DSE E400 Data Sheet US
DSE E400 Data Sheet US
DSEE400 SPECIFICATIONS
DC SUPPLY
ENGINE CONTROLLER CONTINUOUS VOTLAGE RATING
8 V to 32 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 100 ms, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is achieved
without the need for internal batteries.
INPUTS
DIGITAL INPUTS A to D
Configurable as:
Positive switching
Negative switching
ANALOGUE INPUT A to G
Configurable as:
Negative switching digital input
0 V to 10 V
4 mA to 20 mA
Resistive
OUTPUTS
KEY FEATURES • Configurable DC outputs (2) KEY BENEFITS DC OUTPUT A (FUEL) & B (START)
• Sensor alarm levels adjustable in • Configurable PWM/PWMi • 132 x 64 pixel ratio display for clarity 10 A DC for 10 seconds
outputs (2) 5 A DC continuous at supply voltage
front panel editor • Real-time clock provides accurate
• PLC hour timer • Configurable analogue output (1) event logging DC OUTPUTS C & D
• Maintenance alarms (10) • Configurable timers and alarms • Set maintenance periods can be 2 A DC at supply voltage
• Auto run inhibit feature • 3 configurable maintenance alarms configured to maintain optimum
PWMi OUTPUTS E & F
• Configurable CAN • Multiple date and time engine engine performance 4 A at supply voltage
• Built-in governor control scheduler • Can be integrated into remote 20 Hz to 250 Hz
• Automatic speed control • Configurable event log (250) monitoring systems
PULSE PICK-UP
• Fill, empty, maintain fill and maintain • CAN engine support • Licence-free PC software VOLTAGE RANGE
empty control • CAN, magnetic pick-up or • Uses DSE Configuration Suite PC 0.5 V to 60 V RMS
• Manual speed control via push tachometer speed sensing Software for simplified configuration Fully isolated
buttons, digital input or analogue • Fuel usage monitor and low fuel • IP67 rating offers increased
FREQUENCY RANGE
input alarms resistance to water ingress 5 Hz to 10,000 Hz
• Automatic speed ramping • Charge alternator failure alarm • User friendly set-up and button
• Flexible automatic start control • “Protections disabled” feature layout for ease of use GOVERNOR OUTPUT
Fully Isolated
• Clutch control • LCD alarm indication • Compatible with a wide range of
• LCD text display • Low power mode CAN engines VOLTAGE OUTPUT
• Multiple display languages • USB connectivity • Fill, empty, maintain fill and maintain 0 V to 10 V range
• Two-key menu navigation • Backed-up real time clock empty control 1000 Ω minimum load impedance
• Front panel editing with PIN • Fully configurable via DSE CURRENT OUTPUT
protection Configuration Suite PC software 0 to 20 mA range
• Customisable status screens • Configurable display languages 500 Ω maximum load impedance
• Customisable multi instrumentation • Remote SCADA monitoring via DSE DIMENSIONS
screens Configuration Suite PC software OVERALL
• Configurable digital inputs (4) • Modbus RTU support by 189 mm x 125 mm x 54 mm
7.5” x 4.9” x 2.1”
• Configurable analogue configurable RS485 port
inputs (7) PANEL CUTOUT
148 mm x 112 mm
5.8” x 4.4”
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457 055-202/12/20 (2) US
DSEControl®
DSEE400
ENVIRONMENTAL TESTING STANDARDS
ELECTRICAL SAFETY
The DSEE400 is an easy to use The monitoring and configuration The DSE Configuration Suite PC BS EN 60950
engine controller designed to of the system variables allows the Software is used to easily make Safety of Information Technology Equipment,
provide flexible control with built in DSEE400 to start and stop the engine adjustments to the operating including Electrical Business Equipment
monitoring and protection. and increase and decrease engine parameters, sequences, timers
TEMPERATURE
speed as the output demand requires. and alarms. Reducing valuable BS EN 60068
The DSEE400 is compatible with development and commissioning time Ab/Ae Cold Test -30 oC
both electronic and mechanical On board event, data logging and BS EN 60068-2-2
Bb/Be Dry Heat +70 oC
diesel engines. It is fully configurable trending makes it possible to
for a wide range of determine preventative maintenance VIBRATION
applications such as engine driven and improved BS EN 60068-2-6
pumps and compressors. performance criteria for the Ten sweeps in each of three major axes
5 Hz to 8 Hz at +/-7.5 mm, 8 Hz to 500 Hz at
machine. 2 gn
All of the engine control functions,
including the engine start, speed and HUMIDITY
BS EN 60068-2-30
clutch control can be achieved both Db Damp Heat Cyclic 20/55 oC at 95% RH
automatically & manually. 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 oC at 93% RH
48 Hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 ms
DEGREES OF PROTECTION
CONNECTOR A CONNECTOR C PROVIDED BY ENCLOSURES
BS EN 60529
IP67.
RELATED PARTS
TITLE PART NO.
Deutsch connector A (DT16-18SA-K004), 18 way complete with pins 007-850
Deutsch connector C (DT16-18SC-K004), 18 way complete with pins 007-851
Set of 2 harnesses, A & C connectors, pre-wired, 1.2 m, cables marked. 007-852
ISO 9001
Registered
Quality
Managem
ent 015