October 2010

INSULATION MONITORING RELAIS

industrial applications

for use in medical rooms

www.microener.com

www.contrel.it
RI se rie s
The RI isolation monitor series, are designed to permanently monitor the isolation to earth,
in single and three phase networks with isolated neutral or without
neutral (IT systems ) up to 1.000Vac and dc networks up to 1.000Vdc.
In the isolated neutral systems, in case of first leakage to earth, the tripping of
the protection is not required, but according with the IEC 61557.8Standard,
the leakage should be signalled by optical and acoustic means.
The device generates internally a measure signal,
which is applied between the controlled circuit and earth.

HRI se rie s
The working principle of the isolation monitor for use in medical room is based
on applying a dc voltage or a codified signal, between the secondary
of the isolation transformer and the equipotential node of the installation,
pointing out therefore, in a case of an earth leakage, the current flowing in the relay
and its corresponding isolation resistance of the installation.

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
PRODUCTS PAGE
index
Serie RI e HRI 4
Foreword 2

RI Se rie s - FO R IND USTRIA L A P PLIC A TIO NS


INSULATION MONITORING 6

RI-F48 | RI-R48 | RI-R48N 4


Insulation monitoring relay for networks 24 - 48 Vac/dc

RI-R11 | RI-R11D 6
9
Insulation monitoring relay for networks 110 - 220 Vdc

RI-R15 9
Insulation monitoring relay for networks 300 / 500 / 1000 Vdc

RI-F22 | RI-R22 | RI-R38 13 13


Insulation monitoring relay for networks max 440 Vac

ARI-R100 16
Adapters for networks up to 1000 Vac
16
RI-R60 18
Insulation monitoring relay for networks max 760/1000 Vac

RI-SM 22
Insulation monitoring relay for out-voltage systems 20

22
H RI Se rie s - FO R M ED IC A L USE A N D HO SP ITA L A P PLIC A TIO N 24
INSULATION MONITORING
General - Models - Accessories - Options (only for HRI-R40 and HRI-R40W)

HRI-R40 | HRI-R40W 25
25

HRI-R22t 29

HRI-R24 32
Insulation monitoring relay for use in medical rooms
29
PR5 34
Remote repetition panels

EML 36
Remote serial concentrator 32

34

36

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI series
INSULATION MONITORING
FOR ISOLATED NEUTRAL NETWORKS (IT)

The RI isolation monitor series are designed to moni-


tor isolated neutral networks (IT) level. L1
First of all, IT networks are used where the continuity L2
L3
of service is important. For this kind of networks, N
insulation impedance is very high, so in case of lea-
kage to earth, electric currents caused by a failure
are very weak. This works in order to avoid the mas-
ses reaching a dangerous potential. If, in case of
Z
insulation leakage, it’s necessary stop the supply for
isolated neutral networks to earth, for IT networks,
this is not necessary, but the failure has to be poin-
ted out, individuated and eliminated. The RI series, in
PE
their different versions, constantly verify the insula- LOAD
tion level and report failure’s condition.

GENERAL
APPLICATIONS be used in auxiliary networks and in generic networks of distribu-
IT networks are used where the continuity of service is a priority. tion in alternate single and three phase, anyway without direct-
For example, in these cases: current components.
• Chemical and metallurgical industries, where a voltage’s • Versions that apply a measure signal codified and varying in
interruption implies serious economic loss order to allow a correct insulation measure independently from
• Transmission systems and radio links under-control network that has to be monitored. Strong distortion
• Places at explosion and fire’s risk with high harmonic components (sub harmonic) and direct-cur-
• Mines rent components can cause measure’ problems to others techni-
• Networks of emergency’s supply ques. Model RI-R50 belong to this category. This solution let use
• Generators or direct-current group monitoring devices in generic applications for networks in direct-
• networks of auxiliary supply and control current and alternating single and three phase, with rectifiers,
• railways power’s electronics and variable-speed drive.
• Naval applications • Versions useful for testing insulation in out-voltage networks
• Rooms for medical use which use the same measuring technique -already cited- of
direct-current signal applied in network, but in this case the net
PRODUCT SERIES is out-voltage. This works in order to do a preventing monitoring
There are different versions of RI devices, in order to have speci- of insulation’s level. It is very useful for equipments not perma-
fic functionalities available for every networks that has to be nently used, as well as motors, fire-engines and so on where insu-
2
monitored. There are also accessories functions: for example, pre- lation level could decrease because of humidity (condensation).
alarm threshold and display for visualising insulation, very useful This decreasing doesn’t let a normal functioning when they will be
as supply for failure’s search. used. Model RI-SM belongs to this category.
Measuring techniques are different for every model, in order to • Versions for use in medical rooms
have the right insulation available according to the network. Models HRI-R24 (tipically used for scialytic lamps) HRI-R22t
• Versions that measures the variation of two polarities’ poten- HRI-R40 HRI-R40W belong to this category and got different
tial to earth. Models RI-F48, RI-R48, RI-R11, RI-R11D, RI-R15 measuring techniques depending on the model either applying a
belong to this category. These versions are apt for use in direct- direct-current signal and surveying electric leakage to earth or
current networks, in auxiliary supply’s networks and in direct-cur- applying a measuring signal codified and varying.
rent or alternate single phase networks. Panels of remote signalling repeater PR and remote serial concen-
• Versions that apply a measure’s signal in direct-current bet- trator EML for network’s monitoring are available as accessories of
ween network and earth sensing leakage current to earth so that this product. In the next page, there is a table with the description
insulation level could be measured. For every independent net- of technical features for every kind of monitor with specific crite-
work, only one monitor could be used. Models RI-F22, RI-R22, rions of choosing in order to turn the user to the model more use-
RI-R38, RI-R60 belong to this category. These versions are right to ful for his needs.

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI series
INSULATION MONITORING
FOR ISOLATED NEUTRAL NETWORKS (IT)

FUNCTIONS TABLE

NETWORK AUXILIARY TRIPPING MEASURAMENT SIGNALS OUTPUT TEST RESET


MODEL UNDER CONTROL SUPPLY THRESHOLD TECHNOLOGY
RI-F48 24 - 48 Vac/dc read from TRIP Potential variation Fault 1 relais NO-C-NC Local Automatic
under control 10 kohm fixed of polarities
network
RI-R48 24 - 48 Vac/dc read from TRIP Potential variation Fault 1 relais NO-C-NC Local Manual local
under control 10 ÷ 50 kohm of polarities
network
RI-R48N 24 - 48 Vac/dc read from TRIP Potential variation Fault on +/L 1 relais NO-C-NC Local Manual local
under control 10 ÷ 60 kohm of polarities Fault on -/N
network
Alarm
RI-R11 110 80 ÷ 110 Vdc read from TRIP Potential variation Fault on +/L 2 relais NO-C-NC Local and remote Automatic
RI-R11 220 185 ÷ 275 Vdc under control 10 ÷ 100 kohm of polarities Fault on -/N fail safe function Manual local
ALARM Alarm on +/L Fault and remote
network 2 relais NO-C-NC
30 ÷ 100 kohm Alarm on -/N fail safe function
Alarm
RI-R11D 110 80 ÷ 110 Vdc read from TRIP Potential variation Fault on +/L 2 relais NO-C-NC Local and remote Automatic
Fault on -/N
RI-R11D 220 185 ÷ 275 Vdc under control 10 ÷ 100 kohm of polarities Alarm on +/L fail safe function Manual local
ALARM Alarm on -/N Fault and remote
network Insulation level 2 relais NO-C-NC
30 ÷ 100 kohm (by LED bar) fail safe function
RI-R15 300 Vdc read from TRIP=30÷300 kohm Potential variation Fault on +/L 1 relais NO-C-NC Local Automatic
500 Vdc under control Fault on -/N polo +
of polarities Alarm on +/L
fail safe function Manual local
1.000 Vdc network polo -
Alarm on -/N and remote
with adapter ARI-R15

RI-F22 max 230 Vac 230 Vac TRIP dc signal Fault 1 relais NO-C-NC Local Automatic
max 500 Vac 115 Vac opt 100 kohm fixed
(with adapter)
RI-R22 max 230 Vac 230 Vac TRIP dc signal Fault 1 relais NO-C-NC Local Manual local
max 500 Vac 115 Vac opt 25 ÷ 100 kohm and remote
(with adapter)
RI-R38 max 440 Vac 115-230 Vac TRIP dc signal Fault 1 relais NO-C-NC Local Manual local
max 1000 Vac 10 ÷ 100 kohm and remote
(with adapter)
ARI-R100 Upper limit 230 Vac - - - - - -
1000 Vac 115 Vac opt
with RI-R38
max 760 Vac 230 Vac dc signal Alarm fault Alarm Local and remote Local and remote
RI-R60 insulation 1 relais NO-C-NC
max 1000 Vac 115 Vac
with adapter ARI-R60 level Foult
1 relais NO-C-NC

RI-SM Out of voltage read from TRIP dc signal Fault 1 relais NO-C-NC Local Automatic
under control 0.1 ÷ 10 Mohm
network

HRI-R24 max 24 Vac read from TRIP Potential variation Fault 1 relais NO-C-NC Local and remote, Manual local 3
under control 10 ÷ 50 kohm of polarities with appropriate
network remote panels

HRI-R24t max 230 Vac 230 Vac TRIP dc signal Fault for 1 relais NO-C-NC Local and remote, Manual local
115 Vac 50 ÷ 250 kohm visualization with appropriate
insulation level remote panels
by led bar
HRI-R40 max 230 Vac 230 Vac TRIP dc signal Fault alarm 1 relais NO-C-NC Local and remote, Manual local
115 Vac 50 ÷ 500 kohm display 3 led
with appropriate
digit, min. value
remote panels
memorized
HRI-R40W max 230 Vac 230 Vac TRIP Codified and Fault alarm 1 relais NO-C-NC Local and remote, Manual local
115 Vac 50 ÷ 500 kohm variable signal display 3 led with appropriate
digit, min. value remote panels
memorized

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-F48 series
RI-R48 series
RI-R48N series
INSULATION MONITORING
VERSIONS FOR NETWORKS ac/dc MAX 48 V

GENERAL
The devices allow the insulation monitoring to earth of electric net-
works in alternate and direct-current till 48 V isolated (IT systems).
They measure potential’s variation of two polarities on earth so that
provide for a signal of insulation decreasing under a fixed level.
Monitoring is carried out measuring potential’s variation of two pola-
rities on earth.
Auxiliary supply is taken from under-control network.
There are different versions available: some, very cheap, with a fixed
tripping threshold, others with possibility of adjustable calibration of
tripping threshold and versions with indication of polarity (positive or
negative, phase or neutral) on which the failure took place.
Devices have on frontal panel signal for activity ON, for tripping TRIP
(low insulation), a test bottom, a reset bottom and a potentiometer (or
micro switches) for setting the threshold of tripping (only for versions
with adjustable threshold).

MODELS
--------------- ----------------------------------------------------------------------------
RI-F48 fixed threshold
--------------- ----------------------------------------------------------------------------
RI-R48 adjustable threshold
--------------- ----------------------------------------------------------------------------
RI-R48N adjustable threshold, indication of broken down polarity
--------------- ----------------------------------------------------------------------------

FUNCTIONS AND OPERATORS - LEGEND

7 8 9 10 11 12 7 8 9 10 11 12

------------------------------------------------------------------
1 Potentiometer/micro switches for insulation tripping setting
2 (only for models RI-R48 and RI-R48N)
2 4 ------------------------------------------------------------------
RI-R48
INSULATION
MONITORING
2 Manual reset button
RESET RESET
RI-R48N RI-R48N
(only for models RI-R48 and RI-R48N)
1
30
40 3 INSULATION
ON ------------------------------------------------------------------
INSULATION
ON
20 MONITOR

40 60
RESET
5 3
MONITOR

40
Test button +
60
RESET

TEST
10
kΩ
50 TRIP ON TEST 30
20
+
TRIP
30
20
------------------------------------------------------------------
TRIP

5 4 10 TEST
_
contrel
4
10
kΩ
_
Signal of supplied
TEST relay ON (green LED)
kΩ kΩ ALARM

1
kΩ ALARM
------------------------------------------------------------------
3 5 Signal for insulation’s threshold set reached
(indication of broken down polarity for RI-R48N)
------------------------------------------------------------------
4 1 2 3 4 5 6
1 2 3 4 5 6

DIMENSIONS
48 RI-F48 RI-R48 RI-R48N RI-R48N
52,5 58
RI-R48 | RI-F48 7 8 9 10 11 12 RI-R48N

INSULATION
RI-R48 MONITORING
RESET RI-R48N
85,5

30 ON
85

INSULATION
45

40
20 MONITOR RESET

40 60 +
10 50 TRIP ON 30
kΩ TEST 20
TRIP
_
10 TEST
kΩ
kΩ contrel
ALARM

1 2 3 4 5 6

64 44
52,5 68 65

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-F48 series
RI-R48 series
RI-R48N series
INSULATION MONITORING
VERSIONS FOR NETWORK ac/dc MAX 48 V

ELECTRIC CHARACTERISTICS

Auxiliary supply voltage 24 V or 48 V 50-60 Hz ± 20 % or dc ± 20 %


Self-consumption 3 VA MAX
Network voltage 24 ÷ 48 Vac/dc +10 %
Measuring voltage 24 V MAX
Measuring current 0.5 mA MAX
Internal impedance 100 kohm
RI-R48 adjustable 10 ÷ 50 kohm by potentiometer
Tripping threshold RI-R48N adjustable 10 ÷ 60 kohm by micro switches
RI-F48 fixed 10 kohm
Tripping late about 1 second
Signalling and operators led ON - led TRIP
buttons TEST and RESET (only model RI-R48 / RI-R48N)
Output relay switch contact NO-C-NC MAX 5 A 250 Vac
Working temperature - 10 …+ 60 °C
Storing temperature - 20 …+ 70 °C
Relative humidity < 90 %
Insulation test 3 kV 60 sec / 4 kv imp. 1,2 / 50 µs
Assembling position indifferent
Connection type by screw terminals - wire section MAX 4 mm2
Protection's degree IP 40 frontal with cap - IP 20 case
Mounting according with DIN 50022 easy connection snap on DIN rail 35 mm / 3 modules of 17.5 mm
Weight approximately 300 g
Standard reference CEI-EN 61010-1 / CEI-EN 61557-8 / VDE0413 part.8 / CEI-EN 61326-1

WIRING DIAGRAMS - LEGEND

------------------------------------------------------------------------
RI-F48 / RI-R48 / RI-R48N AUXILIARY SUPPLY - TERMINALS 1-3
Auxiliary supply could be taken from under-control network.
------------------------------------------------------------------------ 5
Vaux
INSULATION MONITORING - TERMINALS 1-9
Terminals have to be connected between under-control network
1 2 3 4 5 6 7 8 9 10 and measure’s referring earth.
AUX1 AUX2 RESET TEST OUT-NC OUT-C OUT-NO PE RESET Maximum voltage applicable between these terminals is 48 V
------------------------------------------------------------------------
CONNECTION OUTPUT RELAY - TERMINALS 6-7-8
Connection for remote signal by relays with switch free
from voltage, max 5 A 250 V on resistive load.
PE ------------------------------------------------------------------------
Eventual connection for automatic or remote RESET
_ (only for models RI-R48 and RI-R48N), connect a button NC
between terminals 4 and 10.
LOAD
+ ------------------------------------------------------------------------
Eventual connection for remote TEST
INSULATED LINE max 48Vac/dc (only for models RI-R48 and RI-R48N), connect a button NO
between terminal 5 and earth’s conductor PE
------------------------------------------------------------------------

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R11 series
RI-R11D series
INSULATION MONITORING
VERSIONS FOR NETWORKS dc MAX 250 V

GENERAL
The devices allow permanent monitoring of insulation of electrical
networks in direct-current current isolated on earth (IT networks).
Monitoring is carried out measuring potential’s variation of two pola-
rities of network on earth. Auxiliary supply is taken from under-control
network.
These devices have two trip thresholds, which are adjustable by fron-
tal micro switches, called ALARM and TRIP. This works in order to
signal that insulation’s level decreased under the threshold. Trip is
signalled by frontal LED with indication of polarity (+ or -) that show
low insulation. Remote trip threshold is carried out by double switch
two relays with contacts voltage-free. Relays could be programmed in
positive safe too (FAIL-SAFE function, normally excited). On the front,
there are TEST and RESET buttons; test could be activated locally or
by an external button; push button could be set manually or automa-
tically, either with local button or with external push button.
Model RI-R11D has a monitor of insulation’s level of the device by a
bar.
MODELS
------------------- --------------------------------------------------------------------------------------
RI-R11 110 V Main supply and auxiliary voltage 110 Vdc / -15% +25% (80 ÷ 180 Vdc)
RI-R11D 110 V Main supply and auxiliary voltage 110 Vdc / -15% +25% (80 ÷ 180 Vdc)
------------------- --------------------------------------------------------------------------------------
RI-R11 220 V Main supply and auxiliary voltage 220 Vdc /-15% +25% (185 ÷ 275 Vdc)
------------------- --------------------------------------------------------------------------------------

FUNCTIONS AND OPERATORS - LEGEND

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
3 3
Insulation monitor RI-R11
RI-B32 ON Insulation monitor
Insulation relayRI-B32
monitor RI-R11D ON
4
ON 5kΩ
4
2 TEST
TEST 300
kΩ
ALARM kΩ
150 100
TRIP kΩ
60
TRIP

ALARM
2 TEST 300
kΩ
ALARM kΩ
ALARM
150 100
TRIP kΩ
TRIP kΩ
60
TRIP

ALARM
TRIP

ALARM
10kΩ

20kΩ
80
50
40
20 + 5 80
50
40
20
+ + 50kΩ
5
30 10
- 30 10 - - 100 kΩ

1 RESET
RESET
off
man
F.S. on off
auto man
F.S. on
auto 1 RESET
off
man
F.S. on off
man
auto man
auto
F.S. on
auto 200kΩ

RESET RESET
contrel
con
ntrel 6 RESET RESET
total
trip
on
on
contrel
400kΩ
6
contrel
contrel alarm on
600kΩ
HOLD

6 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
7 7

8 9 8 9
----------------------------------------------------------------------------------------------------------------------------------------------------
1 RESET button. This works only if RESET functioning is set manually.
----------------------------------------------------------------------------------------------------------------------------------------------------
2 TEST button. Pushing TEST button cause either alarm activation or trip activation with output relays’ switching.
----------------------------------------------------------------------------------------------------------------------------------------------------
3 LED ON for active device signalling
----------------------------------------------------------------------------------------------------------------------------------------------------
4 LED TRIP for trip threshold TRIP signalling
----------------------------------------------------------------------------------------------------------------------------------------------------
5 LED ALARM for alarm threshold ALARM signalling
----------------------------------------------------------------------------------------------------------------------------------------------------
6 LED+ and LED- signalling which under-control network’s polarity has low insulation. Ignition of one of these LED will be connected
with ALARM LED and TRIP ignition.
----------------------------------------------------------------------------------------------------------------------------------------------------
7 Screw terminals for connections
----------------------------------------------------------------------------------------------------------------------------------------------------
8 Micro switches for alarm threshold setting
----------------------------------------------------------------------------------------------------------------------------------------------------
9 Micro switches for trip threshold setting
----------------------------------------------------------------------------------------------------------------------------------------------------
10 Led bar for insulation level visualising (only for RI-R11D)
----------------------------------------------------------------------------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R11 series
RI-R11D series
INSULATION MONITORING
VERSIONS FOR NETWORKS dc MAX 250 V

ELECTRIC CHARACTERISTICS

RI-R11 110 V 110 Vdc -15/+25 % (80 ÷ 180 Vdc)


Network voltage and auxiliary supply RI-R11D 110 V 110 Vdc -15/+25 % (80 ÷ 180 Vdc)
RI-R11 220 V 220 Vdc -15/+25 % (185 ÷ 275 Vdc)

Self-consumption 5 W MAX
Alternating residual load 5%
ALARM threshold setting 300 ÷ 30 kohm (5 levels adjustable by micro switches)
TRIP threshold setting 100 ÷ 10 kohm (5 levels adjustable by micro switches)

Signalling led ON, led ALARM, led TRIP, led +, led -


signalling insulation led bar (only for RI-R11D)
Tripping delay about 1 second
Measure's current MAX 1.8 mA
RI-R11 / RI-R11D 110 V 200 kohm L+/L- 100 kohm L/earth
Internal impedance
RI-R11 220 V 400 kohm L+/L- 200 kohm L/earth

Output relay free from voltage contacts ALARM : 2 contacts switched NO-C-NC
TRIP : 2 contacts switched NO-C-NC
5 A 250 Vac – 0.3 A 130 Vdc – 0.2 A 280 Vdc resistive load
Capacity relay contacts 0.15 A 130 Vdc – 0.05 A 280 Vdc inductive load L/R < 40 ms
with 2 serial contacts: 0.7 A 130 Vdc – 0.5 A 280 Vdc resistive load
output alarm function - fail safe function for both outputs
Adjustable functions manual or automatic reset (external reset)
Working temperature - 10 …+ 60 °C
Storing temperature - 20 …+ 70 °C
Relative humidity < 90 %
Insulation test
Assembling position indifferent
Connection type by screw terminals - wire section MAX 2.5 mm2
Protection's degree IP 40 frontal with cap - IP 20 case
Mounting according with DIN 50022 easy connection snap on DIN rail 35 mm / 6 modules of 17.5 mm
Weight approximately 400 g
Standard reference CEI-EN 61010-1 / CEI-EN 61557-8 / VDE 0413 part.8 / CEI-EN 61326-1

DIMENSIONS
7

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

Insulation monitor RI-R11


RI-B32 ON Insulation monitor
Insulation relayRI-B32
monitor RI-R11D ON ON 5kΩ

TRIP TRIP TRIP 10kΩ


kΩ
ALARM kΩ TRIP kΩ kΩ
ALARM kΩ
ALARM TRIP kΩ
TRIP kΩ
TEST
TEST 300 150 100 60 ALARM TEST 300 150 100 60 ALARM ALARM 20kΩ
80 40 80 40
50 20 + 50 20
+ + 50kΩ

90 30 10
- 30 10 - - 100 kΩ 90 54
off F.S. on off F.S. on off F.S. on off F.S. on
man auto man auto man auto man
auto man auto
auto 200kΩ
RESET
RESET RESET total on
RESET RESET
con
contrel
ntrel RESET RESET trip on
contrel
400kΩ
contrel
contrel alarm on
600kΩ
HOLD

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

44
68
105 105 73

RI-R11 RI-R11D

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R11 series
RI-R11D series
INSULATION MONITORING
VERSIONS FOR NETWORKS dc MAX 250 V

WIRING DIAGRAMS - LEGENDA

A1-NO A1-C A1-NC A2-NO A2-C A2-NC


19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

RI-R11 / RI-R11D output relay ALARM

Vaux: output relay TRIP


V control PE remote remote
conn. test reset

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
V+ V- PE TEST RESET T1-NO T1-C T1-NC T2-NO T2-C T2-NC

PE

_
INSULATED NETWORK max 250 Vdc LOAD
+

------------------------- ----------------------------------------------------------------------------------------------------------------------------------
AUXILIARY SUPPLY AND UNDER-CONTROL NETWORK CONNECTION - TERMINALS 1-3.
Positive and negative polarities of under-control network have to be connected to these terminals. Network’s voltage is used for device’s supply.
If positive and negative has been inverted, the device would not be damaged but (+) and (-- ) indications of frontal LED would be inverted too.
The advice is that of making sure about the model with right functioning voltage.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
CONNECTION TO EARTH - TERMINAL 5.
Terminal has to be connected with protection conductor PE (earth) in order to allow insulation’s measure.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
CONNECTION FOR REMOTE TEST - TERMINAL 7.
In case of willing to foresee TEST function also from an external push button, it’s possible to connect a pushbutton with normally open contact NO
between this terminal and under-control network. If it’s connected to (+) polarity, test will cause ALARM LED, TRIP LED and (+) lighting; but if it’s
8 connected to (-- ) polarity, LED - will light.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
CONNECTION FOR REMOTE RESET - TERMINAL 9.
In case of willing to foresee RESET function also from an external push button, it’s possible to connect a pushbutton with normally open contact NO
between this terminal and (-- ) polarity of under-control network.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
OUTPUT TERMINAL FOR TRIP RELAY - TERMINALS 12-13-14 16-17-18.
In order to signal to exterior threshold TRIP activation, it’s available a relay with double change over contact voltage-free. The diagram shows con-
tacts’ condition either with not supplied device or supplied at rest with FAIL SAFE function not active (relay normally not excited). If FAIL SAFE fun-
ction is set, relay will be normally excited when there is not tripping (supplied device) and it will be back at rest in case of tripping, not supplied
device or failure.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
OUTPUT TERMINAL FOR ALARM RELAY - TERMINALS 30-31-32 34-35-36
In order to signal trip threshold ALARM activation, it’s available a relay with double switch voltage-free. The diagram shows contacts’ condition either
with not supplied device or supplied at rest with FAIL SAFE function not active (relay normally not excited). If FAIL SAFE function is set, relay will be
normally excited when there is not tripping (supplied device) and it will be back at rest in case of tripping, not supplied device or failure.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R15 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC

GENERAL
The RI-R15 device allows the permanent insulation monitoring to
earth of electric networks in direct current isolated (IT systems).
Insulation resistance monitoring is carried out measuring the
potential variation of two polarity on ground reference. Auxiliary
supply is taken from under-control network.
The threshold of trip is regulated by a frontal potentiometer. On
the frontal panel there is the signalling of device ON, and three red
LED to signal the tripping (TRIP) and to indicate the polarity of the
line under control that has low insulation. It’s available a chan-
geover contact relay to use the low insulation signalling in a remo-
te panel. The relay can be set as FAIL SAFE function. On front panel
there are a TEST and a RESET push-buttons. The test can be acti-
vated locally while the reset can be set in automatic or manual,
with local or external push-button.

MODELS
------------------- ------------------------------------------------------------------------------------------------------------------------------
RI-R15 300V power supply and network to control 300 Vdc (network 280÷340 Vdc)
RI-R15 500V power supply and network to control 500 Vdc (network 400÷600 Vdc)
RI-R15 1000V power supply and network to control 1000 Vdc (network 600÷1000 Vdc) including ARI-R15 external adapter
------------------- ------------------------------------------------------------------------------------------------------------------------------

FUNCTIONS AND OPERATORS - LEGEND

--------------------------------------------------------------------------------
1 RESET push-button: this button is enabled to function only if is set the
manual RESET. In this mode the instrument can come back in no alarm
condition only when the RESET push-button is pressed or in absence
9
of the power supply.
--------------------------------------------------------------------------------
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
2 TEST push-buttons: the trip relay commute when these buttons is pressed.
3 The TEST+ button will simulate a low insulation on the positive pole:
the LED TRIP and + will turn on. The TEST- button will simulate a
Insulation monitor relay RI-R15 low insulation on the negative pole: the LED TRIP and - will turn on.
ON
100 180 240
--------------------------------------------------------------------------------
6 + TEST+
2 3 LED ON: device ON.
30 kΩ 300
- 2 --------------------------------------------------------------------------------
TEST-

1 4 LED + and LED-: to signal the polarity that has the low insulation of the
TRIP RESET network under control. The lighting on of one of these LED is linked to the
TRIP LED.
--------------------------------------------------------------------------------
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 7 5 LED TRIP: to signal the trip insulation level under the set threshold value
--------------------------------------------------------------------------------
6 Potentiometer to set the trip threshold
4 5 --------------------------------------------------------------------------------
7 Terminal boards for the connections
--------------------------------------------------------------------------------

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R15 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC

ARI-R15 VOLTAGE ADAPTER FOR RI-R15 1000V


The RI-R15 1000V version for network from 600 to 1000V must be used ARI-R15 adapter do not function with RI-R15 300 and 500V. The ARI-R15
only with the ARI-R15 external adapter. This adapter must be positioned adapter is in a box for connection snap on DIN rail, 6 modules:
between the network to control and the control device RI-R15 1000V. The

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

Insulation monitor relay RI-R15


ON
100 180 240
contrel ARI-R15 + TEST+
INSULATION MONITOR VOLTAGE ADAPTER
max 700/800/900/1000Vdc 30 k 300 - TEST-

contrel
TRIP RESET

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

ELECTRIC CHARACTERISTICS

TIPO RI-R15 300V RI-R15 500V RI-R15 1000V (with ARI-R15)


Auxiliary voltage supply 300 Vdc 500 Vdc Max 1000Vdc
and voltage network network 280÷340 Vdc network 400÷600 Vdc network 600÷1000Vdc
Maximum consumption 3W 5.5W 10W
Measure current max 1 mA max 1.5 mA max 2.5 mA
Residual alternate 5%
Internal impedance 800 kΩ L+/L- 450 kΩ L/ground
Tripping delay 1.5÷2.5 seconds
Signalling led ON, led TRIP, led +, led -
Setting TRIP threshold 30 ÷ 300 kohm (using a potentiometer)
Relay outputs TRIP: changeover contacts NO-C-NC
Relay contacts 5 A 250Vac – 0,3 A 130Vdc – 0,2 A 280Vdc resistive load
0,15 A 130Vdc – 0,05 A 280 Vdc inductive load L/R < 40 ms
10 programmable functions fail safe function,
manual or automatic reset (external reset)
Working temperature -10 ÷ 60°C
storing temperature -20 ÷ 70°C
Relative humidity ≤ 95 %
Insulation test 2,5 kV 60 sec. / 6 kV imp. 1,2/50µs
Mounting position any
Connection type By screw terminals – wire section max 2.5 mm2
Protection degree IP 40 frontal with cover - IP 20 case
Mounting according DIN 50022 Connection snap on DIN rail 35mm / 6 modules of 17.5 mm
Weight about 0,4 kg for RI-R15 / about 0.2 kg for ARI-R15
Standards safety EN 61010-1 / CEI 64.8 /
electromagnetic compatibility EN 61326-1-2-4

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R15 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC

DIMENSIONS

90 90 54

105 105 73

RI-R15 300V / RI-R15 500V WIRING CONNECTION - LEGEND

V+
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

RI-R15
connessione PE

INSULATION MONITOR
V control
Vaux: *

relay output
reset TRIP
remote Fail Safe
manual function

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
V- PE RES+ RES- F.S.+ F.S.- T-NC T-C T-NO

PE
_
INSULATED LINE Vdc LOAD
+
----------------------------------------------------------------------------------------------------------------------------------------------------------
POWER SUPPLY AND NETWORK UNDER CONTROL CONNECTION / terminals 21-3 - At these terminals must be connected the negative and positive
pole of the network to control. The same voltage must be used to supply the instrument. If the negative and positive pole are inverted, the instru-
ment will not be damage but the indication of LED+ and LED- will be inverted. It’s necessary to verify the use of the instrument with correct sup- 11
ply voltage.
----------------------------------------------------------------------------------------------------------------------------------------------------------
GROUND REFERENCE CONNECTION / terminals 27-9 - The terminals must be connected to the PE protection conductor (earth referring) to allow
the insulation measuring. ---
-------------------------------------------------------------------------------------------------------------------------------------------------------
REMOTE TEST CONNECTION / AUTOMATIC RESET / terminal 11-12 - For RESET function from external push-button it’s necessary to connect an
external N.O. contact push-button between these terminals. If these terminals are short-circuited the functioning of the reset will be automatic
when the low insulation condition finish.
----------------------------------------------------------------------------------------------------------------------------------------------------------
FAIL SAFE FUNCTION (NORMALLY EXCITED RELAY) / TERMINALS 13-14 - The fail safe function (normally excited relay) will be activated thanks to
a short-circuit between these terminals. With fail safe function enabled the relay will be normally excited in not trip condition (with device sup-
plied) and it will come back at rest with the device off or damage and in case of tripping. With the fail safe the output relay switch for the low
insulation, lack of auxiliary power supply or device failure.
----------------------------------------------------------------------------------------------------------------------------------------------------------

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R15 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC

TRIP RELAY OUTPUT / terminals 16-17-18 - To signal externally the TRIP threshold intervention it’s available a voltage changeover contact relay.
The wiring connection shows the contacts with the device off or on in rest condition with FAIL SAFE function disable (relay normally not excited).
With FAIL SAFE function enabled the relay will be normally excited in not trip condition (with device supplied) and it will come back at rest with
the device off or damage and in case of tripping.
----------------------------------------------------------------------------------------------------------------------------------------------------------
CONNEXION TO THE EXTERNAL ADAPTERS - To activate the instrument it’s necessary to make the short-circuit between the following terminals
23-25 and 5-7. This terminals are used to connect the external adapters when they are used (see specific manual).
----------------------------------------------------------------------------------------------------------------------------------------------------------

RI-R15 1000V WIRING CONNECTION - LEGEND

V+ IN-A IN+A REF


19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
for line 900÷ 1000Vdc

RI-R15 1000V
for line 600÷ 700Vdc

for line 700÷ 800Vdc

for line 800÷ 900Vdc

ARI-R15
INSULATION INSULATION MONITOR
V control
Vaux: *

MONITOR
VOLTAGE relay output
reset TRIP
ADAPTER remote Fail Safe
manual function

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
V- PE IN-B IN+B RES+ RES- F.S.+ F.S.- T-NC T-C T-NO

PE

_
INSULATED LINE Vdc (MAX 700 / 800 / 900 / 1000 V) LOAD
+

In this version is present obligatory the ARI-R15 adapter.


The connections of the relay output, remote reset and fail safe function remain the same while the connections to the network under control and
the earth reference has been changed.
----------------------------------------------------------------------------------------------------------------------------------------------------------
12
POWER SUPPLY AND NETWORK UNDER CONTROL CONNECTION - terminals 21-3 of the ARI-R15 adapter
At these terminals must be connected the negative and positive pole of the network to control.
------------------------------------------------------------------------------------------------------------------------------------------------------
GROUND REFERENCE CONNECTION - terminal 9 of the ARI-R15 adapter
----------------------------------------------------------------------------------------------------------------------------------------------------------
ARI-R15 AND RI-R15 1000V CONNECTIONS - Terminals 5-23-27 to connect between the control device and the adapter
Terminals to connect depending the network under control:

If the network voltage is exactly an expected value


tensione di rete ARI-R15 RI-R15 1000V
for two outputs (700 / 800 / 900V) it’s better to use
600÷700V dc terminals 28 - 10 terminals 25 - 7 the output with the upper nominal values.
700÷800V dc terminals 30 - 12 terminals 25 - 7
For example for a network at 800V is better to use
800÷900V dc terminals 32 - 14 terminals 25 - 7 the output with the terminals 32-14.
900÷1000V dc terminals 34 - 16 terminals 25 - 7

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-F22 series
RI-R22 series
RI-R38 series
INSULATION MONITORING - VERSIONS FOR NETWORKS ac MAX 400 V

GENERAL

These devices allow insulation monitoring on


earth of electric networks in alternating 230 V
and isolated 400 V (IT systems).
Insulation resistance monitoring is carried out
applying a measure’s signalling in direct-cur-
rent between isolated network and earth.
Surveying electric leakage set up on earth it’s
possible to measure insulation level.
Versions with fixed trip threshold are available
and they are very cheap.
MODELS
----------------------------------- -------------------------------------------------------- There are also versions with possibility of adju-
RI-F22 fixed threshold Vaux: 230 V 50-60 Hz (standard version) stable calibration of trip threshold.
RI-F22 fixed threshold Vaux: 110 V 50-60 Hz (optional version) On frontal panel, devices have signal for activi-
----------------------------------- --------------------------------------------------------
RI-R22 adjustable threshold Vaux: 230 V 50-60 Hz (standard version) ty ON, for TRIP (low insulation), a test button, a
RI-R22 adjustable threshold Vaux: 110 V 50-60 Hz (optional version) reset button (only for versions with adjustable
----------------------------------- -------------------------------------------------------- threshold) and a potentiometer for setting the
RI-R38 adjustable threshold Vaux: 230 V 50-60 Hz (standard version) threshold of tripping (model RI-R22) or micro
RI-R38 adjustable threshold Vaux: 110 V 50-60 Hz (optional version)
----------------------------------- -------------------------------------------------------- switches (model RI-R38).

FUNCTIONS AND OPERATORS - LEGEND


7 8 9 10 11 12

RI-R38
----------------------------------------------------------------
4 RI-R38
ON
1 1 LED ON green active device’s indication
INSULATION
MONITOR RESET ----------------------------------------------------------------
100
50
150
2 2 LED TRIP red signal of trip for low insulation 13
30
10 TEST
TRIP
----------------------------------------------------------------
kΩ con
contrel
ntrel 3 TEST button device functioning testing
5 3 ----------------------------------------------------------------
4 RESET button trip signalling reset (manual reset functions)
----------------------------------------------------------------
5 micro switches for trip threshold adjusting
1 2 3 4 5 6
----------------------------------------------------------------

RI-F22 / RI-R22
2 ----------------------------------------------------------------
1 Potentiometer for adjusting insulation’s resistance
(only for model RI-R22)
3 RI-R22 RI-F22
----------------------------------------------------------------
RESET
2 Manual resetting button (only for model RI-R22)
1
50
75
3 ----------------------------------------------------------------
3 Test button
25
kΩ
100 TRIP ON TEST TRIP ON TEST ----------------------------------------------------------------
4 con
contrel
ntrel contrel
con
ntrel
5 4 Signalling lamp of auxiliary supply (green LED)
----------------------------------------------------------------
5 4 5 Signalling lamp for relay tripped (red LED)
----------------------------------------------------------------

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-F22 series
RI-R22 series
RI-R38 series
INSULATION MONITORING
VERSIONS FOR NETWORKS ac MAX 400 V

ELECTRIC CHARACTERISTICS

Auxiliary supply voltage 230 V 50-60 Hz ± 20 % standard


110 V 50-60 Hz ± 20 % optional
Self-consumption 3 VA MAX
RI-F22 / RI-R22 24 ÷ 230 Vac +10 % (400 V on 3 phase network with neutral)
Network voltage
RI-R38 24 ÷ 440 Vac +10 % (760 V on 3 phase network with neutral)

Measure's voltage RI-F22 / RI-R22 12 V MAX


RI-R38 24 V MAX
Measure's current RI-F22 / RI-R22 0.1 mA MAX
RI-R38 0.5 mA MAX
Internal impedance RI-F22 / RI-R22 100 kohm
RI-R38 250 kohm
RI-F22 fixed 100 kohm
Tripping threshold setting RI-R22 adjustable 25 ÷ 100 kohm (by potentiometer)
RI-R38 adjustable 10 ÷ 150 kohm (4 levels by micro switches)
Tripping late about 1 second
led ON - led TRIP
Signals and operators
buttons TEST and RESET (RESET is not available for RI-F22)
Output relay switch contact NO-C-NC MAX 5 A 250 Vac
Working temperature - 10 …+ 60 °C
Storing temperature - 20 …+ 70 °C
Relative humidity < 90 %
Insulation test
Assembling position indifferent
Connection type by screw terminals - wire section MAX 4 mm2
Protection's degree IP 40 frontal with cap - IP 20 case
Mounting according with DIN 50022 easy connection snap on DIN rail 35 mm / 3 modules of 17.5 mm
Weight approximately 300 g
Standard reference CEI-EN 61010-1 / CEI-EN 61557-8 / VDE 0413 part.8 / CEI-EN 61326-1

DIMENSIONS

14 52,5 58
7 8 9 10 11 12

RI-R22
RESET
85,5

RI-R38
85

50 ON
INSULATION
45

75
MONITOR RESET

100 150
25 100 TRIP ON 50
kΩ TEST 30
TRIP
10 TEST
con
contrel
ntrel kΩ con
contrel
ntrel

1 2 3 4 5 6

64 44
52,5 68 65

RI-F22 | RI-R22 RI-R38

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-F22 series
RI-R22 series
RI-R38 series
INSULATION MONITORING
VERSIONS FOR NETWORKS ac MAX 400 V

WIRING DIAGRAMS - LEGEND

RI-F22 / RI-R22
--------------------------------------------------------------------------
AUXILIARY SUPPLY - terminals 1-3
RI-F22 / RI-R22 auxiliary supply available from under-control network
--------------------------------------------------------------------------
Vaux
INSULATION MONITORING - terminals 4-9
the two terminals have to be connected between under-control
network and measure’s referring earth (max. applicable voltage
1 2 3 4 5 6 7 8 9 10 11 12 between these terminals is 230 V, so it’s possible apply insulation
AUX1 AUX2 VC OUT-NC OUT-C OUT-NO PE RESET
monitoring on single phase networks till 230 V, three phase
networks three-wires without neutral till 230 V and three phase
networks with neutral till 400 V)
--------------------------------------------------------------------------
RELAYS’ OUTPUT CONNECTIONS - terminals 6-7-8
PE --------------------------------------------------------------------------
CONNECTIONS FOR REMOTE SIGNALLING
N by relays in switch voltage-free max 5 A 250 V on resistive load
--------------------------------------------------------------------------
L3 LOAD EVENTUAL CONNECTION FOR AUTOMATIC OR REMOTE RESET
L2 (only for RI-R22) it is required to connect a NC button between
terminal 10 and earth’s conductor PE and to link with a bond
L1 terminals 9 and 10 themselves
INSULATED LINE --------------------------------------------------------------------------
max 230 Vac EVENTUAL CONNECTION FOR REMOTE TEST
(only for version RI-R22) it is required to connect a NO button
between terminal 5 and earth’s conductor PE
--------------------------------------------------------------------------

RI-R38
--------------------------------------------------------------------------
RI-R38 AUXILIARY SUPPLY - terminals 1-3
auxiliary supply available from under-control network
Vaux --------------------------------------------------------------------------
INSULATION MONITORING - terminals 5-11
the two terminals have to be connected between under-control
1 2 3 4 5 6 7 8 9 10 11 12 network and measure’s referring earth. Terminal 5 has to be
AUX1 AUX2 VC OUT-NC OUT-C OUT-NO PE RESET connected between under-control network single phase or three phase
and neutral conductor. If three phase network is three-wire, the 15
terminal has to be connected to a phase. max. applicable voltage
between these terminals is 230 V, so it’s possible apply insulation
monitoring on single phase networks up to 440 V, three phase
PE networks three-wire without neutral up to 440 V and three phase
networks with neutral up to 760 V
--------------------------------------------------------------------------
N RELAYS’ OUTPUT CONNECTIONS - terminals 7-8-9
L3 --------------------------------------------------------------------------
LOAD CONNECTIONS FOR REMOTE SIGNALLING
L2 by relays in switch voltage-free max 5 A 250 V on resistive load
--------------------------------------------------------------------------
L1 CONNECTION FOR AUTOMATIC OR REMOTE RESET - terminal 12
INSULATED LINE --------------------------------------------------------------------------
max 440 Vac

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
ARI-R100 series
ADAPTER FOR NETWORKS TILL 1000 Vac
VOLTAGE ADAPTER FOR INSULATION MONITORING RI-R38

GENERAL

ARI-R100 is an adapter which allow the use of insu-


lation monitors RI-R38 on single phase and three
phase up to 1000 V 50-60 Hz.
the adapter have to be connected between RI-R38
insulation ralay and under-control network.
Under-control network could be three phase network
with neutral, three phase without neutral and single
phase network.
Maximum voltage has not to outweigh 1000 V 50-60
Hz (application of adapter for networks in direct-
current or with strong presence of direct-current
components is not possible).
ARI-R100 needs an auxiliary supply (normally the
same of RI-R38 relay).

MODELS
--------------- --------------------------------------------------------------------------------------
ARI-R100 Vaux: 230 V 50-60 Hz (standard version)
--------------- --------------------------------------------------------------------------------------
ARI-R100 Vaux: 110 V 50-60 Hz (optional version)
--------------- --------------------------------------------------------------------------------------

FUNCTIONS AND OPERATORS - LEGENDA

16
MADE IN EU

contrel ARI-R100
AUXILIARY VOLTAGE ADAPTER FOR RI INSULATION MONITOR

V aux: to RI LINE INPUT


230V 50-60Hz insulation monitor PE max. 1000V 50-60Hz

1 3 4 9 23

auxiliary
supply

connection to connection to connection to


RI-R38 reference earth line in check

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
ARI-R100 series
ADAPTER FOR NETWORKS TILL 1000 Vac
VOLTAGE ADAPTER FOR INSULATION MONITORING RI-R38

ELECTRIC CHARACTERISTICS

Input voltage of unde r-control network MAX 1000 V +20 % 50-600 Hz


Auxiliary supply 230 V 50-60 Hz ± 20 % standard or 110 V 50-60 Hz ± 20 % optional
Output voltage for RI-R22 MAX 230 V 50-60 Hz
Working temperature - 10 …+ 60 °C
Storing temperature - 20 …+ 70 °C
Relative humidity < 90 %
Insulation test 6 kV 60 sec
Assembling position indifferent
Connection type by screw terminals - wire section MAX 2.5 mm2
Protection's degree IP 40 frontal with cap - IP 20 case
Mounting according with DIN 50022 easy connection snap on DIN rail 35 mm / 3 modules of 17.5 mm
Standard reference CEI-EN 61010-1 / CEI-EN 61557-8 / VDE 0413 part.8 / CEI-EN 61326-1

WIRING DIAGRAMS
INSULATED LINE IT max 1000 V 50-60 Hz coupled to RI-R38
L1
L2
L3
N
PE
--------------------------------------------------------------
9 8 7 1112 9 23 AUXILIARY SUPPLY - terminals 1-3
PE LINE 230 V 50-60 Hz standard - optional 110 V 50-60 Hz
INPUT
output
--------------------------------------------------------------
relay Ω ARI-R100 Under-control network could be:
• three phase with neutral,
Vaux. Vaux.
RI-R38 • three phase without neutral shared or without neutral,
• single phase.
1 2 3 4 5 1 3 4 Maximum voltage has not to outweigh 1000 V 50-60 Hz.
--------------------------------------------------------------
Terminal 23 of connection between ARI-R100 and
V aux network could be connected single-phase or with neutral,
if shared
-------------------------------------------------------------- 17

DIMENSIONS
73

MADE IN EU

contrel ARI-R100
AUXILIARY VOLTAGE ADAPTER FOR RI INSULATION MONITOR
90 54
V aux: to RI LINE INPUT
230V 50-60Hz insulation monitor PE max. 1000V 50-60Hz

1 3 4 9 23

44
157,5 68

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R60 Series
DEVICE FOR INSULATION PERMANENT CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VAC

GENERAL

RI-R60 is a device that allows to control the insulation to earth in alternating


neutral networks up to 760 V (IT systems) in direct insertion and in network up
to 1000V with ARI-R60 adapter.
Putting a continuous component measure signal between the insulated line
and earth it’s possible to control the insulation resistance reading the disper-
sion current generated to earth.
These devices have two trip thresholds (ALARM and TRIP) adjustable using the
frontal micro-switches to signal when the insulation go under the threshold
level. The frontal LED signalling the trip. Two free voltage changeover contacts
relays allow the remote trip signalling. The relays can be programmed with the
fail safe (normally excited). The device is supplied on the front panel of a TEST
and a RESET push-buttons. The test can be activated thanks to the push-but-
ton on the device or to external push-button while the reset that can be set in
manual or in automatic and activated, as the test, with the local or remote
push-button.
The level of the insulation resistance is displayed on the bar LED on the front
panel with scale 5-500 kohm at 8 point.

MODELS
----------------- ---------------------------------------------------------------------------------------------------------------------
RI-R60-760 network voltage 760Vac max , Uaux 110-230V 50-60 Hz (100÷130 / 220÷240V ± 10%)
----------------- ---------------------------------------------------------------------------------------------------------------------
RI-R60-1000 network voltage 1000Vac max (with ARI-R60 adapter), Uaux 110-230V 50-60 Hz (100÷130 /
220÷240V ± 10%)
----------------- ---------------------------------------------------------------------------------------------------------------------

INSTALLATION
The installation must be carried out by qualified and authorized person- The device is a 6 modules (17.5mm) DIN version with snap on 35mm DIN
nel and in absence of voltage. Make sure that the instrument is O.K. and rail. It has a sealable transparent frontal protection cover.
it has not suffered any damage during transport. Make sure that the vol- The green LED ON will bright after the connections are set and the instru-
tage supply are compatible with the operating voltage of instrument. ment is power on.

FUNCTIONS AND OPERATORS - LEGEND


18
--------------------------------------------------------------------------------
8 9 3 1 Pulsante di RESET. Questo pulsante ha effettiva funzionalità solo se
impostato il funzionamento in RESET manuale.
--------------------------------------------------------------------------------
2 RESET push-button. Only when it’s set the manual reset functioning this
push-button is enable.
--------------------------------------------------------------------------------
3 TEST push-button. Pressing the TEST push-button cause the tripping of the
ALARM and the TRIP and the output relay commute.
4 --------------------------------------------------------------------------------
2 4 LED ON to signal the device turned ON.
--------------------------------------------------------------------------------
6 5 LED TRIP for the signalling overcoming the TRIP threshold.
1 --------------------------------------------------------------------------------
6 LED ALARM for the signalling overcoming the ALARM threshold.
--------------------------------------------------------------------------------
7 LED bar to indicate the measured insulation resistance level. With all LED
on the insulation level is lower than 5 kohm, with all led off the insulation
7 level upper is than 500 kohm.
--------------------------------------------------------------------------------
8 terminals board
--------------------------------------------------------------------------------
9 micro-switches to set the alarm threshold
5 --------------------------------------------------------------------------------
10 micro-switches to set the trip threshold
--------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R60 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC

ELECTRIC CHARACTERISTICS

TYPE RI-R60
Auxiliary power supply 110-230Vac (100÷130V / 220÷240V +-10%) 50-60Hz
Maximum consumption max 5 VA
Network to control 50-760Vac (50÷1000Vac with ARI-R60 adapter)
Measure voltage max 48Vdc
Measure current max 240 µA dc
Internal impedance 200 kΩ
Tripping delay max 5 seconds
Signalling led ON, led ALARM, led TRIP, measuring LED bar 5-500Kohm
Setting threshold tripping ALARM 300 ÷ 30 kohm (5 levels selectable with micro-switches)
Setting threshold tripping TRIP 100 ÷ 10 kohm (5 levels selectable with micro-switches)
Relay output ALARM: changeover contact NA-C-NC
TRIP: changeover contact NA-C-NC
Relay contacts 5 A 250Vac .
functions Fail safe function for both outputs, manual or automatic reset,
local and remote test and reset push-button
Working temperature -10 ÷ 60°C
Storing temperature -20 ÷ 70°C
Relative humidity ≤ 95 %
Insulation test 3 kV 60 sec. / 4 kV imp. 1,2/50µs
Mounting position Any
Wiring type Screw terminals / cross section cables 4 mm2
Protection degree Frontal with cover: IP 40 – Enclosure: IP 20
Mounting according DIN 50022 Snap on DIN rail 35mm / 6 modules 17,5 mm
Weight About 0,5 kg
Standards Safety CEI-EN 61010-1 / Product CEI-EN 61557-8 /
Electromagnetic compatibility CEI-EN 61326-1 CEI-EN 61326-2-4 CEI 64-8

DIMENSIONS 19

28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

contrel ON <5

TRIP 10

ALARMkΩ TRIP kΩ
TEST 300 ALARM 20
contrel
150 100 60
ARI-R60 80
50
40
20 40

90 INSULATION MONITOR VOLTAGE ADAPTER 30 10 60 90 45
off F.S.on off F.S.on
max 1000Vac man auto man auto 100
RESET
RESET RESET 200

RI-R60 insulation monitor relay 500

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

157,5 105 73

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R60 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC

WIRING CONNECTION LINE 760 Vca MAX - LEGEND

-----------------------------------------------------
AUXILIARY POWER SUPPLY Vaux: * VC
Terminals 1-2-3-4 115V 115V 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

The supply section is a double input at 115V VC

(100÷130V 50-60Hz). AUX-L1 AUX-01 AUX-L2 AUX-02


network RI-R60
insulation
INSULATION MONITOR
To supply the instrument at 230V (220÷240V 50- control

60Hz) connect the two section in series. output relays


To supply the instrument at 115V connect the two PE remote TRIP ALARM
Vaux: * conn. test reset
section in parallel. power supply 115V 115V
115Vca
----------------------------------------------------- 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
INSULATION CONTROL AUX-L1 AUX-01 AUX-L2 AUX-02 PE PE TEST RESET T-NC T-C T-NO A-NC A-C A-NO

Terminals (6/7) -22 power supply


230Vca
The two terminals must be connected between the
line under control and the earth of measure referen-
ce. The double terminal 6/7 (connected internal)
must be connected to the earth reference while the
terminal 22 must be connected to the single-phase
line to control or to the neutral conductor in a three- PE
phase line. On this terminals is possible to connect
voltage up to 760Vac. For this reason it’s possible
to use this device on single phase line up to 760V,
on three-phase line at 3 wires without neutral up to N
760V and on three-phase line at 4 wires with neu- L3 LOAD
tral up to 1100V. L2
-----------------------------------------------------
L1 INSULATED LINE (IT) max 760 VL-N (1100 V L-L)
ALARM RELAY OUTPUT CONNECTIONS (ALARM)
Terminals 16-17-18
Connections to remote signalling thanks to free vol-
tage changeover contact, max 5A 250V on resistive Single-phase line Three phase line Three phase line
load. without neutral with neutral
----------------------------------------------------- Max 760V L-N Max 760V L-L Max 1100V L-L

TRIP RELAY OUTPUT CONNECTIONS (TRIP) L3 L3


N
Terminals 12-13-14 L L2 L2
Connections to remote signalling thanks to free vol- L1 L1
tage changeover contact, max 5A 250V on resistive
N
load.
20 -----------------------------------------------------
VC VC VC
REMOTE TEST CONNECTION 19 20 21 22 23 24 19 20 21 22 23 24 19 20 21 22 23 24
Terminal 8 VC VC VC
It’s possible to connect a remote push-button with
a normally open contact between the control device
and the earth reference.
-----------------------------------------------------
REMOTE RESET CONNECTION
Terminal 9
For the RESET function from external signal it’s possible to connect a push-button with normally open contact on the connection between the control
device and the earth reference.
----------------------------------------------------------------------------------------------------------------------------------------------------------

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R60 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC

WIRING CONNECTION LINE 1.000 Vca MAX - LEGEND

-----------------------------------------------------------------------
AUXILIARY POWER SUPPLY - TERMINALS 1-2-3-4 VC
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
The supply section is a double input at 115V (100÷130V 50-60Hz).
to adapter ARI-R60
To supply the instrument at 230V (220÷240V 50-60Hz) connect the (VC insulation control RI-R60
line 1000V)
two section in series. INSULATION MONITOR

To supply the instrument at 115V connect the two section in parallel. output relays
----------------------------------------------------------------------- PE remote TRIP ALARM
Vaux: * conn. test reset
INSULATION CONTROL - TERMINALS (6/7) -22 115V 115V

The two terminals must be connected between the line under control 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
AUX-L1 AUX-01 AUX-L2 AUX-02 PE PE TEST RESET T-NC T-C T-NO A-NC A-C A-NO
and the earth of measure reference.
The double terminal 6/7 (connected internal) must be connected to
the earth reference while the terminal 22 must be connected to the
ARI-R60 adapter power supply
230Vca
-----------------------------------------------------------------------
ALARM RELAY OUTPUT CONNECTIONS (ALARM) - TERMINALS 16-17-18 Vaux: *
115V 115V ARI-R60
Connections to remote signalling thanks to free voltage changeover ADAPTER
contact, max 5A 250V on resistive load. AUX-L1 AUX-01 AUX-L2 AUX-02

-----------------------------------------------------------------------
TRIP RELAY OUTPUT CONNECTIONS (TRIP) - TERMINALS 12-13-14
24 23 9 4
Connections to remote signalling thanks to free voltage changeover PE
contact, max 5A 250V on resistive load. power supply
115Vca
-----------------------------------------------------------------------
REMOTE TEST CONNECTION - TERMINAL 8
PE
It’s possible to connect a remote push-button with a normally open
contact between the control device and the earth reference. N
----------------------------------------------------------------------- L3 LOAD
REMOTE RESET CONNECTION - TERMINAL 9 L2
For the RESET function from external signal it’s possible to connect a L1 INSULATED LINE (IT) max 1000 V 50-60Hz
push-button with normally open contact on the connection between
the control device and the earth reference.
-----------------------------------------------------------------------

21
FUNZIONALITY
In normally condition with the insulation value upper than alarm and trip Depending the set of the micro-switches the RESET can be automatic
thresholds the green LED of the device is turned on and the status of the when the TEST push-button is released or manual with the local or remo-
bar led depending of the insulation resistance level measured (with all te RESET push-button.
led off the insulation value is upper than 500 kohm, with all LED on the In case of low insulation on the line (insulation resistance value lower
measured LED lower than 5 kohm). than threshold set) the ALARM and possibly the TRIP signalling will be
By pressing the TEST push-button at least 5 seconds (delay time) the activated as the correspondent output relays. The Signalling will disap-
alarm and trip signalling with relative LED will be activated, the output pear only after that on the line come back an insulation level upper than
relays commute and the LED bar turn on (simulated value lower than 5 the threshold set.
kohm).

NOTES - It’s not possible to use more than one instrument on a line because the measure of the resistance could be not correct for the overlap of
the signal.
The presence of strong continuous component on the network under control could create some problems for the correct functioning of the device.

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-SM series
INSULATION MONITORING
VERSIONS FOR OUT-VOLTAGE NETWORK

GENERAL

The devices allow insulation monitoring to earth of out-voltage networks


in order to carry out a preventive monitoring on insulation level of devi-
ce. Preventive monitoring is really important in case of applications
which are not used permanently (for example: motors, fire-engines, and
so on). In these applications, humidity and condensate can cause a
serious decrease in insulation’s level and obstruct correct functioning at
the moment of applications’ activation.
Insulation resistance’s monitoring is carried out applying a measure’s
signalling in direct-current component between isolated network and
earth. Surveying leakage current to earth it’s possible to measure insu-
lation’s level.
This device allow regulation of trip threshold by micro switches.
Devices have on frontal panel signal of active device ON, signal TRIP
(low insulation), a test button and micro switches series for regulating
trip threshold.

MODELS
--------------- --------------------------------------------------------------------------------------
RI-SM Vaux: 230 V 50-60 Hz (standard version)
--------------- --------------------------------------------------------------------------------------
RI-SM Vaux: 115 V 50-60 Hz (optional version)
--------------- --------------------------------------------------------------------------------------

FUNCTIONS AND OPERATORS - LEGEND DIMENSIONS

7 8 9 10 11 12

22
52,5 58
1 RI-SM
2 44
ON INSULATION TRIP
MONITOR
10 7 8 9 10 11 12
7,5 0,5

4 5
2,5
TEST
0,25
0,1
1
MΩ
ON OFF
FAIL SAFE 3
contrel

RI-SM
ON
85,5

INSULATION TRIP
45

1 2 3 4 5 6 MONITOR
10
7,5 0,5
5 0,25
2,5 0,1
1 TEST ON OFF

------------------------------------------------------------------------------------ MΩ
FAIL SAFE

1 green led ON indication of active device contrel


------------------------------------------------------------------------------------
2 red led TRIP trip signal for low insulation
------------------------------------------------------------------------------------ 1 2 3 4 5 6
3 test button for testing device’s serviceability
------------------------------------------------------------------------------------ 65
4 micro switches for selecting trip threshold
------------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-SM series
INSULATION MONITORING
VERSIONS FOR OUT-VOLTAGE NETWORK

ELECTRIC CHARACTERISTICS

Auxiliary supply 230 V 50-60 Hz ± 20 % 115 V 50-60 Hz ± 20 % (optional)


Self-consumption 5 VA MAX
Network voltage MAX 700 Vac/dc
Voltage's measure 20 V MAX
Current's measure 15 µA dc MAX
Internal impedance dc 1.5 Mohm - ac 1 Mohm
Trip threshold 0.1 - 0.25 - 0.5 - 1 - 2.5 - 5 - 10 Mohm (by microswitch)
Delay trip 1 - 2.5 sec
Type of monitoring signal direct current component
auxiliary output relay with possibility of fail safe function programming
Output
NO-C-NC MAX 5 A 250 Vac - It could be activated for low insulation
Visualizations green led ON - red led TRIP
Working temperature - 10 …+ 60 °C
Storing temperature - 25 …+ 70 °C
Relative humidity < 95 %
Insulation test 2.5 kV 60 sec
Assembling position indifferent
Connection type by screw terminals - wire section MAX 2.5 mm2
Protection's degree IP 50 frontal with cap (sealable) - IP 20 case
Mounting according with DIN 50022 easy connection snap on DIN rail 35 mm / 3 modules of 17.5 mm
Weight approximately 100 g
Standard reference CEI-EN 61010-1 / CEI-EN 61557-8 / VDE 0413 part.8 / CEI-EN 61326-1

WIRING DIAGRAMS

RI-SM
Vaux

1 2 3 4 5 6 7 8 9 10 11 12 23
AUX1 AUX2 VC OUT-NO OUT-C OUT-NC PE RESET
---------------------------------------------------------------------------
AUXILIARY SUPPLY - terminals 1-3
auxiliary supply available from under-control network
---------------------------------------------------------------------------
INSULATION MONITORING - terminals 5-11
both terminals have to be connected between under-control network
PE and referring earth.
Terminal 5 have to be connected to under-control network single phase
N or three phase and to neutral conductor. If three phase network is three
wires, it is required to connect single phase network.
Maximum applicable voltage between these terminals is 700 V ac/dc.
LOAD

L3 ---------------------------------------------------------------------------
CONNECTIONS RELAY OUTPUT - terminals 7-8-9.
L2 connections for remote signal by relay with switch voltage-free,
max 5 A 250 V on resistive load
---------------------------------------------------------------------------
L1

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS

GENERAL
Devices allow insulation monitoring for IT systems in medical use rooms, codified signal between the secondary of insulation and device’s unipo-
as well as hospital and ambulatory clinic, in compliance with standard tential node. In case of failure to earth, it surveys current flowing inside
IEC 60364-7-710. the relay and correspondent insulation resistance of device.
Measure’s modality consist in application of a direct-current voltage or

MODELS
HRI-R40 network voltage 230 Vac, auxiliary supply 110-230 Vac
HRI-R40W network voltage 230 Vac, auxiliary supply 110-230 Vac
----------------- ---------------------------------------------------------------------------------------------------------------------
HRI-R22t network voltage 230 Vac, auxiliary supply 230 Vac
----------------- ---------------------------------------------------------------------------------------------------------------------
HRI-R24 network voltage 240 Vac/dc, auxiliary supply 24 Vac/dc

HRI-R22t HRI-R24
HRI-R40W
HRI-R40

ACCESSORIES

PR5 remote signalling panel for wall mounted (universal box E503) coupled
with HRI-R22t, HRI-R24, HRI-R40 e HRI-R40W
(indication of low insulation ALARM and overload and over temperature).

PR 5

24

OPTIONAL (only for HRI-R40 and HRI-R40W)


T2 second temperature input from PT100 or PTC probe
----------------- ---------------------------------------------------------------------------------------------------------------------
S serial output RS485 bidirectional with MODBUS-RTU protocol communication

----------------- ---------------------------------------------------------------------------------------------------------------------
* On requested, insulation’s transformers single phase and three phase are available
for hospital use 230 V / 230 V and 230 V / 24 V up to power 10 kVA.
(for information please contact our sales dept.)

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R40 series
HRI-R40W series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS

GENERAL

HRI-R40 series
This device allow insulation monitoring to earth of supply network and Device has two input of temperature’s measure (one is optional) for tem-
thermal and electric overcharge monitoring of transformer. perature’s probe PT100 or PTC (DIN 44081) for monitoring thermal over-
This works in order to serve everything requested in specific standard charge of insulation’s transformer.
regulation for these applications. There is also a input of current’s measure of current transformer for
Insulation’s resistance monitoring is carried out applying a measure’s monitoring overcharge on network.
signalling between isolated network and earth. Signalling output are apt for coupling with specific panels of signalling
Surveying leakage generated to earth it’s possible to measure insulatio- and remote monitoring PR5 (max 2 panels, on request 4 panels).
n’s level. There is also a output for relay voltage-free with functions adjustable by
Modern and sophisticated measure’s techniques integrated allow correct the user.
measure of insulation’s resistance level also in case of strong obstruc- Optionally it’s available a serial output RS485 for bidirectional commu-
tions, with high harmonic and direct-current components. nication with monitoring system (PLC, PC, and so on). 25
HRI-R40 model uses a monitoring signalling with direct-current compo- Communication’s protocol used is MODUBUS-RTU.
nent. For reducing problems caused by the presence of direct-current Specific characteristics make these devices conform to standard regula-
components on network (rectifiers), device has a digital filter which is tion:
able to divide the majority of direct-current from eventual direct-current EN 61557-8
components in network. IEC 60364-7-710
HRI-R40 could set a large number of programming possibilities with VDE 0100 part 710
frontal button and 3 digit digital display for visualising measuring and CEI 64.8/7-710 V2
programming parameters. UNE 20615.

HRI-R40W series
HRI-R40W version has same fundamental characteristics of previous Actually presence in network of strong distortions with high harmonic
model but it uses particular measuring technique applying a measure’s components (sub harmonic) and direct-current components could cause
signal codified and varying, in order to guarantee a correct measure of measure’s problems to others techniques.
insulation independently from under-control network type. This solution allow the using of HRI-R40W in network with rectifiers,
power’s electronics, variable-speed drive and so on.

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R40 series
HRI-R40W series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS

FUNCTIONS AND OPERATORS - LEGEND

------------------------------------------------------------------------------------
1 display for visualising under-control parameters’ degree and for
visualising settings
------------------------------------------------------------------------------------
2 green LED SET for indication of programming status
------------------------------------------------------------------------------------
3 yellow LED ALARM for indication alarm for parameter’s
degree out-threshold
2 3 4 5 ------------------------------------------------------------------------------------
4 red LED OUTPUT RELAY for indication status of auxiliary relay output
------------------------------------------------------------------------------------
5 red LED ERROR / LINK FAIL for indication alarm of internal failure,
lack connection to under-control network, temperature’s probe
PT100 open or short circuit
contrel insulation monitor HRI-R40 ------------------------------------------------------------------------------------
1
SET ALARM OUTPUT ERROR /
6 red LED R for indication visualisation of insulation’s resistance
6 RELAY LINK FAIL
parameter; flashing light for out-threshold parameter
R [kΩ]
Z [kΩ] MIN / MAX
------------------------------------------------------------------------------------
7 T1 [°C] 7 red LED Z for indication visualisation of insulation’s impedance
T2 [°C]
+
_ RESET
SET
TEST
ENTER parameter; flashing light for out-threshold parameter.
8 I [A]
------------------------------------------------------------------------------------
9 8 red LED T1 for indication visualisation parameter of transformer’s
temperature; flashing light for out-threshold parameter.
10 ------------------------------------------------------------------------------------
9 red LED T2 for indication visualisation parameter of second sensor
temperature; flashing light for out-threshold parameter.
------------------------------------------------------------------------------------
11 12 13 10 red LED I for indication visualisation current of network parameter;
flashing light for out-threshold parameter.
------------------------------------------------------------------------------------
11 button +/- UP/DOWN for selecting parameter that has to be
visualised, for regulating device’s setting and for visualising
maximum and minimum memorized degrees
------------------------------------------------------------------------------------
12 button RESET / SET for entering device’s programming, for stopping
alarms and memorized degrees resetting
------------------------------------------------------------------------------------
13 button TEST / ENTER for testing device and remote signalling panels
and for confirming SETUP settings
------------------------------------------------------------------------------------

DIMENSIONS
26 74

contrel insulation monitor HRI-R40

SET ALARM OUTPUT ERROR /


RELAY LINK FAIL

90 R [kΩ]
45
Z [kΩ] MIN / MAX
T1 [°C]
T2 [°C]
+
_ RESET
SET
TEST
ENTER
I [A]

44
105 68 HRI-R40 / HRI-R40W

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R40 series
HRI-R40W series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS

ELECTRIC CHARACTERISTICS

TYPE HRI-R40 HRI-R40W


Auxiliary supply 110 - 230 V ±20% 110 - 230 V ±20%
Frequency 50 ÷ 60 Hz 50 ÷ 60 Hz
Self-consumption 5 VA 5 VA
Unde-control network voltage 24 ÷ 230 V 50 ÷ 60 Hz 24 ÷ 230 V 50 ÷ 60 Hz
Voltage's measure 24 V 24 V
Current's measure 1 mA 1 mA
Internal impedance for resistive measure 200 kohm 200 kohm
Selectable trip threshold 50 ÷ 500 kohm (low insulation)
hysteresis 10 % 20 ÷ 180 °C (over-temperature)
precision 2 % - 1 ÷ 99.9 A (over-current)
precision 2 % - delay 1 ÷ 60 sec
Visualisation insulation and impedance’s degree by three digits display 1 ÷ 999 kohm
temperature’s degree 0 ÷ 200 °C (1st and 2nd probe) by display
current’s value 0 ÷ 99.9 A by display
parameters’ configuration
output status:
- signalling alarms’ led
- led of signalling output of active relays
- led of failed insertion signalling

Output for PR5 (max 5) panel + 1 contact NO-C-NC 5 A - 250 V


low insulation, overload
+ option serial RS485 MODBUS-RTU
Input from isolated network 230 Vac (insulation measure)
1st probe PT100 2 or 3 wires (temperature measure) 30 ÷ 200 °C ±2%
2nd probe PT100 2 or 3 wires (temperature measure) (OPTIONAL) 30 ÷ 200 °C ±2%
CT (overload current’ measure max 5 A precision 2 %
current transformer ratio selectable 1 ÷ 40
Voltage of signal circuit < 24 Vdc < 24 Vdc
Measure’s method signalling dc codified and varying signal
Insulation’s test 2.5 KV 60 sec
Working temperature -10 ÷ 60 °C
Storing temperature -20 ÷ 80 °C
Relative humidity MAX 90 % 27
Standard regulation CEI-EN 61010-1 / CEI-EN 61557-8 / VDE 0413 part.8 / CEI 64.8/7-710 V2
IEC 60364-7-710 / VDE 0100 part.710 / UNE 20615 / CEI-EN 61326-1
Assembling according to DIN 50022 snap on DIN rail 35 mm
Dimensions 6 modules DIN 17.5 mm
Protection’s degree IP50 frontal - IP20 case
Connections by screw terminals max 2.5 mm2

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R40 series
HRI-R40W series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS

WIRING DIAGRAMS - LEGENDA HRI-R40AND HRI-R40W

PT100

PT100
A B C PT2+A PT2+B PT2- PT1+A PT1+B PT1- CT-S2 CT-S1 R-NO R-C R-NC

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

RS485 input 2 input 1 input 2


serial port probe probe current relay aux
(optional) PT100 PT100 TA .../5A output
remote panel
(o PTC) (o PTC)
HRI-R40 PR5

Vaux: * link fail insulation


115V 115V check check remote check panel
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 COM-S F-S V-P ACUS ACK OVER FAULT COM-P TEST- TEST-S TEST+
AUX-L1 AUX-01 AUX-L2 AUX-02 LF-PE LF-L VC-L VC-PE TEST+ TEST- ACK ACUS OVER COM-P V-P FAULT

auxiliary
supply
Vaux: 230 Vac

PE

TO OTHER
REMOTE
PANELS PR5
S S

L
INSULATION PC
TRANSFORMER INSULATED LINE (IT-M) LOAD
N

-----------------------------------------------------------------------------------------------------------------------------------------------------------
AUXILIARY SUPPLY - TERMINALS 1-2-3-4
supply’s section is carried out with double input 115 V nominal
for device supplying with 230 V, it is required to connect both sections in series
for device supplying with 115 V, it is required to connect both sections in parallel
-----------------------------------------------------------------------------------------------------------------------------------------------------------
LINK-FAIL MONITORING - TERMINALS 6-7
both terminals have to be connected between a isolated network’s phase and unipotential node (PE)
Maximum applicable voltage is 250 V (see insulation’s monitoring)
-----------------------------------------------------------------------------------------------------------------------------------------------------------
INSULATION’S MONITORING - TERMINALS 8-9
both terminals have to be connected between centre tap of secondary transformer or a isolated network’s phase and unipotential node (PE)
Maximum applicable voltage is 230 Vca so single phase networks could have max voltage of 230 V, three phase networks three wires
could have max voltage of 230 V phase-phase; but three phase networks four wires could have max voltage of 230 V phase-neutral
-----------------------------------------------------------------------------------------------------------------------------------------------------------
REMOTE PANEL’S CONNECTIONS PR5 - TERMINALS 10-11-12-13-14-15-16-18
connections for linking to remote panels PR5, Max voltage on these conductors is 24 V
-----------------------------------------------------------------------------------------------------------------------------------------------------------
SERIAL PORT RS485 (OPTIONAL) - TERMINALS 19-20-21
28 terminals A-B (19-20) head to serial bus, terminal C (21) is a mass’ reference that could be connected to eventual screen of cable RS485
Standard protocol used is modbus-rtu, documented in a specific handbook [IM833-U]
-----------------------------------------------------------------------------------------------------------------------------------------------------------
INPUT TEMPERATURE PROBE 2 (OPTIONAL) - TERMINALS 25-26-27
connections for linking to a temperature’s sensor - PT100 (EN 60751) or PTC (DIN 44081) sensor could be used.
In case of PT100 probes three wires, it is required to connect compensation’s conductor to the same terminal of correspondent conductor.
In case of PTC, it is necessary external resistor of 120 ohm min 1/4 W
-----------------------------------------------------------------------------------------------------------------------------------------------------------
INPUT TEMPERATURE PROBE 1 - TERMINALS 28-29-30
connections for linking to a temperature’s sensor - PT100 (EN 60751) or PTC (DIN 44081) sensor could be used.
In case of PT100 probes three wires, it is required to connect compensation conductor to the same terminal of correspondent conductor.
In case of PTC, it is necessary external resistor of 120 kohm min 1/4 W
-----------------------------------------------------------------------------------------------------------------------------------------------------------
INPUT FOR CURRENT MEASURE - TERMINALS 31-32
connection for external current transformer with secondary 5 A (current transformer ratio is programmable); if there is 3-phase network
must be used the special adapter type TSA-03 for 3 current transformer to permit to monitor in the insulation relay the highest value
of the 3-phase currents.
Only the module of the current value is measured (i.e. it is not important S1-S2 connection sequence).
-----------------------------------------------------------------------------------------------------------------------------------------------------------
OUTPUT AUXILIARY RELAY - TERMINALS 34-35-36
switch contact free from voltage and with programmable functions. Contact’s performance MAX 250 V 5 A resistive load
-----------------------------------------------------------------------------------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R22t series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS

GENERAL

HRI-R22t series
The device has similar characteristics of previous model but it’s more
cheap and it has less functions.
There is measuring signalling and it is able to verify temperature of
insulation’ power transformer (1 PTC input with contact NO or NC direc-
tly supplied by device) and insulation’s level.
These inputs are available: for remote repeaters panels PR2 and PR2-t
and 1 relay NO-C-NC, that is activate when fixed threshold (insulation
and temperature) are over-ride. HRI-R22t has frontally a bar led for
visualising insulation’s level of device and eventual alarm’s presence is
visualised frontally by led.
Testing button is available and it works for monitoring insulation’s level
preset with calibration on relay (for example, with 50 kohm calibration
all the led with inferior limit of 50 kohm will light during the test).
This button monitors eventual remote reply panels PR-5 (max 2 panels).

FUNCTIONS AND OPERATORS - LEGEND

------------------------------------------------------------------------------------
3 4 6 1 TEST PUSHBUTTON
------------------------------------------------------------------------------------ 29
2 MICRO SWITCH for threshold set
- turning the switch to right, corresponding insulation’s resistance
degree has to be digit, highest degree heads
- with all the switches turned to left, fixed degree of 50 kohm
doesn’t change
contrel HRI-R22t insulation monitor ------------------------------------------------------------------------------------
2 3 LED signalling supplied relay
ON ALARM Link Fail

1 TEST
------------------------------------------------------------------------------------
4 LED signalling pre-fixed insulation’s threshold reached
SET ------------------------------------------------------------------------------------
alarm 50 kΩ 100 kΩ 250 kΩ 500 kΩ 1 MΩ >1 MΩ
Temp. 5 LED signalling temperature’s threshold reached
------------------------------------------------------------------------------------
6 LED signalling relay connected correctly
------------------------------------------------------------------------------------
7 LED signalling instant insulation’s value of device,
identified by lowest degree between active led
------------------------------------------------------------------------------------
5 7

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R22t series
INSULATION MONITORING
VERSIONS FOR MEDICAL USE ROOMS

ELECTRIC CHARACTERISTICS

TYPE HRI-R22t
Auxiliary supply 230 V ± 20%
Frequency 50 ÷ 60 Hz
Self-consumption 3 VA
Unde-control network voltage 24 ÷ 230 V 50 ÷ 60 Hz
Voltage's measure < 15 V
Current's measure < 0.6 mA
Internal impedance for resistive measure 1 Mohm
Selectable trip threshold 50-100-250 kohm (low insulation) by switches

Visualisation led of insulation value by led bar 50 ÷ 1000 kohm


led of signalling network’s presence
led of signalling low insulation
led of signalling over-temperature
led of failed insertion signalling

Output for panel PR5 (max 2) total


+ 1 contact NO-C-NC 5 A - 250 V (low insulation)
+ 1 contact NO-C-NC 5 A - 250 V (over-temperature )
Input from isolated network 230 Vac (insulation measure)
PTC probe (temperature measurement)

Voltage of signal circuit < 24 Vdc


Measure’s method signalling dc
Insulation’s test 2.5 kV 60 sec
Working temperature -10 ÷ 60 °C
Storing temperature -20 ÷ 80 °C
Relative humidity MAX 90 %
Standard regulation CEI-EN 61010-1 / CEI-EN 61557-8 / VDE 0413 part.8
CEI 64.8/7-710 V2 / IEC 60364-7-710 / UNE 20615 / CEI-EN 61326-1
Assembling according to DIN 50022 snap on DIN rail 35 mm
Dimensions 6 modules DIN 17.5 mm
Protection’s degree IP50 frontal - IP20 case
30
Connections by screw terminals max 2.5 mm2

DIMENSIONS

contrel HRI-R22t insulation monitor

ON ALARM Link Fail


TEST 90

SET
alarm 50 kΩ 100 kΩ 250 kΩ 500 kΩ 1 MΩ >1 MΩ
Temp.

105 58

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R22t series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS

WIRING DIAGRAMS - LEGEND

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

remote input
check panel relay thermostat
HRI-R22t temperature
remote panel
output
relay aux PR5
output
Vaux: * link fail insulation remote
230V check check check panel

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11
AUX-L1 AUX-01 LF-L LF-PE VC-L VC-PE COM-P FAULT V-P R-NC R-NO R-C COM-S F-S V-P ACUS ACK OVER FAULT COM-P TEST- TEST-S TEST+

auxiliary
supply
Vaux: 230 Vac

PE

TO OTHER
REMOTE
PANELS PR5
S S

L
INSULATION PC
INSULATED LINE (IT-M) LOAD
TRANSFORMER
N

---------------------------------------------------------------------------------------------------------------------------------------------------
31
AUXILIARY SUPPLY - TERMINALS 1-3
---------------------------------------------------------------------------------------------------------------------------------------------------
MONITORING INSULATION - TERMINALS 5-9
both terminals have to be connected between centre tap of secondary transformer or isolated network’s phase and unipotential node (PE).
Maximum voltage applicable is 230 Vca. Consequentially single phase networks could be maximum 230 V, three phase networks of three
wires is 230 V phase-phase but three phase networks four wires is max 230 V phase-neutral
---------------------------------------------------------------------------------------------------------------------------------------------------
CONNECTIONS FOR REMOTE PANELS PR5 - TERMINALS 12-13-14-26
---------------------------------------------------------------------------------------------------------------------------------------------------
INPUT THERMAL PROBE - TERMINALS 33-34 or 35-36.
PTC (DIN 44081) probe could be used
---------------------------------------------------------------------------------------------------------------------------------------------------
AUXILIARY RELAY OUTPUT - TERMINALS 29-30-31
contact in switch voltage-free with programmable functions. Contact’s capacity 250 V 5 A resistive load
--------------------------------------------------------------------------------------------------------------------------------------------------

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R24 series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS

GENERAL

HRI-R24 series
For monitoring 24 V networks (scialytic lamps), monitor HRI-R24 is used.
This is able to supply insulation’s control adjustable by frontal potentio-
meter. Frontally there is also testing button for allowing the test of devi-
ce’s correct functionality and eventual remote repeaters panels.
Outputs are available for remote repeaters panels PR-5 (max 2 panels).

FUNCTIONS AND OPERATORS - LEGEND

2 ------------------------------------------------------------------------------------
1 Potentiometer for regulating trip threshold
INSULATION
------------------------------------------------------------------------------------
HRI-R24 MONITORING 2 Button of manual resetting
3 RESET
30 ------------------------------------------------------------------------------------
1 20
40
3 Test pushbutton
10
kΩ
50 TRIP ON TEST
------------------------------------------------------------------------------------
4 4 LED signalling supplied relay
con
contrel
ntrel ------------------------------------------------------------------------------------
5 5 LED signalling pre-fixed threshold reached
------------------------------------------------------------------------------------

32

DIMENSIONS

INSULATION
HRI-R24 MONITORING
RESET
85

30
40
20

10 50 TRIP ON
kΩ TEST

con
contrel
ntrel

64
52,5 68

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R24 series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS

ELECTRIC CHARACTERISTICS

TYPE HRI-R24
Auxiliary supply 24 Vdc/ac -20 % +10 %
Frequency 50 ÷ 60 Hz
Self-consumption 3W
Unde-control network voltage 24 Vdc/ac 50 ÷ 60 Hz
Current's measure < 0.5 mA
Internal impedance for resistive measure 50 kohm
Internal impedance for resistive measure 10 ÷ 50 kohm (by potentiometer)
Visualisation led of signalling network’s presence
led of signalling low insulation
Output for PR5 panel (max 2)
Input from isolated network 240 Vac/dc (insulation measure)
Voltage of signal circuit < 24 Vdc
Measure’s method variation of polarity’s potential
Insulation’s test 2.5 kV 60 sec
Working temperature -10 ÷ 60 °C
Storing temperature -20 ÷ 80 °C
Relative humidity MAX 90 %
Standard regulation CEI-EN 61010-1 / CEI-EN 61557-8 / VDE 0413 part.8
CEI 64.8/7-710 V2 / IEC 60364-7-710 / UNE 20615 / CEI-EN 61326-1
Assembling according to DIN 50022 snap on DIN rail 35 mm
Dimensions 3 modules DIN 17.5 mm
Protection’s degree IP50 frontal - IP20 case
Connections by screw terminals max 2.5 mm2

WIRING DIAGRAMS - LEGEND

insulation check remote panel


HRI-R24 PR5

1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 11
V+ V- OUT-NO OUT-C OUT-NC PE COM-S F-S V-P ACUS ACK OVER FAULT COM-P TEST- TEST-S TEST+

33

PE

TO OTHER
S S REMOTE
PANELS PR5

L(+)
INSULATED LINE 24V ca/cc LOAD
N(-)

INSULATION TRANSFORMER
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
PR5
REPEATER PANELS

GENERAL

PR 5

Panels of remote signalling PR allow to give alarm signalling of insula- forecasted).


tion’s monitoring devices HRI. They have also an acoustic signaller incorporated, a test button and a
HRI devices monitor permanently insulation’s level and the overload of button for stopping acoustic signal.
supply network in medical use rooms (IT- M networks). Board is flush mounted universal box (E503) in order to be located in
Signals of low insulation alarm and/or overload could be signalled in rooms supplied by under-control network. Maximum of repeater boards
rooms supplied from network and by board, which incorporate signals associable with HRI device is 2.
with LED of active device and low insulation alarm (and overload, if it is

PR5 remote signal panel network insulation control

4 TEST ON
1
TEST PERIODICALLY

6 OVERLOAD
2
5 SILENCE FAULT
3
7

34 MODEL
---------------------------------------------------------------------------------------------------------------------------------------------------------------------

PR5
Repeater panel for HRI-R22t, HRI-R24, HRI-R40V, HRI-R40W
(indication of low insulation alarm)
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
1 green LED of signalling active device (voltage presence)
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
2 red LED of sigalling overload or overtemperature
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
3 yellow LED of sigalling FAILURE (low insulation)
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
4 test button for testing functionality of HRI system and PR board
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
5 internal buzzer
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
6 internal buzzer
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
7 space for notes
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
PR2-PR2t-PR4
REPEATER PANELS

ELECTRIC CHARACTERISTICS

Operative voltage 12 - 24 Vac/dc (from HRI device)


Signallings green led NETWORK - red led ALARM of overload
yellow led ALARM of FAILURE low insulation, acoustic signal
Operators test button - stopping acoustic signal button
Working temperature - 10 …+ 60 °C
Storing temperature - 25 …+ 80 °C
Relative humidity MAX 95 %
Insulation test 2.5 kVrms 50 Hz for 60 sec
Connection type by screw terminals - wire section MAX 2.5 mm2
Protection's degree IP 30 front panel - IP 20 case
Mounting universal flush-mount box E503
Weight approximately 200 g
CEI-EN 61010-1 | CEI-EN 61557-8 / VDE 0413 part.8
Standard reference CEI 64.8/7-710 V2/ IEC 60364-7-710 / UNE 20615 | CEI-EN 61326-1

ASSEMBLING PANEL’S CONNECTIONS

WIRING
MOUNTING SEQUENCE

DIMENSIONS 35

PR5 remote signal panel network insulation control

TEST ON
TEST PERIODICALLY
79

OVERLOAD

SILENCE FAULT

E503
123 7 13 15

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
EML-12S
SERIAL REMOTE CONCENTRATOR
FOR REMOTE MONITORING OF NETWORK’S PARAMETERS

GENERAL
Serial remote concentrator is a device which allow remote monitoring of data-logger function.
parameters originated from insulation’s supervisors for medical use By its time, device could be connected to a PC and transmit different
rooms HRI-R40 and HRI-R40W with serial output RS485. parameters gathered. It could also be connected to a remote visualisa-
By serial communication RS485 Modbus-RTU protocol different supervi- tion panel with function of signalling alarms in network.
sors are connected to concentrator EML-12S.
Device could supply degrees of insulation and impedance’s resistance, of
network’s temperature and current, and eventual alarm’s presence with

MODELS
-------- ---------------------------------------------------------------------------
EML-12 remote concentrator Vaux 24 Vdc/ac
-------- ---------------------------------------------------------------------------
HRI NETWORK
Devices HRI-R40 or HRI-R40W are connected to EML-12S concentrator by serial output RS485.
Maximum 12 HRI devices could be connected

HRI NETWORK

HRI HRI HRI HRI HRI

RS485MODBUS

36
RS485MODBUS

RS485MODBUS

contrel

PC VISUAL DISPLAY

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
EML-12S
SERIAL REMOTE CONCENTRATOR
FOR REMOTE MONITORING OF NETWORK’S PARAMETERS

VISUALISATION

For every device connected it’s possible to


visualise
INSULATION’S RESISTANCE,
IMPEDANCE,
TEMPERATURES AND CURRENTS.

For every device connected it’s possible to


visualise instrument’s status
ON = (online)
OFF (offline).

For every instrument


it’s possible to visualise
last 4 intervened alarms.

EVENTS
When there is an alarm,
it’s automatically visualised on display with
indication of total alarms active
in that moment.
37

MENU AND SETTINGS


By menu, it’s possible to set parameters
as date and hour,
language,
number of connected devices and
settings for serial communication.

49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
According to the copyright and the civil
law,the reproduction of this catalogue, or
any part of this one, by electronic, mecha-
nical methods, by means of photocopies,
microfilms, recordings or other, is perem-
ptorily forbidden. Rights are reserved for
all countries.

Drawings, specifications and reference


numbers may be modified and changed.
CONTREL s.r.l reserves itself the right, to
make changes for technical or quality
improvements, without any notice.

RI_HRI-UK-04 - © Contrel elettronica - all rights reserved - end print october 2010