Liebert Ita2 5 40kva Brochure Asia

The document provides technical specifications for uninterruptible power supply units ranging from 5 kVA to 40 kVA capacity including input parameters, battery details, output specifications, efficiency ratings, dimensions and weights. It lists specifications for nominal voltage and frequency ranges, overload capacity, noise levels and environmental limits.

Uploaded by

1905319104
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views1 page

Liebert Ita2 5 40kva Brochure Asia

The document provides technical specifications for uninterruptible power supply units ranging from 5 kVA to 40 kVA capacity including input parameters, battery details, output specifications, efficiency ratings, dimensions and weights. It lists specifications for nominal voltage and frequency ranges, overload capacity, noise levels and environmental limits.

Uploaded by

1905319104
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Technical Specifications

Nominal Ratings (kVA) 5 6 10 16 20 30 40


ITA- IITA- ITA- ITA- ITA- ITA- ITA-
Long Backup Model 05k00AL1102P00 06k00AL1102P00 10k00ALA102P00 16k00AL3A02P00 20k00AL3A02P00 30k00AL3302P00 40k00AL3302P00

Part Number 01202670 01202671 01202672 01202682 01202683 01202660 01202897

Input Parameters

220/230/240 VAC
1-Phase, 2 Wire;
Nominal Input Voltage (V) 220/230/240 VAC 1-Phase, 2 Wire 380/400/415 VAC 3-Phase, 4 Wire
380/400/415 VAC
3-Phase, 4 Wire

Input Voltage Range (V) 176-288 VAC at full load; 100-176 VAC at linear derating; 100 VAC at half load

Nominal Input Frequency (Hz) 50/60

Input Frequency Range (Hz) 40-70

Input Power Factor (kW/kVA)3 0.99

Current THD at full linear load3 <3

Battery

Battery Blocks Per String 12*, 15, 16, 17, 18, 19, 20 24*, 30, 32, 34, 36, 38, 40 32-40 24-40**

Battery Charger Max. Power (A) 5 8 13

P/C : ITA-BCI0020K01 ( built-in battery module of 16 block X 12 V X 9 AH) Only external


Battery Option
Battery cabinet Dimensions in rack arrangement - 430 (W) x 750 (D) x 85 (H) battery cabinet

Output

220/230/240 VAC (1-Phase),


Nominal Output Voltage (V) 220/230/240 VAC (1-phase) 380/400/415 VAC (3-Phase)
380/400/415 VAC (3-Phase)

Nominal Output Frequency (Hz) 50/60

Rated Power Factor (kW/kVA) Unity

Voltage Harmonic Distortion (%) <2% for Linear loads & <5% for Non-linear loads

105~125%, 10 min;
105~125%, 10 min; 125~150%, 1 min;
Overload Capacity @ at 25 °C 125~150%, 1 min;
>150%, 200 ms
150~200%, 5 s

Efficiency

Online Mode Efficiency Up to 95.5% Up to 95.8% Up to 96.2% Up to 96.5%

ECO Mode Efficiency Up to 99%

Dimensions and Weight

Dimensions (W x D x H) in mm-Rack
430 x 480 x 85 430 x 590 x 85 430 x 600 x 130 430 x 730 x 130
Mounted Arrangement

Weight (kg) 11 15 23 23.5 30

General

Nosie at 1 m (dBA) <55 <58 <60 <63

Operating Temperature (°C) 0 ~ 50*

Relative Humidity (%RH) 5 ~ 95, non-condensing

Altitude (m) 3000 without derating

General and safety requirements for


IEC/EN 62040-1
UPS

EMC requirements for UPS IEC/EN 62040-2

UPS classification according to


VFI-SS-111
IEC 62040-3
Note: Specification are subject to change without any further notification

*Dearting conditions apply ** 24-26-28-30 with de-rating (1) with ABS certification (2) Not Available in 30 & 40 kVA (3) Conditions apply