100% found this document useful (1 vote)
1K views

Midea Ac Error Code

The document describes various error codes displayed on a digital display output for a heating or cooling system. The error codes indicate issues with temperature or pressure sensors. The troubleshooting procedure involves checking sensor connections, replacing sensors if failed, and replacing the main circuit board if needed.

Uploaded by

Nabil Ali
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
1K views

Midea Ac Error Code

The document describes various error codes displayed on a digital display output for a heating or cooling system. The error codes indicate issues with temperature or pressure sensors. The troubleshooting procedure involves checking sensor connections, replacing sensors if failed, and replacing the main circuit board if needed.

Uploaded by

Nabil Ali
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

E3, E4, E5, E7, Eb, Ed, EF, EP, EU, Fb, Fd Troubleshooting

Digital display output


Description
▪ E3 indicates a combined water outlet temperature sensor error.
▪ E4 indicates a water outlet temperature sensor error.
▪ E5 indicates an air side heat exchanger refrigerant outlet temperature sensor error.
▪ E7 indicates an outdoor ambient temperature sensor error.
▪ 1Eb indicates a water side heat exchanger anti-freezing temperature sensor 1 error.
▪ 2Eb indicates a water side heat exchanger anti-freezing temperature sensor 2error.
▪ 1Ed indicates a discharge pipe temperature sensor 1 error.
▪ 2Ed indicates a discharge pipe temperature sensor 2 error.
▪ EF indicates a water inlet temperature sensor error.
▪ EP indicates a discharge pipe temperature sensor failure alarm.
▪ EU indicates an air side heat exchanger refrigerant total outlet temperature sensor error.
▪ Fb indicates a pressure sensor error.
▪ Fd indicates an air suction temperature sensor error.
▪ All stop running.
▪ Error code is displayed on main PCB and user interface.

Possible causes
▪ Temperature sensor or pressure sensor not connected properly or has malfunctioned.
▪ Damaged main PCB.

Procedure

E3 / E4 / E5 / E7 / Eb / Ed / EF / EP / EU /
Fb / Fd

Temperature sensor or pressure sensor Yes Ensure the sensor is connected properly
connection on main PCB is loose
No

Temperature or pressure sensor has Yes Replace the sensor


short-circuited or failed2
No

Replace main PCB