Fire Fighting EC
Fire Fighting EC
COURSE
NFPA 15 Standard for Water Spray Fixed Systems for Fire Protection
NFPA 16 Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray
NFPA 25 Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems
NFPA 415 Standard on Airport Terminal Buildings, Fueling Ramp Drainage and Loading Walkways
NFPA PUBLICATIONS
DEFINITIONS • Code
A standard that is an extensive compilation of provisions co
vering broad subject matter or that is suitable for adoption i
nto law independently of other codes and standards.
• Guide
A document that is advisory or informative in nature and th
at contains only nonmandatory provisions.
• Standard
A document, the main text of which contains only
mandatory provisins using the word “shall” to ind
icate requirements and which is in a form generall
y suitable for mandatory reference by another sta
NFPA OFFICIAL ndard code or for adoption into law.
DEFINITIONS • Shall
Indicates a mandatory requirement.
• Should
Indicates a recommendation or that which is advi
sed but not required.
FIRE PROTECTION SYSTEMS
FIRE PROTECTION COMPONENT
• FIRE RATED WALLS , WINDOWS AND DOORS …ETC
• FIRE DETECTION AND ALARM SYSTEM
• FIRE FIGHTING SYSTEM
• FIRE FIGHTERS
CLASSIFYING FIRES
FIRE
TRIANGLE
FIRE FIGHTING SYSTEMS
FIRE FIGHTING SYSTEMS
AUTOMATIC MANUAL
SPRINKLER FIRE
CLEAN AGENT FIRE CABINET
SYSTEM EXTINGUISHER
SIAMESE
CO2
CONNECTION
PUMP ROOM
WATER MIST PUMP ROOM
PUMP
CLASSIFICATIONS
PUMP TYPES
H-SPLIT CASE ( DIESEL DRIVEN)
H-SPLIT CASE ( ELECTRIC DRIVEN)
VERTICAL TURBINE (DIESEL DRIVEN)
VERTICAL INLINE (ELECTRIC DRIVEN)
MULTISTAGE – MULTI PORT
CH-HEAD
الشروط الواجب توافرها في مضخات الحريق -:
.1ان تعطى ال Q , Hالمرادان .
.2يجب عند اختيارها ﻻبد ان تكون في الجزء اﻷوسط للمنحنى لتعطى اكبر كفاءه .
.3عند زياده ال Qبمقدار % 150ان ﻻ يقل ال Hعن % 65من قيمته اﻷصلية .
Shut down pressure .4ﻻ يزيد عن % 140
.5ان تكون المضخة خضعت لﻼختبار FM & UL.
ZONE CONTROL STATION
DIESEL & ELECTRICAL CONTROLLER
DIESEL
PUMP
COOLING
LINE
Steel
Concrete
TANK
MATERIAL Fiberglass
Beverage Manufacturing
Electronic Plants
Libraries – Large Stack Room Area
Metal Working
Chemical Plants
Distillers
ORDINARY Exterior Loading Docks
HAZARD Machine Shops
Agricultural Facilities
(GROUP 2) Printing & Publishing
Plastic Fabrication
Textile Manufacturing
Wood Machining
Mercantile (Malls – markets….)
Aircraft Hangers (except as governed by NFPA 409)
2- Temperature rating
SPRINKLERS 3- K-factor
CLASSIFICATION
4- Orientation
SERVICE
Corrosion
CONDITIONS resistant
sprinkler
Institutional
sprinkler
SK Rack
storage
sprinkler
Dry sprinkler
Corrosion
Resistant
Sprinkler
Rack
Storage
Sprinkler
Decorative Sprinkler
Institutional sprinkler
1- WET SYSTEM 2- DRY SYSTEM
3- PREACTION 4- DELUGE
SYSTEM SYSTEM
FIRE SPRINKLER
SYSTEM TYPES 5- COMBINED
6- ANTI-FREEZE
SYSTEM
7- WATER 8- COMMERCIAL
CURTAIN KITCHENS
WET PIPE SYSTEM
WET PIPE SYSTEM
THE MOST COMMON TYPE OF PIPING CONTAINS WATER AT ALL TIME GENERALLY USED WHEREVER THERE
SPRINKLER SYSTEMS IN USE NOW SO THAT WATER DISCHARGES IS NO DANGER OF THE WATER IN THE
DAYS IMMEDIATELY FROM SPRINKLER PIPES FREEZING AND NO SPECIAL
WHEN IT ACTIVATED CONDITIONS REQUIRING ONE OF
OTHER SYSTEMS.
ACV & PRV IN WET SYSTEM
DRY PIPE SYSTEM
DRY PIPE SYSTEM
A sprinkler system employing automatic Generally used wherever there is danger of the
sprinklers attached to a piping system contains water in the pipes freezing where
air or nitrogen under pressure , when fire temperature reaches below 40 0F (4.4 0C)
occur the sprinkler open making air release so
the pressure of water can open the dry valve
and out through opened sprinklers
DRY PIPE VALVE
• Dry valve shall be maintained at
temperature ≥ 4 0C
SYSTEM PIPE SIZE
WATER
DELIVERY
Gridded Dry Pipe System Shall not be Installed
PREACTION
SYSTEM
PREACTION
SYSTEM
Installation Installation
Requirements for Requirements for Installation
Standard Pendent, Extended Coverage Requirements for
Upright, and Sidewall Upright, Pendent, Residential Sprinklers
Spray Sprinklers Sidewall Spray Sprinkler
Installation Installation
Installation
Requirements for Requirements for Early
Requirements for
Control Mode Specific Suppression Fast
Special Sprinklers
Application Sprinklers Response Sprinklers
A- Installation
Requirements for Standard • In any case, the maximum area of coverage of a
Pendent and Upright Spray sprinkler shall not exceed 225 ft2 (20 m2).
Sprinklers
• CMSA- Control Mode Specific Application
• ESFR- Early Suppression Fast Response
Maximum Distance Between Sprinklers
The maximum distance permitted between sprinklers shall comply with Table 10.2.4.2.1
NOTE : Sprinklers shall be permitted to be placed less than 6 ft (1.8 m) REFER TO SEC 10.2.5.4.2 AND SEC 10.2.5.4.3 NFPA 13 2019 EDITION
The distance from sprinklers to walls shall not exceed one-half of the allowable distance between sprinklers.
Sprinklers shall be permitted to be located not more than 9 ft (2.7 m) from any single wall.
NOTE: THESE RULES SHALL NOT APPLY IN SPECIAL CASES REFER TO SEC 10.2.5.2.2 2019 EDITION
Small Room
𝐴 ≤ 74,3𝑚
𝐿𝑖𝑔ℎ𝑡 𝐻𝑎𝑧𝑎𝑟𝑑
𝑊 ≤ 2.4 𝑚
Unobstructed Construction
WALL
SPRINKLER
Sidewall sprinklers shall only be
installed as follows:
4- AT THE TOP AND BOTTOM OF 5- FOR THE PROTECTION OF STEEL 6- UNDER OBSTRUCTIONS THAT
ELEVATOR HOISTWAYS BUILDING COLUMNS REQUIRE SPRINKLERS
EXCEPT THIS REFER TO NFPA
13 SEC 10.3.4.4 2019ed
𝒅
𝒔
No.ZCV
سرعة المياه داخل المواسير:
• SINGLE INTERLOCK
• NON-INTERLOCK
• DOUBLE INTERLOCK
Class I Standpipe Systems
Classification
of Standpipe Class II Standpipe Systems
Systems
• IN LOW-RISE BUILDINGS
System shall be permitted to be automatic dry, automatic wet, semiautomatic dry, manual dry, or
manual wet
• IN HIGH-RISE BUILDINGS
System shall be automatic wet or semiautomatic.
• Manual standpipes shall be permitted in open parking garages where the highest floor is located
not more than 150 ft (45,7 mm) above the lowest level of fire department vehicle access.
• NOTE : Class I standpipe systems shall be wet systems except where piping is subject to freezing.
Class II Standpipe Systems
TRAVEL DISTANCE 61m for SK building 39.7m for 1.5in 61m for SK building
39.7m for non-SK 36.6m for 1in 39.7m for non-SK
• IF BUILDING SPRINKLERED
1000 GPM AS FOLLOWING
500 FOR 1st STANDPIPE + 250 FOR 2nd STANDPIPE + 250 FOR 3rd STANDPIPE
NOTE : For class II hose cabinet flow 100gpm and no additional flow for additional standpipe.
BUILDING > 80000 Ft2 (7342 m2)
• IF BUILDING SPRINKLERED
1000 GPM AS FOLLOWING
500 FOR 1st STANDPIPE + 500 FOR 2nd STANDPIPE
• IF BUILDING NON SPRINKLERED
1250 GPM AS FOLLOWING
500 FOR 1st STANDPIPE + 500 FOR 2nd STANDPIPE + 250 FOR 3rd STANDPIPE
NOTE : THIS FOR CLASS I & CLASS III
NOTE : For class II hose cabinet flow 100gpm and no additional flow for additional standpipe.
COMBINED SYSTEM
FIRE DEPARTMENT CONNECTION
The fire department connection shall be installed as follows:
• Automatic wet and manual wet standpipe systems.
On the system side of the system control valve, check valve, or any pump
• Automatic dry standpipe systems.
On the system side of the control valve and check valve and the supply side of the dry pipe valve
• Semiautomatic dry standpipe systems.
On the system side of the deluge valve
• Manual dry standpipe systems.
Directly connected to system piping with a check valve in the piping
NOTE: Fire department connections shall not be connected on the suction side of fire pumps.
FIRE DEPARTMENT CONNECTION
FIRE DEPARTMENT CONNECTION
1- WATER EXTINGUISHERS
Have a capacity of 2.5 gallons (9.5 liters) and pressurized with
100 psi (690 kilopascals) of compressed air and are suitable for
use on class A fires only
FIRE EXTINGUISHERS TYPES
FIRE EXTINGUISHERS TYPES
5- HALON EXTINGUISHERS
contain a halogenated hydrocarbon agent
forced into a liquid state by pressure. The
most common halons for portable
extinguishers are Halon 1211
(bromochlorodifluoromethane) and Halon
1301 (bromotrifluoromethane). This type
of extinguisher is available in several sizes
from 1.5 to 22 pounds (0.68 to 9.9 kilos).
FIRE EXTINGUISHERS TYPES
6- FE-36
FE-36 is another halon substitute agent.
Extinguishers using FE-36 are available
in sizes ranging from 4.75 to 14 pounds
(2.2 to 6.4 kilos).
FIRE EXTINGUISHERS
TYPES
• In no case shall the clearance between WEIGHT > 18.14 kg not more than 3.5 ft (1.07 m)
the bottom of the hand portable fire (EXCEPT WHEEL TYPE)
extinguisher and the floor be less than
4 in. (102 mm).
NOTE: Distance measured from the top of the fire
extinguisher to the floor.
and Placement for • Divide the floor area by the maximum area to be
protected per extinguisher in accordance with Table
Class A Hazards E.3.5
• Determine the fewest number of extinguishers that
will satisfy the 75 ft (22.9 m) travel distance rule.
Installations for Class B Hazards
• Fire extinguishers or extinguishing agents (media) shall be located not more than 75 ft (22.9 m) of
travel distance from the Class D hazard
• NOTE : In This Case THE Use of the wrong fire extinguisher can instantly increase or spread the fire
Installations for Class K Hazards
• Maximum travel distance shall not exceed 30 ft (9.1 m) from the hazard to the
extinguishers.
• All solid fuel cooking appliances (whether or not under a hood) with fire boxes of 5 ft3
(0.14 m3) volume or less shall have at least a listed 2-A rated water-type fire extinguisher
or a 1.6 gal (6 L) wet chemical fire extinguisher that is listed for Class K fires.
ADDITIONAL INFORMATION
FLOW CHART
Characteristics
of
Extinguishers
Characteristics
of
Extinguishers
Internal Maintenance and
Hydrostatic Testing of Fire Extinguishers
FIRE FIGHTING SYSTEMS
GAS
SYSTEMS
CLEAN
AEROSOL CO2
AGENT
Hand Hose Line System
• Low-pressure Cylinders
Low-pressure storage containers shall be
designed to maintain the carbon dioxide
supply at a nominal pressure of 300 psi
(2068 kPa) corresponding to a temperature
of approximately 0°F (−18°C).
• High-Pressure Cylinders
High-pressure systems utilize carbon
dioxide stored in cylinders at an ambient
temperature between -18 °C (0 °F ) and 54
°C (130 °F ) and the cylinder pressure is
approximately 58.6 bar (850 psi) absolute.
Discharge Nozzles
• TEMPERATURE VARIATION
LEAKAGE FROM OPENING
TEMPERATURE VARIATION
A.Removing the fuel (very unlikely), but if the fire runs out of fuel, it
will stop
B.Removing the heat
Water (fire brigade, sprinkler systems, water mist systems*)
Chemical agents** (FM-200, Nove 1230)
C.Reducing the oxygen level
CO2 systems
Inert gas systems (Inergen , IG-55, Argon etc.)
D.A combination of B. and C.
FM-200 Properties
Chemical Formula: CF3CHFCF3
-16.4 °C
Boiling Point @ 1 atm:
1.407 kg/l
Liquid Density @ 20°C:
FM200 EXTINGUISHING MECHANISM
• The present understanding of the functioning of FM-200 is that 80% of its fire
fighting effectiveness is achieved through heat absorption and 20% through direct
chemical means (action of the fluorine radical on the chain reaction of a flame).
Agent (FM-200)
Agent storage
Agent Delivery System
Actuation System
Accessories
CONTAINERS
Container Valve
DETECTORS &
ACTUATORS
• ELECTRIC
• PENUMATIC
• MANUAL
Valve Outlet
Connection
• Flexible discharge hose
• Union adaptor
Manifolds
Discharge Nozzles
• Material
• aluminium as standard
• brass or stainless steel optional
• LIQUID LEVEL INDICATOR
• TIME DELAY DEVICES
• DIRT TRAP
• HANGER AND SUPPORTS
SYSTEM DESIGN
AGENT CHEMISTRY TRADE NAME
DESIGNATION
HFC-227ea CF3CHFCF3 FM-200
CLEAN
IG-541 Nitrogen (52%) N2
Argon (40%) Ar INERGEN
Carbon dioxide (8%) CO2
AGENTS INERT
IG-55 Nitrogen (50%) N2 ARGONITE
GASES Argon (50%) Ar PROINERT
IG-01 Ar Argon
IG-100 N2 Nitrogen
FK-5-1-12 CF3CF2C(O)CF(CF3)2 NOVEC 1230
SYSTEM
ARRANGMENT
• SINGLE SYSTEM
• Modularized System
• Manifolded System
PROTECTED • SMALL AREA
No. of nozzles = clean agent flow rate / flow rate per nozzle
USING FLOODING FACTOR
V C
W ( )
S 100 C
95%
CLASS A OR C SURFACE FIRE
120 SECONDS
Container Selection
DISCHARGE NOZZLES
Pipe shall be of material having The internal pressure shall not be
Network
Design The normal charging pressure in
the agent container at 70°F (21°C)
Eighty percent of the maximum
pressure in the agent container at
a maximum storage temperature
of not less than 130°F (55°C)
Minimum Design Working Pressure for Halocarbon Clean Agent System Piping
Minimum Design Working Pressure for Inert Gas Clean Agent System Piping
FM-200
FLOW RATE
NETWORK
ARRANGMENT
NETWORK
ARRANGMENT
VENTING
AREA