Line Differential Protection
Line Differential Protection
Preamble:
Line differential Protection can be applied on overhead lines and cables. It is a very reliable unit
protection. All faults on the line, between the line CTs, are cleared instantaneously. It has ability to
detect high resistive earth faults It is a preferred protection scheme for underground cable and also
for short lines where Distance protection would have limitations.
compensation. This process is called “time criteria for protection of a three-terminal feeder,
alignment”. but the principle is similar for a two-terminal
feeder also wherein instead of three currents only
* Differential current (IDiff) = vector summation
two currents are considered ie I1 & I2 only.
of all currents entering the protected zone.
* Bias current (IBias) = half the scalar sum of the
2.0 PHASE CURRENT DIFFERENTIAL
currents entering the protected zone.
TRIPPING CRITERIA;[2]
Line Differential Protection
The differential and bias currents are compared • If it is below the graph, the relay shall restrain.
against a tripping criterion which is defined by a As when the phase-differential protection issues
dual-slope characteristic in fig.2.shows the tripping a trip command, it sends a per-phase ‘differential
inter trip’ signal to the remote terminals to enable
remote breaker to trip. This is to ensure that all
ends of the protected line trip, even for marginal
fault conditions.
By default, the delay characteristic is set to
definite time with a zero second delay, resulting
in instantaneous tripping, however it can be
programed for either definite time or on inverse
Fig.2: Bias Characteristic graph.[2]
time for grading with other protections. grading or
www.electricalmirror.net
function of Phase Is1 and Phase k1 as shown in the a voltage applied over the line capacitances as seen
following calculation (note: Phase Is1 and Phase k1 in the fig.3. If an external short circuit with negligible
have been shortened to just Is1 and k1 for clarity). fault resistance occurs close to the line, the voltage
Idiff = k1(Ibias) + Is1 ... in the fault location will be approximately zero.
Idiff = (k1)(0.5Idiff) + Is1 ...
Consequently, zero voltage will also be applied
Is1 = Idiff - k1.0.5Idiff = Idiff.(1 - 0.5k1) ...
over part of the line capacitance, which in turn will
Idiff = Is1/ (1 - 0.5k1)
decrease the charging current compared to the pre-
If, k1 has a value of 30% for example, this means fault value.
that the minimum trip current is 1.176 Is1.
3.0 Calculation for charging current;
Where, Is1 (basic differential current setting which
Say for 220kV line of 15km line.
determines the minimum pick-up level of the
protection.) Line charging MVR/km for 220kV line = 0.132
MVAR / km,
2.3 Charging current compensation;
Formula for Line charging current ;
Since, this calculated Susceptance value being ii. CVT ratio 220kV/110V
very low, therefore considering the default value
iii. Characteristic slope:- 20%
of 0.2 sec., while Charging current calculations
iv. Operating current:- 0.15 A
4.0 Operation as Distance protection
Relay; v. Charging current:- not considered as it is <<
0.2A default value (refer Cl.3.1)
In every numerical line difference relay, there is a
Line Differential Protection
feature, if optical fiber link fails, then it switches vi. Differential Current calculation:
– over to Distance Protection Relay, in which (a)Please refer Cl.2 [calculation is reproduced for
local CVTs & CTs connected to Line Difference Easy reference;
Protection are used in Distance Protection.
• Phase Is1: The basic differential current setting
The settings thereof are similar to any other which determines the minimum pick-up level
Distance protection for any feeder ie. Z1, Z2 & Z3, of the protection.
impedances .
• Phase k1: The lower percentage bias setting
5.0 Constraints in respect of usage of used when the bias current is below the Phase
Line Differential Relay [3]; Is2 setting. This provides stability for small CT
With fiber-optic communication there is no mismatches, while ensuring good sensitivity to
length limitation on Transmission lines for Line resistive faults under heavy load conditions.]
Differential Protection. Relay to relay dedicated (b) minimum Trip current ie operating ;(please
communication channel can be used up to 200 to refer Cl.2.2)
250 km. above this length fiber optic repeaters are Idiff = phase Is1/ (1 - 0.5.phase k1).where, Phase
required. In modern numerical differential relays, K1 is % slope.
Errors due to communication channel propagation
delay as well as errors due to channel asymmetry
(v) Operating current;
can be compensated in modern Line Differential (Differential current calculation adopting
protection. [3] Can be compensated by appropriate Characteristic slope of 20%);
settings and communication algorithm.
Idiff = phase Is1/ (1 - 0.5.phase k1).
Note:
Idiff= 0.15/1- 0.5 x 0.20) = 0.1666 Amp
»» It can be used in any network including weak (vii) Restating current;
in-feed condition can be used for any type of
network earthing. 1/2 of Operating current;
www.electricalmirror.net
Fig.5:pdf copy of actual relevant settings provided on
the Line differential relay for the said 11.7 kV Line.
7.0 Conclusion;
Note: 1. This protection is preferably used for short
i. Kindly refer Cl.6.0.as regards settings adopted. lines by most of the STUs and CTU in addition
to DPR.
ii. Kindly refer fig.5 .enclosed in red rectangle are
the real settings adopted in the Line Differential 2. It has an advantage of built in Single phase to
Relay. ground fault auto-reclose function.
iii. For clarity the settings adopted are reproduced 3. If the transmission line is through Underground
– hereunder ;(table 6). cable, Auto reclose function should be disabled
8.0 References;
1. ABB’s Line deferential Protraction manual
RED-615.
2. MiCOM P54x (P543, P544, P545 & P546)
Current Differential Protection Relay-mannual. Chief Engineer (Testing & Commun.),M.P. Power
Transmission co. Ltd. Jabalpur, for permitting Shri
3. In consultation with Er.Shri Sanjay Patki,
Rajat Jain. AE(Testing) 400kV.S/S BINA, to get
former Vice-president-Corporate Engineering
associated himself with me as my Co-author. EM
( Protection Expert), Tata Power ,Mumbai and
a distinguished member in CIGRE, Paris.
9.0 Gratitude & acknowledgement;
Line Differential Protection
10.0 Authors
• Retd. Chief Engineer (Testing & Commun.), M.P.Power Transmission Co. Ltd.
Jabalpur. (Served in MPSEB & MPPTCL, Jabalpur for 33 years).
• Empanelled as an Expert Professional on the panel of CPRI, Bangalore
(2008 to 2012) and carried out Third Party Inspections on behalf of CPRI
Bangaluru /Bhopal.
• Worked as Advisor (Testing) in SOUTHCO, Berhampur. Odisha (A DISCOM
in Odisha of Anil Dhirubhai Ambani group).(from 2004 to 2006).
• Recipient of plaque in recognition of his eminence and contribution to the
K.K.Murty. BE (Hons), profession of Electrical Engineering at the National level by The Institute of
Elect,FIE(India) ,CE(India),M.
CIGRE’ Engineers India, Kolkata in Oct 2015.