Isolation Monitoring
Isolation Monitoring
industrial applications
www.microener.com
www.contrel.it
RI se rie s
The RI isolation monitor series, are designed to permanently monitor the isolation to earth,
in single and three phase networks with isolated neutral or without
neutral (IT systems ) up to 1.000Vac and dc networks up to 1.000Vdc.
In the isolated neutral systems, in case of first leakage to earth, the tripping of
the protection is not required, but according with the IEC 61557.8Standard,
the leakage should be signalled by optical and acoustic means.
The device generates internally a measure signal,
which is applied between the controlled circuit and earth.
HRI se rie s
The working principle of the isolation monitor for use in medical room is based
on applying a dc voltage or a codified signal, between the secondary
of the isolation transformer and the equipotential node of the installation,
pointing out therefore, in a case of an earth leakage, the current flowing in the relay
and its corresponding isolation resistance of the installation.
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
PRODUCTS PAGE
index
Serie RI e HRI 4
Foreword 2
RI-R11 | RI-R11D 6
9
Insulation monitoring relay for networks 110 - 220 Vdc
RI-R15 9
Insulation monitoring relay for networks 300 / 500 / 1000 Vdc
ARI-R100 16
Adapters for networks up to 1000 Vac
16
RI-R60 18
Insulation monitoring relay for networks max 760/1000 Vac
RI-SM 22
Insulation monitoring relay for out-voltage systems 20
22
H RI Se rie s - FO R M ED IC A L USE A N D HO SP ITA L A P PLIC A TIO N 24
INSULATION MONITORING
General - Models - Accessories - Options (only for HRI-R40 and HRI-R40W)
HRI-R40 | HRI-R40W 25
25
HRI-R22t 29
HRI-R24 32
Insulation monitoring relay for use in medical rooms
29
PR5 34
Remote repetition panels
EML 36
Remote serial concentrator 32
34
36
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI series
INSULATION MONITORING
FOR ISOLATED NEUTRAL NETWORKS (IT)
GENERAL
APPLICATIONS be used in auxiliary networks and in generic networks of distribu-
IT networks are used where the continuity of service is a priority. tion in alternate single and three phase, anyway without direct-
For example, in these cases: current components.
• Chemical and metallurgical industries, where a voltage’s • Versions that apply a measure signal codified and varying in
interruption implies serious economic loss order to allow a correct insulation measure independently from
• Transmission systems and radio links under-control network that has to be monitored. Strong distortion
• Places at explosion and fire’s risk with high harmonic components (sub harmonic) and direct-cur-
• Mines rent components can cause measure’ problems to others techni-
• Networks of emergency’s supply ques. Model RI-R50 belong to this category. This solution let use
• Generators or direct-current group monitoring devices in generic applications for networks in direct-
• networks of auxiliary supply and control current and alternating single and three phase, with rectifiers,
• railways power’s electronics and variable-speed drive.
• Naval applications • Versions useful for testing insulation in out-voltage networks
• Rooms for medical use which use the same measuring technique -already cited- of
direct-current signal applied in network, but in this case the net
PRODUCT SERIES is out-voltage. This works in order to do a preventing monitoring
There are different versions of RI devices, in order to have speci- of insulation’s level. It is very useful for equipments not perma-
fic functionalities available for every networks that has to be nently used, as well as motors, fire-engines and so on where insu-
2
monitored. There are also accessories functions: for example, pre- lation level could decrease because of humidity (condensation).
alarm threshold and display for visualising insulation, very useful This decreasing doesn’t let a normal functioning when they will be
as supply for failure’s search. used. Model RI-SM belongs to this category.
Measuring techniques are different for every model, in order to • Versions for use in medical rooms
have the right insulation available according to the network. Models HRI-R24 (tipically used for scialytic lamps) HRI-R22t
• Versions that measures the variation of two polarities’ poten- HRI-R40 HRI-R40W belong to this category and got different
tial to earth. Models RI-F48, RI-R48, RI-R11, RI-R11D, RI-R15 measuring techniques depending on the model either applying a
belong to this category. These versions are apt for use in direct- direct-current signal and surveying electric leakage to earth or
current networks, in auxiliary supply’s networks and in direct-cur- applying a measuring signal codified and varying.
rent or alternate single phase networks. Panels of remote signalling repeater PR and remote serial concen-
• Versions that apply a measure’s signal in direct-current bet- trator EML for network’s monitoring are available as accessories of
ween network and earth sensing leakage current to earth so that this product. In the next page, there is a table with the description
insulation level could be measured. For every independent net- of technical features for every kind of monitor with specific crite-
work, only one monitor could be used. Models RI-F22, RI-R22, rions of choosing in order to turn the user to the model more use-
RI-R38, RI-R60 belong to this category. These versions are right to ful for his needs.
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI series
INSULATION MONITORING
FOR ISOLATED NEUTRAL NETWORKS (IT)
FUNCTIONS TABLE
RI-F22 max 230 Vac 230 Vac TRIP dc signal Fault 1 relais NO-C-NC Local Automatic
max 500 Vac 115 Vac opt 100 kohm fixed
(with adapter)
RI-R22 max 230 Vac 230 Vac TRIP dc signal Fault 1 relais NO-C-NC Local Manual local
max 500 Vac 115 Vac opt 25 ÷ 100 kohm and remote
(with adapter)
RI-R38 max 440 Vac 115-230 Vac TRIP dc signal Fault 1 relais NO-C-NC Local Manual local
max 1000 Vac 10 ÷ 100 kohm and remote
(with adapter)
ARI-R100 Upper limit 230 Vac - - - - - -
1000 Vac 115 Vac opt
with RI-R38
max 760 Vac 230 Vac dc signal Alarm fault Alarm Local and remote Local and remote
RI-R60 insulation 1 relais NO-C-NC
max 1000 Vac 115 Vac
with adapter ARI-R60 level Foult
1 relais NO-C-NC
RI-SM Out of voltage read from TRIP dc signal Fault 1 relais NO-C-NC Local Automatic
under control 0.1 ÷ 10 Mohm
network
HRI-R24 max 24 Vac read from TRIP Potential variation Fault 1 relais NO-C-NC Local and remote, Manual local 3
under control 10 ÷ 50 kohm of polarities with appropriate
network remote panels
HRI-R24t max 230 Vac 230 Vac TRIP dc signal Fault for 1 relais NO-C-NC Local and remote, Manual local
115 Vac 50 ÷ 250 kohm visualization with appropriate
insulation level remote panels
by led bar
HRI-R40 max 230 Vac 230 Vac TRIP dc signal Fault alarm 1 relais NO-C-NC Local and remote, Manual local
115 Vac 50 ÷ 500 kohm display 3 led
with appropriate
digit, min. value
remote panels
memorized
HRI-R40W max 230 Vac 230 Vac TRIP Codified and Fault alarm 1 relais NO-C-NC Local and remote, Manual local
115 Vac 50 ÷ 500 kohm variable signal display 3 led with appropriate
digit, min. value remote panels
memorized
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-F48 series
RI-R48 series
RI-R48N series
INSULATION MONITORING
VERSIONS FOR NETWORKS ac/dc MAX 48 V
GENERAL
The devices allow the insulation monitoring to earth of electric net-
works in alternate and direct-current till 48 V isolated (IT systems).
They measure potential’s variation of two polarities on earth so that
provide for a signal of insulation decreasing under a fixed level.
Monitoring is carried out measuring potential’s variation of two pola-
rities on earth.
Auxiliary supply is taken from under-control network.
There are different versions available: some, very cheap, with a fixed
tripping threshold, others with possibility of adjustable calibration of
tripping threshold and versions with indication of polarity (positive or
negative, phase or neutral) on which the failure took place.
Devices have on frontal panel signal for activity ON, for tripping TRIP
(low insulation), a test bottom, a reset bottom and a potentiometer (or
micro switches) for setting the threshold of tripping (only for versions
with adjustable threshold).
MODELS
--------------- ----------------------------------------------------------------------------
RI-F48 fixed threshold
--------------- ----------------------------------------------------------------------------
RI-R48 adjustable threshold
--------------- ----------------------------------------------------------------------------
RI-R48N adjustable threshold, indication of broken down polarity
--------------- ----------------------------------------------------------------------------
7 8 9 10 11 12 7 8 9 10 11 12
------------------------------------------------------------------
1 Potentiometer/micro switches for insulation tripping setting
2 (only for models RI-R48 and RI-R48N)
2 4 ------------------------------------------------------------------
RI-R48
INSULATION
MONITORING
2 Manual reset button
RESET RESET
RI-R48N RI-R48N
(only for models RI-R48 and RI-R48N)
1
30
40 3 INSULATION
ON ------------------------------------------------------------------
INSULATION
ON
20 MONITOR
40 60
RESET
5 3
MONITOR
40
Test button +
60
RESET
TEST
10
kΩ
50 TRIP ON TEST 30
20
+
TRIP
30
20
------------------------------------------------------------------
TRIP
5 4 10 TEST
_
contrel
4
10
kΩ
_
Signal of supplied
TEST relay ON (green LED)
kΩ kΩ ALARM
1
kΩ ALARM
------------------------------------------------------------------
3 5 Signal for insulation’s threshold set reached
(indication of broken down polarity for RI-R48N)
------------------------------------------------------------------
4 1 2 3 4 5 6
1 2 3 4 5 6
DIMENSIONS
48 RI-F48 RI-R48 RI-R48N RI-R48N
52,5 58
RI-R48 | RI-F48 7 8 9 10 11 12 RI-R48N
INSULATION
RI-R48 MONITORING
RESET RI-R48N
85,5
30 ON
85
INSULATION
45
40
20 MONITOR RESET
40 60 +
10 50 TRIP ON 30
kΩ TEST 20
TRIP
_
10 TEST
kΩ
kΩ contrel
ALARM
1 2 3 4 5 6
64 44
52,5 68 65
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-F48 series
RI-R48 series
RI-R48N series
INSULATION MONITORING
VERSIONS FOR NETWORK ac/dc MAX 48 V
ELECTRIC CHARACTERISTICS
------------------------------------------------------------------------
RI-F48 / RI-R48 / RI-R48N AUXILIARY SUPPLY - TERMINALS 1-3
Auxiliary supply could be taken from under-control network.
------------------------------------------------------------------------ 5
Vaux
INSULATION MONITORING - TERMINALS 1-9
Terminals have to be connected between under-control network
1 2 3 4 5 6 7 8 9 10 and measure’s referring earth.
AUX1 AUX2 RESET TEST OUT-NC OUT-C OUT-NO PE RESET Maximum voltage applicable between these terminals is 48 V
------------------------------------------------------------------------
CONNECTION OUTPUT RELAY - TERMINALS 6-7-8
Connection for remote signal by relays with switch free
from voltage, max 5 A 250 V on resistive load.
PE ------------------------------------------------------------------------
Eventual connection for automatic or remote RESET
_ (only for models RI-R48 and RI-R48N), connect a button NC
between terminals 4 and 10.
LOAD
+ ------------------------------------------------------------------------
Eventual connection for remote TEST
INSULATED LINE max 48Vac/dc (only for models RI-R48 and RI-R48N), connect a button NO
between terminal 5 and earth’s conductor PE
------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R11 series
RI-R11D series
INSULATION MONITORING
VERSIONS FOR NETWORKS dc MAX 250 V
GENERAL
The devices allow permanent monitoring of insulation of electrical
networks in direct-current current isolated on earth (IT networks).
Monitoring is carried out measuring potential’s variation of two pola-
rities of network on earth. Auxiliary supply is taken from under-control
network.
These devices have two trip thresholds, which are adjustable by fron-
tal micro switches, called ALARM and TRIP. This works in order to
signal that insulation’s level decreased under the threshold. Trip is
signalled by frontal LED with indication of polarity (+ or -) that show
low insulation. Remote trip threshold is carried out by double switch
two relays with contacts voltage-free. Relays could be programmed in
positive safe too (FAIL-SAFE function, normally excited). On the front,
there are TEST and RESET buttons; test could be activated locally or
by an external button; push button could be set manually or automa-
tically, either with local button or with external push button.
Model RI-R11D has a monitor of insulation’s level of the device by a
bar.
MODELS
------------------- --------------------------------------------------------------------------------------
RI-R11 110 V Main supply and auxiliary voltage 110 Vdc / -15% +25% (80 ÷ 180 Vdc)
RI-R11D 110 V Main supply and auxiliary voltage 110 Vdc / -15% +25% (80 ÷ 180 Vdc)
------------------- --------------------------------------------------------------------------------------
RI-R11 220 V Main supply and auxiliary voltage 220 Vdc /-15% +25% (185 ÷ 275 Vdc)
------------------- --------------------------------------------------------------------------------------
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
3 3
Insulation monitor RI-R11
RI-B32 ON Insulation monitor
Insulation relayRI-B32
monitor RI-R11D ON
4
ON 5kΩ
4
2 TEST
TEST 300
kΩ
ALARM kΩ
150 100
TRIP kΩ
60
TRIP
ALARM
2 TEST 300
kΩ
ALARM kΩ
ALARM
150 100
TRIP kΩ
TRIP kΩ
60
TRIP
ALARM
TRIP
ALARM
10kΩ
20kΩ
80
50
40
20 + 5 80
50
40
20
+ + 50kΩ
5
30 10
- 30 10 - - 100 kΩ
1 RESET
RESET
off
man
F.S. on off
auto man
F.S. on
auto 1 RESET
off
man
F.S. on off
man
auto man
auto
F.S. on
auto 200kΩ
RESET RESET
contrel
con
ntrel 6 RESET RESET
total
trip
on
on
contrel
400kΩ
6
contrel
contrel alarm on
600kΩ
HOLD
6 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
7 7
8 9 8 9
----------------------------------------------------------------------------------------------------------------------------------------------------
1 RESET button. This works only if RESET functioning is set manually.
----------------------------------------------------------------------------------------------------------------------------------------------------
2 TEST button. Pushing TEST button cause either alarm activation or trip activation with output relays’ switching.
----------------------------------------------------------------------------------------------------------------------------------------------------
3 LED ON for active device signalling
----------------------------------------------------------------------------------------------------------------------------------------------------
4 LED TRIP for trip threshold TRIP signalling
----------------------------------------------------------------------------------------------------------------------------------------------------
5 LED ALARM for alarm threshold ALARM signalling
----------------------------------------------------------------------------------------------------------------------------------------------------
6 LED+ and LED- signalling which under-control network’s polarity has low insulation. Ignition of one of these LED will be connected
with ALARM LED and TRIP ignition.
----------------------------------------------------------------------------------------------------------------------------------------------------
7 Screw terminals for connections
----------------------------------------------------------------------------------------------------------------------------------------------------
8 Micro switches for alarm threshold setting
----------------------------------------------------------------------------------------------------------------------------------------------------
9 Micro switches for trip threshold setting
----------------------------------------------------------------------------------------------------------------------------------------------------
10 Led bar for insulation level visualising (only for RI-R11D)
----------------------------------------------------------------------------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R11 series
RI-R11D series
INSULATION MONITORING
VERSIONS FOR NETWORKS dc MAX 250 V
ELECTRIC CHARACTERISTICS
Self-consumption 5 W MAX
Alternating residual load 5%
ALARM threshold setting 300 ÷ 30 kohm (5 levels adjustable by micro switches)
TRIP threshold setting 100 ÷ 10 kohm (5 levels adjustable by micro switches)
Output relay free from voltage contacts ALARM : 2 contacts switched NO-C-NC
TRIP : 2 contacts switched NO-C-NC
5 A 250 Vac – 0.3 A 130 Vdc – 0.2 A 280 Vdc resistive load
Capacity relay contacts 0.15 A 130 Vdc – 0.05 A 280 Vdc inductive load L/R < 40 ms
with 2 serial contacts: 0.7 A 130 Vdc – 0.5 A 280 Vdc resistive load
output alarm function - fail safe function for both outputs
Adjustable functions manual or automatic reset (external reset)
Working temperature - 10 …+ 60 °C
Storing temperature - 20 …+ 70 °C
Relative humidity < 90 %
Insulation test
Assembling position indifferent
Connection type by screw terminals - wire section MAX 2.5 mm2
Protection's degree IP 40 frontal with cap - IP 20 case
Mounting according with DIN 50022 easy connection snap on DIN rail 35 mm / 6 modules of 17.5 mm
Weight approximately 400 g
Standard reference CEI-EN 61010-1 / CEI-EN 61557-8 / VDE 0413 part.8 / CEI-EN 61326-1
DIMENSIONS
7
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
90 30 10
- 30 10 - - 100 kΩ 90 54
off F.S. on off F.S. on off F.S. on off F.S. on
man auto man auto man auto man
auto man auto
auto 200kΩ
RESET
RESET RESET total on
RESET RESET
con
contrel
ntrel RESET RESET trip on
contrel
400kΩ
contrel
contrel alarm on
600kΩ
HOLD
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
44
68
105 105 73
RI-R11 RI-R11D
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R11 series
RI-R11D series
INSULATION MONITORING
VERSIONS FOR NETWORKS dc MAX 250 V
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
V+ V- PE TEST RESET T1-NO T1-C T1-NC T2-NO T2-C T2-NC
PE
_
INSULATED NETWORK max 250 Vdc LOAD
+
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
AUXILIARY SUPPLY AND UNDER-CONTROL NETWORK CONNECTION - TERMINALS 1-3.
Positive and negative polarities of under-control network have to be connected to these terminals. Network’s voltage is used for device’s supply.
If positive and negative has been inverted, the device would not be damaged but (+) and (-- ) indications of frontal LED would be inverted too.
The advice is that of making sure about the model with right functioning voltage.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
CONNECTION TO EARTH - TERMINAL 5.
Terminal has to be connected with protection conductor PE (earth) in order to allow insulation’s measure.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
CONNECTION FOR REMOTE TEST - TERMINAL 7.
In case of willing to foresee TEST function also from an external push button, it’s possible to connect a pushbutton with normally open contact NO
between this terminal and under-control network. If it’s connected to (+) polarity, test will cause ALARM LED, TRIP LED and (+) lighting; but if it’s
8 connected to (-- ) polarity, LED - will light.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
CONNECTION FOR REMOTE RESET - TERMINAL 9.
In case of willing to foresee RESET function also from an external push button, it’s possible to connect a pushbutton with normally open contact NO
between this terminal and (-- ) polarity of under-control network.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
OUTPUT TERMINAL FOR TRIP RELAY - TERMINALS 12-13-14 16-17-18.
In order to signal to exterior threshold TRIP activation, it’s available a relay with double change over contact voltage-free. The diagram shows con-
tacts’ condition either with not supplied device or supplied at rest with FAIL SAFE function not active (relay normally not excited). If FAIL SAFE fun-
ction is set, relay will be normally excited when there is not tripping (supplied device) and it will be back at rest in case of tripping, not supplied
device or failure.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
OUTPUT TERMINAL FOR ALARM RELAY - TERMINALS 30-31-32 34-35-36
In order to signal trip threshold ALARM activation, it’s available a relay with double switch voltage-free. The diagram shows contacts’ condition either
with not supplied device or supplied at rest with FAIL SAFE function not active (relay normally not excited). If FAIL SAFE function is set, relay will be
normally excited when there is not tripping (supplied device) and it will be back at rest in case of tripping, not supplied device or failure.
------------------------- ----------------------------------------------------------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R15 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC
GENERAL
The RI-R15 device allows the permanent insulation monitoring to
earth of electric networks in direct current isolated (IT systems).
Insulation resistance monitoring is carried out measuring the
potential variation of two polarity on ground reference. Auxiliary
supply is taken from under-control network.
The threshold of trip is regulated by a frontal potentiometer. On
the frontal panel there is the signalling of device ON, and three red
LED to signal the tripping (TRIP) and to indicate the polarity of the
line under control that has low insulation. It’s available a chan-
geover contact relay to use the low insulation signalling in a remo-
te panel. The relay can be set as FAIL SAFE function. On front panel
there are a TEST and a RESET push-buttons. The test can be acti-
vated locally while the reset can be set in automatic or manual,
with local or external push-button.
MODELS
------------------- ------------------------------------------------------------------------------------------------------------------------------
RI-R15 300V power supply and network to control 300 Vdc (network 280÷340 Vdc)
RI-R15 500V power supply and network to control 500 Vdc (network 400÷600 Vdc)
RI-R15 1000V power supply and network to control 1000 Vdc (network 600÷1000 Vdc) including ARI-R15 external adapter
------------------- ------------------------------------------------------------------------------------------------------------------------------
--------------------------------------------------------------------------------
1 RESET push-button: this button is enabled to function only if is set the
manual RESET. In this mode the instrument can come back in no alarm
condition only when the RESET push-button is pressed or in absence
9
of the power supply.
--------------------------------------------------------------------------------
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
2 TEST push-buttons: the trip relay commute when these buttons is pressed.
3 The TEST+ button will simulate a low insulation on the positive pole:
the LED TRIP and + will turn on. The TEST- button will simulate a
Insulation monitor relay RI-R15 low insulation on the negative pole: the LED TRIP and - will turn on.
ON
100 180 240
--------------------------------------------------------------------------------
6 + TEST+
2 3 LED ON: device ON.
30 kΩ 300
- 2 --------------------------------------------------------------------------------
TEST-
1 4 LED + and LED-: to signal the polarity that has the low insulation of the
TRIP RESET network under control. The lighting on of one of these LED is linked to the
TRIP LED.
--------------------------------------------------------------------------------
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 7 5 LED TRIP: to signal the trip insulation level under the set threshold value
--------------------------------------------------------------------------------
6 Potentiometer to set the trip threshold
4 5 --------------------------------------------------------------------------------
7 Terminal boards for the connections
--------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R15 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
contrel
TRIP RESET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
ELECTRIC CHARACTERISTICS
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R15 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC
DIMENSIONS
90 90 54
105 105 73
V+
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
RI-R15
connessione PE
INSULATION MONITOR
V control
Vaux: *
relay output
reset TRIP
remote Fail Safe
manual function
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
V- PE RES+ RES- F.S.+ F.S.- T-NC T-C T-NO
PE
_
INSULATED LINE Vdc LOAD
+
----------------------------------------------------------------------------------------------------------------------------------------------------------
POWER SUPPLY AND NETWORK UNDER CONTROL CONNECTION / terminals 21-3 - At these terminals must be connected the negative and positive
pole of the network to control. The same voltage must be used to supply the instrument. If the negative and positive pole are inverted, the instru-
ment will not be damage but the indication of LED+ and LED- will be inverted. It’s necessary to verify the use of the instrument with correct sup- 11
ply voltage.
----------------------------------------------------------------------------------------------------------------------------------------------------------
GROUND REFERENCE CONNECTION / terminals 27-9 - The terminals must be connected to the PE protection conductor (earth referring) to allow
the insulation measuring. ---
-------------------------------------------------------------------------------------------------------------------------------------------------------
REMOTE TEST CONNECTION / AUTOMATIC RESET / terminal 11-12 - For RESET function from external push-button it’s necessary to connect an
external N.O. contact push-button between these terminals. If these terminals are short-circuited the functioning of the reset will be automatic
when the low insulation condition finish.
----------------------------------------------------------------------------------------------------------------------------------------------------------
FAIL SAFE FUNCTION (NORMALLY EXCITED RELAY) / TERMINALS 13-14 - The fail safe function (normally excited relay) will be activated thanks to
a short-circuit between these terminals. With fail safe function enabled the relay will be normally excited in not trip condition (with device sup-
plied) and it will come back at rest with the device off or damage and in case of tripping. With the fail safe the output relay switch for the low
insulation, lack of auxiliary power supply or device failure.
----------------------------------------------------------------------------------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R15 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC
TRIP RELAY OUTPUT / terminals 16-17-18 - To signal externally the TRIP threshold intervention it’s available a voltage changeover contact relay.
The wiring connection shows the contacts with the device off or on in rest condition with FAIL SAFE function disable (relay normally not excited).
With FAIL SAFE function enabled the relay will be normally excited in not trip condition (with device supplied) and it will come back at rest with
the device off or damage and in case of tripping.
----------------------------------------------------------------------------------------------------------------------------------------------------------
CONNEXION TO THE EXTERNAL ADAPTERS - To activate the instrument it’s necessary to make the short-circuit between the following terminals
23-25 and 5-7. This terminals are used to connect the external adapters when they are used (see specific manual).
----------------------------------------------------------------------------------------------------------------------------------------------------------
RI-R15 1000V
for line 600÷ 700Vdc
ARI-R15
INSULATION INSULATION MONITOR
V control
Vaux: *
MONITOR
VOLTAGE relay output
reset TRIP
ADAPTER remote Fail Safe
manual function
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
V- PE IN-B IN+B RES+ RES- F.S.+ F.S.- T-NC T-C T-NO
PE
_
INSULATED LINE Vdc (MAX 700 / 800 / 900 / 1000 V) LOAD
+
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-F22 series
RI-R22 series
RI-R38 series
INSULATION MONITORING - VERSIONS FOR NETWORKS ac MAX 400 V
GENERAL
RI-R38
----------------------------------------------------------------
4 RI-R38
ON
1 1 LED ON green active device’s indication
INSULATION
MONITOR RESET ----------------------------------------------------------------
100
50
150
2 2 LED TRIP red signal of trip for low insulation 13
30
10 TEST
TRIP
----------------------------------------------------------------
kΩ con
contrel
ntrel 3 TEST button device functioning testing
5 3 ----------------------------------------------------------------
4 RESET button trip signalling reset (manual reset functions)
----------------------------------------------------------------
5 micro switches for trip threshold adjusting
1 2 3 4 5 6
----------------------------------------------------------------
RI-F22 / RI-R22
2 ----------------------------------------------------------------
1 Potentiometer for adjusting insulation’s resistance
(only for model RI-R22)
3 RI-R22 RI-F22
----------------------------------------------------------------
RESET
2 Manual resetting button (only for model RI-R22)
1
50
75
3 ----------------------------------------------------------------
3 Test button
25
kΩ
100 TRIP ON TEST TRIP ON TEST ----------------------------------------------------------------
4 con
contrel
ntrel contrel
con
ntrel
5 4 Signalling lamp of auxiliary supply (green LED)
----------------------------------------------------------------
5 4 5 Signalling lamp for relay tripped (red LED)
----------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-F22 series
RI-R22 series
RI-R38 series
INSULATION MONITORING
VERSIONS FOR NETWORKS ac MAX 400 V
ELECTRIC CHARACTERISTICS
DIMENSIONS
14 52,5 58
7 8 9 10 11 12
RI-R22
RESET
85,5
RI-R38
85
50 ON
INSULATION
45
75
MONITOR RESET
100 150
25 100 TRIP ON 50
kΩ TEST 30
TRIP
10 TEST
con
contrel
ntrel kΩ con
contrel
ntrel
1 2 3 4 5 6
64 44
52,5 68 65
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-F22 series
RI-R22 series
RI-R38 series
INSULATION MONITORING
VERSIONS FOR NETWORKS ac MAX 400 V
RI-F22 / RI-R22
--------------------------------------------------------------------------
AUXILIARY SUPPLY - terminals 1-3
RI-F22 / RI-R22 auxiliary supply available from under-control network
--------------------------------------------------------------------------
Vaux
INSULATION MONITORING - terminals 4-9
the two terminals have to be connected between under-control
network and measure’s referring earth (max. applicable voltage
1 2 3 4 5 6 7 8 9 10 11 12 between these terminals is 230 V, so it’s possible apply insulation
AUX1 AUX2 VC OUT-NC OUT-C OUT-NO PE RESET
monitoring on single phase networks till 230 V, three phase
networks three-wires without neutral till 230 V and three phase
networks with neutral till 400 V)
--------------------------------------------------------------------------
RELAYS’ OUTPUT CONNECTIONS - terminals 6-7-8
PE --------------------------------------------------------------------------
CONNECTIONS FOR REMOTE SIGNALLING
N by relays in switch voltage-free max 5 A 250 V on resistive load
--------------------------------------------------------------------------
L3 LOAD EVENTUAL CONNECTION FOR AUTOMATIC OR REMOTE RESET
L2 (only for RI-R22) it is required to connect a NC button between
terminal 10 and earth’s conductor PE and to link with a bond
L1 terminals 9 and 10 themselves
INSULATED LINE --------------------------------------------------------------------------
max 230 Vac EVENTUAL CONNECTION FOR REMOTE TEST
(only for version RI-R22) it is required to connect a NO button
between terminal 5 and earth’s conductor PE
--------------------------------------------------------------------------
RI-R38
--------------------------------------------------------------------------
RI-R38 AUXILIARY SUPPLY - terminals 1-3
auxiliary supply available from under-control network
Vaux --------------------------------------------------------------------------
INSULATION MONITORING - terminals 5-11
the two terminals have to be connected between under-control
1 2 3 4 5 6 7 8 9 10 11 12 network and measure’s referring earth. Terminal 5 has to be
AUX1 AUX2 VC OUT-NC OUT-C OUT-NO PE RESET connected between under-control network single phase or three phase
and neutral conductor. If three phase network is three-wire, the 15
terminal has to be connected to a phase. max. applicable voltage
between these terminals is 230 V, so it’s possible apply insulation
monitoring on single phase networks up to 440 V, three phase
PE networks three-wire without neutral up to 440 V and three phase
networks with neutral up to 760 V
--------------------------------------------------------------------------
N RELAYS’ OUTPUT CONNECTIONS - terminals 7-8-9
L3 --------------------------------------------------------------------------
LOAD CONNECTIONS FOR REMOTE SIGNALLING
L2 by relays in switch voltage-free max 5 A 250 V on resistive load
--------------------------------------------------------------------------
L1 CONNECTION FOR AUTOMATIC OR REMOTE RESET - terminal 12
INSULATED LINE --------------------------------------------------------------------------
max 440 Vac
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
ARI-R100 series
ADAPTER FOR NETWORKS TILL 1000 Vac
VOLTAGE ADAPTER FOR INSULATION MONITORING RI-R38
GENERAL
MODELS
--------------- --------------------------------------------------------------------------------------
ARI-R100 Vaux: 230 V 50-60 Hz (standard version)
--------------- --------------------------------------------------------------------------------------
ARI-R100 Vaux: 110 V 50-60 Hz (optional version)
--------------- --------------------------------------------------------------------------------------
16
MADE IN EU
contrel ARI-R100
AUXILIARY VOLTAGE ADAPTER FOR RI INSULATION MONITOR
1 3 4 9 23
auxiliary
supply
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
ARI-R100 series
ADAPTER FOR NETWORKS TILL 1000 Vac
VOLTAGE ADAPTER FOR INSULATION MONITORING RI-R38
ELECTRIC CHARACTERISTICS
WIRING DIAGRAMS
INSULATED LINE IT max 1000 V 50-60 Hz coupled to RI-R38
L1
L2
L3
N
PE
--------------------------------------------------------------
9 8 7 1112 9 23 AUXILIARY SUPPLY - terminals 1-3
PE LINE 230 V 50-60 Hz standard - optional 110 V 50-60 Hz
INPUT
output
--------------------------------------------------------------
relay Ω ARI-R100 Under-control network could be:
• three phase with neutral,
Vaux. Vaux.
RI-R38 • three phase without neutral shared or without neutral,
• single phase.
1 2 3 4 5 1 3 4 Maximum voltage has not to outweigh 1000 V 50-60 Hz.
--------------------------------------------------------------
Terminal 23 of connection between ARI-R100 and
V aux network could be connected single-phase or with neutral,
if shared
-------------------------------------------------------------- 17
DIMENSIONS
73
MADE IN EU
contrel ARI-R100
AUXILIARY VOLTAGE ADAPTER FOR RI INSULATION MONITOR
90 54
V aux: to RI LINE INPUT
230V 50-60Hz insulation monitor PE max. 1000V 50-60Hz
1 3 4 9 23
44
157,5 68
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R60 Series
DEVICE FOR INSULATION PERMANENT CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VAC
GENERAL
MODELS
----------------- ---------------------------------------------------------------------------------------------------------------------
RI-R60-760 network voltage 760Vac max , Uaux 110-230V 50-60 Hz (100÷130 / 220÷240V ± 10%)
----------------- ---------------------------------------------------------------------------------------------------------------------
RI-R60-1000 network voltage 1000Vac max (with ARI-R60 adapter), Uaux 110-230V 50-60 Hz (100÷130 /
220÷240V ± 10%)
----------------- ---------------------------------------------------------------------------------------------------------------------
INSTALLATION
The installation must be carried out by qualified and authorized person- The device is a 6 modules (17.5mm) DIN version with snap on 35mm DIN
nel and in absence of voltage. Make sure that the instrument is O.K. and rail. It has a sealable transparent frontal protection cover.
it has not suffered any damage during transport. Make sure that the vol- The green LED ON will bright after the connections are set and the instru-
tage supply are compatible with the operating voltage of instrument. ment is power on.
ELECTRIC CHARACTERISTICS
TYPE RI-R60
Auxiliary power supply 110-230Vac (100÷130V / 220÷240V +-10%) 50-60Hz
Maximum consumption max 5 VA
Network to control 50-760Vac (50÷1000Vac with ARI-R60 adapter)
Measure voltage max 48Vdc
Measure current max 240 µA dc
Internal impedance 200 kΩ
Tripping delay max 5 seconds
Signalling led ON, led ALARM, led TRIP, measuring LED bar 5-500Kohm
Setting threshold tripping ALARM 300 ÷ 30 kohm (5 levels selectable with micro-switches)
Setting threshold tripping TRIP 100 ÷ 10 kohm (5 levels selectable with micro-switches)
Relay output ALARM: changeover contact NA-C-NC
TRIP: changeover contact NA-C-NC
Relay contacts 5 A 250Vac .
functions Fail safe function for both outputs, manual or automatic reset,
local and remote test and reset push-button
Working temperature -10 ÷ 60°C
Storing temperature -20 ÷ 70°C
Relative humidity ≤ 95 %
Insulation test 3 kV 60 sec. / 4 kV imp. 1,2/50µs
Mounting position Any
Wiring type Screw terminals / cross section cables 4 mm2
Protection degree Frontal with cover: IP 40 – Enclosure: IP 20
Mounting according DIN 50022 Snap on DIN rail 35mm / 6 modules 17,5 mm
Weight About 0,5 kg
Standards Safety CEI-EN 61010-1 / Product CEI-EN 61557-8 /
Electromagnetic compatibility CEI-EN 61326-1 CEI-EN 61326-2-4 CEI 64-8
DIMENSIONS 19
28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
contrel ON <5
TRIP 10
kΩ
ALARMkΩ TRIP kΩ
TEST 300 ALARM 20
contrel
150 100 60
ARI-R60 80
50
40
20 40
kΩ
90 INSULATION MONITOR VOLTAGE ADAPTER 30 10 60 90 45
off F.S.on off F.S.on
max 1000Vac man auto man auto 100
RESET
RESET RESET 200
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
157,5 105 73
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R60 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC
-----------------------------------------------------
AUXILIARY POWER SUPPLY Vaux: * VC
Terminals 1-2-3-4 115V 115V 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-R60 Series
DEVICE FOR PERMANENT INSULATION CONTROL
VERSION FOR NEUTRAL NETWORKS (IT) UP TO 1000VDC
-----------------------------------------------------------------------
AUXILIARY POWER SUPPLY - TERMINALS 1-2-3-4 VC
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
The supply section is a double input at 115V (100÷130V 50-60Hz).
to adapter ARI-R60
To supply the instrument at 230V (220÷240V 50-60Hz) connect the (VC insulation control RI-R60
line 1000V)
two section in series. INSULATION MONITOR
To supply the instrument at 115V connect the two section in parallel. output relays
----------------------------------------------------------------------- PE remote TRIP ALARM
Vaux: * conn. test reset
INSULATION CONTROL - TERMINALS (6/7) -22 115V 115V
The two terminals must be connected between the line under control 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
AUX-L1 AUX-01 AUX-L2 AUX-02 PE PE TEST RESET T-NC T-C T-NO A-NC A-C A-NO
and the earth of measure reference.
The double terminal 6/7 (connected internal) must be connected to
the earth reference while the terminal 22 must be connected to the
ARI-R60 adapter power supply
230Vca
-----------------------------------------------------------------------
ALARM RELAY OUTPUT CONNECTIONS (ALARM) - TERMINALS 16-17-18 Vaux: *
115V 115V ARI-R60
Connections to remote signalling thanks to free voltage changeover ADAPTER
contact, max 5A 250V on resistive load. AUX-L1 AUX-01 AUX-L2 AUX-02
-----------------------------------------------------------------------
TRIP RELAY OUTPUT CONNECTIONS (TRIP) - TERMINALS 12-13-14
24 23 9 4
Connections to remote signalling thanks to free voltage changeover PE
contact, max 5A 250V on resistive load. power supply
115Vca
-----------------------------------------------------------------------
REMOTE TEST CONNECTION - TERMINAL 8
PE
It’s possible to connect a remote push-button with a normally open
contact between the control device and the earth reference. N
----------------------------------------------------------------------- L3 LOAD
REMOTE RESET CONNECTION - TERMINAL 9 L2
For the RESET function from external signal it’s possible to connect a L1 INSULATED LINE (IT) max 1000 V 50-60Hz
push-button with normally open contact on the connection between
the control device and the earth reference.
-----------------------------------------------------------------------
21
FUNZIONALITY
In normally condition with the insulation value upper than alarm and trip Depending the set of the micro-switches the RESET can be automatic
thresholds the green LED of the device is turned on and the status of the when the TEST push-button is released or manual with the local or remo-
bar led depending of the insulation resistance level measured (with all te RESET push-button.
led off the insulation value is upper than 500 kohm, with all LED on the In case of low insulation on the line (insulation resistance value lower
measured LED lower than 5 kohm). than threshold set) the ALARM and possibly the TRIP signalling will be
By pressing the TEST push-button at least 5 seconds (delay time) the activated as the correspondent output relays. The Signalling will disap-
alarm and trip signalling with relative LED will be activated, the output pear only after that on the line come back an insulation level upper than
relays commute and the LED bar turn on (simulated value lower than 5 the threshold set.
kohm).
NOTES - It’s not possible to use more than one instrument on a line because the measure of the resistance could be not correct for the overlap of
the signal.
The presence of strong continuous component on the network under control could create some problems for the correct functioning of the device.
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
RI-SM series
INSULATION MONITORING
VERSIONS FOR OUT-VOLTAGE NETWORK
GENERAL
MODELS
--------------- --------------------------------------------------------------------------------------
RI-SM Vaux: 230 V 50-60 Hz (standard version)
--------------- --------------------------------------------------------------------------------------
RI-SM Vaux: 115 V 50-60 Hz (optional version)
--------------- --------------------------------------------------------------------------------------
7 8 9 10 11 12
22
52,5 58
1 RI-SM
2 44
ON INSULATION TRIP
MONITOR
10 7 8 9 10 11 12
7,5 0,5
4 5
2,5
TEST
0,25
0,1
1
MΩ
ON OFF
FAIL SAFE 3
contrel
RI-SM
ON
85,5
INSULATION TRIP
45
1 2 3 4 5 6 MONITOR
10
7,5 0,5
5 0,25
2,5 0,1
1 TEST ON OFF
------------------------------------------------------------------------------------ MΩ
FAIL SAFE
ELECTRIC CHARACTERISTICS
WIRING DIAGRAMS
RI-SM
Vaux
1 2 3 4 5 6 7 8 9 10 11 12 23
AUX1 AUX2 VC OUT-NO OUT-C OUT-NC PE RESET
---------------------------------------------------------------------------
AUXILIARY SUPPLY - terminals 1-3
auxiliary supply available from under-control network
---------------------------------------------------------------------------
INSULATION MONITORING - terminals 5-11
both terminals have to be connected between under-control network
PE and referring earth.
Terminal 5 have to be connected to under-control network single phase
N or three phase and to neutral conductor. If three phase network is three
wires, it is required to connect single phase network.
Maximum applicable voltage between these terminals is 700 V ac/dc.
LOAD
L3 ---------------------------------------------------------------------------
CONNECTIONS RELAY OUTPUT - terminals 7-8-9.
L2 connections for remote signal by relay with switch voltage-free,
max 5 A 250 V on resistive load
---------------------------------------------------------------------------
L1
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS
GENERAL
Devices allow insulation monitoring for IT systems in medical use rooms, codified signal between the secondary of insulation and device’s unipo-
as well as hospital and ambulatory clinic, in compliance with standard tential node. In case of failure to earth, it surveys current flowing inside
IEC 60364-7-710. the relay and correspondent insulation resistance of device.
Measure’s modality consist in application of a direct-current voltage or
MODELS
HRI-R40 network voltage 230 Vac, auxiliary supply 110-230 Vac
HRI-R40W network voltage 230 Vac, auxiliary supply 110-230 Vac
----------------- ---------------------------------------------------------------------------------------------------------------------
HRI-R22t network voltage 230 Vac, auxiliary supply 230 Vac
----------------- ---------------------------------------------------------------------------------------------------------------------
HRI-R24 network voltage 240 Vac/dc, auxiliary supply 24 Vac/dc
HRI-R22t HRI-R24
HRI-R40W
HRI-R40
ACCESSORIES
PR5 remote signalling panel for wall mounted (universal box E503) coupled
with HRI-R22t, HRI-R24, HRI-R40 e HRI-R40W
(indication of low insulation ALARM and overload and over temperature).
PR 5
24
----------------- ---------------------------------------------------------------------------------------------------------------------
* On requested, insulation’s transformers single phase and three phase are available
for hospital use 230 V / 230 V and 230 V / 24 V up to power 10 kVA.
(for information please contact our sales dept.)
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R40 series
HRI-R40W series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS
GENERAL
HRI-R40 series
This device allow insulation monitoring to earth of supply network and Device has two input of temperature’s measure (one is optional) for tem-
thermal and electric overcharge monitoring of transformer. perature’s probe PT100 or PTC (DIN 44081) for monitoring thermal over-
This works in order to serve everything requested in specific standard charge of insulation’s transformer.
regulation for these applications. There is also a input of current’s measure of current transformer for
Insulation’s resistance monitoring is carried out applying a measure’s monitoring overcharge on network.
signalling between isolated network and earth. Signalling output are apt for coupling with specific panels of signalling
Surveying leakage generated to earth it’s possible to measure insulatio- and remote monitoring PR5 (max 2 panels, on request 4 panels).
n’s level. There is also a output for relay voltage-free with functions adjustable by
Modern and sophisticated measure’s techniques integrated allow correct the user.
measure of insulation’s resistance level also in case of strong obstruc- Optionally it’s available a serial output RS485 for bidirectional commu-
tions, with high harmonic and direct-current components. nication with monitoring system (PLC, PC, and so on). 25
HRI-R40 model uses a monitoring signalling with direct-current compo- Communication’s protocol used is MODUBUS-RTU.
nent. For reducing problems caused by the presence of direct-current Specific characteristics make these devices conform to standard regula-
components on network (rectifiers), device has a digital filter which is tion:
able to divide the majority of direct-current from eventual direct-current EN 61557-8
components in network. IEC 60364-7-710
HRI-R40 could set a large number of programming possibilities with VDE 0100 part 710
frontal button and 3 digit digital display for visualising measuring and CEI 64.8/7-710 V2
programming parameters. UNE 20615.
HRI-R40W series
HRI-R40W version has same fundamental characteristics of previous Actually presence in network of strong distortions with high harmonic
model but it uses particular measuring technique applying a measure’s components (sub harmonic) and direct-current components could cause
signal codified and varying, in order to guarantee a correct measure of measure’s problems to others techniques.
insulation independently from under-control network type. This solution allow the using of HRI-R40W in network with rectifiers,
power’s electronics, variable-speed drive and so on.
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R40 series
HRI-R40W series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS
------------------------------------------------------------------------------------
1 display for visualising under-control parameters’ degree and for
visualising settings
------------------------------------------------------------------------------------
2 green LED SET for indication of programming status
------------------------------------------------------------------------------------
3 yellow LED ALARM for indication alarm for parameter’s
degree out-threshold
2 3 4 5 ------------------------------------------------------------------------------------
4 red LED OUTPUT RELAY for indication status of auxiliary relay output
------------------------------------------------------------------------------------
5 red LED ERROR / LINK FAIL for indication alarm of internal failure,
lack connection to under-control network, temperature’s probe
PT100 open or short circuit
contrel insulation monitor HRI-R40 ------------------------------------------------------------------------------------
1
SET ALARM OUTPUT ERROR /
6 red LED R for indication visualisation of insulation’s resistance
6 RELAY LINK FAIL
parameter; flashing light for out-threshold parameter
R [kΩ]
Z [kΩ] MIN / MAX
------------------------------------------------------------------------------------
7 T1 [°C] 7 red LED Z for indication visualisation of insulation’s impedance
T2 [°C]
+
_ RESET
SET
TEST
ENTER parameter; flashing light for out-threshold parameter.
8 I [A]
------------------------------------------------------------------------------------
9 8 red LED T1 for indication visualisation parameter of transformer’s
temperature; flashing light for out-threshold parameter.
10 ------------------------------------------------------------------------------------
9 red LED T2 for indication visualisation parameter of second sensor
temperature; flashing light for out-threshold parameter.
------------------------------------------------------------------------------------
11 12 13 10 red LED I for indication visualisation current of network parameter;
flashing light for out-threshold parameter.
------------------------------------------------------------------------------------
11 button +/- UP/DOWN for selecting parameter that has to be
visualised, for regulating device’s setting and for visualising
maximum and minimum memorized degrees
------------------------------------------------------------------------------------
12 button RESET / SET for entering device’s programming, for stopping
alarms and memorized degrees resetting
------------------------------------------------------------------------------------
13 button TEST / ENTER for testing device and remote signalling panels
and for confirming SETUP settings
------------------------------------------------------------------------------------
DIMENSIONS
26 74
90 R [kΩ]
45
Z [kΩ] MIN / MAX
T1 [°C]
T2 [°C]
+
_ RESET
SET
TEST
ENTER
I [A]
44
105 68 HRI-R40 / HRI-R40W
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R40 series
HRI-R40W series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS
ELECTRIC CHARACTERISTICS
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R40 series
HRI-R40W series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS
PT100
PT100
A B C PT2+A PT2+B PT2- PT1+A PT1+B PT1- CT-S2 CT-S1 R-NO R-C R-NC
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
auxiliary
supply
Vaux: 230 Vac
PE
TO OTHER
REMOTE
PANELS PR5
S S
L
INSULATION PC
TRANSFORMER INSULATED LINE (IT-M) LOAD
N
-----------------------------------------------------------------------------------------------------------------------------------------------------------
AUXILIARY SUPPLY - TERMINALS 1-2-3-4
supply’s section is carried out with double input 115 V nominal
for device supplying with 230 V, it is required to connect both sections in series
for device supplying with 115 V, it is required to connect both sections in parallel
-----------------------------------------------------------------------------------------------------------------------------------------------------------
LINK-FAIL MONITORING - TERMINALS 6-7
both terminals have to be connected between a isolated network’s phase and unipotential node (PE)
Maximum applicable voltage is 250 V (see insulation’s monitoring)
-----------------------------------------------------------------------------------------------------------------------------------------------------------
INSULATION’S MONITORING - TERMINALS 8-9
both terminals have to be connected between centre tap of secondary transformer or a isolated network’s phase and unipotential node (PE)
Maximum applicable voltage is 230 Vca so single phase networks could have max voltage of 230 V, three phase networks three wires
could have max voltage of 230 V phase-phase; but three phase networks four wires could have max voltage of 230 V phase-neutral
-----------------------------------------------------------------------------------------------------------------------------------------------------------
REMOTE PANEL’S CONNECTIONS PR5 - TERMINALS 10-11-12-13-14-15-16-18
connections for linking to remote panels PR5, Max voltage on these conductors is 24 V
-----------------------------------------------------------------------------------------------------------------------------------------------------------
SERIAL PORT RS485 (OPTIONAL) - TERMINALS 19-20-21
28 terminals A-B (19-20) head to serial bus, terminal C (21) is a mass’ reference that could be connected to eventual screen of cable RS485
Standard protocol used is modbus-rtu, documented in a specific handbook [IM833-U]
-----------------------------------------------------------------------------------------------------------------------------------------------------------
INPUT TEMPERATURE PROBE 2 (OPTIONAL) - TERMINALS 25-26-27
connections for linking to a temperature’s sensor - PT100 (EN 60751) or PTC (DIN 44081) sensor could be used.
In case of PT100 probes three wires, it is required to connect compensation’s conductor to the same terminal of correspondent conductor.
In case of PTC, it is necessary external resistor of 120 ohm min 1/4 W
-----------------------------------------------------------------------------------------------------------------------------------------------------------
INPUT TEMPERATURE PROBE 1 - TERMINALS 28-29-30
connections for linking to a temperature’s sensor - PT100 (EN 60751) or PTC (DIN 44081) sensor could be used.
In case of PT100 probes three wires, it is required to connect compensation conductor to the same terminal of correspondent conductor.
In case of PTC, it is necessary external resistor of 120 kohm min 1/4 W
-----------------------------------------------------------------------------------------------------------------------------------------------------------
INPUT FOR CURRENT MEASURE - TERMINALS 31-32
connection for external current transformer with secondary 5 A (current transformer ratio is programmable); if there is 3-phase network
must be used the special adapter type TSA-03 for 3 current transformer to permit to monitor in the insulation relay the highest value
of the 3-phase currents.
Only the module of the current value is measured (i.e. it is not important S1-S2 connection sequence).
-----------------------------------------------------------------------------------------------------------------------------------------------------------
OUTPUT AUXILIARY RELAY - TERMINALS 34-35-36
switch contact free from voltage and with programmable functions. Contact’s performance MAX 250 V 5 A resistive load
-----------------------------------------------------------------------------------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R22t series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS
GENERAL
HRI-R22t series
The device has similar characteristics of previous model but it’s more
cheap and it has less functions.
There is measuring signalling and it is able to verify temperature of
insulation’ power transformer (1 PTC input with contact NO or NC direc-
tly supplied by device) and insulation’s level.
These inputs are available: for remote repeaters panels PR2 and PR2-t
and 1 relay NO-C-NC, that is activate when fixed threshold (insulation
and temperature) are over-ride. HRI-R22t has frontally a bar led for
visualising insulation’s level of device and eventual alarm’s presence is
visualised frontally by led.
Testing button is available and it works for monitoring insulation’s level
preset with calibration on relay (for example, with 50 kohm calibration
all the led with inferior limit of 50 kohm will light during the test).
This button monitors eventual remote reply panels PR-5 (max 2 panels).
------------------------------------------------------------------------------------
3 4 6 1 TEST PUSHBUTTON
------------------------------------------------------------------------------------ 29
2 MICRO SWITCH for threshold set
- turning the switch to right, corresponding insulation’s resistance
degree has to be digit, highest degree heads
- with all the switches turned to left, fixed degree of 50 kohm
doesn’t change
contrel HRI-R22t insulation monitor ------------------------------------------------------------------------------------
2 3 LED signalling supplied relay
ON ALARM Link Fail
1 TEST
------------------------------------------------------------------------------------
4 LED signalling pre-fixed insulation’s threshold reached
SET ------------------------------------------------------------------------------------
alarm 50 kΩ 100 kΩ 250 kΩ 500 kΩ 1 MΩ >1 MΩ
Temp. 5 LED signalling temperature’s threshold reached
------------------------------------------------------------------------------------
6 LED signalling relay connected correctly
------------------------------------------------------------------------------------
7 LED signalling instant insulation’s value of device,
identified by lowest degree between active led
------------------------------------------------------------------------------------
5 7
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R22t series
INSULATION MONITORING
VERSIONS FOR MEDICAL USE ROOMS
ELECTRIC CHARACTERISTICS
TYPE HRI-R22t
Auxiliary supply 230 V ± 20%
Frequency 50 ÷ 60 Hz
Self-consumption 3 VA
Unde-control network voltage 24 ÷ 230 V 50 ÷ 60 Hz
Voltage's measure < 15 V
Current's measure < 0.6 mA
Internal impedance for resistive measure 1 Mohm
Selectable trip threshold 50-100-250 kohm (low insulation) by switches
DIMENSIONS
SET
alarm 50 kΩ 100 kΩ 250 kΩ 500 kΩ 1 MΩ >1 MΩ
Temp.
105 58
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R22t series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
remote input
check panel relay thermostat
HRI-R22t temperature
remote panel
output
relay aux PR5
output
Vaux: * link fail insulation remote
230V check check check panel
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11
AUX-L1 AUX-01 LF-L LF-PE VC-L VC-PE COM-P FAULT V-P R-NC R-NO R-C COM-S F-S V-P ACUS ACK OVER FAULT COM-P TEST- TEST-S TEST+
auxiliary
supply
Vaux: 230 Vac
PE
TO OTHER
REMOTE
PANELS PR5
S S
L
INSULATION PC
INSULATED LINE (IT-M) LOAD
TRANSFORMER
N
---------------------------------------------------------------------------------------------------------------------------------------------------
31
AUXILIARY SUPPLY - TERMINALS 1-3
---------------------------------------------------------------------------------------------------------------------------------------------------
MONITORING INSULATION - TERMINALS 5-9
both terminals have to be connected between centre tap of secondary transformer or isolated network’s phase and unipotential node (PE).
Maximum voltage applicable is 230 Vca. Consequentially single phase networks could be maximum 230 V, three phase networks of three
wires is 230 V phase-phase but three phase networks four wires is max 230 V phase-neutral
---------------------------------------------------------------------------------------------------------------------------------------------------
CONNECTIONS FOR REMOTE PANELS PR5 - TERMINALS 12-13-14-26
---------------------------------------------------------------------------------------------------------------------------------------------------
INPUT THERMAL PROBE - TERMINALS 33-34 or 35-36.
PTC (DIN 44081) probe could be used
---------------------------------------------------------------------------------------------------------------------------------------------------
AUXILIARY RELAY OUTPUT - TERMINALS 29-30-31
contact in switch voltage-free with programmable functions. Contact’s capacity 250 V 5 A resistive load
--------------------------------------------------------------------------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R24 series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS
GENERAL
HRI-R24 series
For monitoring 24 V networks (scialytic lamps), monitor HRI-R24 is used.
This is able to supply insulation’s control adjustable by frontal potentio-
meter. Frontally there is also testing button for allowing the test of devi-
ce’s correct functionality and eventual remote repeaters panels.
Outputs are available for remote repeaters panels PR-5 (max 2 panels).
2 ------------------------------------------------------------------------------------
1 Potentiometer for regulating trip threshold
INSULATION
------------------------------------------------------------------------------------
HRI-R24 MONITORING 2 Button of manual resetting
3 RESET
30 ------------------------------------------------------------------------------------
1 20
40
3 Test pushbutton
10
kΩ
50 TRIP ON TEST
------------------------------------------------------------------------------------
4 4 LED signalling supplied relay
con
contrel
ntrel ------------------------------------------------------------------------------------
5 5 LED signalling pre-fixed threshold reached
------------------------------------------------------------------------------------
32
DIMENSIONS
INSULATION
HRI-R24 MONITORING
RESET
85
30
40
20
10 50 TRIP ON
kΩ TEST
con
contrel
ntrel
64
52,5 68
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
HRI-R24 series
INSULATION MONITORING
VERSIONS FOR USE IN MEDICAL ROOMS
ELECTRIC CHARACTERISTICS
TYPE HRI-R24
Auxiliary supply 24 Vdc/ac -20 % +10 %
Frequency 50 ÷ 60 Hz
Self-consumption 3W
Unde-control network voltage 24 Vdc/ac 50 ÷ 60 Hz
Current's measure < 0.5 mA
Internal impedance for resistive measure 50 kohm
Internal impedance for resistive measure 10 ÷ 50 kohm (by potentiometer)
Visualisation led of signalling network’s presence
led of signalling low insulation
Output for PR5 panel (max 2)
Input from isolated network 240 Vac/dc (insulation measure)
Voltage of signal circuit < 24 Vdc
Measure’s method variation of polarity’s potential
Insulation’s test 2.5 kV 60 sec
Working temperature -10 ÷ 60 °C
Storing temperature -20 ÷ 80 °C
Relative humidity MAX 90 %
Standard regulation CEI-EN 61010-1 / CEI-EN 61557-8 / VDE 0413 part.8
CEI 64.8/7-710 V2 / IEC 60364-7-710 / UNE 20615 / CEI-EN 61326-1
Assembling according to DIN 50022 snap on DIN rail 35 mm
Dimensions 3 modules DIN 17.5 mm
Protection’s degree IP50 frontal - IP20 case
Connections by screw terminals max 2.5 mm2
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 11
V+ V- OUT-NO OUT-C OUT-NC PE COM-S F-S V-P ACUS ACK OVER FAULT COM-P TEST- TEST-S TEST+
33
PE
TO OTHER
S S REMOTE
PANELS PR5
L(+)
INSULATED LINE 24V ca/cc LOAD
N(-)
INSULATION TRANSFORMER
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
PR5
REPEATER PANELS
GENERAL
PR 5
4 TEST ON
1
TEST PERIODICALLY
6 OVERLOAD
2
5 SILENCE FAULT
3
7
34 MODEL
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
PR5
Repeater panel for HRI-R22t, HRI-R24, HRI-R40V, HRI-R40W
(indication of low insulation alarm)
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
1 green LED of signalling active device (voltage presence)
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
2 red LED of sigalling overload or overtemperature
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
3 yellow LED of sigalling FAILURE (low insulation)
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
4 test button for testing functionality of HRI system and PR board
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
5 internal buzzer
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
6 internal buzzer
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
7 space for notes
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
PR2-PR2t-PR4
REPEATER PANELS
ELECTRIC CHARACTERISTICS
WIRING
MOUNTING SEQUENCE
DIMENSIONS 35
TEST ON
TEST PERIODICALLY
79
OVERLOAD
SILENCE FAULT
E503
123 7 13 15
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
EML-12S
SERIAL REMOTE CONCENTRATOR
FOR REMOTE MONITORING OF NETWORK’S PARAMETERS
GENERAL
Serial remote concentrator is a device which allow remote monitoring of data-logger function.
parameters originated from insulation’s supervisors for medical use By its time, device could be connected to a PC and transmit different
rooms HRI-R40 and HRI-R40W with serial output RS485. parameters gathered. It could also be connected to a remote visualisa-
By serial communication RS485 Modbus-RTU protocol different supervi- tion panel with function of signalling alarms in network.
sors are connected to concentrator EML-12S.
Device could supply degrees of insulation and impedance’s resistance, of
network’s temperature and current, and eventual alarm’s presence with
MODELS
-------- ---------------------------------------------------------------------------
EML-12 remote concentrator Vaux 24 Vdc/ac
-------- ---------------------------------------------------------------------------
HRI NETWORK
Devices HRI-R40 or HRI-R40W are connected to EML-12S concentrator by serial output RS485.
Maximum 12 HRI devices could be connected
HRI NETWORK
RS485MODBUS
36
RS485MODBUS
RS485MODBUS
contrel
PC VISUAL DISPLAY
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
EML-12S
SERIAL REMOTE CONCENTRATOR
FOR REMOTE MONITORING OF NETWORK’S PARAMETERS
VISUALISATION
EVENTS
When there is an alarm,
it’s automatically visualised on display with
indication of total alarms active
in that moment.
37
49 rue de l'université – F93191 NOISY LE GRAND – Tel: +33 1 48 15 09 09/Fax: +33 1 43 05 08 24 / E-mail: [email protected] / www.microener.com
According to the copyright and the civil
law,the reproduction of this catalogue, or
any part of this one, by electronic, mecha-
nical methods, by means of photocopies,