code of the Philippines and its Latest and Amended IRR
1.5 Existing Local Codes and Ordinances
1.00 GENERAL
All drawings shall be computer drafted. Drawings shall be submitted both in printed and
electronic copies.
Keep the same orientation for all plans. The north orientation shall be indicated in all
architectural plans. The orientation of the architectural plans shall be consistent with all the
engineering plans.
Existing buildings and new works shall be clearly indicated and labelled in site plans.
Detailed plans shall have a scale not smaller than 1:50 meters.
Spot detailed plans, elevations and sections shall have a scale not smaller than 1:20 meters.
Avoid notes such as “see architectural detail” or “see structural”. Always refer with a callout to
the specific detail drawing and sheet number.
8.00 DETAILS
Provide a minimum of one (1) section of a scale not smaller than 1:50 meters for each area
preferably cut along the area with special construction design.
Provide spot detail plans, elevations and sections of a scale not smaller than 1:10 meters for
special designs with aesthetic treatment and ornamentation.
Provide detail plan of a scale not smaller than 1:50 meters for all areas needing tile pattern, e.g.
dwelling units, toilets, corridors, stairs, lobby, common areas, entrance walk, showing the
position and pattern of tiles.
Centreline location of plumbing fixtures shall be indicated in detail plan with lines of reference
and its corresponding dimensions. This is to indicate the exact locations of the
plumbing/sanitary roughing-ins.
C. SITE WORKS
A porte-cochere shall be provided at the main entrance of the building. Where required,
covered walkways shall be provided for access and connection to other buildings.
Ramps shall be provided in all main entrances of the buildings and other access opening to
walkways leading to other buildings.
3.00 FLOORS
If floor tiles in two adjacent areas with different material, color or design meet at the door
opening, the cut shall be located middle of the door thickness when in a closed position. Provide
details in the floor pattern designs. Provide aluminum threshold, when required.
Floors at the openings of toilets for persons with disability shall be sloping. Indicate in the plans
and sections.
Toilet floor tiles shall be at least 600mm x 600mm, unless otherwise specified. Toilet dimensions
shall be based on the modular sizing of tiles to avoid tile serujo and or excessive tile wastage.
Pantry and kitchen floor tiles shall be at least 600mm x 600mm, unless otherwise specified.
Kitchen dimensions shall be based on the modular sizing of tiles to avoid tile serujo and or
excessive tile wastage.
Lobby and corridor floor tiles shall be 600mm x 600mm, unless otherwise specified.
Layout and work on wall and floor tiles must be aligned, plumb, level and square.
All edges, corners and intersections of toilet tiles, shall be provided with polyvinyl chloride tile
trims.
Tile color and design shall be approved first before installation.
Laboratory flooring shall be anti-static, anti-microbial, seamless vinyl flooring or epoxy flooring.
9.00 PAINTING
Painted ceiling shall be in flat latex finish, while cornices and mouldings shall be in gloss enamel
finish unless otherwise noted.
Painted interior wall shall be at least in semi-gloss latex finish for rooms, unless specified to a
higher type of paint.
Paint in special rooms for containment or barrier areas shall be epoxy system.
Painted exterior wall shall be at least in moisture-resistant/water- repellant solvent-based paint
finish, textured or smooth, unless otherwise specified.
Paint color and shade shall be approved first before application.
E. SPECIFIC REQUIREMENTS
Provide Room Data Sheets, including detail floor plan, ceiling plan and sections in coordination
with the requirements of the electrical, sanitary and mechanical designs
F. SUMMARY OF MATERIALS
G. DRAWING REQUIREMENTS
The Civil/Structural Design shall be in accordance with the following Laws, Codes and Standards.
1.00 LAWS AND CODES
1.1 National Structural Code of the Philippines (NSCP) 2010
1.2 PD 1096 or National Building Code of the Philippines and its Latest and Amended IRR
1.3 BP 344 or Accessibility Law and its Latest and Amended IRR
1.4 Existing Local Codes and Ordinances
2.00 STANDARDS
2.1 Bureau of Product Standards (BPS)
2.2 Philippine National Standards (PNS)
2.3 DPWH Blue Book
2.4 American Concrete Institute (ACI)
2.5 American Society for Testing Materials (ASTM)
2.6 American Welding Society (AWS)
B. SITE WORKS
1.00 GENERAL
Based on the Master Site Development Plan, provide where applicable complete design and details of
road (concrete with curb gutter, including drainage) network, walkways parking areas and fencing.
1. The main driveway leading to the main entrance of the building shall be capable of two-lane traffic (at
least 6.00 meters wide) with a minimum thickness of 150mm (8 inches). The perimeter road shall be
capable of one way traffic. Concrete strength should be at least 3000psi. Roads shall be so designed to
accommodate delivery vehicles.
2. Walkway should be at least 100mm thick with concrete strength of 2500psi. Ramps should be
provided, instead of steps, for any change in elevations.
3. Parking area slabs should be at least 150mm thick with concrete strength of 3000psi.
C. BUILDINGS
The buildings should be designed using seismic importance factor of 1.25 for immediate
occupancy category. Buildings should be designed in accordance with NSCP requirements up to
magnitude 7 for those near seismic source Type A. Seismic gaps between buildings (old and
new) should be properly observed.
The buildings should be designed also using wind importance factor of 1.15 (especially for
design of trusses/roofing system). Concrete gutters and parapet walls should be provided as
additional protection to the roofing system during strong typhoons.
The structural designer should verify with Philippine Volcanology and Seismology (PHIVOLCS)
the distance of the proposed building to the nearest active fault lines and with the DENR for
geo-hazard mapping.
The structural designer shall confirm the required fire ratings for building components based on
the laboratory occupancy and design structural elements accordingly. Materials that have low or
no volatile organic compounds should be used.
The structural designer is encouraged to use fire-resistive and non-toxic materials.
Geotechnical investigation or soil tests have been conducted on site to determine soil bearing
capacity and recommended foundation design. The structural designer shall study the results
and recommendations of these tests and take such into consideration in designing the
appropriate foundation system for the building.
D. SPECIFIC REQUIREMENTS
E. SUMMARY OF MATERIALS
Concrete shall be Portland cement and conforming to ASTM Specification C150, Type I to Type II.
Coarse Aggregates shall consist of washed gravel, crushed stone or rock or a combination
thereof conforming to ASTM C33.
Concrete hollow blocks shall be a standard product of recognized manufacturer conforming to
PNS 16 with at least 350psi strength.
Reinforcing bars shall conform to PNS Grade 60 for 16mm diameter and above and PNS Grade
40 for 12mm diameter and below.
Structural steel shall conform to ASTM A36.
Bolts and studs shall conform to ASTM A325.
Welding electrodes shall be E60 or E70 and conform to AWS D.1.1.
F. DRAWING REQUIREMENTS
The Sanitary/Plumbing Design shall be in accordance with the following Laws, Codes and Standards.
1.00 LAWS AND CODES
1.1 National Plumbing Code of the Philippines (NPCP)
1.2 Sanitation Code of the Philippines
1.3 PD 1096 or National Building Code of the Philippines and its Latest and Amended IRR
1.4 RA 9514 or Fire Code of the Philippines and its Latest and Amended IRR
1.5 Existing Local Codes and Ordinances
2.00 STANDARDS
2.1 Bureau of Product Standards (BPS)
2.2 Philippine National Standards for Drinking Water
2.3 Underwriters Laboratory (UL)
2.4 National Water Resources Board (NWRB)
2.5 National Plumbers Association of the Philippines (NAMPAP)
2.6 Philippines Society of Sanitary Engineers, Inc. (PSSE)
2.7 Biosafety in Microbiological and Biomedical Laboratories, 5th Edition, United States Centers for
Disease Control and the National Institutes of Health, Bethesda, MD.
2.8 Vivarium to seek accreditation by Association for Assessment and Accreditation of Laboratory
Animal Care International (AAALAC International)
B. SITE WORKS
1.00 GENERAL
Based on the Master Site Development Plan, the Site Works shall provide complete layout of the
following:
1. Storm Drainage Network, indicating Drainage Manholes and Pipe Culverts;
2. Sewerage Pipe Network, indicating Sewage Manholes, Sewage Pipes and the location of the proposed
Sewage Treatment Plant;
3. Water Supply Network, indicating the location of Water Service entrance, Cisterns, Elevated Water
Tank and proposed Pump House.
The Storm Drainage Network shall accommodate the magnitude of peak rates of surface run-off
including drainage coming from the buildings. The system shall be capable of handling the
design flows routing to the designated outfall. For rainfall calculation and sizing of drainage
pipes, refer to Table-D2, Appendix-D, National Plumbing Code of the Philippines and current
rainfall record from PAG-ASA (250mm/hr).
The Sewerage Pipe Network design shall accommodate all sewage coming from all the facilities,
conveyed by gravitational flow leading to the proposed or existing Sewage Treatment Plant.
The Water Supply Network shall include the provision of Fire Hydrants, accessible Drinking
Fountain that will serve as testing point for safe and potable water supply.
C. BUILDING FACILITIES SANITARY/PLUMBING SYSTEM
E. SUMMARY OF MATERIALS
Sewer and vent pipes: unplasticized Polyvinyl Chloride (uPVC) extra series 1000 conforming to
ISO 3633 ASTM D2729 including trims and fittings
Storm drainage pipes: downspouts, unplasticized Polyvinyl Chloride (uPVC) extra series 1000
conforming to ISO 3633 ASTM D2729 including trims and fittings (BPS Certified)
Drainage pipes: 250mm dia. and below, Non-Reinforced Concrete Pipe (NRCDP)
F. DRAWING REQUIREMENTS
The Mechanical Design shall be in accordance with the following Laws, Codes and Standards.
1.00 LAWS AND CODES
1.1 Mechanical Engineering Code of the Philippines
1.2 Sanitation Code of the Philippines
1.3 PD 1096 or National Building Code of the Philippines and its Latest and Amended IRR
1.4 RA 9514 or Fire Code of the Philippines and its Latest and Amended IRR
1.5 Existing Local Codes and Ordinances
2.00 STANDARDS
2.1 Bureau of Product Standards (BPS)
2.2 Philippine National Standards (PNS)
2.3 Underwriters Laboratory (UL) and Factory Mutual (FM)
2.4 International Electrotechnical Commission (IEC) 1988
2.5 National Fire Protection Association (NFPA)
2.6 Biosafety in Microbiological and Biomedical Laboratories, 5th Edition, United States Centers for
Disease Control and the National Institutes of Health, Bethesda, MD.
2.7 Vivarium to seek accreditation by Association for Assessment and Accreditation of Laboratory
Animal Care International (AAALAC International)
B. BUILDING VENTILATION
Non-Laboratory Air Supply and Exhaust can recirculate and shall be separated from laboratory
and vivarium ventilation systems.
Laboratory and vivarium ventilation shall be on two different systems. Each type of space shall
have a ventilation system shall provide the optimal number of air changes to meet or exceed
biosafety guidelines, and realized energy savings based on benchmarks established among
research facilities.
Air that is exhausted from BSL-3, ABSL-2 and ABSL-3 spaces shall be HEPA filtered and non-
recirculating to other areas of the building.
Exhaust fans in BSL-3, ABSL-2 and ABSL-3 areas, as well as Fume hoods and similar fume or
aerosol extraction devices shall avoid reversal of airflows through emergency power and room
location.
C. SPECIFIC REQUIREMENTS
D. DRAWING REQUIREMENTS
The Electrical Design shall be in accordance with the following Laws, Codes and Standards.
1.00 LAWS AND CODES
1.1 Philippine Electrical Code
1.2 National Electrical Code
1.3 PD 1096 or National Building Code of the Philippines and its Latest and Amended IRR
1.4 RA 9514 or Fire Code of the Philippines and its Latest and Amended IRR
1.5 Existing Local Codes and Ordinances
2.00 STANDARDS
2.1 Bureau of Product Standards (BPS)
2.2 Underwriters Laboratory (UL)
2.3 National Fire Protection Association (NFPA)
2.4 International Electrotechnical Commission (IEC)
2.5 Illumination Engineering Society (IES)
2.6 National Electrical Manufacturer’s Association (NEMA)
2.7 Biosafety in Microbiological and Biomedical Laboratories, 5th Edition, United States Centers for
Disease Control and the National Institutes of Health, Bethesda, MD.
2.8 Vivarium to seek accreditation by Association for Assessment and Accreditation of Laboratory
Animal Care International (AAALAC International)
2.9 United States Green Building Council LEED Sustainable Design certification
2.10 Integrated Resilient Design Program sponsored by the Science and Technology Directorate of the
US Department of Homeland Security.
B. SITE WORKS
Based on the Master Site Development, the Site Works shall provide complete Electrical layout of the
following:
1. KVA rating and other specifications of Transformer
2. Switchgear requirements
3. Panel board Layout
4. Electrical Metering Devices
5. Service Conductors and Conduit Layout
6. Grounding System
7. Emergency Standby Generators
8. Street and Perimeter Lighting System
9. Laboratory electrical panels and circuit breakers for laboratory equipment
10. Life safety features of electrical system in laboratories and auditorium
11. Lighting calculations for offices, laboratories, meeting rooms and auditorium
12. Energy saving measures to decrease relative energy consumption
C. BUILDING FACILITIES ELECTRICAL SYSTEM
6.00 EARTHGROUNDING
The building electrical system should provide laboratories with earth-grounded connections.
Laboratory equipment manufacturers may require earth-grounding and reliable power for
special connections and services at the laboratory benches.
D. SPECIFIC REQUIREMENTS
E. SUMMARY OF MATERIALS
5.00 CONDUCTORS
Wires and cables shall be of the approved type and unless specified or indicated otherwise, all power
and lighting conductors shall be insulated for 600 volts.
The conductors used in the wiring system shall be of soft-annealed copper having a conductivity
of not less than 98% of that of pure copper and insulated for 60°C temperature.
All conduits of convenience outlets and wire ways for lighting branch circuit homeruns shall be
wired with a minimum of 3.5mm square in size.
6.00 MASTER ANTENNA TELEVISION (MATV) AND CABLE TELEVISION (CATV) SYSTEM
Install provisions for MATV and CATV wiring pathways into program spaces.
There shall be individual trunking for master antenna and cable television rising in the building.
F. DRAWING REQUIREMENTS