This document provides technical specifications for a 1600 kVA 3 phase 50 Hz transformer, including its rated power, voltages, currents, insulation class, temperature rises, and testing procedures.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views4 pages

1600STC223800DDSL - BOX Type1

This document provides technical specifications for a 1600 kVA 3 phase 50 Hz transformer, including its rated power, voltages, currents, insulation class, temperature rises, and testing procedures.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

THAI PATANAKIT

TRANSFORMER

TRANSFORMER SPECIFICATION
1600 kVA 3 Ph 50 Hz
22000 - 800 V
OPEN TYPE WITH CONSERVATOR

Thaipatanakit Transformer Co.,Ltd.


23/1 Mu 7, Soi Wat Salut , Bangna-Trad Rd. , Bangkaew , Bangphli , Samutprakarn , Thailand 10540

E-mail : [email protected]
www.thaipatanakit.co.th
DRAWING No. 1600STC223800DDSL REV. 0 A4 PAGE 1/4
THAI PATANAKIT
TRANSFORMER
TRANSFORMER TECHNICAL DATA
Rated power kVA 1600
Type of transformer - Oil immersed ( Open type with conservator )
Phase - 3
Frequency Hz 50
Rated primary voltage & current V&A 22000 & 41.99
Rated secondary voltage & current V&A 800 & 1154.70
Connection symbol - Dd0
Standard - IEC 60076 , TIS 384-2543
Cooling system - ONAN
Class of insulation - Class A
Primary tapping - Off-load tap changer
Percent of rated voltage of each tapping % ± 2x2.5 %
No load current & Tolerance %&% 0.7 & +30
Short-circuit impedance at 75 °C & Tolerance %&% 6.0 & ±10
No load loss & Tolerance W&% 2300 & +15
Load loss at 75 °C & Tolerance W&% 19800 & +15
Total loss at 75 °C & Tolerance W&% 22100 & +10
Efficiency at 75 °C
25% of rated power and P.F. = 1 % 99.12
50% of rated power and P.F. = 1 % 99.10
75% of rated power and P.F. = 1 % 98.89
100% of rated power and P.F. = 1 % 98.64
Voltage regulation at P.F. = 0.8 % 4.59
Voltage regulation at P.F. = 0.9 % 3.79
Voltage regulation at P.F. = 1.0 % 1.41
Ambient temperature °C 40
Average temperature rise of winding K 65
Average temperature rise of top oil K 60
Winding Primary Secondary
Material copper copper
Full wave impulse withstand voltage ( BIL ) kV peak 125 -
Power frequency test voltage , 1 minute kV r.m.s. 50 3
Bushings Primary Secondary
Applied standard DIN 42531 DIN 42530
Full wave impulse withstand voltage ( BIL ) kV peak 125 30
Power frequency test voltage , 1 minute kV r.m.s. 50 3
Rated current A 250 2000
Stud thread size , Metric mm. 12 42
DRAWING No. 1600STC223800DDSL REV. 0 A4 PAGE 2/4
THAI PATANAKIT
TRANSFORMER
TRANSFORMER TECHNICAL DATA
Rated power kVA 1600
Terminal arrangement Primary Secondary
Terminal conductor sq.mm. 35-95 185-400
Diameter range mm. 7.5-12.6 15.9-25.6
Number of circuit - 1 4
Transformer oil grade IEC 60296
Type of oil - Mineral oil ( PCB content free )
Oil dielectric breakdown ( ASTM D 877 ) kV ≥ 30
Insulation resistance test by Pri. - Sec. Pri. - E. Sec. - E.
2500 Vdc Megger M ohm ≥ 1000 ≥ 1000 ≥ 1000
Noise level dB ≤ 56
Colour of tank - Grey

Accessories Routine test


HV & LV Bushing with terminal connectors. Measurement of voltage ratio and check of phase-
Bird guard cap (bushing cover). displacement.
Arcing horns. Insulation resistance test.
Tap changer. Measurement of winding resistance.
Thermometer pocket. Separated source voltage withstand test.
Nameplate with connection diagram. Induce overvoltage withstand test.
Oil drain , filter press lower filter valve. Measurement of no-load loss and exciting current.
Earthing terminal. Measurement of short circuit impedance and-
lifting eyes on the cover. load loss.
lifting lugs. Oil dielectric strength test.
Dehydrating breather filled with silica gel.
Oil level gauge.
Thermometer indicator
Pressure relief device.
Buchholz relay.
Other …CABLE BOX TYPE 1…………..……

DRAWING No. 1600STC223800DDSL REV. 0 A4 PAGE 3/4


9 18 17 2 3 16 15 19 10 5

14

1 13
H

11

7 4 6
12

c b a
w

C B A

บริษัท ไทยพัฒนกิจ หม้อแปลงไฟฟ้า จํากัด