Data Sheet XV-3190
Data Sheet XV-3190
XV -3190
2 Manufacturer Model TYCO / MORIN MBWB/1 / 79B-072-US-080
3 Requisition Item No.
GENERAL 4 Line Size / Schedule 6 in / Sch 40
5 P&ID No. PCAM-538-PL-Y-220
6 Service VBA-3190 PROPANE INLET
7 Line No. 6"-PL-22001-B1-B
8 Area Classification CLASS I, DIV 2, Gr. D
9 Valve Type / Standards BLOCK VALVE / API-6D
10 Body Size Port Size 6 in 4 in
11 Body Type / Body Material BALL / ASTM A-105
12 Guiding No. of Ports
VALVE 13 End Connection & Rating RF ANSI #300
BODY 14 Packing Lubrication & Isolation VITON
15 Seat Material ASTM A-36 + ENP O`RINGS VITON
16 Trim Material BALL ASTM A-105 + ENP STEM AISI 4140 + ENP
17 Trunnion Mounted Ball YES
18 Valve Failure Position CLOSED
19 Type MFR Pneumatic - Spring Return MORIN
20 Mod 79B 072 US080
21 Manual Override Handwheel
22 Supply to Act. (Norm) Supply to Act. (Max) 80 psi-g 100 psi-g
23 Fluid / Power Supply Allowable INSTRUMENT AIR (2) 80 psi-g
24 Air Surge Tank Quick Exhaust NO
ACTUATOR 25 Solenoid Model ASCO
26 Solenoid Valve Solenoid Type XY-3190 3 way - 24 VDC L.C. (3)
27 Limit Switch Closed Limit Switch Open YES ZSC-3190 YES ZSO-3190
28 Limit Switch Model TYCO AVID MOD XA041D00
29 Additional Switches / Equipment
30 Controls Mounted Valve / Panel Closed Cabinet IP65
31 Firesafe Certificate YES
32 NACE Certificate NO
STANDARDS
33 ANSI/FCI Leakage Class ANSI CL VI
34
35 Fluid PROPANE LIQUID
36 Fluid Type Phase
37 Normal Inlet Pressure psi-g
38 Max Inlet Pressure psi-g
39 Operating Temperature
PROCESS
40 Max Temperature / Min Temperature 225 ºF / ºF
DATA 41 Max. Diff. Pressure for Actuator Size (5) 325 psi
42 Viscosity cP
43
44
45 Design
46 Actual
47
Notes: 1_ Valves shall be according to PCAM-100-ET-K-0014
2_ Valve, Filter Regulator, Gauge, Relief Valve, Open Time Regulator (Variable Orifice).
3_ Solenoid 3 way, 24 vdc, Low Comsumption, Terminal Block, Continous Duty with Arc Suppresor Diode.
4_ Stainless Steel tubing and Swakelog Fittings.
5_ For Actuator Sizing, Minimum Safety Factor shall be 1,5.
6_ Control System accesories shall be Nonincendive, FM approval or other recognized laboratory shall by required.
INSTRUMENT SPECIFICATION