Unit II
Unit II
sense but miniature circuit breaker does it in more reliable This was a simple explanation of miniature circuit breaker
way. MCB is much more sensitive to over current than fuse. working principle.
2. Another advantage is, as the switch operating knob Miniature Circuit Breaker Construction
comes at its off position during tripping, the faulty zone of Miniature circuit breaker construction is very simple,
the electrical circuit can easily be identified. But in case of robust and maintenance free. Generally a MCB is not
fuse, fuse wire should be checked by opening fuse grip or repaired or maintained, it just replaced by new one when
cutout from fuse base, for confirming the blow of fuse wire. required. A miniature circuit breaker has normally three
3. Quick restoration of supply cannot be possible in case main constructional parts. These are:
of fuse as because fuses have to be replaced for restoring Frame of Miniature Circuit Breaker
the supply. But in the case of MCB, quick restoration is The frame of miniature circuit breaker is a molded case.
possible by just switching on operation. This is a rigid, strong, insulated housing in which the other
4. Handling MCB is more electrically safe than fuse. components are mounted.
Because of too many advantages of MCB over fuse units, in Operating Mechanism of Miniature Circuit Breaker
modern low voltage electrical network, miniature circuit The operating mechanism of miniature circuit breaker
breaker is mostly used instead of backdated fuse unit. Only provides the means of manual opening and closing
one disadvantage of MCB over fuse is that this system is operation of miniature circuit breaker. It has three-
more costly than fuse unit system. positions “ON,” “OFF,” and “TRIPPED”. The external
Working Principle Miniature Circuit Breaker switching latch can be in the “TRIPPED” position, if the
There are two arrangement of operation of miniature MCB is tripped due to over-current. When manually switch
circuit breaker. One due to thermal effect of over current off the MCB, the switching latch will be in “OFF” position. In
and other due to electromagnetic effect of over current. close condition of MCB, the switch is positioned at “ON”.
The thermal operation of miniature circuit breaker is By observing the positions of the switching latch one can
achieved with a bimetallic strip whenever continuous over determine the condition of MCB whether it is closed,
current flows through MCB, the bimetallic strip is heated tripped or manually switched off.
and deflects by bending. This deflection of bimetallic strip Trip Unit of Miniature Circuit Breaker
releases mechanical latch. As this mechanical latch is The trip unit is the main part, responsible for proper
attached with operating mechanism, it causes to open the working of miniature circuit breaker. Two main types of trip
miniaturecircuit breaker contacts. But during short circuit mechanism are provided in MCB. A bimetal provides
condition, sudden rising of current, causes protection against over load current and an electromagnet
electromechanical displacement of plunger associated with provides protection against shortcircuit current.
tripping coil or solenoid of MCB. The plunger strikes the Operation of Miniature Circuit Breaker
trip lever causing immediate release of latch mechanism There are three mechanisms provided in a single miniature
consequently open the circuit breaker contacts. circuit breaker to make it switched off. If we carefully
observe the picture beside, we will find there are mainly
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.3) PRINCIPLES OF CIRCUIT BREAKERS
one bi – metallic strip, one trip coil and one hand operated reduced to zero the breakers are operated to cut off the
on – off lever. Electric current carrying path of a miniature current. This will avoid the striking of the arc. But this
circuit breaker shown in the picture is like follows. First left conditions is difficult to achieve and very much expensive.
hand side power terminal – then bimetallic strip – then The restriking of arc when current is interrupted is
current coil or trip coil – then moving contact – then fixed dependent on the voltage between the contact gap at
contact and – lastly right had side power terminal. All are that instant which will inturn depend on power factor.
arranged in series. Higher the factor ,lesser is the voltage appearing across
If circuit is overloaded for long time, the bi – metallic strip the gap than its peak value.
becomes over heated and deformed. This deformation of
2.3 ARC PHENOMENON
bi metallic strip causes, displacement of latch point. The When a short-circuit occurs, a heavy current flows through
moving contact of the MCB is so arranged by means of the contacts of the circuit breaker before they are opened
by the protective system. At the instant when the contacts
spring pressure, with this latch point, that a little
begin to separate, the contact area decreases rapidly and
displacement of latch causes, release of spring and makes large fault current causes increased current density and
hence rise in temperature. The heat produced in the
the moving contact to move for opening the MCB. The
medium between contacts (usually the medium is oil or air)
current coil or trip coil is placed such a manner, that during is sufficient to ionise the air or vapourise and ionise the oil.
short circuit fault the mmf of that coil causes its plunger to The ionised air or vapour acts as conductor and an arc is
struck between the contacts. The p.d. between the contacts
hit the same latch point and make the latch to be is quite small and is just sufficient to maintain the arc. The
displaced. Hence the MCB will open in same manner. Again arc provides a low resistance path and consequently the
current in the circuit remains uninterrupted so long as the
when operating lever of the miniature circuit breaker is
arc persists. During the arcing period, the current flowing
operated by hand, that means when we make the MCB at between the contacts depends upon the arc resistance. The
greater the arc resistance, the smaller the current that
off position manually, the same latch point is displaced as
flows between the contacts.
a result moving contact separated from fixed contact in The arc resistance depends upon the following factors:
same manner. So, whatever may be the operating (i) Degree of Ionization : The arc resistance increases
with the decrease in the number of ionized particles
mechanism, that means, may be due to deformation of bi –
between the contacts.
metallic strip, due to increased mmf of trip coil or may due
(ii) Length of the Arc : the arc resistance increases with
to manual operation, actually the same latch point is the length of the arc i.e., separation of contacts.
displaced and same deformed spring is released, which (iii) Cross-section of Arc : the arc resistance increases
with the decrease in area of X-section of the arc.
ultimately responsible for movement of the moving
2.4 PRINCIPLES OF ARC EXTINCTION
contact. When the the moving contact separated from
Before discussing the methods of arc extinction, it is
fixed contact, there may be a high chance of arc. necessary to examine the factors responsible for the
maintenance of arc between the contacts. These are :
2.2.2 A.C Circuit Breaking
(i) p.d. between the contacts
There is difference between breaking in case of d.c and a.c (ii) ionised particles between contacts
circuits.In a.c circuits the current passes through zero Taking these in turn,
twice in one complete cycle. When the currents are (i) When the contacts have a small separation, the p.d.
between them is sufficient to maintain the arc. One
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.4) PRINCIPLES OF CIRCUIT BREAKERS
way to extinguish the arc is to separate the contacts to 2. Low Resistance or Current Zero Method :
such a distance that p.d. becomes inadequate to This method is employed for arc extinction in a.c.
maintain the arc. However, this method is circuits only. In this method, arc resistance is kept low
impracticable in high voltage system where a until current is zero where the arc extinguishes
separation of many metres may be required. naturally and is prevented from restriking inspite of the
(ii) The ionised particles between the contacts tend to rising voltage across the contacts. All modern high
maintain the arc. If the arc path is deionised, the arc power a.c. circuit breakers employ this method for arc
extinction will be facilitated. This may be achieved by extinction.
cooling the arc or by bodily removing the ionised In an a.c. system, current drops to zero after every half-
particles from the space between the contacts. cycle. At every current zero, the arc extinguishes for a
2.5 METHODS OF ARC EXTINCTION brief moment. Now the medium between the contacts
contains ions and electrons so that it has small
There are two methods of extinguishing the arc in circuit
dielectric strength and can be easily broken down by
breakers viz.
the rising contact voltage known as restriking voltage.
1. High resistance method.
If such a breakdown does occur, the arc will persist for
2. Low resistance or current zero method another halfcycle.
1. High Resistance Method : If immediately after current zero, the dielectric strength
In this method, arc resistance is made to increase with of the medium between contacts is built up more
time so that current is reduced to a value insufficient rapidly than the voltage across the contacts, the arc
to maintain the arc. Consequently, the current is fails to restrike and the current will be interrupted. The
interrupted or the arc is extinguished. The principal rapid increase of dielectric strength of the medium
disadvantage of this method is that enormous energy near current zero can be achieved by :
is dissipated in the arc. Therefore, it is employed only (a) Causing the ionised particles in the space between
in d.c. circuit breakers and low-capacity a.c. circuit contacts to recombine into neutral molecules.
breakers. The resistance of the arc may be increased
(b) Sweeping the ionised particles away and replacing
by :
them by un-ionised particles
Lengthening the Arc : The resistance of the arc is
Therefore, the real problem in a.c. arc interruption is to
directly proportional to its length. The length of
rapidly deionise the medium between contacts as soon as
the arc can be increased by increasing the gap
the current becomes zero so that the rising contact voltage
between contacts.
or restriking voltage cannot breakdown the space between
Cooling the Arc : Cooling helps in the contacts. The de-ionisation of the medium can be achieved
deionisation of the medium between the contacts. by:
This increases the arc resistance. Efficient cooling
Lengthening of the Gap : The dielectric strength
may be obtained by a gas blast directed along the
of the medium is proportional to the length of the
arc.
gap between contacts. Therefore, by opening the
Reducing X-section of the Arc : If the area of X- contacts rapidly, higher dielectric strength of the
section of the arc is reduced, the voltage necessary medium can be achieved.
to maintain the arc is increased. In other words, the
High Pressure : If the pressure in the vicinity of
resistance of the arc path is increased. The cross-
the arc is increased, the density of the particles
section of the arc can be reduced by letting the arc
constituting the discharge also increases. The
pass through a narrow opening or by having
increased density of particles causes higher rate of
smaller area of contacts.
de-ionisation and consequently the dielectric
Splitting the Arc : The resistance of the arc can be strength of the medium between contacts is
increased by splitting the arc into a number of increased.
smaller arcs in series. Each one of these arcs
Cooling : Natural combination of ionised particles
experiences the effect of lengthening and cooling.
takes place more rapidly if they are allowed to
The arc may be split by introducing some
cool. Therefore, dielectric strength of the medium
conducting plates between the contacts.
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.5) PRINCIPLES OF CIRCUIT BREAKERS
now −3Vgm and once again the two halves of the circuit resistance. This results in the decrease of arc current
are separated and the line is isolated at this potential. and an increase in the rate of de-ionisation of the arc
After about half a cycle further, the aforesaid events path. Consequently, the arc resistance is increased.
are repeated even on more formidable scale and the The increased arc resistance leads to a further increase
line may be left with a potential of 5Vgm above earth in current through shunt resistance. This process
potential. continues until the arc current becomes so small that it
Theoretically, this phenomenon may proceed infinitely fails to maintain the arc. Now, the arc is extinguished
increasing the voltage by successive increment of 2 and circuit current is interrupted. The shunt resistor
times Vgm. While the above description relates to the also helps in limiting the oscillatory growth of re-
worst possible conditions, it is obvious that if the gap striking voltage. It can be proved mathematically that
breakdown strength does not increase rapidly enough, natural frequency of oscillations of the circuit shown in
successive re-strikes can build up a dangerous voltage Fig. 2.7 is given by :
in the open circuit line. However, due to leakage and fn =
corona loss, the maximum voltage on the line in such The effect of shunt resistance R is to prevent the
cases is limited to 5 Vgm. oscillatory growth of re-striking voltage and cause it to
Resistance Switching grow exponentially upto recovery voltage. This is being
It has been discussed above that current chopping, most effective when the value of R is so chosen that
capacitive current breaking etc. give rise to severe the circuit is critically damped. The value of R required
voltage oscillations. These excessive voltage surges for critical damping is 0·5 Fig. 2.8 shows the
during circuit interruption can be prevented by the use oscillatory growth and exponential growth when the
of shunt resistance R connected across the circuit circuit is critically damped.
breaker contacts as shown in the equivalent circuit in To sum up, resistors across breaker contacts may be
Fig. 2.7. This is known as resistance switching. used to perform one or more of the following
functions:
To reduce the rate of rise of re-striking voltage and
the peak value of re-striking voltage.
To reduce the voltage surges due to current
chopping and capacitive current breaking.
To ensure even sharing of re-striking voltage
transient across the various breaks in multi break
Fig. 2.7
circuit breakers.
It may be noted that value of resistance required to
perform each function is usually different. However, it is
often necessary to compromise and make one resistor do
more than one of these functions.
Fig. 2.8
2.6.2 Expression for RRRV
Referring to Fig. 2.7, when a fault occurs, the contacts
of the circuit breaker are opened and an arc is struck
between the contacts. Since the contacts are shunted
by resistance R, a part of arc current flows through this
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.9) PRINCIPLES OF CIRCUIT BREAKERS
Fig. 2.10
Fig. 2.9
In air blast circuit breakers it is observed that the rate at
Applying KVL to loop (I),
which dielectric strength of gap increases is lower than in
= I1(s) I2 (x) (i)
oil breakers. Since air has a much lower dielectric strength
Applying KVL to loop (II), than the gases at same temperature and pressure in oil
= I1 (s) + I2(s) (ii) circuit breaker. The dielectric strength of a gas increases
From equation (ii), with pressure. Thus the air blast circuit breaker is more
I2(s) = (1 + sCR) I2(s) sensitive to restriking voltage transient. In low or medium
Substituting this value in equation (i) voltage air blast circuit breaker the rate or rise of restriking
voltage is higher. Thus shunt resistors are used for low and
= (1 + sCR) I2 (s) I2 (s)
medium voltage air blast circuit breakers. Also in case of oil
= I2(s)
circuit breakers the resistance switching is not employed as
= I2(s) it is not sensitive to RRRV.
= (RLCs2 + Ls + R) I2(s)
Example 1 : In 132 kV transmission system, the phase to
Is(s) = = ground capacitance is 0.01 F. The inductance being 6 H.
Using partial fractions, Calculate the voltage appearing across the pole of a circuit
Is(s) = breaker if a magnetizing current of 10 A is interrupted. Find
Put x = , y = the value of resistance to be used across contact space to
eliminate the striking voltage transient.
I2(s) = Solution : L = 6H
C = 0.01 F = 0.01 106 F
i = 10 A
Voltage appearing across poles of circuit breaker, is
given by
The natural frequency of oscillation is given by,
V = I
fn =
= 10
It can be seen that with the value of the resistance R equal
= 10 (24494.89)
to or less than , the oscillatory nature of the transient will
V = 254 kV
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.10) PRINCIPLES OF CIRCUIT BREAKERS
(i) Breaking Capacity : When the short-circuit current is flowing, there is only
a small voltage across the breaker contacts, while the
It is current (r.m.s.) that a circuit breaker is capable of
service voltage appears across the contacts only after
breaking at given recovery voltage and under specified
the current has been interrupted. Thus MVA rating is
conditions (e.g., power factor, rate of rise of restriking
the product of two quantities which do not exist
voltage).
simultaneously in the circuit.
Therefore, the *agreed international standard of
specifying breaking capacity is defined as the rated
symmetrical breaking current at a rated voltage.
(ii) Making Capacity :
There is always a possibility of closing or making the
circuit under shortcircuit conditions. The capacity of a
breaker to “make” current depends upon its ability to
withstand and close successfully against the effects of
Fig. 2.11 electromagnetic forces. These forces are proportional
The breaking capacity is always stated at the r.m.s. to the square of maximum instantaneous current on
value of fault current at the instant of contact closing. Therefore, making capacity is stated in terms
separation. When a fault occurs, there is considerable of a peak value of current instead of r.m.s. value.
asymmetry in the fault current due to the presence of a The peak value of current (including d.c. component)
d.c. component. The d.c. component dies away rapidly, during the first cycle of current wave after the closure of
a typical decrement factor being 0·8 per cycle. circuit breaker is known as making capacity.
Referring to Fig.2.11, the contacts are separated at DD´. It may be noted that the definition is concerned
At this instant, the fault current has with the first cycle of current wave on closing the circuit
x = maximum value of a.c. component breaker. This is because the maximum value of fault
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.11) PRINCIPLES OF CIRCUIT BREAKERS
current possibly occurs in the first cycle only when (v) Short time rating = 17496 A for 3 seconds
maximum asymmetry occurs in any phase of the breaker. (vi) Rated service voltage = 33 kV (r.m.s)
In other words, the making current is equal to the
Example 2 : A 50 Hz, 11 kV, 3-phase alternator with
maximum value of asymmetrical current. To find this value,
earthed neutral has a reactance of 5 ohms per phase and is
we must multiply symmetrical breaking current by to
connected to a bus-bar through a circuit breaker. The
convert this from r.m.s. to peak, and then by 1·8 to include
distributed capacitance upto circuit breaker between phase
the “doubling effect” of maximum asymmetry. The total
and neutral in 0·01 μF. Determine
multiplication factor becomes 2 . 1·8 = 2·55.
(i) peak re-striking voltage across the contacts of the
∴ Making capacity =2·55 . Symmetrical breaking capacity
breaker
(iii) Short-Time Rating :
(ii) frequency of oscillations
It is the period for which the circuit breaker is able to
(iii) the average rate of rise of re-striking voltage upto the
carry fault current while remaining closed.
first peak.
Sometimes a fault on the system is of very temporary
Solution : Inductance per phase
nature and persists for 1 or 2 seconds after which the
fault is automatically cleared. In the interest of L = = = 0.0159 H
continuity of supply, the breaker should not trip in Capacitance per phase,
such situations. C = 0.01 F = 108 F
This means that circuit breakers should be able to carry (i) Maximum value of recovery voltage (phase to neutral)
high current safely for some specified period while Emax = = 8.98 kV
remaining closed i.e., they should have proven short- Peak re-striking voltage = 2 Emax = 2 8.98 = 17.96 kV
time rating. However, if the fault persists for a duration
(ii) Frequency of oscillations is
longer than the specified time limit, the circuit breaker
fn = =
will trip, disconnecting the faulty section.
= 12,628 Hz
The short-time rating of a circuit breaker depends
upon its ability to withstand (a) the electromagnetic (iii) Peak re-striking voltage occurs at a time t given by
force effects and (b) the temperature rise. The oil t = = =
circuit breakers have a specified limit of 3 seconds = 39.6 106 sec = 39.6 sec
when the ratio of symmetrical breaking current to the Average rate of rise or re-string voltage
rated normal current does not exceed 40. However, if = =
this ratio is more than 40, then the specified limit is 1
= 0.453 kV/ sec = 453 103 kV/sec
second.
Example 3 : In a short circuit test on a circuit breaker, the
Normal current rating. It is the r.m.s. value of current
following readings were obtained on single frequency
which the circuit breaker is capable of carrying
transient :
continuously at its rated frequency under specified
conditions. The only limitation in this case is the (i) time to reach the peak re-striking voltage, 50 μ sec
temperature rise of current-carrying parts. (ii) the peak re-striking voltage, 100 kV
Example 2 : A circuit breaker is rated as 1500 A, Determine the average RRRV and frequency of oscillations
1000 MVA, 33 kV, 3-second, 3-phase oil circuit breaker. Find Solution :
(i) rated normal current (ii) breaking capacity (iii) rated Average RRRV =
symmetrical breaking current (iv) rated making current = = 2 k V/ sec
(v) short-time rating (vi) rated service voltage. = 2 106 kV/sec
Solution : Natural frequency of oscillations,
(i) Rated normal current = 1500 A fn =
(ii) Breaking capacity = 1000 MVA =
(iii) Rated symmetrical breaking current = = 17495 A = = 10,000 Hz
(r.m.s)
(iv) Rated making current = 2.55 17496 = 44614 A (peak)
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.12) PRINCIPLES OF CIRCUIT BREAKERS
Example 2 : An air-blast circuit breaker is designed to There are several ways of classifying the circuit breakers.
interrupt a transformer magnetizing current of 11 (r.m.s.) However, the most general way of classification is on the
chops are 35.2 H and 0.0023 F, find the value of voltage basis of medium used for arc extinction. The medium used
that appears across the contacts of the breaker. Assume that for arc extinction is usually oil, air, sulphur hexafluoride
all the inductive energy is transferred to the capacitance. (SF6) or vacuum. Accordingly, circuit breakers may be
Solution : Voltage across breaker contacts at chopping is classified into :
e = i (i) Oil circuit breakers which employ some insulating oil
(e.g., transformer oil) for arc extinction.
Here , i = 7A ; L = 35.2 H and C = 0.0023 F
(ii) Air-blast circuit breakers in which high pressure air-
e = 7 volts
blast is used for extinguishing the arc.
= 866 103 V = 866 kV
(iii) Sulphur hexafluroide circuit breakers in which sulphur
hexafluoride (SF6) gas is used for arc extinction.
2.8 AUTOMATIC RECLOSING (iv) Vacuum circuit breakers in which vacuum is used for
arc extinction. Each type of circuit breaker has its own
About 90% of faults on overhead lines are of transient advantages and disadvantages. In the following
nature. Transient faults are caused by lightning or sections, we shall discuss the construction and working
external bodies falling on the lines. Such faults are of these circuit breakers with special emphasis on the
always associated with arcs. If the line is disconnected way the arc extinction is facilitated.
from the system for a short time, the arc is 2.10 OIL CIRCUIT BREAKERS
extinguished and the fault disappears. Immediately
after this, the circuit breaker can be reclosed
automatically to restore the supply.
Most faults on EHV lines are caused by lightning.
Flashover across insulators takes place due to
overvoltages caused by lightning and exists for a short
time. Hence, only on instantaneous reclosure is used in
the case of EHV lines. There is no need for more than
one reclosurc for such a situation. For EHV lines, one
reclosurc in 12 cycles is recommended. A fast reclosure
is desired from the stability point of view.
On lines up 33 k V, most faults are caused by external Fig. 2.12
objects such as tree branches, etc. falling on the In such circuit breakers, some insulating oil (e.g.,
overhead lines. This is due to the fact that the support transformer oil) is used as an arc quenching medium. The
height is less than that of the trees. The external contacts are opened under oil and an arc is struck between
objects may not be burnt clear at the first reclosure them. The heat of the arc evaporates the surrounding oil
and may require additional reclosures. Usually three and dissociates it into a substantial volume of gaseous
reclosures at 15-120 seconds' intervals arc made to hydrogen at high pressure. The hydrogen gas occupies a
clear the fault. Statistical reports show that over 80% volume about one thousand times that of the oil
faults are cleared after the first reclosure, 10% require decomposed. The oil is, therefore, pushed away from the
the second reclosure and 2% need the third reclosure, arc and an expanding hydrogen gas bubble surrounds the
while the remaining 8% are permanent faults. If the arc region and adjacent portions of the contacts (See Fig.
fault is not cleared after 3 reclosures, it indicates that 2.12). The arc extinction is facilitated mainly by two
the fault is of permanent nature. Automatic reclosurc processes. Firstly, the hydrogen gas has high heat
arc not used on cables as the breakdown of insulation conductivity and cools the arc, thus aiding the de-
in cables causes a permanent fault. ionisation of the medium between the contacts. Secondly,
the gas sets up turbulence in the oil and forces it into the
space between contacts, thus eliminating the arcing
2.9 CLASSIFICATION OF CIRCUIT BREAKERS
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.13) PRINCIPLES OF CIRCUIT BREAKERS
Therefore, for successful interruption, long arc length is (a)Plain Explosion Pot
necessary. It is a rigid cylinder of insulating material and encloses
These breakers have long and inconsistent arcing the fixed and moving contacts (See Fig. 2.14). The
times. moving contact is a cylindrical rod passing through a
These breakers do not permit high speed interruption. restricted opening (called throat) at the bottom. When
Due to these disadvantages, plain-break oil circuit a fault occurs, the contacts get separated and an arc is
breakers are used only for low-voltage applications struck between them.
where high breaking-capacities are not important. It is
a usual practice to use such breakers for low capacity
installations for voltages not exceeding 11 kV.
2.11.2 Arc Control Oil Circuit Breakers
In case of plain-break oil circuit breaker discussed above,
there is very little artificial control over the arc. Therefore,
comparatively long arc length is essential in order that
turbulence in the oil caused by the gas may assist in
quenching it. However, it is necessary and desirable that
final arc extinction should occur while the contact gap is
still short. For this purpose, some arc control is Fig. 2.14
incorporated and the breakers are then called arc control
The heat of the arc decomposes oil into a gas at very
circuit breakers. There are two types of such breakers,
high pressure in the pot. This high pressure forces the
namely :
oil and gas through and round the arc to extinguish it.
(i) Self-Blast Oil Circuit Breakers : in which arc If the final arc extinction does not take place while the
control is provided by internal means i.e. the Arc moving contact is still within the pot, it occurs
itself is employed for its own extinction efficiently. immediately after the moving contact leaves the pot. It
(ii) Forced-Blast Oil Circuit Breakers : in which arc is because emergence of the moving contact from the
control is provided by mechanical means external pot is followed by a violent rush of gas and oil through
to the circuit breaker. the throat producing rapid extinction.
(i) Self-Blast Oil Circuit Breakers : The principal limitation of this type of pot is that it
In this type of circuit breaker, the gases produced cannot be used for very low or for very high fault
during arcing are confined to a small volume by the currents. With low fault currents, the pressure
use of an insulating rigid pressure chamber or pot developed is small, thereby increasing the arcing time.
surrounding the contacts. Since the space available for On the other hand, with high fault currents, the gas is
the arc gases is restricted by the chamber, a very high produced so rapidly that explosion pot is liable to
pressure is developed to force the oil and gas through burst due to high pressure. For this reason, plain
or around the arc to extinguish it. explosion pot operates well on moderate short-circuit
The magnitude of pressure developed depends upon currents only where the rate of gas evolution is
the value of fault current to be interrupted. As the moderate.
pressure is generated by the arc itself, therefore, such (b) Cross Jet Explosion Pot :
breakers are sometimes called self-generated pressure This type of pot is just a modification of plain
oil circuit breakers. explosion pot and is illustrated in Fig. 2.15. It is made
The pressure chamber is relatively cheap to make and of insulating material and has channels on one side
gives reduced final arc extinction gap length and which act as arc splitters. The arc splitters help in
arcing time as against the plain-break oil circuit increasing the arc length, thus facilitating arc
breaker. Several designs of pressure chambers extinction. When a fault occurs, the moving contact of
(sometimes called explosion pots) have been the circuit breaker begins to separate.
developed and a few of them are described below : As the moving contact is withdrawn, the arc is initially
struck in the top of the pot. The gas generated by the
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.15) PRINCIPLES OF CIRCUIT BREAKERS
arc exerts pressure on the oil in the back passage. may be noted that as the severity of the short-circuit
When the moving contact uncovers the arc splitter current increases, the device operates less and less as a
ducts, fresh oil is forced across the arc path. The arc is, plain explosion pot and more and more as a cross-jet
therefore, driven sideways into the “arc splitters” which explosion pot. Thus the tendency is to make the
increase the arc length, causing arc extinction. control self-compensating over the full range of fault
currents to be interrupted.
Fig. 2.16
(ii) Forced-Blast Oil Circuit Breakers :
In the self-blast oil circuit breakers discussed above,
Fig. 2.15 the arc itself generates the necessary pressure to force
The cross-jet explosion pot is quite efficient for the oil across the arc path. The major limitation of such
interrupting heavy fault currents. However, for low breakers is that arcing times tend to be long and
fault currents, the gas pressure is †small and inconsistent when operating against currents
consequently the pot does not give a satisfactory considerably less than the rated currents. It is because
operation. the gas generated is much reduced at low values of
fault currents.
(c) Self-Compensated Explosion Pot :
This difficulty is overcome in forced-blast oil circuit
This type of pot is essentially a combination of plain
breakers in which the necessary pressure is generated
explosion pot and cross jet explosion pot. Therefore, it
by external mechanical means independent of the fault
can interrupt low as well as heavy short circuit currents
currents to be broken. In a forced -blast oil circuit
with reasonable accuracy. Fig. 2.16 shows the
breaker, oil pressure is created by the piston-cylinder
schematic diagram of self-compensated explosion pot.
arrangement.
It consists of two chambers, the upper chamber is the
The movement of the piston is mechanically coupled
cross-jet explosion pot with two arc splitter ducts while
to the moving contact. When a fault occurs, the
the lower one is the plain explosion pot. When the
contacts get separated by the protective system and
short-circuit current is heavy, the rate of generation of
an arc is struck between the contacts. The piston forces
gas is very high and the device behaves as a cross-jet
a jet of oil towards the contact gap to extinguish the
explosion pot.
arc. It may be noted that necessary oil pressure
The arc extinction takes place when the moving
produced does not in any way depend upon the fault
contact uncovers the first or second arc splitter duct.
current to be broken.
However, on low short-circuit currents, the rate of gas
Advantages
generation is small and the tip of the moving contact
has the time to reach the lower chamber. During this Since oil pressure developed is independent of the
time, the gas builds up sufficient pressure as there is fault current to be interrupted, the performance at low
very little leakage through arc splitter ducts due to the currents is more consistent than with self-blast oil
obstruction offered by the arc path and right angle circuit breakers.
bends. When the moving contact comes out of the The quantity of oil required is reduced considerably.
throat, the arc is extinguished by plain pot action. It
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.16) PRINCIPLES OF CIRCUIT BREAKERS
Fig. 2.21
Fig. 2.18 When a fault occurs, the tripping impulse causes
2. Cross-blast type opening of the air valve which connects the circuit
Cross-blast type in which the air-blast is directed at breaker reservoir to the arcing chamber. The high
right angles to the arc path as shown in Fig. 2.19 below pressure air entering the arcing chamber pushes away
the moving contact against spring pressure. The
moving contact is separated and an arc is struck. At the
same time, high pressure air blast flows along the arc
and takes away the ionized gases along with it.
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.19) PRINCIPLES OF CIRCUIT BREAKERS
Consequently, the arc is extinguished and current flow The conducting free electrons in the arc are rapidly
is interrupted. captured by the gas to form relatively immobile
It may be noted that in such circuit breakers, the negative ions. This loss of conducting electrons in the
contact separation required for interruption is arc quickly builds up enough insulation strength to
generally small (1·75 cm or so). Such a small gap may extinguish the arc. The SF6 circuit breakers have been
constitute inadequate clearance for the normal service found to be very effective for high power and high
voltage. Therefore, an isolating switch is incorporated voltage service.
as a part of this type of circuit breaker. This switch Construction :
opens immediately after fault interruption to provide Fig. 2.23 shows the parts of a typical SF6 circuit
the necessary clearance for insulation. breaker. It consists of fixed and moving contacts
2.14.2 Cross-Blast Air Breaker enclosed in a chamber (called arc interruption
In this type of circuit breaker, an air-blast is directed at chamber) containing SF6 gas. This chamber is
right angles to the arc. The cross-blast lengthens and connected to SF6 gas reservior. When the contacts of
forces the arc into a suitable chute for arc extinction. breaker are opened, the valve mechanism permits a
Fig. 2.22 shows the essential parts of a typical cross- high pressure SF6 gas from the reservoir to flow
blast air circuit breaker. When the moving contact is towards the arc interruption chamber.
withdrawn, an arc is struck between the fixed and The fixed contact is a hollow cylindrical current
moving contacts. The high pressure cross-blast forces carrying contact fitted with an arc horn. The moving
the arc into a chute consisting of arc splitters and contact is also a hollow cylinder with rectangular holes
baffles. in the sides to permit the SF6 gas to let out through
The splitters serve to increase the length of the arc and these holes after flowing along and across the arc. The
baffles give improved cooling. The result is that arc is tips of fixed contact, moving contact and arcing horn
extinguished and flow of current is interrupted. Since are coated with copper-tungsten arc resistant material.
blast pressure is same for all currents, the inefficiency Since SF6 gas is costly, it is reconditioned and
at low currents is eliminated. The final gap for reclaimed by suitable auxiliary system after each
interruption is great enough to give normal insulation operation of the breaker.
clearance so that a series isolating switch is not
necessary.
Fig. 2.22
absorbs the free electrons in the arc path to form immobile 2.16 VACUUM CIRCUIT BREAKERS(VCB)
negative ions which are ineffective as charge carriers. The
In such breakers, vacuum (degree of vacuum being in the
result is that the medium between the contacts quickly
range from 10−7 to 10−5 torr) is used as the arc
builds up high dielectric strength and causes the extinction
quenching medium. Since vacuum offers the highest
of the arc. After the breaker operation (i.e., after arc
insulating strength, it has far superior arc quenching
extinction), the valve is closed by the action of a set of
properties than any other medium. For example, when
springs.
contacts of a breaker are opened in vacuum, the
Advantages : Due to the superior arc quenching interruption occurs at first current zero with dielectric
properties of SF6 gas, the SF6 circuit breakers have many strength between the contacts building up at a rate
advantages over oil or air circuit breakers. Some of them thousands of times higher than that obtained with other
are listed below : circuit breakers.
Due to the superior arc quenching property of SF6, Principle :
such circuit breakers have very short arcing time.
The production of arc in a vacuum circuit breaker and its
Since the dielectric strength of SF6 gas is 2 to 3 times extinction can be explained as follows : When the contacts
that of air, such breakers can interrupt much larger of the breaker are opened in vacuum (10−7 to 10−5 torr),
currents. an arc is produced between the contacts by the ionisation
The SF6 circuit breaker gives noiselss operation due to of metal vapours of contacts. However, the arc is quickly
its closed gas circuit and no exhaust to atmosphere extinguished because the metallic vapours, electrons and
unlike the air blast circuit breaker. ions produced during arc rapidly condense on the surfaces
The closed gas enclosure keeps the interior dry so that of the circuit breaker contacts, resulting in quick recovery
there is no moisture problem. of dielectric strength. As soon as the arc is produced in
There is no risk of fire in such breakers because SF6 vacuum, it is quickly extinguished due to the fast rate of
gas is non-inflammable. recovery of dielectric strength in vacuum.
There are no carbon deposits so that tracking and Construction :
insulation problems are eliminated. Fig. 2.24 shows the parts of a typical vacuum circuit
The SF6 breakers have low maintenance cost, light breaker. It consists of fixed contact, moving contact and
foundation requirements and minimum auxiliary arc shield mounted inside a vacuum chamber. The movable
equipment. member is connected to the control mechanism by
Since SF6 breakers are totally enclosed and sealed stainless steel bellows. This enables the permanent sealing
from atmosphere, they are particularly suitable where of the vacuum chamber so as to eliminate the possibility of
explosion hazard exists e.g., coal mines. leak. A glass vessel or ceramic vessel is used as the outer
insulating body. The arc shield prevents the deterioration
Disadvantages
of the internal dielectric strength by preventing metallic
SF6 breakers are costly due to the high cost of SF6.
vapours falling on the inside surface of the outer insulating
Since SF6 gas has to be reconditioned after every cover.
operation of the breaker, additional equipment is
requried for this purpose.
Applications :
A typical SF6 circuit breaker consists of interrupter
units each capable of dealing with currents upto 60 kA
and voltages in the range of 50—80 kV. A number of
units are connected in series according to the system
voltage. SF6 circuit breakers have been developed for
voltages 115 kV to 230 kV, power ratings 10 MVA to 20
MVA and interrupting time less than 3 cycles.
Fig. 2.24
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.21) PRINCIPLES OF CIRCUIT BREAKERS
Working : When the breaker operates, the moving contact It is a usual practice to provide isolating switches in series
separates from the fixed contact and an arc is struck with fuses where it is necessary to permit fuses to be
between the contacts. The production of arc is due to the replaced or rewired with safety. If such means of isolation
ionisation of metal ions and depends very much upon the are not available, the fuses must be so shielded as to
material of contacts. The arc is quickly extinguished protect the user against accidental contact with the live
because the metallic vapours, electrons and ions produced metal when the fuse carrier is being inserted or removed.
during arc are diffused in a short time and seized by the 2.18 LOW VOLTAGE FUSES
surfaces of moving and fixed members and shields. Since
Low voltage fuses can be subdivided into two classes viz.,
vacuum has very fast rate of recovery of dielectric strength,
(i) semi-enclosed rewireable fuse
the arc extinction in a vacuum breaker occurs with a short
contact separation (say 0·625 cm). (ii) high rupturing capacity (H.R.C.) cartridge fuse.
Advantages : Vacuum circuit breakers have the following 1. Semi-Enclosed Rewireable Fuse :
advantages : Rewireable fuse (also known as kit-kat type) is used
They are compact, reliable and have longer life. where low values of fault current are to be interrupted.
It consists of (i) a base and (ii) a fuse carrier. The base is
There are no fire hazards.
of porcelain and carries the fixed contacts to which the
There is no generation of gas during and after
incoming and outgoing phase wires are connected.
operation.
The fuse carrier is also of porcelain and holds the fuse
They can interrupt any fault current. The outstanding element (tinned copper wire) between its terminals.
feature of a VCB is that it can break any heavy fault The fuse carrier can be inserted in or taken out of the
current perfectly just before the contacts reach the base when desired.
definite open position.
When a fault occurs, the fuse element is blown out and
They require little maintenance and are quiet in the circuit is interrupted. The fuse carrier is taken out
operation. and the blown out fuse element is replaced by the new
They can successfully withstand lightning surges. one. The fuse carrier is then reinserted in the base to
They have low arc energy. restore the supply. This type of fuse has two
They have low inertia and hence require smaller power advantages. Firstly, the detachable fuse carrier permits
for control mechanism. the replacement of fuse element without any danger of
Applications : coming in contact with live parts. Secondly, the cost of
replacement is negligible.
For a country like India, where distances are quite large
and accessibility to remote areas difficult, the installation of Disadvantages :
such outdoor, maintenance free circuit breakers should There is a possibility of renewal by the fuse wire of
prove a definite advantage. Vacuum circuit breakers are wrong size or by improper material.
being employed for outdoor applications ranging from 22 This type of fuse has a low-breaking capacity and
kV to 66 kV. Even with limited rating of say 60 to 100 MVA, hence cannot be used in circuits of high fault level.
they are suitable for a majority of applications in rural The fuse element is subjected to deterioration due to
areas. oxidation through the continuous heating up of the
2.17 TYPES OF FUSES element. Therefore, after some time, the current rating
of the fuse is decreased
Fuse is the simplest current interrupting device for
protection against excessive currents. Since the invention i.e., the fuse operates at a lower current than originally
of first fuse by Edison, several improvements have been rated.
made and now-a-days, a variety of fuses are available. The protective capacity of such a fuse is uncertain as it
Some fuses also incorporate means for extinguishing the is affected by the ambient conditions.
arc that appears when the fuse element melts. In general, Accurate calibration of the fuse wire is not possible
fuses may be classified into : because fusing current very much depends upon the
(i) Low voltages fuses length of the fuse element. Semi-enclosed rewireable
(ii) High voltage fuses fuses are made upto 500 A rated current, but their
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.22) PRINCIPLES OF CIRCUIT BREAKERS
breaking capacity islow e.g., on 400 V service, the Heat produced by the arc may affect the associated
breaking capacity is about 4000 A. Therefore, the use switches.
of this type of fuses is limited to domestic and lighting 3. H.R.C. Fuse with Tripping Device :
loads. Sometime, H.R.C. cartridge fuse is provided with a
2. High-Rupturing Capacity (H.R.C.) Cartridge Fuse : tripping device. When the fuse blows out under fault
The primary objection of low and uncertain breaking conditions, the tripping device causes the circuit
capacity of semi-enclosed rewireable fuses is overcome breaker to operate. Fig. 2.26 shows the essential parts
in H.R.C. cartridge fuse. Fig. 2.25 shows the essential of a H.R.C. fuse with a tripping device. The body of the
parts of a typical H.R.C. cartridge fuse. It consists of a fuse is of ceramic material with a metallic cap rigidly
heat resisting ceramic body having metal end-caps to fixed at each end.
which is welded silver current-carrying element. The These are connected by a number of silver fuse
space within the body surrounding the element is elements. At one end is a plunger which under fault
completely packed with a filling powder. The filling conditions hits the tripping mechanism of the circuit
material may be chalk, plaster of paris, quartz or breaker and causes it to operate. The plunger is
marble dust and acts as an arc quenching and cooling electrically connected through a fusible link, chemical
medium. charge and a tungsten wire to the other end of the cap
as shown.
Fig. 2.25
Under normal load conditions, the fuse element is at a
temperature below its melting point. Therefore, it carries
the normal current without overheating. When a fault
occurs, the current increases and the fuse element melts
before the fault current reaches its first peak. The heat Fig. 2.26
produced in the process vapourises the melted silver When a fault occurs, the silver fuse elements are the
element. The chemical reaction between the silver vapour first to be blown out and then current is transferred to
and the filling powder results in the formation of a high the tungsten wire. The weak link in series with the
resistance substance which helps in quenching the arc. tungsten wire gets fused and causes the chemical
Advantages charge to be detonated. This forces the plunger
They are capable of clearing high as well as low fault outward to operate the circuit breaker. The travel of
currents. the plunger is so set that it is not ejected from the fuse
body under fault conditions.
They do not deteriorate with age.
Advantages : H.R.C. fuse with a tripping device has the
They have high speed of operation.
following advantages over a H.R.C. fuse without tripping
They provide reliable discrimination.
device :
They require no maintenance.
In case of a single phase fault on a three-phase system,
They are cheaper than other circuit interrupting the plunger operates the tripping mechanism of circuit
devices of equal breaking capacity. breaker to open all the three phases and thus prevents
They permit consistent performance. “single phasing”.
Disadvantages The effects of full short circuit current need not be
They have to be replaced after each operation. considered in the choice of circuit breaker. This permits
the use of a relatively inexpensive circuit breaker.
SWITCHGEAR AND PROTECTION (BATU ELECTRICAL) (2.23) PRINCIPLES OF CIRCUIT BREAKERS
but is affected also by the length, the state of surface and 2. Discuss the arc phenomenon in a circuit breaker.
the surroundings of the fuse. When the fuse element 3. Explain the various methods of arc extinction in a
attains steady temperature, circuit breaker.
Heat produced per sec = Heat lost per second by 4. Define and explain the following terms as applied to
convection, ration and conduction circuit breakers.
or I2R = Constant Effective surface area (i) Arc voltage
or I2 = constant d l (ii) Restriking voltage
where d = diameter of fuse element (iii) Recovery voltage
l = length of fuse element 5. Describe briefly the action of an oil circuit breaker.
I2 = constant d l How does oil help in arc extinction?
or I2 = constant d3 6. What are the important components common to
or I d
2 3
(i) most of circuit breakers? Discuss each component
Expression (i) is known as ordinary fuse law. briefly.
2.19.1 Difference Between a Fuse and Circuit Breaker 7. Write a short note on the rate of re-striking voltage
indicating its importance in the arc extinction.
It is worthwhile to indicate the salient differences between
a fuse and a circuit breaker in the tabular form. 8. Explain the difference between bulk oil circuit
breakers and low-oil circuit breakers.
Sr. Particular Fuse Circular Breaker
9. Discuss the constructional details and operation of a
No.
typical low-oil circuit breaker What are its relative
1. Function It performs both It performs interruption merits and demerits?
detection and function only. The 10. Discuss the principle of operation of an air-blast
interruption detection of fault is circuit breaker. What are the advantages and
functions. made by relay system. disadvantage of using air as the arc quenching
2. Operation Inherently Requires elaborate medium ?
completely equipment (i.e. relays) 11. Explain briefly the following types of air-blast circuit
automatic. for automatic action. breakers :
3. Breaking Small Very large. (i) Axial-blast type
capacity (ii) Cross-blast type
4. Operating time Very small Comparatively large 12. Write a short note on the rate of re-striking voltage
(0.002 sec or (0.1 to 0.2 sec) indicating its importance in the arc extinction.
so) 13. Discuss the phenomenon of
5. Replacement Requires No replacement after (i) Current chopping
replacement operation. (ii) Capacitive current breaking
after every 14. Write short notes on the following :
operation. (i) Resistance switching
EXERCISE (ii) Circuit breaker ratings
1. What is a circuit breaker? Describe its operating (iii) Circuit interruption problems
principle.