VRF
VRF
•• Expansion
Expansion valves,
valves,
fans, bypass
fans, bypass solenoid
solenoid
valves also
valves also affect
affect
system performance
system performance
3
VRF System & Inverter VRF
• The inverter reacts to indoor and outdoor
temperature fluctuation by varying the power
consumption and adjusting the compressor
speed to its optimum energy usage.
• The refrigerant is
compressed to the
required high
pressure level
• Inverter provides
superior energy
efficiency
performance 4
VRF Outdoor Fan Motor Control
• Multi stage fan speed operation provides:
• Input power savings, lower steps have lower
power consumption compared to higher steps.
• Optimizes condenser pressure
control to achieve desired
discharge pressure and
ensure optimum mass flow
through the system.
• Cycle stabilization provides
optimum efficiency as
compared to fix fan speed. 5
VRF Piping VRF
• Improves
refrigerant cycle
efficiency by
connecting
multiple indoor
units to a
common liquid
and suction line
through the use
of STA Separation Tube Assemblies and/or
Headers and EEV Electronic Expansion Valves
6
Reduces piping cost and work VRF
7
Video
VRF
8
VRF Benefits VRF
• Less copper versus multi-split
• Eliminates most ductwork
• Quicker installation
• OEM software simplifies layout
• Long piping lengths
• Compact ductless system
9
Flexible piping design VRF
10
Design freedom VRF
This extra-long piping system can also cope
with buildings of various shapes.
Rectangular type L type Square type
Indoor
units
Outdoor unit
Refrigerant piping
12
Advanced Computer Controlled VRF
13
Central Air Inefficiency
Central
• VRF systems allows
you to minimize
inefficient ductwork.
– Save money
– Improve comfort
– Protect health
– Save Space
– Reduce Noise
14
According to D.O.E.
Central
•• VRF
VRF
systems
systems
minimize
minimize
inefficient
inefficient
ductwork.
ductwork.
16
Multi-Split vs. VRF System
• VRF systems allows you to minimize the refrigerant
path compared to a multi-zone mini-split.
Multi-Split VRF
17
The heart of a VRF system VRF
Temperature Temperature
Sensor sensor
Indoor unit Indoor unit
Outdoor unit
Senses the temperature of each
room and optimizes operation.
18
What Zoning does for Efficiency VRF
Time Time
48,000 BTU
48,000 BTU
48,000 BTU 72,000 BTU
22
Connectable Capacity
• Ability to connect up to
24,000 BTU 150% of name plate rated
Apartment indoor units*
VRF
used only at
* Varies by manufacturer
night
• If all indoor units are
operated simultaneously
system will not produce
more than 110% of system
capacity
• Example A:
– 2-Story Building
Mixed Use. VRF
stretches square footage
covered by a single
48,000 BTU system when not all
Small Office areas are occupied
150% used only
Connectable simultaneously
during the day
23
Lack of Connectable Capacity
Multi-Split
4K 18K
7K 5K
10K 9K 9K
12K 5K 5K
18K 9K 9K
9K 9K 7K 7K 9K 9K 25
Benefits of Connectable Capacity
Multi-Split VRF
9K 7K
18K 14K 7K
9K 9K
18K 9K 9K 7K 7K
9K 9K
6-Tons when only 4-Tons required Indoor unit for every room yet 4-Tons
Refrigerant Short piping Long piping but Shorter piping run with Quicker cooling,
Cycle / Air run but great efficient air flow better refrigerant greater comfort,
Distribution efficiency loss with evaporator in distribution more stable room
in ductwork A/C space temperature
Simple
Wired
Remote
Full Featured
Wired Remote
Control
Wireless Remote
28
Group Remote Controller
Wiring A
Wiring B
30
Simplified Wiring
• NEC compliant
• Disconnect switch may be required
• Outdoor units requires 208/230V 40A single
phase or 3-phase, depends on BTU’s
• Indoor units powered from the outdoor unit using
3 wires and ground. Usually 14AWG.
• Indoor required two lines for power, typically
208/230 V single phase 15A.
• 3rd line used for networking and data
communication
31
Mix and Match Flexibility Large and Small
Ceiling Cassettes
1/4 Liquid From 7-42K BTU
1/2 Gas
3/8 Liquid
3/4 Gas Condensing Unit
Combinations from
Compact Duct Coils 1/4 Liquid 2Tons to 31.5 Tons
from 7K to 18K BTU 3/8 Gas
3/8 Liquid
3/4 Gas
Wall Mount Coils
from 7K to 36K BTU
1/4 Liquid
5/8 Gas 3/8 Liquid, 3/4 Gas 32
Piping system
Refrigerant flow is accumulated by using
STA separation tube assemblies in reverse
and then dividing refrigerant flow to as many
as 48 indoor units
33
VRF
HALL
8 Because room
temperature
sensor is
THERMOSTAT 1
housed in
thermostat,
the temp
of only two
rooms can be
controlled.
35
Individual Temperature
Individual Temperature Control
Control
VRF Individual Air
Individual Air Flow
Flow Settings
Settings
Equipment:
Equipment:
1-Outdoor
1- Outdoorunit
unit
88--Indoor
Indoorunits
units
88--Remote
Remotecontrols
controls
Each indoor
Each indoor
9
HALLWAY
units has
units has anan
individual
individual
remote control
remote control
and aa room
and room
temperature
temperature
sensor
sensor
36
NoIndividual
No Individualtemperature/air
temperature/airflow
flowsettings
settings
Central
Because setset
8 Because
temperature isis
temperature
matched to
matched to
living room,
living room,
the ideal
the ideal
temperature
temperature
cannot be
cannot be
selected for
selected for
other rooms.
other rooms.
37
Individualtemperature/air
Individual temperature/airflow
flowsetting
setting
VRF
9 Individual units
Individual units
with temperature
with temperature
sensors in
sensors in each
each
room provide
room provide
comfortable
comfortable
HALL
separate room
separate room
temperatures
temperatures
matched to
matched to the
the
room’s use.
room’s use.
38
No Individual
No Individual temperature/air
temperature/air flow
flow setting
setting
Central Heat-sensitive adults
present in living room
Cold-sensitive infant
Present in the bedroom
Whentemperature
When temperatureandandair
airflow
floware
areset
setto
toaccommodate
accommodateinfant
infantininbedroom,
bedroom,
peopleininother
people otherrooms
roomsare
aretoo
toohot
hotbecause
becausesetting
settingare
aresame
sameininall
allrooms.
rooms.
39
VRF
Temperature
9 and air flow
can be
individually
set according
to the room
usage
conditions.
Quiet
9 operation as
low as 23db
40
Central Changing Sun Load
8 When direct sunlight or other disturbances
change room load, system response for individual
rooms is impossible because set temperature
matched to living room.
A.M. P.M.
41
VRF Changing Sun Load
When the heat load changes by direct sunlight or
9 other disturbance, settings can be changed for
each room. All the rooms can be kept comfortable.
A.M. P.M.
42
Time to Reach Set Point
Central Ex: When returning home in the summer VRF
TXVOperation
TXV Operationisis
TotallyIndependent
Totally Independentof of
CompressorOperation
Compressor Operation
47
Lack of TXV Integration
• What standard TXVs do not do:
– Control evaporator pressure
– Cycle the compressor
– Control running time
– Control room temperature
• Three main working forces on the TXV are:
– Remote bulb or sensing bulb pressure (opening
force)
– Spring pressure (closing force)
– Evaporator pressure (closing force)
48
Thermal Expansion Valve TXV
TXV
Evaporator
Condenser
Compressor
52
EEV – Positioning System
• Expansion valve is the component that controls
the rate at which liquid refrigerant can flow into
an evaporator coil
• Control algorithm is continuously providing
signals to the EEV to open or close by small
amounts to vary the amount of refrigerant being
delivered to the
evaporator meeting
targeted superheat.
53
Thermistors
• A type of resistor used to measure temperature
changes, relying on the change in its resistance
with changing temperature.
54
Control Loop Components
• Measurement
By a sensor (thermistor) connected to
the refrigerant cycle or the “space"
• Decision
Made in Advanced Computer
Controller
• Action
Taken through an output device
("actuator") such as the stepper motor
in the EEV or Variable speed inverter
compressor
55
Control Loop at Local Evaporator
57
Controller’s algorithm
59
So what’s an Inverter?
• An inverter controls the operating speed of
a DC motor by controlling the frequency
and voltage of the power supplied to the
motor.
• An inverter provides the controlled power.
In most cases, the inverter includes a
rectifier so that DC power for the inverter
can be provided from mains AC power.
60
Inverter Principle
• Bridge Rectifier
Provides the same polarity of output voltage for
any polarity of the input voltage. In other words,
converts alternating current (AC) input into
direct current (DC) output.
Diodes are used to rectify AC by blocking the
negative or positive portion of the waveform
61
• Alternating current
Diode Bridge (AC) whose magnitude
and direction vary
cyclically (60Hz)
• Basic Operation:
current flows to the right
along the upper colored
path to the output, and
Load
returns to the supply via
the lower one.
• If supplied current
direction changes output
current direction remains
the same, DC
• Result: Negative part of
the waveform has been
eliminated
62
Inverter Principle
• Smoothing Condenser
used to smooth the ripple voltage present
in a pulsating DC voltage output of a
power supply rectifier.
• Most modern electronic devices require a
steady DC supply
63
Inverter Block Diagram
64
VRF
Inverter Control Video
65
Inverter Principle
• IPM (Inverter Power Module)
It is composed of 6 transistors and drives the
motor by high speed signal switching.
• The drive voltage signal is transferred to the
drive circuit from a microcomputer, and varies
the supply frequency to the motor (PWM
system) to rotate the motor.
• Currently, insulated gate bipolar transistors
IGBT’s are used in most inverter circuits
66
PWM Pulse Width Modulation
• Signal involves the modulation of its duty cycle, to
control the amount of power sent to a load.
• Many digital circuits can generate PWM signals
outputs to control an electrical motor.
• Usually use a counter that increments periodically
and is reset at the end of every period of PWM.
• If counter value is more than the reference value,
the PWM output changes state from high to low.
67
PWM
68
DC Inverter Control Function
Basic Circuit of 3-Phase Inverter
69
Why do I want an Inverter?
• Benefits of an Inverter Air Conditioner:
– Compared to the common On-Off controlled
compressor; the inverter controlled
compressor is able to run at the proper
revolution to provide the best efficiency and
reduce losses.
– When the maximum capacity is not required,
the compressor revolution is decreased. This
means the input power decreases too, which
results in increased system efficiency.
70
Low Electric Consumption
Power balance control technology achieves high
operational efficiencies by detecting low pressure and
high pressure and precisely controls the optimum
refrigerant condition via refrigerant flow rate.
72
Effective use of heat exchanger
The outdoor unit can achieve the most efficient
operation by matching the heat exchanger of the
outdoor unit to the systems requirements and the
required load capacity of the conditioned space.
Example
9 HP of compressors
by using 3 outdoor
units together
Max. 10.5 HP Max. 10.5 HP Max. 10.5 HP
73
Operation / Comfort
• Quiet operation (varies by manufacturer)
Normal operation mode: 57dB(A)
Night operation mode 54 dB(A)
• Inverter compressor makes system even quieter
when it is operating at slower RPMs
74
Central remote controller
Central control
by tenant
76
PC Control
Rotating 3-D display Floor layout display List table display
Up to 400 indoor
units or 400 groups PC controller
can be controlled
77
PC controller (Calculating electricity charges)
Each tenant bill can be made by calculating function of PC controller
Power supply
Tenant bill
Tenant-D
Tenant bill
Apportioned Tenant-B
charges
Tenant bill
PC controller Tenant-A
79
Service tool (Software)
80
VRF - Summary
• Climate control & zoning comfort
• Effective energy consumption
• Inverter driven scroll compressor &
digital temperature controls,
• Produces a highly responsive cooling
and/or heating.
• Cooling/Heating only on demand
81
Thank You
for your time and
attention.
We hope you will
consider VRF
technology for
your next project
82