PI C/60Hz: KW KW
PI C/60Hz: KW KW
Air Systems
Air Filter Type Light duty dry replaceable element
50 Hz 60 Hz
Combustion Air Flow
Prime - 651 (1380)
Liter/second (cfm)
Standby - 712 (1510)
Maximum Air Filter Intake Restriction - 3.73KPa
Fuel System
Fuel Filter Type Fuel Filter (Replaceable)
Recommended Fuel Class A2 Diesel
Engine Speed 1500 rpm 1800 rpm
Fuel Standby - 35.9) 135.9)
Consumption Prime Power - 117.8 (31.1)
l/hr (US gal/hr) %75 of Prime Power - 90.5 (23.9)
%50 of Prime Power - 65.3 (17.2)
Fuel Tank Capacity: Open / Close 955 L / 955 L
Lubrication System
Lube Oil API-CH4/CI4 SAE 15W-40 (-°10 C to °50 C Ambient Temperature)
Lube Oil Capacity 91 L
Oil Pan 83 L
Oil Filter Type Oil Filter (Replaceable)
Oil Cooling Method Water
Cooling System
Coolant Capacity 42 L
Cooling System Mounted Radiator, AIR-AIR Charge cooled
Cooling Fan Air Flow m3/s - 11.8
50 Hz 60 Hz
Heat Radiation to Room Prime - 42kWm
Standby - 36kWm
Exhaust System
Grade Industrial
Silencer Size 6”
Qty 1
Exhaust Gas Flow Prime - 975 (2065)
Litre/s (cfm) Standby - 1076 (2280)
Maximum Allowable Backpressure - 10.13 kPa
50 Hz 60 Hz
Exhaust Gas Maximum
Prime - 468°C
Temp
Standby - 488°C
Shipping Data
Type Length (mm) Width (mm) Height (mm) Weight (kg)
Open 3601 1500 2133 4200
Enclosed 5141 1563 2643 6250
Notes:
*Prime power rating of the generating set is where a variable load and unlimited hours usage are applied
on the generating set with an average load factor of 80% of the prime rating over each 24 hour period.
Noting that a 10% overload is available for 1 hour in every 12 hours operation
**Standby power rating of the generating set is where a variable load limited to an annual usage upto
500 hours is applied, with 300 hours
of which may be continuous running. Noting that no overload is permitted
In line with our policy of continuous development, PI reserves the right to change specification without
notice