REM610 - Technical Presentation
REM610 - Technical Presentation
Functionality Outputs
Trip curve animation
Ordering
Connections
© Company name - 2 -
REM 610
Motor Protection Introduction
Area of application
Medium.sized and large MV asynchronous (induction)
motors (motors started direct on line, 50 Hz or 60 Hz)
Back-up protection of or integrated in protection
schemes for synchronous motors
Circuit-breaker and contactor controlled drives
Feeder cables, power transformers and other requiring
thermal overload protection and functionality included in
the relay
© Company name - 4 -
REM 610
Motor Protection Introduction
Other protective
functions Thermal overload
protection
Continuous
self-testing
of the relay
Start-up supervision
and thermal
sensor (RTD) unit
© Company name - 6 -
Short-circuit and
earth-fault protection
REM 610
Motor Protection Mechanical design
Basic parts
Metal case
Plug-in unit
© Company name - 9 -
Case unit
REM 610
Motor Protection Mechanical design
Front plate
2 x 16 character alphanumeric
display (LCD)
3 pre-assigned LEDs
6-button keypad
Local communication port,
wireless or via cable
8 programmable LEDs
© Company name - 10 -
REM 610
Motor Protection Mechanical design
Flush mounting
1 mm
165,5±
© Company name - 17 -
REM 610
Motor Protection Functionality
Price
REM 543
REM 610
© Company name - 18 -
SPAM150C
Functionality
REM 610
Motor Protection Functionality
General
50/60 Hz rated frequency
Real-time clock (chip) for time stamps
Non-volatile memory for settings (EEPROM)
Non-volatile memory for recorded fault values (battery back-up)
CT inputs for screw-compression or ring-lug type wire connection
Signal connectors for screw-compression type wire connection
Withdrawable design with automatic short-circuiting of CT secondaries
Five fault recordings with time stamps, 100 event codes for SCADA
Disturbance recorder, 5 seconds, one recording
Self-supervision of hardware and software
© Company name - 19 -
REM 610
Motor Protection Functionality
Inputs
4 analog inputs for current measurement (IL1, IL2, IL3 and I0)
6 RTD inputs in two groups available with optional RTD module
RTD types can be mixed in the same module, e.g. Pt-100 and Ni-120
2 thermistor (PTC) inputs can be used instead of RTDs
RTDs and PTCs can be mixed, e.g. up to 4 RTDs + 2 PTCs
2 binary inputs (+ 3 additional in the optional RTD module)
Output contacts
3 heavy-duty contacts capable of operating a circuit-breaker
2 freely assignable signalling contacts
1 pre-assigned signalling contact for IRF alarm
© Company name - 20 -
REM 610
Motor Protection Functionality
LCD, 2 x 16 characters
Built-in support for 7 languages: English, Finnish, Swedish, German,
Spanish, French, Italian
IEC symbols / ANSI codes selectable
Fault indications
5 fault recordings with time stamp
Measurements and displays
Currents and temperatures
Calculated motor thermal capacity used and cooling time required before
next motor start, etc.
Historical data since commissioning, running hours, etc.
Settings in units of the motor full load current (FLC), 2 groups
Configurations such as protocol settings, etc.
© Company name - 21 -
Protection functions
Thermal overload protection (49)
Temperature supervision based on RTDs (49/38)
Motor startup supervision (48)
Cumulative motor start-up time counter (66)
Short-circuit protection (50)
Overcurrent protection (51)
Earth-fault protection (50N/51N)
Phase unbalance / phase reversal protection (46)
Undercurrent (loss of load) protection (37)
Circuit-breaker failure protection (62BF)
Electrically latched lockout relay (86)
© Company name - 24 -
Emergency restart
REM 610
Motor Protection Functionality
Non-volatile memory
As many as 100 event codes with time stamps (RAM, battery backup)
Relay setting values (EEPROM)
Disturbance recorder data (RAM, battery backup)
The five most recent events with time stamps and recorded data (RAM,
battery backup)
Number of starts of each protection stage (RAM, battery backup)
Operation indication messages and LEDs showing the status at the
moment of a power failure (RAM, battery backup)
Maximum fault currents (RAM, battery backup)
Data to be stored in non-volatile memory user-selectable
© Company name - 26 -
REM 610
Motor Protection Functionality
Communication Protocols
SPA bus communication (via front and rear port )
IEC 60870-103-5 communication (via rear port only)
Modbus communication (via rear port only)
© Company name - 27 -
REM 610
Motor Protection Ordering
Ordering key:
REM610A55HCMP
Motor settings
Motor rated current, starting
current and starting time
CT ratings
Ambient temperature in
degrees Celsius or
Fahrenheit
© Company name - 31 -
REM 610
Motor Protection Required information
Relay settings
Number of hot/cold starts allowed
Type of motor: p and kc settings
Protection principles: I>> doubling, use of I2 protection, etc
Protection requirements: I>> operation time, E/F sensitivity, etc
© Company name - 32 -
REM 610
Motor Protection Outputs
On multimedia CD
© Company name - 36 -