0% found this document useful (0 votes)
9 views2 pages

Manostat ENP VOITH

This document provides information about metal diaphragm pressure switches, including their features, technical specifications, pressure ranges, dimensions, electrical ratings, and ordering information. The switches use stainless steel wetted parts and are available for intrinsically safe applications. They have high accuracy and repeatability and are suitable for uses in various industries.

Uploaded by

Karl Heinz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9 views2 pages

Manostat ENP VOITH

This document provides information about metal diaphragm pressure switches, including their features, technical specifications, pressure ranges, dimensions, electrical ratings, and ordering information. The switches use stainless steel wetted parts and are available for intrinsically safe applications. They have high accuracy and repeatability and are suitable for uses in various industries.

Uploaded by

Karl Heinz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Index: L / 923-1485

Metal Diaphragm Pressure Switches D1T/D2T


Mechanical single/dual pressure switch
Repeatability ±1.0 % at constant temperature

Features
► Metal diaphragm pressure switch
► Wetted parts welded
► Direct acting, no friction, high accuracy
► Approvals: Ex ia, UL, CSA, marine, SIL2/3 (IEC 61508)

Adjustment ranges
0.005 ... 10.3 bar and
-0.006 ... -1 bar (Vaccum)

Applications
Machine and tool engineering,
Autoclaves, pump control,
Refrigerant monitoring, chemical industry
Ship building applications

Technical Data
Wetted parts: Stainless steel 17 - 7PH / SS304 Intrinsically safe: The switches are also available for
intrinsically safe applications. In
Repeatability: ±1 % at constant temperature this case we recommend gold
Switching rate: max. 20/min contacts. Add "Exi" in case of
ordering. Maximum rating
Temperature range: -40 °C... +75 °C according to ATEX:
Protection class: IP65 Umax = 28 V Imax = 50 mA
Housing: Top part: aluminium powder coated Approval: Cert. No.: TÜV 20 ATEX 248753X,
bottom part: aluminium anodized IECEx TUN 21.0002X

Process connection: 1/4" NPT female thread D1T, D2T:


Optional: 1/2" NPT female thread (Ex) II 1 G Ex ia IIC T6 Ga or
(P2) II 1 D Ex ia IIIC T200 100°C Da
Electrical connection: WAGO terminal and cable gland -40 °C < Ta < +75 °C
M20 x 1.5; Ui = 28 V Ii = 50 mA Pi = 0.84 W
clamping range ø 5 ... 11 mm Ci, Li = negligibly small
Electrical load capacity Many micro switch versions with
and hysteresis: different switching powers and D1T with connector ST1, D2T with
hysteresis are available and make it connector ST3:
possible to make customized (Ex) II 1 G Ex ia IIB T6 Ga or
changes. II 1 D Ex ia IIIC T200 100°C Da
Weight: D1T-...: approx. 1.0 kg -40 °C < Ta < +75 °C
D2T-...: approx. 1.1 kg Ui = 28 V Ii = 50 mA Pi = 0.84 W
Set point adjustment: Turn the adjustment screw Ci, Li = negligibly small
clockwise to decrease the set point

Pressure Ranges
Pressure range Adjustment range [bar] Max. operating Proof pressure The resulting hysteresis is approx. ...
code pressure [bar] [bar] bar at the end of range
Increasing press. Decreasing press. short term H, GH [bar] M, GM [bar]
Overpressure
2SS 0.005 ... 0.11 0.001 ... 0.11 0.13 . 0.2 . 0.004 . 0.006 .

3SS 0.012 ... 0.20 0.002 ... 0.196 0.47 . 0.7 . 0.005 . 0.010 .

18SS 0.050 ... 1.20 0.030 ... 1.20 2.7 . 4.0 . 0.018 . 0.040 .

80SS 0.300 ... 5.50 0.030 ... 5.30 7.1 . 10.7 . 0.110 . 0.240 .

150SS 0.500 ... 10.30 0.100 ... 9.90 13.3 . 20.0 . 0.190 . 0.420 .

Vacuum
3SS -0.006 ... -0.20 -0.002 ... -0.196 0.13 . 0.2 . 0.004 . 0.009 .

18SS -0.040 ... -1.00 -0.020 ... -0.970 0.67 . 1.0 . 0.030 . 0.060 .

Barksdale ®
Subject to technical changes. 1
Metal Diaphragm Pressure Switches
Pressure D1T/D2T

Dimensions (mm / inch)

Electrical Ratings
Micro Special features Volt AC Ind. load Res. load Volt DC Ind. load Res. load Comments
switch 50/60 Hz A A A A
Micro switch with silver 6 Small hysteresis;
contacts 125 10 10
H to 0.50 0.5 High AC-/
250 10 10
. .

24 low DC-load
Micro switch with silver 12 5.00 15.0 Medium hysteresis;
contacts 125 10 10
M 24 1.00 2.0 High AC- and
250 10 10
250 0.25 0.4 DC-loads
GH Micro switch with gold 125 . 1 . 1 . 24 . 1.00. 1.00 .
Small hysteresis
contacts for low voltage and/
GM or low current (e. g. "Exi") 30 . 0.1 . 0.1 . 30 . 0.10. 0.1 . Medium hysteresis

Options
D1T-... D2T-...
ST1 Plug, 3-pin + E, DIN EN 175 301-801 (prev. DIN 43650) ST3 Plug, 6-pin + E, DIN 43651
EXI for intrinsically safe application EXI for intrinsically safe application

Order Code
Example for order number

Type Micro switch Pressure range code Options Approval


D1T or D2T - GH 3SS - ST1 - EXI

Your order number


Type Micro switch Pressure range code Options Approval
or - - -