Description of Dust Monitor Communication

The document describes a post-scatter digital communication system that uses RS-485 and Modbus protocols. It exchanges data with external devices via an RS-485 electrical port using Modbus protocol. It then outlines the electrical port configuration, protocol details, and register descriptions with address and usage.

Uploaded by

Apply Softtech
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views2 pages

Description of Dust Monitor Communication

The document describes a post-scatter digital communication system that uses RS-485 and Modbus protocols. It exchanges data with external devices via an RS-485 electrical port using Modbus protocol. It then outlines the electrical port configuration, protocol details, and register descriptions with address and usage.

Uploaded by

Apply Softtech
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Description of Post-Scatter Digital Communication

The communication adopts RS-485 electrical port, and uses modbus protocol to
exchange data with the outside.

1. Electrical port

The communication port adopts the electrical protocol of RS-485. The configurations are in a
commonly used and stable format, and cannot be modified. See the following table for details:
Baud Rate Check Digit Data Bit Stop Bit
9600 no test 8 bits 1 person

2. Protocol

The communication uses modbus-rtu protocol, and the instrument is used as a slave to send
and receive data, and the slave address is 01. It can read and write real-time data. 0x64 for
reading and 0x65 for writing.
Slave Address Use of Function Code Register Address Number of Inspection Type
Registers
0x01 0x64/0x65 0x00 0x01 0x00 0x01 crc16

3. Register Description

The length of all registers is 0x01, occupying two bytes. See the following table for register
address and description:
Register Description Register Mode Default Remark
Address Length
0x0001 Smoke 2 R 0 Floating-point, occupying two
concentration value registers.
0x0003 Raw value of smoke 2 R 0 Floating-point, uncorrected
concentration raw data occupying two
registers.
0x0005 PD value 1 R 0 Integer, the unit of monitoring
value of the laser’s optical
power is Mv.
0x0006 LD value 1 R 0 Integer, the unit of monitoring
value of the laser’s optical
power is Mv.
0x0007 ADC value 1 R 0 Integer, the unit of signal
returned by the demodulator
is Mv.
0x0008 DAC1 1 R 800 Integer, controlling the output
voltage of the current loop,
the unit is Mv.
0x0009 DAC2 1 R 254 Integer, controlling the output
voltage of the comparator, the
unit is Mv.
0x000A Range 1 RS
0x000B Smoke correction K 1 RS 1 Integer, the value of this
value*100 register divided by 100 is the
real value.
0x000C Smoke correction b 1 RS 0 Integer, the value of this
value*100 register divided by 100 is the
real value.
0x000D Device number 2 RS 0 Integer, occupying two
(MSN) registers.
0x000F equipment running 2 R 0 Integer in hours
time
0x0011 Software version 1 R 0 Decimal value
number (year)
0x0012 Software version 1 R 0 Decimal value
number (month)
0x0013 Software version 1 R 0 Decimal value
number (day)
0x0014 Software version 1 R 0 Decimal value
number (suffix)
0x0015 Correction factor a 2 R/s Floating-point, occupying two
registers

0x0017 Correction factor b 2 R/s Floating-point, occupying two


registers
0x0019 VPD 2 R/s Floating-point, occupying two
registers
0x001b Modify slave 1 R/S
address
0x001c Current Loop Offset 1 R/S
Coefficient
0x001d Operating status 1 R
0x001e filter time 1 R/S Integer in seconds

For example, reading smoke concentration value and register address (0x0001)
Host computer sends: 02 64 00 01 00 01 E0 31
02 : Lower computer address (please refer to the product manual for the actual address)
64 : function code
00 01 : register address
00 01 : the number of registers to read
E0 31 : ModBus_CRC16 check

Host computer receives: 02 64 02 43 48 D2 36


02 : Lower computer address (please refer to the product manual for the actual address)
64 : function code
02 : the number of registers returned
43 48 D2 36 : returned data