0% found this document useful (0 votes)
200 views36 pages

REM610 - Technical Presentation

The document discusses the REM 610 motor protection relay. It provides an introduction to the relay, describing its intended use for protecting motors and associated circuits. It also covers the relay's mechanical design, functionality, and mounting options.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
200 views36 pages

REM610 - Technical Presentation

The document discusses the REM 610 motor protection relay. It provides an introduction to the relay, describing its intended use for protecting motors and associated circuits. It also covers the relay's mechanical design, functionality, and mounting options.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 36

ABB Oy REM 610

Substation Automation Technical Presentation


„ Insert
image
here
© Company name - 1 -
12/3/2003
REM 610
Motor Protection Contents…

„ Introduction „ Setting and calculation tool


„ Mechanical design „ Required information

„ Functionality „ Outputs
„ Trip curve animation
„ Ordering
„ Connections
© Company name - 2 -
REM 610
Motor Protection Introduction

„ REM 610 is a protection relay intended for the


protection of motors against thermal overload.
„ REM 610 also protects the associated feeder circuit
and the motor drive.
„ REM 610 measures and analyses the phase currents
feeding the motor and the zero sequence current to
detect earth (ground) faults.
„ As an option REM 610 can monitor temperatures in
the motor stator (“case”) and bearings via RTDs or
thermistors.
„ Based on the information measured and analysed the
relay starts, generates alarms and eventually trips the
circuit breaker or contactor switch to prevent motor
damage.
© Company name - 3 -
REM 610
Motor Protection Introduction

„ Area of application
„ Medium.sized and large MV asynchronous (induction)
motors (motors started direct on line, 50 Hz or 60 Hz)
„ Back-up protection of or integrated in protection
schemes for synchronous motors
„ Circuit-breaker and contactor controlled drives
„ Feeder cables, power transformers and other requiring
thermal overload protection and functionality included in
the relay
© Company name - 4 -
REM 610
Motor Protection Introduction

„ Area of application cont.


„ Low-voltage motors, typical power range 500 kW - 4 MW
„ Drives for ventilation & fans, crushers, conveyors, pumps,
mills, etc. and applications in marine, offshore, mining and
other demanding environments
„ Due to large number of protection functions integrated, the
reliability protects the motor against damage
© Company name - 5 -
REM 610
Motor Protection Introduction

„ Common causes for motor damage and means of protection

Other protective
functions Thermal overload
protection

Continuous
self-testing
of the relay

Start-up supervision
and thermal
sensor (RTD) unit
© Company name - 6 -

Short-circuit and
earth-fault protection
REM 610
Motor Protection Mechanical design

„ Withdrawable mechanical design


„ Easy to install and handle
„ Automatic short-circuiting of CT secondaries
„ Communication maintained even when relay unit withdrawn
„ Mechanical coding for identification of plug-in unit
„ Height 4U (~177 mm)
„ Depth behind the panel only about 150 mm (100 mm possible!)
„ Easy mounting - no loose mounting accessories
„ Both compression type connection and ring-lug terminal connection
of CT secondary wires
„ IP 54 degree of protection by enclosure of the relay case when
flush-mounted.
© Company name - 7 -
REM 610
Motor Protection Mechanical design

„ Basic parts

Metal rear plate

Metal case

Plastic front plate


© Company name - 8 -
REM 610
Motor Protection Mechanical design

„ Withdrawable relay unit

Plug-in unit
© Company name - 9 -

Case unit
REM 610
Motor Protection Mechanical design

„ Front plate

2 x 16 character alphanumeric
display (LCD)

3 pre-assigned LEDs

6-button keypad
Local communication port,
wireless or via cable

8 programmable LEDs
© Company name - 10 -
REM 610
Motor Protection Mechanical design

„ Inputs and outputs

Binary inputs and outputs


RTD/Thermistor inputs
Power supply
etc.
CT secondary current
inputs prepared for ring-
lug and scew-compression
type wire connection.

Remote communication card


© Company name - 11 -
REM 610
Motor Protection Mechanical design

„ The CT secondaries are automatically short-circuited when the


relay unit is withdrawn from the case
„ No need for separate short-circuiting arrangements
© Company name - 12 -
REM 610
Motor Protection Mechanical design

„ REM 610 product information under the handle


„ Easy access of type specifications and ratings
© Company name - 13 -
REM 610
Motor Protection Mechanical design

„ Battery backup of the real-time clock (RTC) and memory circuits,


disturbance recorder (DR), etc.
„ Automatically supervised and easy to change
© Company name - 14 -
REM 610
Motor Protection Mechanical design

„ Flush, semi-flush or surface mounting using suitable mounting


accessories
© Company name - 15 -

50 mm raising frame for semi-flush mounting


REM 610
Motor Protection Mechanical design

„ Mounting alternatives in COMBIFLEX equipment frames

2. Left side x 2 + 12c rails

1. Left side + right side+18c rails


© Company name - 16 -

3. Right side x 2 + 24c rails


REM 610
Motor Protection Mechanical design

„ Flush mounting

Cut-out on cubicle front

19” mounting panel for one or two relays


161,5±1 mm

1 mm
165,5±
© Company name - 17 -
REM 610
Motor Protection Functionality

„ ABB motor protection from basic to high range solutions

Price

REM 543

REM 610
© Company name - 18 -

SPAM150C

Functionality
REM 610
Motor Protection Functionality

„ General
„ 50/60 Hz rated frequency
„ Real-time clock (chip) for time stamps
„ Non-volatile memory for settings (EEPROM)
„ Non-volatile memory for recorded fault values (battery back-up)
„ CT inputs for screw-compression or ring-lug type wire connection
„ Signal connectors for screw-compression type wire connection
„ Withdrawable design with automatic short-circuiting of CT secondaries
„ Five fault recordings with time stamps, 100 event codes for SCADA
„ Disturbance recorder, 5 seconds, one recording
„ Self-supervision of hardware and software
© Company name - 19 -
REM 610
Motor Protection Functionality

„ Inputs
„ 4 analog inputs for current measurement (IL1, IL2, IL3 and I0)
„ 6 RTD inputs in two groups available with optional RTD module
„ RTD types can be mixed in the same module, e.g. Pt-100 and Ni-120
„ 2 thermistor (PTC) inputs can be used instead of RTDs
„ RTDs and PTCs can be mixed, e.g. up to 4 RTDs + 2 PTCs
„ 2 binary inputs (+ 3 additional in the optional RTD module)

„ Output contacts
„ 3 heavy-duty contacts capable of operating a circuit-breaker
„ 2 freely assignable signalling contacts
„ 1 pre-assigned signalling contact for IRF alarm
© Company name - 20 -
REM 610
Motor Protection Functionality

„ LCD, 2 x 16 characters
„ Built-in support for 7 languages: English, Finnish, Swedish, German,
Spanish, French, Italian
„ IEC symbols / ANSI codes selectable
„ Fault indications
„ 5 fault recordings with time stamp
„ Measurements and displays
„ Currents and temperatures
„ Calculated motor thermal capacity used and cooling time required before
next motor start, etc.
„ Historical data since commissioning, running hours, etc.
„ Settings in units of the motor full load current (FLC), 2 groups
„ Configurations such as protocol settings, etc.
© Company name - 21 -

„ Product information, identification, etc.


REM 610
Motor Protection Functionality

„ 3 dedicated and 8 user-assignable LEDs + 1 dedicated LED


indicating communication
„ Fast fault location and clearance (20 signals can be freely
associated with 8 user-assignable LEDs), BI status, Restart
Inhibit, Alarms, Trips…
„ 3 dedicated LEDs for Ready, Start and Trip indication
„ 1 dedicated LED for indicating local communication activity
„ Local communication port
„ 6 push buttons
„ Arrow keys, Enter/Edit, Cancel/Clear
© Company name - 22 -
REM 610
Motor Protection Functionality

„ Self-supervision and alarms


„ Continuous testing of memory circuits, RAM, ROM, EEPROM
„ Supervision of CT secondary circuits, MPX, ADC
„ Watchdog functions for monitoring CPU operation and program
excecution
„ Internal trip path continuity check
„ Internal power supply voltage drop-out check

„ External Trip Circuit Supervision (TCS)


„ Temperature sensor (RTD) circuit open or short-circuited
„ RTD card alarm
„ Communication card alarm
© Company name - 23 -

„ Low memory backup battery alarm


„ Overtemperature alarm of internal power supply
REM 610
Motor Protection Functionality

„ Protection functions
„ Thermal overload protection (49)
„ Temperature supervision based on RTDs (49/38)
„ Motor startup supervision (48)
„ Cumulative motor start-up time counter (66)
„ Short-circuit protection (50)
„ Overcurrent protection (51)
„ Earth-fault protection (50N/51N)
„ Phase unbalance / phase reversal protection (46)
„ Undercurrent (loss of load) protection (37)
„ Circuit-breaker failure protection (62BF)
„ Electrically latched lockout relay (86)
© Company name - 24 -

„ Emergency restart
REM 610
Motor Protection Functionality

„ Measurements & Display


„ Phase & residual current (RMS)
„ Negative phase sequence current
„ Display of measured values in primary units
„ Motor stress during start-up
„ Temperature via RTDs
© Company name - 25 -
REM 610
Motor Protection Functionality

„ Non-volatile memory
„ As many as 100 event codes with time stamps (RAM, battery backup)
„ Relay setting values (EEPROM)
„ Disturbance recorder data (RAM, battery backup)
„ The five most recent events with time stamps and recorded data (RAM,
battery backup)
„ Number of starts of each protection stage (RAM, battery backup)
„ Operation indication messages and LEDs showing the status at the
moment of a power failure (RAM, battery backup)
„ Maximum fault currents (RAM, battery backup)
„ Data to be stored in non-volatile memory user-selectable
© Company name - 26 -
REM 610
Motor Protection Functionality

„ Communication Protocols
„ SPA bus communication (via front and rear port )
„ IEC 60870-103-5 communication (via rear port only)
„ Modbus communication (via rear port only)
© Company name - 27 -
REM 610
Motor Protection Ordering

„ Ordering key:
REM610A55HCMP

Communication: P = plastic fibre, R = RS - 485,


N = none

RTD / thermistor card: M = included, N = none


Terminals: C = compression type
Power supply: H = 100-240 Vac / 110-250 Vac
Earth-fault current input: 5 = 5 A, 1 = 1 A
Phase current inputs: 5 = 5 A, 1 = 1 A
Revision
© Company name - 28 -
REM 610
Motor Protection Connections
© Company name - 29 -
REM 610
Motor Protection Setting calculation tool
© Company name - 30 -
REM 610
Motor Protection Required information

Motor settings
„ Motor rated current, starting
current and starting time
„ CT ratings
„ Ambient temperature in
degrees Celsius or
Fahrenheit
© Company name - 31 -
REM 610
Motor Protection Required information

Relay settings
„ Number of hot/cold starts allowed
„ Type of motor: p and kc settings
„ Protection principles: I>> doubling, use of I2 protection, etc
„ Protection requirements: I>> operation time, E/F sensitivity, etc
© Company name - 32 -
REM 610
Motor Protection Outputs

„ The software guides the user through the settings and


executes the calculations required
Î Faster and easier calculation and selection of settings
© Company name - 33 -
REM 610
Motor Protection Outputs

„ The software allows the thermal behaviour of the motor


to be simulated
Î Verification of settings
Î Better understanding of protection and settings
© Company name - 34 -
REM 610
Motor Protection Outputs

„ Graphical visualization of trip


curves
„ Hardcopy report including
settings and graphs
© Company name - 35 -
REM 610
Motor Protection Trip curve animation

„ On multimedia CD
© Company name - 36 -