Modbus User Manual

The document details the Acti 9 Smartlink Modbus Communication System, including an overview of the system architecture and components, technical specifications, installation instructions, and configuration of Modbus communication. It provides information on connecting input/output channels and using associated software. The document is an extensive user manual for setting up and implementing the Acti 9 Smartlink system.

Uploaded by

utenzebelou
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views

Modbus User Manual

The document details the Acti 9 Smartlink Modbus Communication System, including an overview of the system architecture and components, technical specifications, installation instructions, and configuration of Modbus communication. It provides information on connecting input/output channels and using associated software. The document is an extensive user manual for setting up and implementing the Acti 9 Smartlink system.

Uploaded by

utenzebelou
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 136

Acti 9 Smartlink Modbus Communication System

DOCA0004EN 05/2015

Acti 9 Smartlink Modbus


Communication System
User Manual
05/2015
DOCA0004EN-05

www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not intended as
a substitute for and is not to be used for determining suitability or reliability of these products for specific
user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. If you have any suggestions for improvements or amendments
or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical,
including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2015 Schneider Electric. All rights reserved.

2 DOCA0004EN 05/2015
Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1 Acti 9 Communication System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 2 Architecture of Acti 9 Communication System . . . . . . . . . . . . . . . . . . . . 13
Acti 9 Smartlink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Acti 9 Communication System Pre-assembled Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Acti 9 Devices with Ti24 Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Acti 9 Devices without Ti24 Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Devices out of the Acti 9 Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Chapter 3 Technical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Technical Characteristics of the Acti 9 Smartlink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Chapter 4 Sizing the 24 Vdc Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Definition of the 24 Vdc Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Protection Against a 240 Vac Fault on the Acti 9 Smartlink Channels . . . . . . . . . . . . . . . . . 28
Electromagnetic Compatibility (EMC) Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Chapter 5 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Chapter 6 Connection of Input/Output Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Acti 9 Devices with Ti24 Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Volt-Free Low Level Indication Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Volt-Free Standard Indication Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Surge Arresters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Contactor and Relay (Not in the Acti 9 Range) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Direct Output Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Indirect Output Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Generating Summary Data Using iOF+SD24 or OF+SD24 . . . . . . . . . . . . . . . . . . . . . . . . . 52
Chapter 7 Ecoreach . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Ecoreach Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Chapter 8 Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Acti 9 Smart Test Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Chapter 9 Setting Up Modbus Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Modbus Master/Slave Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Resetting with Factory Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Acti 9 Smartlink Device Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Modbus Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Modbus Exception Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Description of LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Chapter 10 Tables of Modbus Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
10.1 General Description of Modbus Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Modbus Table Format and Data Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Global Modbus Address Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
10.2 Summary and Detailed Modbus Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Summary of Channels 1 to 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Details of Channels 1 to 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

DOCA0004EN 05/2015 3
10.3 Modbus Tables for Connected Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
iOF+SD24 Indication Auxiliary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
OF+SD24 Indication Auxiliary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
iEM2000T, iEM3110, iEM3155, iEM3210, iEM3255 Meters or Meter with Pulse Output
(Standard CEI 62053-31) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
iACT24 Auxiliary for iCT Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
iATL24 Auxiliary for iTL Impulse Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Contactor and Relay (Not in the Acti 9 Range) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Acti 9 RCA iC60 Remote Control with Ti24 Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Acti 9 Reflex iC60 Integrated Control Circuit Breaker With Ti24 Interface. . . . . . . . . . . . . . . 100
Chapter 11 Integration of Acti 9 Smartlink in an EGX System . . . . . . . . . . . . . . . . . 101
Introduction to the EGX System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Appendix A Details of Modbus Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Function 8: Modbus Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Function 43-14: Read Acti 9 Smartlink ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Function 43–15: Read Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Function 43-16: Write Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Function 100–4: Read n Non-Adjacent Words. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Appendix B Connecting Acti 9 Devices Directly to a PLC . . . . . . . . . . . . . . . . . . . . . 125
iACT24 Auxiliary for iCT Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
iATL24 Auxiliary for iTL Impulse Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
iOF+SD24 Indication Auxiliary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
OF+SD24 Indication Auxiliary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Acti 9 RCA iC60 Remote Control with Ti24 Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Acti 9 Reflex iC60 Integrated Control Circuit Breaker With Ti24 Interface. . . . . . . . . . . . . . . 131

4 DOCA0004EN 05/2015
Safety Information

Important Information

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, or maintain it. The following special messages may appear throughout this
documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.

PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.

DOCA0004EN 05/2015 5
6 DOCA0004EN 05/2015
About the Book

At a Glance

Document Scope
The purpose of this manual is to provide users, installers and maintenance personnel with the technical
information necessary to install and use the Acti 9 communication system.

Validity Note
The Acti 9 communication system can be easily integrated into any building management architecture.
It combines command and control, metering and protection functions designed for energy efficiency
solutions in any type of environment. Based on the Modbus protocol, the Acti 9 communication system
allows switchboard data to be exchanged in real time with a supervision system or a PLC.
This system’s pre-wired connectors can save time and prevent wiring errors during installation.

Related Documents

Title of Documentation Reference Number


Instruction Sheet for the iACT24 Auxiliary on the iCT Contactor S1B33421
(English, Dutch, French, German, Italian, Portuguese, Spanish,
Chinese, Russian)
Instruction Sheet for the iATL24 Auxiliary on the iTL Remote Control S1B33422
Switch
(English, Dutch, French, German, Italian, Portuguese, Spanish,
Chinese, Russian)
Instruction Sheet for the Acti 9 Smartlink S1B33423
(English, Dutch, French, German, Italian, Portuguese, Spanish,
Chinese, Russian)
Instruction Sheet for the RCA iC60 Remote Control S1A4079001
(English, Dutch, French, German, Italian, Portuguese, Spanish,
Chinese, Russian)
Instruction Sheet for the Reflex iC60 Integrated Control Circuit S1B8674701
Breaker
(English, Dutch, French, German, Italian, Portuguese, Spanish,
Chinese, Russian)
Instruction Sheet for the iEM2000T Meter S1A89364
(English, Dutch, French, Finnish, German, Hungarian, Italian,
Norwegian, Polish, Portuguese, Spanish, Swedish, Chinese,
Russian)
Instruction Sheet for the iEM3100, iEM3110, iEM3115 Meters S1B46581
(English, French, German, Italian, Portuguese, Spanish, Chinese,
Russian)
Instruction Sheet for the iEM3150, iEM3155 Meters S1B46583
(English, French, German, Italian, Portuguese, Spanish, Chinese,
Russian)
Instruction Sheet for the iEM3200, iEM3210, iEM3215 Meters S1B46598
(English, French, German, Italian, Portuguese, Spanish, Chinese,
Russian)
Instruction Sheet for the iEM3250, iEM3255 Meters S1B46602
(English, French, German, Italian, Portuguese, Spanish, Chinese,
Russian)
Reference Manual for the RCA iC60 Remote Control for iC60 Circuit A9MA01EN
Breakers
(English)

DOCA0004EN 05/2015 7
Title of Documentation Reference Number
Reference Manual for the Reflex iC60 Integrated Control Circuit A9MA03EN
Breaker
(English)
User Manual for the PowerLogic EGX300 Ethernet Gateway 63230-319-216
(English, French, German, Spanish)
Technical Advice on the Acti 9 Smartlink Device CA908033EN
(English)
User Manual - Acti 9 Communication System Diagnostics DOCA0042EN
(English)
User Manual - Acti 9 Smart Test Software DOCA0029EN
(English)

You can download these technical publications and other technical information from our website at
www.schneider-electric.com.

8 DOCA0004EN 05/2015
Acti 9 Smartlink Modbus Communication System
Acti 9 Communication System
DOCA0004EN 05/2015

Chapter 1
Acti 9 Communication System

Acti 9 Communication System

Overview

Introduction
The Acti 9 communication system is used to connect final distribution boards to any supervision system.
Modular equipment in the Acti 9 communication system is used to monitor, measure and control electrical
distribution boards via a Modbus communication network.
The Acti 9 communication system concentrates the data from electrical distribution boards in real time,
thus contributing to achieving energy efficiency targets.
The Acti 9 communication system collects data from any meter (including kilowatt-hour, water, air, gas or
steam meters).
This system consists of:
z Acti 9 Smartlink and its test kit
z iOF+SD24 and OF+SD24 indication auxiliaries
z iACT24 and iATL24 auxiliaries for contactors and impulse relays in the Acti 9 range
z The Acti 9 RCA iC60 remote control module with Ti24 interface
z The Reflex iC60 integrated control circuit breaker with Ti24 interface
z iEM2000T, iEM3110, iEM3155, iEM3210 and iEM3255 meters
z Pre-wired cables

This system offers the following advantages and services:


z An automatic connection to the Modbus network
z No configuration operation required
z Calculation functions

The Acti 9 communication system is an open system:


z Acti 9 Smartlink can be used as a standard I/O distributed module.
z Acti 9 Smartlink is equipped with 11 24 Vdc channels. Each channel is represented by a Ti24 interface
consisting of:
z Two power supply terminals: 0 V and 24 Vdc
z Two 24 Vdc logic inputs (I1 and I2)
z One 24 Vdc logic output (Q)

z Each Ti24 interface is compatible with Miniconnect Phoenix standard connectors (at intervals of
3.81 mm) or equivalent.
z Acti 9 Smartlink is compatible with any type of counter (pulse output) compliant with standard
IEC 62053-21 (minimum pulse 30 ms):
z The pulse weight must be configured (written in a Modbus register).
z Acti 9 Smartlink calculates consumption and flow.

z Acti 9 Smartlink is compatible with any type of device equipped with low level inputs and outputs
(24 Vdc).
The Acti 9 communication system is simple and safe to use:
z The Acti 9 communication system pre-wired cables reduce complexity and wiring time by allowing
connection on an Acti 9 Smartlink module of all the Acti 9 communication system components and
24 Vdc compatible products.
z All Acti 9 communication system functions can be created by sending messages (Modbus protocol) to
Acti 9 Smartlink devices (Modbus slaves) that act on devices via Ti24 interfaces.

DOCA0004EN 05/2015 9
Acti 9 Communication System

Acti 9 Communication System Block Diagram

10 DOCA0004EN 05/2015
Acti 9 Communication System

Integration of Acti 9 Smartlink (Modbus Protocol) in Schneider Electric Offers


Acti 9 Smartlink can connect via an RS 485 link to the following offers:
z PLCs
z UNITY platform PLCs, version V3.0 or later: M340 and Premium
z Small Twido and Zelio PLCs

z Building management system:


z Struxureware Building Operation platform, version V1.2 or later

z Supervisors and human machine interfaces (HMIs):


z Struxureware Power Monitoring ION-E electrical distribution supervisor, version V6.0 or later
z EGX300 Web server, version V4.200 or later
z Control and display of Magelis interfaces

z Controllers dedicated to energy management:


z iRIO Xflow, version V3.3.1.0 or later

On installations where the connection is via Ethernet, compatibility is assured by means of EGX100
(Modbus RS 485 - Modbus Ethernet TCP/IP) and EGX300 gateways.
Integration of Acti 9 Smartlink in the iRIO Xflow, Struxureware Power Monitoring ION-E, Struxureware
Building Operation, and EGX300 software product libraries allows:
z Automatic connection, without setting any parameters, when Acti 9 Smartlink is connected to one of
these systems
z Access to predefined pages for viewing the Acti 9 Smartlink I/O in order to simplify system
implementation and installation maintenance
For the UNITY platform, three function blocks (DFBs) have been created which can respectively, in a single
operation:
z Manage automatic connection and set the energy meter parameters (pulse weight and initialization)
z Read the state of the I/O
z Obtain Acti 9 Smartlink statuses for diagnostic purposes

For installations using other communication systems (LON, KNX, BACnet, etc.), compatibility is assured
by means of suitable gateways (for example: Modbus/KNX).

DOCA0004EN 05/2015 11
Acti 9 Communication System

12 DOCA0004EN 05/2015
Acti 9 Smartlink Modbus Communication System
Architecture of Acti 9 Communication System
DOCA0004EN 05/2015

Chapter 2
Architecture of Acti 9 Communication System

Architecture of Acti 9 Communication System

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Acti 9 Smartlink 14
Acti 9 Communication System Pre-assembled Cables 15
Acti 9 Devices with Ti24 Interface 17
Acti 9 Devices without Ti24 Interface 18
Devices out of the Acti 9 Range 19

DOCA0004EN 05/2015 13
Architecture of Acti 9 Communication System

Acti 9 Smartlink

Introduction
The Acti 9 Smartlink device has 11 channels (24 Vdc) and can be connected to devices in the Acti 9 range
equipped with a Ti24 interface. Thanks to the Ti24 link, data can be transmitted from the Acti 9 Smartlink
device to a PLC or a supervision system via a Modbus communication network.
The Acti 9 Smartlink device channels can also be used to transmit standardized I/O. The Acti 9 Smartlink
device can also therefore communicate with devices (not in the Acti 9 range) with or without a Ti24 link.
Devices which can be connected to the Acti 9 Smartlink device include:
z Acti 9 products: control switch for iACT24 contactors and iATL24 impulse relays, iC60 iOF+SD24
indication auxiliary, C60 OF+SD24 indication auxiliary, RCA iC60 remote control with Ti24 interface,
Reflex iC60 integrated control circuit breaker with Ti24 interface
z Meters: iEM2000T or other meters (Schneider Electric or other manufacturers) in compliance with
IEC 62053-21 (minimum pulse 30 ms).
z Any product (not in the Acti 9 range) that has command and control information: two discrete 24 V
outputs and one discrete 24 V inputs.
The Acti 9 Smartlink device is an intermediary between the supervisor and various electrical appliances. It
can therefore be used to retrieve and process data received from devices and also control them. The
functions available depend on the type of connected devices.
The Acti 9 Smartlink functions are described in detail (see page 67).

Description
The following figure shows the Acti 9 Smartlink device:

A 11 Digital I/O channels


B One 24 Vdc power supply connector
C LEDs that show the Acti 9 Smartlink device operating status
D Two thumbwheels for the device Modbus address
E One 4-pin Modbus connector

14 DOCA0004EN 05/2015
Architecture of Acti 9 Communication System

Acti 9 Communication System Pre-assembled Cables

Description
Acti 9 communication pre-assembled cables are a very quick way to connect all the Acti 9 communication
system components and compatible products (24 Vdc) to the channels of an Acti 9 Smartlink module.
The pre-assembled cables are:

Product Reference Description Length (mm)


A9XCAS06 Set of six pre-assembled cables with two Ti24 connectors 100
A9XCAM06 Set of six pre-assembled cables with two Ti24 connectors 160
A9XCAH06 Set of six pre-assembled cables with two Ti24 connectors 450
A9XCAL06 Set of six pre-assembled cables with two Ti24 connectors 870
A9XCAU06 Set of six pre-assembled cables with one Ti24 connector 870
A9XCAC01 One pre-assembled cable with one Ti24 connector 4,000
A9XC2412 Set of 12 connectors with 5-pin spring -

Each Ti24 interface (I/O channel) is compatible with Miniconnect Phoenix standard connectors (at intervals
of 3.81 mm) or equivalent.

NOTE: The connectors in each pre-assembled cable have a flat surface where a self-adhesive label can
be placed to identify the channel number used.
Self-adhesive labels are not supplied by Schneider Electric.

DOCA0004EN 05/2015 15
Architecture of Acti 9 Communication System

Description of the Connector at the Ti24 Interface End


Terminal Description
24 V 24 V of the 24 Vdc power supply
Q Control output
I2 Input number 2
I1 Input number 1
0V 0 V of the 24 Vdc power supply

NOTE:
z Do not connect two wires in each of the Ti24 connector terminals (A9XC2412).

z Do not connect a wire with cable end in each of the Ti24 connector terminals.
The table shows the characteristics of cables that can be used with the A9XC2412 connector:

10 mm 0.5...1.5 mm² 0.4 x 2.5

16 DOCA0004EN 05/2015
Architecture of Acti 9 Communication System

Acti 9 Devices with Ti24 Interface

Description
Devices that can be conneted to the Acti 9 Smartlink are listed in the following table:

Device Product Description


Reference
iACT24 auxiliary for iCT contactor A9C15924 The iACT24 auxiliary:
z Can be used to control a contactor (iCT) via its Y1, Y2 and Y3
inputs. The Y3 (24 Vdc) input can be controlled by one of the
Acti 9 Smartlink device channels.
z Is used to find out the contactor status (O/C status).

iATL24 auxiliary for iTL contactor A9C15424 The iATL24 auxiliary:


z Can be used to control an (iTL) impulse relay via its Y1, Y2
and Y3 inputs. The Y3 (24 Vdc) input can be controlled by one
of the Acti 9 Smartlink device channels.
z Is used to find out the impulse relay status (O/C status).

iOF+SD24 indication auxiliary for A9A26897 The iOF+SD24 indication auxiliary is used to find out the status
iC60, iC65 and iDPN circuit
of a iC60, iC65 (OF and states) and iDPN circuit breaker
breakers
(sold in China).
OF+SD24 indication auxiliary for A9N26899 The OF+SD24 indication auxiliary is used to find out the status
C60, C120, C60H-DC and iDPN
of a C60, C120, C60H-DC (OF and ) and iDPN circuit
circuit breakers
breaker (sold in every country except China).
Acti 9 RCA iC60 remote control A9C7012• The Acti 9 RCA iC60 remote control:
with Ti24 interface z Should have a Ti24 interface (with product references
A9C70122 and A9C70124).
z Can be used to control an iC60 circuit breaker via input Y3 of
its Ti24 interface. Input Y3 (24 V DC) can be controlled by one
of the device channels Acti 9 Smartlink.
z Can be used to find out the OF and status of the circuit
breaker associated with the RCA iC60 remote control.
Acti 9 Reflex iC60 integrated A9C6•••• The Acti 9 Reflex iC60 integrated control circuit breaker:
control circuit breaker with Ti24 z Should have a Ti24 interface (with product references
interface A9C6••••).
z Can allow the device to be controlled via input Y3 of its Ti24
interface. The Y3 (24 Vdc) input can be controlled by one of
the Acti 9 Smartlink channels.
z Can be used to communicate its O/C and auto/OFF status.

NOTE: All the devices in the preceding table can be connected to channel N (1 ≤ N ≤ 11) of an
Acti 9 Smartlink module with A9XCAS06 pre-wired cable (or A9XCAM06 or A9XCAL06 or A9XCAH06).

DOCA0004EN 05/2015 17
Architecture of Acti 9 Communication System

Acti 9 Devices without Ti24 Interface

Description
Devices that can be connected to the Acti 9 Smartlink are listed in the following table:

Designation Product Description


Reference
iEM2000T A9MEM2000T Single-phase energy meter without display
iEM3110 A9MEM3110 Three-phase energy meter with display
iEM3155 A9MEM3155 Three-phase energy meter with display
iEM3210 A9MEM3210 Three-phase energy meter with display
iEM3255 A9MEM3255 Three-phase energy meter with display
iPRD (Type 2) A9L••••1 Withdrawable surge arresters with remote indication
contact iPRD65r/iPRD40r/iPRD20r/iPRD8r
iPRD 40r PV (Type 2) A9L40271 Withdrawable surge arresters with remote indication
A9L40281 contact
iPRF1 12.5r (Type 1 + Type 2; A9L16632 Monobloc surge arresters with remote indication contact
Type B+C) A9L16633
A9L16634
PRD1 25r (Type 1 + Type 2) 16329 Withdrawable surge arresters with remote indication
16330 contact
16331
16332
PRD1 Master (Type 1) 16360 Withdrawable surge arresters with remote indication
16361 contact
16362
16363
iQuick PRD (Type 2) A9L16292 Withdrawable surge arresters with integrated backup MCB
A9L16293 and remote indication contact
A9L16294
A9L16295
A9L16296
A9L16297
A9L16298
A9L16299
A9L16300

NOTE: The connection of these devices can be done with an A9XCAU06 or A9XCAC01 pre-wired cable:
molded connector (at Smartlink end), and with five wires (at device end).
The table describes the products that need a low level interface relay to connect to Acti 9 Smartlink:

Designation Product Description


Reference
IH, IHP see catalog Timer switches with RBN type low level relays or equivalent
IC see catalog Light sensitive switches with RBN type low level relays or equivalent
TH, THP see catalog Thermostats with RBN type low level relays or equivalent

18 DOCA0004EN 05/2015
Architecture of Acti 9 Communication System

Devices out of the Acti 9 Range

Description
Devices that can be connected to the Acti 9 Smartlink are:
z Meter with a pulse output and compliant with standard IEC 62053-31
z Volt-Free Low Level Indication Contact
z Volt-Free Standard Indication Contact
z Contactor and Relay
z Indication device or PLC input can be directly connected to the output (Q) of Acti 9 Smartlink channel.
The connected device should have the following characteristics:
z To be powered with 24 Vdc
z The consumption must be less than 100 mA

z Any device (for example: motor) that needs a command circuit of more than 100 mA can be controlled
by the output (Q) of a channel of Acti 9 Smartlink. The electrical diagram must be indirect between
Acti 9 Smartlink and this device: a low level relay must be installed between the command of this device
and Acti 9 Smartlink.
NOTE: The connection of these devices can be done with an A9XCAU06 or A9XCAC01 pre-wired cable:
molded connector (at Smartlink end), and with five wires (at device end).

DOCA0004EN 05/2015 19
Architecture of Acti 9 Communication System

20 DOCA0004EN 05/2015
Acti 9 Smartlink Modbus Communication System
Technical Characteristics
DOCA0004EN 05/2015

Chapter 3
Technical Characteristics

Technical Characteristics

Technical Characteristics of the Acti 9 Smartlink

General Characteristics

Characteristic Value
Product marking CE, GOST
Temperature Operation (horizontal) –25...+60°C
Operation (vertical) –25...+50°C
Storage –40...+85°C
Tropicalization Execution 2 (relative humidity of 93% at 40°C)
Resistance to voltage dips 10 ms, class 3 according to IEC 61000-4-29
Degree of protection IP 20
Level of pollution 3
Overvoltage category OVC II
Conforming to SELV specifications Yes
Altitude Operation 0...2,000 m
Storage 0...3,000 m
Immunity to vibration IEC 60068-2-6 1 g/± 3.5 mm, 5...300 Hz, 10 cycles
Immunity to mechanical shock 15 g/11 ms
Immunity to electrostatic IEC 61000-4-2 Air: 8 kV
discharge Contact: 4 kV
Immunity to radiated IEC 61000-4-3 10 V/m – 80 MHz to 3 GHz
electromagnetic interference
Immunity to fast transients IEC 61000-4-4 1 kV for the I/O and Modbus communication.
2 kV for the 24 Vdc - 5 kHz - 100 kHz power supply
Immunity to conducted magnetic IEC 61000-4-6 10 V from 150 kHz to 80 MHz
fields
Immunity to magnetic fields at IEC 61000-4-8 30 A/m continuous
line frequency 100 A/m pulse
Resistance to corrosive IEC 60721-3-3 Level 3C2 on H²S/SO²/NO²/Cl²
atmospheres
Fire withstand For live parts 30 s at 960°C. IEC 60695-2-10 and IEC 60695-2-11
For other parts 30 s at 650°C. IEC 60695-2-10 and IEC 60695-2-11
Salt mist IEC 60068-2-52 Severity 2
Environment Conforms to RoHS directives
Installation position Horizontal or vertical
Mean time between failures More than 1 M hours

Mechanical Characteristics

Characteristic Value
Dimensions Length 359 mm
Height 22.5 mm
Depth 42 mm
Weight 195 g

DOCA0004EN 05/2015 21
Technical Characteristics

Communication Module

Characteristic Value
Type of interface module Modbus, RTU, RS485 serial connection
Transmission Transfer rate 9600...19 200 Baud
Medium Double shielded twisted pair
Impedance 120 Ω
Structure Type Modbus
Method Master/slave
Device type Slave
Turnaround time 10 ms (approx.)
Max. length of Modbus line 1,000 m
Type of bus connector 4-pin connector
Power supply Nominal Non-isolated 24 Vdc with protection against negative
voltages up to -28.8 Vdc
Voltage limits 19.2... 28.8 Vdc with ripple
Current consumption, no- 35 mA
load
Maximum input intensity 1.5 A
Maximum current inrush 3 A (limited internally)
Isolation Between the Modbus 1,500 V RMS for 1 minute
serial connection and
24 Vdc Ti24 I/O interfaces
Number of digital I/O channels 11

Integrated Functions

Characteristic Value
Counter Number of counters Up to 22 (22 inputs)
Maximum frequency 16.667 Hz, IEC 62053-31
Period stored in backup memory 10 years

Inputs

Characteristic Value
Number of logic inputs 22 (2 per channel)
Rated input voltage 24 Vdc
Input type Current sink, type 1
IEC 61131-2
Weight (0 V) 1 for 2 inputs (1 per channel)
Input voltage limits 19.2...28.8 Vdc
Rated input current 2.5 mA
Maximum input current 5 mA
Filter time 2 ms
Acquisition time 10 ms
Isolation No isolation between the Ti24 interfaces
Negative voltage protection Yes
Maximum length of cables and cordsets 500 m (conductor c.s.a. of at least 0.5 mm2)

22 DOCA0004EN 05/2015
Technical Characteristics

Outputs

Characteristic Value
Number of logic outputs 11 (1 per channel)
Logic output Current source, 24 Vdc 0.1 A
IEC 61131-2
Weight (0 V) 1
Rated output voltage Voltage 24 Vdc
Maximum current 100 mA
Filter time 1 ms
Voltage drop (voltage at state 1) 1 V max.
Maximum current inrush 500 mA
Leakage current 0.1 mA
Overvoltage protection 33 Vdc
Short-circuit protection Yes
Overload protection Yes
Current limiting Yes
Maximum length of cables and cordsets 500 m (conductor c.s.a. of at least 0.5 mm2)

iACT24

Characteristic Value
Control voltage (Ue) 230 Vac, +10 %, -15 % (Y2)
24 Vdc, ± 20 % (Y3)
Control voltage frequency 50/60 Hz
Insulation voltage (Ui) 250 Vac
Rated impulse withstand voltage (Uimp) 8 kV (OVC IV)
Level of pollution 3
Degree of protection IP20B device only
IP40 device in modular enclosure
Width in 9 mm modules ) 2
Auxiliary contact (O/C) Ti24 24 Vdc protected output, min. 2 mA, max. 100 mA
Contact 1 O/C operating category AC 14
Temperature Operation -25 … 60°C
Storage -40 … +80°C
Consumption <1W
Standard IEC/EN 60947-5-1

DOCA0004EN 05/2015 23
Technical Characteristics

iATL24

Characteristic Value
Control voltage (Ue) 230 Vac, +10 %, -15 % (Y2)
24 Vdc, ± 20 % (Y3)
Control voltage frequency 50/60 Hz
Insulation voltage (Ui) 250 Vac
Rated impulse withstand voltage (Uimp) 8 kV (OVC IV)
Level of pollution 3
Degree of protection IP20B device only
IP40 device in modular enclosure
Width in 9 mm modules ) 2
Auxiliary contact (O/C) Ti24 24 Vdc protected output, min. 2 mA, max. 100 mA
Contact 1 O/C operating category AC 14
Temperature Operation -25 … 60°C
Storage -40 … +80°C
Consumption <1W
Standard IEC/EN 60947-5-1

24 DOCA0004EN 05/2015
Acti 9 Smartlink Modbus Communication System
Sizing the 24 V DC Power Supply
DOCA0004EN 05/2015

Chapter 4
Sizing the 24 Vdc Power Supply

Sizing the 24 Vdc Power Supply

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Definition of the 24 Vdc Power Supply 26
Protection Against a 240 Vac Fault on the Acti 9 Smartlink Channels 28
Electromagnetic Compatibility (EMC) Recommendations 29

DOCA0004EN 05/2015 25
Sizing the 24 V DC Power Supply

Definition of the 24 Vdc Power Supply

Safety Information

DANGER
RISK OF ELECTROCUTION
Isolate the Acti 9 Smartlink power terminals from the power terminals connected to the Modbus network
line.
Failure to follow these instructions will result in death or serious injury.

Example: The 0 V and the 24 V of a 24 Vdc power supply connected to the TRV00210 ULP
communication module must be isolated from the 0 V or +24 V terminals of the 24 Vdc power supply for
the Acti 9 Smartlink device.

General Characteristics
Acti 9 Smartlink device consumption:

Status Consumption
Device with no load 35 mA
Device under load 1.5 A maximum

Products in the Acti 9 Range


If products connected to the channels (Ti24 interfaces) of an Acti 9 Smartlink device are in the Acti 9 range,
the consumption of a channel output is the same as the consumption of an input because the output is
connected to the input. All that needs to be done is to add up the consumption of 3 input currents per
channel.
Example: Assuming that the input current is less than 5 mA, the consumption of an Acti 9 Smartlink device
is as follows:
No-load consumption + number of outputs x 3 input currents = 35 mA + 11 x (3 x 5 mA) = 200 mA

Products that can be Controlled by a Channel


If products connected to the channels (Ti24 interfaces) of an Acti 9 Smartlink device are in a different
range, the maximum consumption of a device channel is 110 mA. The output for each channel supplies
100 mA and the inputs can consume up to 5 mA each.
Example: Assuming that the consumption of one channel is 110 mA, the consumption of one
Acti 9 Smartlink device is as follows:
No-load consumption + number of outputs x consumption per channel = 35 mA + 11 x (110 mA) = 1.3 A

Selection of the Acti 9 Smartlink 24 Vdc Power Supply


The 24 Vdc power supply must correspond to the following criteria:
z It must be local to the electrical cabinet.
z It must be different from the Modbus network 24 Vdc power supply so as to maintain galvanic isolation
between the Modbus network (common to several electrical cabinets) and the 24 Vdc I/O.
z It must be Safety Extra Low Voltage (SELV) type.
z Galvanic isolation between the power supply input (AC voltage) and the power supply output
(DC voltage) must be at least 4 kVac at 50 Hz.
z The rated AC voltage of the power supply input must be 240 Vac +15/–20%.
z This power supply can be used to supply other products inside the electrical cabinet provided that these
products are double insulated or with reinforced insulation so as to preserve the power supply’s SELV
quality.
Phaseo ABL8MEM240xx (OVC II) or ABL7RM24025 (OVC II) modular power supplies and their
accessories comply with the earlier recommendations in this topic. These accessories provide the
redundancy and backup power supply functions and can eliminate micro-cuts on the line.
The upstream and downstream protection functions of the Phaseo power supply must be installed as
indicated in their respective manuals.
NOTE: OVC indicates the overvoltage category.

26 DOCA0004EN 05/2015
Sizing the 24 V DC Power Supply

If overvoltage category IV or III is needed in the installation, we recommend using:


z Either power supplies (limited to 1 A) in the ULP (Universal Logic Plug) system with product references
54440 to 54445. See the User’s Manual, ULP Connection System, product reference TRV99100
z Or use the Phaseo power supply recommended earlier in this topic, protecting it with an isolating
transformer from the Phaseo Optimum (ABL6TS) range or the Universal (ABT7PDU) range.
NOTE: For each of these solutions, you should refer to the respective manuals.

Protection Against a 240 Vac Fault on the Acti 9 Smartlink Device 24 Vdc Input
In case a 240 Vac power supply is accidentally connected to the 24 Vdc input on the Acti 9 Smartlink power
supply, fuse protection is provided.

DOCA0004EN 05/2015 27
Sizing the 24 V DC Power Supply

Protection Against a 240 Vac Fault on the Acti 9 Smartlink Channels

Protection Against a 240 Vac Fault on the Acti 9 Smartlink Channels


In the event of a wiring error or electrical fault, the 240 Vac voltage may be present on the
Acti 9 Smartlink device channels: the neutral or phase (240 Vac) can be in contact with the Ti24 interfaces
or the 24 Vdc power supply.
The insulation inside the Acti 9 Smartlink device prevents propagation of this dangerous voltage (240 Vac)
over the Modbus network.
The protection function inside the Acti 9 Smartlink device eliminates the risk of fire inside the
Acti 9 Smartlink device.
These two protection functions (internal insulation and internal protection) cannot prevent wiring errors or
electrical faults. A risk of dangerous voltage remains on the Acti 9 Smartlink device channels.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
z Implement a TT or TN-S earthing system.
z Connect the SELV power supply 0 Vdc to the protective earth to make it a PELV (Protective Extra Low
Voltage) power supply. The upstream residual current protection must be type A.
Failure to follow these instructions will result in death or serious injury.

NOTE: In the majority of cases, the presence of a PELV means an upstream residual current protection
can trip, thus protecting people and property.

DANGER
ACCIDENTAL EQUIPMENT BEHAVIOR
z Connect the 0 Vdc of the SELV power supply to the protective earth at a single point to avoid any stray
currents (50 Hz, harmonics, or transient currents) circulating across the 0 Vdc.
z Check that products supplied by this power supply are not already connecting the 0 Vdc to the
protective earth.
Failure to follow these instructions will result in death or serious injury.

NOTICE
RISK OF DAMAGING THE ACTI 9 SMARTLINK DEVICE
z Connect the 0 Vdc of the SELV power supply to the protective earth at a single point to avoid any stray
currents (50 Hz, harmonics, or transient currents) circulating across the 0 Vdc.
z Check that products supplied by this power supply are not already connecting the 0 Vdc to the
protective earth.
Failure to follow these instructions can result in equipment damage.

28 DOCA0004EN 05/2015
Sizing the 24 V DC Power Supply

Electromagnetic Compatibility (EMC) Recommendations

Electromagnetic Compatibility (EMC) Recommendations


A star 24 Vdc distribution is preferable to a serial 24 Vdc distribution because star 24 Vdc distribution can
minimize the wiring impedance.
If serial distribution is used, it is advisable to wire two serial loopback wires (see the two blue wires in the
following drawing) in order to minimize impedance.

In a poor-quality electrical distribution network, it is advisable to use a Phaseo power supply from the
Universal range (ABL8MEM240xx (OVC II) or ABL7RM24025 (OVC II)) which can withstand up to 500 Vac
incoming and also offers galvanic insulation between the power supply AC input and the power supply DC
output of 4 kVac at 50 Hz.
It is advisable to comply with the segregation rules between low level signals (24 Vdc) and power
conductors, see:
z www.electrical-installation.org see the "ElectroMagnetic Compatibility (EMC)" part,
"Wiring recommendations" section (information only available in English).
z Electrical Installation Guide in pdf format: Document No. EIGED306001EN.

DOCA0004EN 05/2015 29
Sizing the 24 V DC Power Supply

30 DOCA0004EN 05/2015
Acti 9 Smartlink Modbus Communication System
Installation
DOCA0004EN 05/2015

Chapter 5
Installation

Installation

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Mounting 32
Connection 37

DOCA0004EN 05/2015 31
Installation

Mounting

Introduction
The Acti 9 Smartlink device can be mounted on:
z DIN rail
z Multiclip 80
z Multiclip 200
z Mounting brackets

Acti 9 Smartlink can be installed horizontally or vertically:


z In a horizontal mounting, Acti 9 Smartlink is clipped onto DIN rails with fixing centers of 150 mm or more.
z Wall-mounted and floor-standing enclosures must be at least 24 modules wide (18 mm x 24 = 432 mm).
z The distance between the DIN rail and the back of the wall-mounted or floor-standing enclosure must
be at least 50 mm.

The ambient operating temperature is:


z Horizontal mounting: −25° to +60°C
z Vertical mounting: −25° to +50°C

Mounting Components

Product Reference Description


A9XMSB11 Acti 9 Smartlink
A9XMFA04 Set of bracelets, adaptors and feet for DIN rail mounting
A9XM2B04 Spacers for Multiclip 200 mounting
A9XMBP02 Mounting brackets kit

32 DOCA0004EN 05/2015
Installation

DIN Rail Mounting


The side of the foot (A or B in the following drawing) used to mount the system on the DIN rail depends on
the type of rail (aluminum or iron).

The table describes the procedure for mounting the Acti 9 Smartlink device on a DIN rail:

Step Action
1 Clip one bracelet onto one foot according to the type of rail. Repeat this step three times.
2 Clip the Acti 9 Smartlink device on top of the bracelets.
3 Place the top of the foot at an angle against the top lip of the rail.
4 Clip the bottom of the foot into place.
5 Repeat steps 3 and 4 for each of the other three feet.

DOCA0004EN 05/2015 33
Installation

Simple DIN Rail Mounting


To mount the system on a simple DIN rail (iron), use side A of the foot.

The table describes the procedure for mounting the Acti 9 Smartlink device on a simple DIN rail:

Step Action
1 Clip one bracelet onto side A of a foot. Repeat this step three times.
2 Place one M6 nut inside a foot. Repeat this step three times.
3 Position the top of an adaptor diagonally at the front of a foot.
4 Clip the bottom of the adaptor into place. Repeat steps 3 and 4 three times.
5 Drill the rail making sure that the drill hole diameters and positioning dimensions are correct, as shown in
the preceding graphic.
6 Screw the feet onto the rail.

34 DOCA0004EN 05/2015
Installation

Mounting on Multiclip 80

The table describes the procedure for mounting the Acti 9 Smartlink device on Multiclip 80.

Step Action
1 Position the two clips in the notches on the Acti 9 Smartlink device.
2 Slide the Acti 9 Smartlink device front first onto the Multiclip 80 until fully inserted.
3 Push down the two clips until they click into place.

Mounting on Multiclip 200

The table describes the procedure for mounting the Acti 9 Smartlink device on Multiclip 200.

Step Action
1 Slide the four spacers from the back into the notches on top of the Multiclip 200.
2 Slide the Acti 9 Smartlink device front first onto the spacers, until it clicks into place.

DOCA0004EN 05/2015 35
Installation

Mounting with Brackets

The table describes the procedure for mounting the Acti 9 Smartlink device with brackets.

Step Action
1 Drill the plate of the cubicle making sure that the drill hole diameters and positioning dimensions are correct,
as shown in the preceding graphic.
2 Slide the 2 brackets, from the back of the Acti 9 Smartlink device, into the notches on the bottom of the
Acti 9 Smartlink device until they click into place.
3 Screw the brackets onto the plate.

36 DOCA0004EN 05/2015
Installation

Connection

Safety Instructions

DANGER
RISK OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
z Wear suitable personal protective equipment and follow the currently applicable electrical safety
instructions.
z This equipment may only be installed by qualified electricians who have read all the relevant
information.
z NEVER work alone.
z Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources
of electric power. Assume that all circuits are live until they have been completely de-energized, tested
and tagged. Pay particular attention to the design of the power system. Consider all power supply
sources, particularly the potential for backfeed.
z Before closing protective covers and doors, carefully inspect the work area to ensure that no tools or
objects have been left inside the equipment.
z Take care when removing or replacing panels. Take special care to ensure that they do not come into
contact with live busbars. To minimize the risk of injuries, do not tamper with the panels.
z The successful operation of this equipment depends upon proper handling, installation, and operation.
Failure to follow basic installation procedures can lead to personal injury as well as damage to
electrical equipment or other property.
z NEVER shunt an external fuse/circuit breaker.
z This equipment must be installed inside a suitable electrical cabinet.
Failure to follow these instructions will result in death or serious injury.

DANGER
RISK OF ELECTROCUTION
Isolate the Acti 9 Smartlink power terminals from the power terminals connected to the Modbus network
line.
Failure to follow these instructions will result in death or serious injury.

Connecting the Power Supply Connector

The table describes the procedure for connecting the power supply connector:

Step Action
1 Insert both stripped power supply wires in the connector.
2 Fix the wires in place using the connector tightening screws.

DOCA0004EN 05/2015 37
Installation

The table gives the characteristics of cables that can be used to connect the 24 Vdc power supply:

7 mm 0.2...1.5 mm² 0.8 N.m 0.6 x 3.5

Connecting the Modbus Connector


The Schneider Electric communication cables to be used are:

Product Description Length (m)


Reference
50965 RS 485 double shielded twisted pair cable for Modbus serial link (supplied 60
without connector)

38 DOCA0004EN 05/2015
Installation

NOTE:
z It is possible to use a common 24 Vdc power-supply for several Acti 9 Smartlink devices if installed in
the same switchboard.

NOTICE
HAZARD OF NON-OPERATION OF MODBUS NETWORK
Comply with the wiring and connection rules described later in this topic to create a working Modbus
network.
Failure to follow these instructions can result in equipment damage.

The table describes the procedure for connecting the Modbus connector:

Step Action
1 Coil up the Modbus communication cable shielding.
2 Cut the shielding 20 mm from the sheath.
3 Insert the stripped wires in the connector terminals as shown in the preceding graphic.
4 Fix the wires in place using the connector tightening screw.

The table gives the characteristics of cables that can be used to connect the Modbus connector:

7 mm 0.2...1.5 mm² 0.8 N.m 0.6 x 3.5

DOCA0004EN 05/2015 39
Installation

Checking the Modbus Serial Link


The table gives the characteristics of the RS 485 link that need to be checked during installation:

Designation Description
Shielding connection Each Modbus serial link must have shielding connected at one point to an earthed
link.
Bus polarization z Pull-up resistor connected to the 5 V: 450...650 Ohm
z Pull-down resistor connected to ground (Modbus 0 V): 450...650 Ohm

NOTE: This polarization is recommended for the master.


Line terminator 2 Modbus line terminators (120 Ohm + 1 nF), reference VW3A8306DRC.
The Modbus cable communication pair has characteristic impedance of 120 Ohm.
The Modbus cable must therefore have a Modbus line terminator with 120 Ohm
impedance at each end.
The Modbus master is at one end of the Modbus cable and usually has a switchable
terminal impedance. At the other end of the Modbus cable, a Modbus line terminator
with 120 Ohm impedance must be connected.
To obtain a high-frequency impedance of 120 Ohm without loading the cable with
direct current, the Modbus line terminator is optimized in the form of an RC cell:
120 Ohm in series with a 1 nF capacitor and two 10 cm wires for direct connection to
the 5-pin connector of the last Modbus interface module, between D0 and D1.
Ground polarity The ground circuit (0 V of an optional power supply) must be connected directly to a
protected earth, preferably at a single point on the bus.
This point is usually placed on the master or its slaves.
Trunk cable A pair of shielded twisted cables and a third conductor at minimum.
Maximum length of bus 1000 m at 19,200 Baud with the Schneider Electric 50965 cable

Setting the Modbus Address Parameters


The Acti 9 Smartlink device addressing is performed using two thumbwheels:
z The left-hand thumbwheel sets the tens.
z The right-hand thumbwheel sets the units.

NOTE:
z The Acti 9 Smartlink device addressing must be between 01 and 99.
z A standard Modbus network consists of up to 31 slaves.
z In run mode, the user can change the Modbus slave address without having to de-energize the
Acti 9 Smartlink.
z To reset the Acti 9 Smartlink factory settings (pulse weight at value 10, meters at 0, communication
parameters), proceed as follows:
z De-energize Acti 9 Smartlink
z Set the Modbus address to value 00
z Re-energize Acti 9 Smartlink
z Set the selected address

40 DOCA0004EN 05/2015
Acti 9 Smartlink Modbus Communication System
Connection of Input/Output Channels
DOCA0004EN 05/2015

Chapter 6
Connection of Input/Output Channels

Connection of Input/Output Channels

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Acti 9 Devices with Ti24 Interface 42
Meters 43
Volt-Free Low Level Indication Contact 44
Volt-Free Standard Indication Contact 45
Surge Arresters 46
Contactor and Relay (Not in the Acti 9 Range) 49
Direct Output Connection 50
Indirect Output Connection 51
Generating Summary Data Using iOF+SD24 or OF+SD24 52

DOCA0004EN 05/2015 41
Connection of Input/Output Channels

Acti 9 Devices with Ti24 Interface

Overview
Devices (iACT24, iATL24, iOF+SD24, OF+SD24, RCA iC60, Reflex iC60) can be connected to the
Acti 9 Smartlink with Acti 9 communication system pre-asssembled cables.

Wiring
The following figure shows the connection of devices to the Acti 9 Smartlink using pre-assembled cables:

NOTE: A9XCAU06 or A9XCAC01 cable could be used to link Acti 9 devices with Ti24 interface to
Acti 9 Smartlink.
In this case, for the connection of iACT24 and iATL24, input I2 must be connected on both ends of
A9XCAU06 or A9XCAC01 cable.

42 DOCA0004EN 05/2015
Connection of Input/Output Channels

Meters

Overview
The iEM2000T, iEM3110, iEM3155, iEM3210 and iEM3255 products are kilowatt-hour meters from the
Schneider Electric range.
Meters not in the Acti 9 range can be controlled by an Acti 9 Smartlink channel. These meters must have
the following characteristics:
z One pulse output
z Compatibility with standard CEI 62053-31

Wiring
iEM2000T, iEM3110, iEM3155, iEM3210 and iEM3255 kilowatt-hour meters can be connected to channel
N (1 ≤ N ≤ 11) of an Acti 9 Smartlink module with an A9XCAU06 or A9XCAC01 pre-wired cable: molded
connector (at Acti 9 Smartlink end), and with five wires (at iEM2000T end).

NOTE: A single Acti 9 Smartlink channel can take account of two meters, one meter on input I1 and
1 meter on input I2.
NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

Example of Connection of iEM2000T Meters

(1) iEM2000T meter


(2) iEM2000T meter

DOCA0004EN 05/2015 43
Connection of Input/Output Channels

Volt-Free Low Level Indication Contact

Overview
A low level type indication contact (NO or NC) can be connected to input I1 or I2 of an Acti 9 Smartlink
channel.
NOTE: A single Acti 9 Smartlink channel can take account of two indication contacts, one contact on input
I1 and one contact on input I2.

Wiring
An indication contact can be connected with an A9XCAU06 or A9XCAC01 pre-wired cable: molded
connector (at Acti 9 Smartlink end), and with the five wires (indication contact end).

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

Example of Connection
The OF and SD contacts of a NSX circuit breaker could be directly connected to Acti 9 Smartlink.

44 DOCA0004EN 05/2015
Connection of Input/Output Channels

Volt-Free Standard Indication Contact

Overview
A standard indication contact (NO or NC) can be connected to input I1 or I2 of an Acti 9 Smartlink channel.
NOTE: A single Acti 9 Smartlink channel can take account of two indication contacts, one contact on input
I1 and one contact on input I2. The electrical diagram must be indirect between Acti 9 Smartlink and this
device: a low level relay must be installed between the contact of this device and Acti 9 Smartlink.

Wiring
An indication contact can be connected with an A9XCAU06 or A9XCAC01 pre-wired cable: molded
connector (at Acti 9 Smartlink end), and with the five wires (indication contact end).

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

Example of Connection

(1) NG125 circuit breaker: OF+SD auxiliary contacts with a minimum current of 100 mA
(2) iRBN relay for OF signal
(3) iRBN relay for SD signal

DOCA0004EN 05/2015 45
Connection of Input/Output Channels

Surge Arresters

Overview
Acti 9 surge arresters can be connected to Acti 9 Smartlink:
z The remote transfer contact (indication contact: NO) of an Acti 9 surge arrester can be connected to
input I1 or I2 of an Acti 9 Smartlink channel.
z The SD fault-trip indication contact (indication contact: NC) of the circuit breaker associated to an Acti 9
surge arrester can be connected to input I1 or I2 of an Acti 9 Smartlink channel.
NOTE: A single Acti 9 Smartlink channel can take account of two indication contacts, one contact on input
I1 and one contact on input I2.

Wiring
An indication contact can be connected with an A9XCAU06 or A9XCAC01 pre-wired cable: molded
connector (at Acti 9 Smartlink end), and with the five wires (indication contact end).
The following wiring is dedicated to surge arresters:
z iPRD
z iPRD 40r PV
z iQuick PRD

The following wiring is dedicated to surge arresters:


z iPRF1 12.5r
z PRD1 25r
z PRD1 Master

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

46 DOCA0004EN 05/2015
Connection of Input/Output Channels

Examples of Connection
The following electrical diagram is dedicated to iPRD surge arrester.

(1) Remote transfer contact of iPRD surge arrester: cartridges status


(2) iSD fault-trip indication contact of iC60 circuit breaker associated to iPRD surge arrester

The following electrical diagram is dedicated to surge arresters:


z iPRD 40r PV
z iQuick PRD

(1) Remote transfer contact of surge arrester: cartridges status

DOCA0004EN 05/2015 47
Connection of Input/Output Channels

The following electrical diagram is dedicated to iPRF1 12.5r surge arresters:

(1) Remote transfer contact of iPRF1 12.5r surge arrester: surge arrester status
(2) iSD fault-trip indication contact of NSX160F or NG125 circuit breaker associated to iPRF1 12.5r surge arrester

The following electrical diagram is dedicated to surge arresters:


z PRD1 25r
z PRD1 Master

(1) Remote transfer contact of PRD1 25r or PRD1 Master surge arrester: cartridges status
(2) iSD fault-trip indication contact of NSX160 circuit breaker associated to PRD1 25r or PRD1 Master surge arrester

48 DOCA0004EN 05/2015
Connection of Input/Output Channels

Contactor and Relay (Not in the Acti 9 Range)

Overview
A contactor or relay powered with 24 Vdc can be connected to Acti 9 Smartlink. This should have the
following characteristics:
z The contactor or relay coil must not draw more than 100 mA
z The indication contact must be low level type

Only contactors in the Acti 9 range can be connected to Acti 9 Smartlink using the iACT24 auxiliary.

Wiring
A contactor can be connected with an A9XCAU06 or A9XCAC01 pre-wired cable: molded connector (at
Acti 9 Smartlink end), and with five wires (at contactor end).

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

Example of Connection

(1) Low level relay (for example, iRBN)


(2) 24 Vdc relay
(3) Power contactor (e.g. TeSys D, type LC1)

DOCA0004EN 05/2015 49
Connection of Input/Output Channels

Direct Output Connection

Overview
An indication device or a PLC input can be directly connected to the output (Q) of Acti 9 Smartlink channel.
The connected device should have the following characteristics:
z To be powered with 24 Vdc
z The consumption must be less than 100 mA

Wiring
The wiring can be done with an A9XCAU06 or A9XCAC01 pre-wired cable: molded connector (at
Acti 9 Smartlink end), and with five wires (at contactor end).

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

Example of Connection

(1) Indication light 24 Vdc

50 DOCA0004EN 05/2015
Connection of Input/Output Channels

Indirect Output Connection

Overview
Any device (for example: motor) that needs a command circuit of more than 100 mA can be could
controlled by the output (Q) of a channel of Acti 9 Smartlink. The electrical diagram must be indirect
between Acti 9 Smartlink and this device: a low level relay must be installed between the command of this
device and Acti 9 Smartlink.

Wiring
The wiring can be done with an A9XCAU06 or A9XCAC01 pre-wired cable: molded connector (at
Acti 9 Smartlink end), and with five wires (at contactor end).

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).

z Do not connect a wire with cable end in each of the Ti24 connector terminals.

Example of Connection

(1) Relay iRTBT


(2) Contactor Tesys D LC1D•25 with an 230 Vac coil
(3) Motor 10 kW with power supply 3-phases 380 Vac

DOCA0004EN 05/2015 51
Connection of Input/Output Channels

Generating Summary Data Using iOF+SD24 or OF+SD24

Overview
The electrical summary of the SD contacts or summary of the OF contacts can be generated with
iOF+SD24 and/or OF+SD24 auxiliaries.
The electrical summary of the OF signals can be done by cabling in series of all OF signals and by
connecting this circuit to the I1 input of a channel of Acti 9 Smartlink.
The electrical summary of the SD signals can be done by cabling in series of all SD signals and by
connecting this circuit to the I2 input of another channel of Acti 9 Smartlink.
The OF connections (on I1 input) and the SD connections (on I2 input) cannot be connected to the same
channel of Acti 9 Smartlink, as the summary information dedicated to the OF signals cannot be separated
from the summary information dedicated to the SD signals in Acti 9 Smartlink.
The summary of OF (or SD) signals can be wired in series using the A9XC2412 15-pin connector (spring
cage). A maximum of 10 OF (or SD) signals can be wired in the same summary.

Wiring SD Contacts on iOF+SD24 or OF+SD24 in Series

(1) Input I2 (of a channel) on Acti 9 Smartlink or PLC input

52 DOCA0004EN 05/2015
Connection of Input/Output Channels

Wiring OF Contacts on iOF+SD24 or OF+SD24 in Series

(1) Input I1 (of a channel) on Acti 9 Smartlink or PLC input

DOCA0004EN 05/2015 53
Connection of Input/Output Channels

54 DOCA0004EN 05/2015
Acti 9 Smartlink Modbus Communication System
Ecoreach
DOCA0004EN 05/2015

Chapter 7
Ecoreach

Ecoreach

Ecoreach Software

Definition
Ecoreach software enables the firmware upgrades of the following devices:
z Acti 9 Smartlink Modbus (RS485)
z Acti 9 Smartlink Ethernet

For more information, see the Ecoreach Online Help.

Features
Ecoreach software allows you to perform the following actions:
z Create projects by device discovery and selection of devices from Schneider Electric catalog
z Monitor the status of protection and IO status
z Read information like, alarms, measurements, parameters
z Configuration or settings download and upload for single or multiple devices
z Perform control actions in a secured way
z Generate and print device settings report and communication test report
z Manage multiple devices with electrical and communication hierarchy model
z Manage artifacts (project and device documents)
z Check consistency in settings between devices in a communication network
z Compare configuration settings between the project and device (online)
z Download latest firmware and upgrade devices
z Safe repository of projects in Ecoreach cloud and sharing of projects with other users

Legacy Software
Ecoreach software replaces the following legacy software:
z Acti 9 Smart Test software
z Acti 9 Smartlink Ethernet web page

DOCA0004EN 05/2015 55
Ecoreach

56 DOCA0004EN 05/2015
Acti 9 Smartlink Modbus Communication System
Test
DOCA0004EN 05/2015

Chapter 8
Test

Test

Acti 9 Smart Test Software

Overview
The main purpose of the Acti 9 Smart Test software is to help technical personnel to check that all devices
are correctly wired and function properly after installation.
The Acti 9 Smart Test software offers a quick test process based on a very intuitive Graphical User
Interface.
This software has the ability to deal with multiple Acti 9 Smartlink devices at the same time. They can be
chained and multiple Acti 9 devices can be connected to the computer using Smartlink Modbus, EGX/IFE,
and Smartlink Ethernet network. The maximum number of Acti 9 Smartlink devices that can be connected
for Smartlink Modbus and EGX/IFE network is 10. The maximum number of Acti 9 Smartlink slave devices
that can be connected for Smartlink Ethernet network is eight. The slave devices can include
Acti 9 Smartlink Modbus.
The Acti 9 Smart Test software is used to update the Acti 9 Smartlink firmware.
The Acti 9 Smartlink Modbus can only be updated through IFE or Acti 9 Smartlink Ethernet. The firmware
upgrade for Acti 9 Smartlink Modbus is not supported through EGX gateway.
When Acti 9 Smartlink Modbus firmware upgrade is initiated, Acti 9 Smartlink Modbus product should be
in an isolated network along withe the gateway. No other Modbus master should be polling any other
Modbus device connected in the same network.

Main Functions
The Acti 9 Smart Test software has four main functions:
z Testing the installation
z Generating test reports
z Upgrading the firmware version
z Configuring the channels and recovering the configuration of Acti 9 Smartlink channels

The Acti 9 Smart Test has one complementary function; updating the firmware on Acti 9 Smartlink.
In order to test the installation, the software:
z Tests the communication network (Modbus SL/Modbus TCP/IP).
z Tests the connection and the status of the electrical devices connected to Acti 9 Smartlink.

Also, the software provides the following reports:


z List of tested devices (.pdf file)
z Acti 9 Smartlink channels assignment (.dxf file)

DOCA0004EN 05/2015 57
Test

The screenshot shows the main interface of the Acti 9 Smart Test software.

Downloading and Installation


Acti 9 Smart Test software can be downloaded from Schneider Electric website.
Acti 9 Smart Test software is available in two versions:
z Full version including Microsoft .NET Framework (package that contains light version and Microsoft
.NET Framework)
z Light version without Microsoft .NET Framework

We recommend to install the full version if Microsoft .NET Framework (3.5 or later) is not installed on the
PC.
The table describes the procedure for installing the Acti 9 Smart Test software:

Step Description
1 Go to the Schneider Electric website: www.schneider-electric.com or Schneider Electric country
website.
2 In the search field, enter SmartTest without space character.
3 Select "Acti 9 Smart Test Software 3.1.1 (with .NET Framework)" or "Acti 9 Smart Test Software 3.1.1
(without .NET Framework)".
4 Download the Acti 9 Smart Test software.
5 Install the Acti 9 Smart Test software.
6 Acti 9 Smart Test user guide can be downloaded from Schneider Electric web site.
z In the search field, enter:
z DOCA0029EN for English user guide,
z DOCA0029ES for Spanish user guide,
z DOCA0029FR for French user guide,
z DOCA0029DE for German user guide,
z DOCA0029IT for Italian user guide,
z DOCA0029PT for Portuguese user guide,
z DOCA0029RU for Russian user guide,
z DOCA0029ZH for Chinese user guide,

z Select the user manual.


z Download the user guide.

Acti 9 Smart Test software is also available in the Power Launcher library.

58 DOCA0004EN 05/2015
Test

Registration
Acti 9 Smart Test software requires a user registration.
The software can be started 10 times before online registration.
The software is always free of charge even after online registration.

DOCA0004EN 05/2015 59
Test

60 DOCA0004EN 05/2015
Acti 9 Smartlink Modbus Communication System
Setting Up Modbus Communication
DOCA0004EN 05/2015

Chapter 9
Setting Up Modbus Communication

Setting Up Modbus Communication

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Modbus Master/Slave Principle 62
Setup 65
Resetting with Factory Parameters 66
Acti 9 Smartlink Device Functions 67
Modbus Functions 69
Modbus Exception Codes 70
Description of LEDs 71

DOCA0004EN 05/2015 61
Setting Up Modbus Communication

Modbus Master/Slave Principle

Overview
The Modbus protocol exchanges data using a request/response mechanism between a master and a
slave. The master/slave principle is a type of communication protocol in which a device (the master)
controls one or more devices (the slaves). A standard Modbus network consists of one master and up to
31 slaves.
NOTE: For more information, a detailed description of the Modbus protocol is available on
www.modbus.org.

Characteristics of the Master/Slave Principle


The master/slave principle has the following characteristics:
z Only one master at a time is connected to the network.
z Only the master can launch communication and send requests to slaves.
z The master can address each slave individually using its dedicated address or all slaves simultaneously
using address 0.
z The slaves can only send responses to the master.
z Slaves cannot launch communication with either the master, or the other slaves.

Master/Slave Communication Modes


The Modbus protocol can exchange data using two communication modes:
z Request/response mode
z Broadcast mode

Each Acti 9 Smartlink has a Modbus address (1 to 99), and concentrates data from connected devices on
its 11 channels (Ti24 interface).
The states and orders for each device connected to Acti 9 Smartlink are accessible in registers whose
address depends on the channel (1 to 11) on which the device is connected.

62 DOCA0004EN 05/2015
Setting Up Modbus Communication

Request/Response Mode
In request/response mode, the master addresses 1 slave using the slave’s dedicated address. The slave
processes the request, then responds to the master.

Broadcast Mode
In broadcast mode, the master addresses all the slaves using address 0. Slaves do not respond to
broadcast messages.

Turnaround Time
The turnaround time Tr is the time between the end of receipt of a request and sending the response.

The typical value of the turnaround time Tr is less than 10 ms with the Modbus protocol.

DOCA0004EN 05/2015 63
Setting Up Modbus Communication

Data Exchange
The Modbus protocol uses two data types:
z Bits
z 16-bit words called registers

Each register has a register number. Each data type (bit or register) has a 16-bit address.
Messages exchanged with the Modbus protocol contain the address of the data to be processed.

Frames
All frames exchanged with the Modbus protocol are 256 bytes maximum and consist of four fields:

Field Definition Size Description


1 Slave number 1 byte Destination of the request
z 0: broadcast (all slaves are affected)
z 1...247: unique destination

2 Function code 1 byte Modbus (see page 69) Function


3 z Data n bytes z Request or response data
z Sub-function code z Sub-function code

4 Check 2 bytes CRC16 (to check transmission errors)

Data Format
The data format is configured as shown in the following table according to Modbus RTU format:

Start Data Parity Stop


1 bit 8 bits 1 bit 1 bit

NOTE: The Modbus RTU data format is composed of 11 bits.


Even parity is required, other modes (odd parity, no parity) may be also used.
If no parity is implemented in the Modbus Master, an additional stop bit must be transmitted by the Modbus
Master to fill out the character frame to a full 11 bit asynchronous character.
NOTE: For more information, a detailed description of the Modbus protocol is available on
www.modbus.org.

64 DOCA0004EN 05/2015
Setting Up Modbus Communication

Setup

Initialization
The table describes the two initialization phases for the Acti 9 Smartlink device:

Phase Description
1 z Acti 9 Smartlink must be connected to a Modbus master.
z When the 24 Vdc power supply is activated, the Modbus communication for the Acti 9 Smartlink device
is initialized and addressing is taken into account.
2 After receiving a maximum of 25 frames from the master, Acti 9 Smartlink automatically adapts its
communication parameters to those of the master (speed, parity and number of stop bits).

NOTE: The Modbus network communication speed is the same for all serial connections for the Modbus
devices used. It is imposed by the lowest communication speed of a slave device.
NOTE: Automatic adaptation to the communication parameters only occurs on powering up the
Acti 9 Smartlink.

Setting the Modbus Address Parameters


The Acti 9 Smartlink device addressing is performed using two thumbwheels:
z The left-hand thumbwheel sets the tens
z The right-hand thumbwheel sets the units

NOTE:
z The Acti 9 Smartlink device address must be between 01 and 99.
z A standard Modbus network consists of up to 31 slaves.
z In run mode, the user can change the Modbus slave address without having to de-energize the
Acti 9 Smartlink.

Communication Parameters
The communication parameter values are as follows:

Settings Authorized Values Default Value


Data rate (in Baud) 4800, 9600, and 19,200 19,200
Parity z Even and one stop bit Even (with one stop bit)
z Odd and one stop bit
z No parity (parity bit eliminated), 2 stop bits
are needed.

NOTE: The Modbus network communication speed is the same for all serial connections for the Modbus
devices used. It is imposed by the lowest communication speed of a slave device.

DOCA0004EN 05/2015 65
Setting Up Modbus Communication

Resetting with Factory Parameters

Description
To reset the Acti 9 Smartlink device, proceed as follows:

Step Action
1 De-energize Acti 9 Smartlink.
2 Set the Modbus address to value 00.
3 Re-energize Acti 9 Smartlink.

The reset data is as follows:


z The communication parameters become: 19,200 Baud, even parity, one stop bit.
z The operation counters are set to 0.
z The running hours counters are set to 0.
z The counter modification dates are set to the value "1 January 2000".
z The counter pulse weights are set to 10.

66 DOCA0004EN 05/2015
Setting Up Modbus Communication

Acti 9 Smartlink Device Functions

Acti 9 Device Command and Control Functions


The products concerned are:
z iOF+SD24
z OF+SD24
z iACT24
z iATL24
z Reflex iC60
z RCA iC60

Input state acquisition function:


z Open/closed state (input I1 of the Ti24 interface)
z Trip signal (input I2 of the Ti24 interface) for the protection devices

Open and close order function:


Each Acti 9 Smartlink channel offers an output (Q):
z Output Q is set to 1 by forcing the bit of the channel concerned to 1 in the activation register (ON). The
Modbus command register bit is automatically set to 0 by Acti 9 Smartlink as soon as the order has been
sent to output Q.
z Output Q is set to 0 by forcing the bit of the channel concerned to 1 in the deactivation register (OFF).
The Modbus command register bit is automatically set to 0 by Acti 9 Smartlink as soon as the order has
been sent to output Q.
Installation life management function:
z Acti 9 Smartlink stores the number of changes of state (or number of operations) for the control and
protection devices, which allows the wear on these devices to be estimated. To do this, Acti 9 Smartlink
counts the changes of state of input I1 (on falling edge) for each channel.
z Acti 9 Smartlink stores the number of protection device trips, thus highlighting faults in the electrical
installation. To do this, Acti 9 Smartlink counts the changes of state of input I2 (on falling edge) for each
channel.
z Acti 9 Smartlink stores the total time when control products are closed, which allows the wear on
controlled loads to be estimated. To do this, Acti 9 Smartlink counts the changes of state of input I1
(OF state) for each channel.
z This data (number of changes of state, running hours) can be reset to 0, and the initialization date can
be stored.

Command and Control Functions of Devices Not in the Acti 9 Range


Input state acquisition function:
All other types of device offering low level I/O (24 Vdc) can be connected to the 22 inputs and 11 outputs
offered by Acti 9 Smartlink. Each Acti 9 Smartlink channel offers 2 inputs (I1 and I2).
Command function:
Each Acti 9 Smartlink channel offers an output (Q).
z Output Q is set to 1 by forcing the bit of the channel concerned to 1 in the activation register (ON). The
Modbus command register bit is automatically set to 0 by Acti 9 Smartlink as soon as the order has been
sent to output Q.
z Output Q is set to 0 by forcing the bit of the channel concerned to 1 in the deactivation register (OFF).
The Modbus command register bit is automatically set to 0 by Acti 9 Smartlink as soon as the order has
been sent to output Q.

Counting Functions
Schneider Electric energy meters with pulse output:
z iEM2000T (the pulse weight equals 10)
z iEM3110 (the pulse weight can be configured)
z iEM3155 (the pulse weight can be configured)
z iEM3210 (the pulse weight can be configured)
z iEM3255 (the pulse weight can be configured)

Acti 9 Smartlink calculates the energy consumption and the average power between two pulses.
Energy consumption = Number of pulses counted × pulse weight
Average power between two pulses = (3600 × Pulse weight)/t; the result is expressed for one hour.
With t, the time in seconds between the last two pulses received.

DOCA0004EN 05/2015 67
Setting Up Modbus Communication

Other types of meter with pulse output:


z water, gas meters, etc.
z Any type of meter whose pulse output complies with standard IEC 62053-21 (minimum pulse 30 ms).

The pulse weight can be configured.


Acti 9 Smartlink calculates the consumption and the average flow between two pulses.
Consumption = Number of pulses counted × pulse weight
Average flow = (3600 × pulse weight)/t; the result is expressed for one hour.
With t, the time in seconds between the last two pulses received.
The average power data (or average flow) between two pulses is reset to 0:
z After a duration d = 3 x t; if 3 x t is less than 5 seconds, the duration d equals five seconds
With t, the time in seconds between the last two pulses received.
z After 24 hours without a pulse
z After loss of the 24 Vdc input/output voltage

Every 10 minutes, the meter values are saved in the EEPROM memory.
Each time it changes, the value of each pulse is saved instantly in the EEPROM memory.
The meter parameter setting dates are saved instantly in the EEPROM memory.

System Behavior in the Event of Loss of the 24 Vdc Power Supply


Up to a duration of 10 ms, Acti 9 Smartlink is unaffected by voltage dips. If the voltage is below 19.2 Vdc
(24 Vdc - 20%) for more than 10 ms, Acti 9 Smartlink changes to downgraded mode:
z All the outputs are set to zero. However the Acti 9 control auxiliaries (iACT24, iATL24, Reflex iC60,
RCA iC60) distinguish this loss of voltage event in actual order. They do not therefore change state.
z The time between two write operations in the EEPROM memory is 10 min. Data previously written to
this memory is not modified on loss of voltage. Saved values therefore date back a maximum of 10 min.
z Calculated power (or flow) values are not saved. They are set to zero.

System Behavior at the Time the 24 Vdc Power Supply is Energized or Returns
NOTE: The Acti 9 Smartlink power supply must be between 19.2 Vdc (24 Vdc - 20%) and 28.8 Vdc
(36 Vdc - 20%).
z The outputs remain at zero.
z The Acti 9 control auxiliaries (iACT24, iATL24, Reflex iC60, RCA iC60) do not change status since they
operate according to rising or falling edge.
z Data stored in the EEPROM memory is written to the corresponding registers (pulse weights, event
counters, impulse counters, running hours counters, counter reset dates). The values in the registers
are therefore those of the last save to the EEPROM memory. These values may differ from the last
values read in the registers before the power failure.
NOTE: If the Acti 9 Smartlink thumbwheels are set to zero during the loss of voltage, Acti 9 Smartlink is
reset when the power returns. For more information, see Resetting with factory parameters (see page 66).

68 DOCA0004EN 05/2015
Setting Up Modbus Communication

Modbus Functions

General Description
The Modbus protocol offers functions for reading or writing data on the Modbus network. This protocol also
offers diagnostic and network management functions.
Only Modbus functions managed by the Acti 9 Smartlink device are described here.

Table of Modbus Functions


The following table describes in detail the functions supported by Acti 9 Smartlink devices:

Function Code Sub-Function Code Function Name


01 – Read n output or internal bits
02 – Read n input bits
03 – Read n output or internal words
05 – Write 1 bit
06 – Write 1 word
08 (1) Modbus diagnostics
15 – Write n bits
16 – Write n words
43 14 (2) Read identification

15(3) Read the date and time

16(4) Write the date and time

100 4 (5) Read n non-adjacent words where n ≤ 100.


NOTE:
Thanks to the read distributed holding register function, the user
can:
z Avoid reading a large block of adjacent words when only a few
words are needed.
z Avoid multiple use of function 3 in order to read non-adjacent
words.
(1) For more details, see the appendix describing function 8 (see page 118)
(2) For more details, see the appendix describing function 43–14 (see page 119)
(3) For more details, see the appendix describing function 43-15 (see page 121)
(4) For more details, see the appendix describing function 43-16 (see page 122)
(5) For more details, see the appendix describing function 100-4 (see page 123)

NOTE: For more information, a detailed description of the Modbus protocol is available on
www.modbus.org.

DOCA0004EN 05/2015 69
Setting Up Modbus Communication

Modbus Exception Codes

Exception Responses
Exception responses issued by the master or a slave can be the result of data processing errors. One of
the following events can occur after a request from the master:
z If the slave receives the request from the master without a communication error and manages the
request correctly, it sends back a normal response.
z If the slave does not receive the request from the master due to a communication error, it does not send
back a response. The master program ends by applying a time delay condition to the request.
z If the slave receives the request from the master but detects a communication error, it does not send
back a response. The master program ends by applying a time delay condition to the request.
z If the slave receives the request from the master without a communication error but cannot manage it
(for example, the request consists of reading a register that does not exist), the slave sends back an
exception response to inform the master of the nature of the error.

Exception Frame
The slave sends an exception frame to the master to indicate an exception response. An exception
response consists of four fields:

Field Definition Size


1 Slave number 1 byte
2 Exception function code 1 byte
3 Exception code n bytes
4 Check 2 byte

Managing Modbus Exceptions


The exception response frame consists of 2 fields that distinguish it from a normal response frame:
z The exception response’s exception function code is the same as the original request function code plus
128 (0x80).
z The exception code depends on the communication error detected by the slave.
The table describes the exception codes managed by the Acti 9 Smartlink device:

Exception Code Name Description


01 Illegal function The function code received in the request is not a permitted action for
the slave. It is possible that the slave is in an unsuitable state to
process a specific request.
02 Illegal data address The data address received by the slave is not a permitted address for
the slave.
03 Illegal data value The value of the request data field is not a permitted value for the
slave.
04 Slave device failure The slave is unable to perform a required action due to an
unrecoverable error.
06 Slave device busy The slave is busy processing another command. The master should
send the request once the slave is free.

NOTE: For more information, a detailed description of the Modbus protocol is available on
www.modbus.org.

Access to Variables
A Modbus variable can have the following attributes:
z Read-only
z Read/write
z Write-only

NOTE: An attempt to write to a read-only variable generates an exception response.

70 DOCA0004EN 05/2015
Setting Up Modbus Communication

Description of LEDs

LED Status

The table lists the LED status according to the operating mode:

Mode LEDs Status


Initialization COM: On, yellow

STATUS: On, green

Start-up COM :
z On yellow during communication with the Modbus serial port
z Off if there is no Modbus communication

STATUS: On alternately green and red once a second.


Operation COM :
z On yellow during communication with the Modbus serial port
z Off if there is no Modbus communication

STATUS: Green LED permanently on


Downgraded COM :
z On yellow during communication with the Modbus serial port
z Off if there is no Modbus communication

STATUS: Permanently orange. Peripheral device problem:


z Short-circuit or overload on the 24 Vdc I/O
z The power supply level is less than 19.2 Vdc

Failure COM :
z On yellow during communication with the Modbus serial port
z Off if there is no Modbus communication

STATUS: On, red (internal problem)

DOCA0004EN 05/2015 71
Setting Up Modbus Communication

72 DOCA0004EN 05/2015
Acti 9 Smartlink Modbus Communication System
Tables of Modbus Registers
DOCA0004EN 05/2015

Chapter 10
Tables of Modbus Registers

Tables of Modbus Registers

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
10.1 General Description of Modbus Tables 74
10.2 Summary and Detailed Modbus Tables 80
10.3 Modbus Tables for Connected Products 92

DOCA0004EN 05/2015 73
Tables of Modbus Registers

Section 10.1
General Description of Modbus Tables

General Description of Modbus Tables

What Is in This Section?


This section contains the following topics:
Topic Page
Overview 75
Modbus Table Format and Data Types 76
Global Modbus Address Table 79

74 DOCA0004EN 05/2015
Tables of Modbus Registers

Overview

Overview
All the Modbus tables in the Acti 9 Smartlink device have been designed to minimize the number of
Modbus requests that the master system needs to send in order to collect the data prepared by
Acti 9 Smartlink.
The Modbus tables in the Acti 9 Smartlink device are compact and are summaries of all the data collected
on the 11 channels of the Acti 9 Smartlink device.
The Modbus tables in the Acti 9 Smartlink device are described in:
z The section presenting:
z The overall list of Acti 9 Smartlink (see page 79) device address zones
z The summary of channel 1 to 11 address zones (see page 86)

z The section presenting the address zones for each type of device that can be connected to
Acti 9 Smartlink: iOF+SD24, OF+SD24, iACT24, iATL24, RCA iC60, Reflex iC60, iEM2000T, meter,
contactor and impulse relay (see page 92)
z The section presenting the address zones for each type of data (status, orders, measurements and
parameter settings) with a description of the summary zones and a description of the detailed data
zones for each channel.

General Organization of Modbus Tables in Acti 9 Smartlink Devices

Item Description Link


1 Channel summary data (see page 83)
2 System data independent of the channel (see page 81)
3 Data for channel 1 (see page 86)
Devices that can be connected to channel 1 (see page 92)
4 Data for channel 2 to 11 (see page 86)
Devices that can be connected to channel 2 to 11 (see page 92)

DOCA0004EN 05/2015 75
Tables of Modbus Registers

Modbus Table Format and Data Types

Table Formats
Register tables have the following columns:

Address No. RW X Unit Type Range Default Svd Function Description


Value Code

Designation Description
Address 16-bit register address that allows the user to access the variable. The address is expressed in decimal
notation.
Modbus Address:
The list of Modbus addresses, defined by the Modbus protocol, starts at 0. The detailed tables in
subsequent chapters of this manual give the Modbus addresses.
If the programmable controller ( master) refers to the data model addresses, the addresses to be
supplied to this controller must meet the following rule: Data model address = Modbus address + 1.
If the programmable controller (Modbus master) refers to the procotol addresses, the addresses to be
supplied to this controller must be the Modbus addresses.
No. Number of 16-bit registers that need to be read/written to access the complete information.
RW Whether the register is read only (R) or read-write (RW).
X Scale factor:
z Scale “X1” means that the value of the register is the right one with the unit indicated.
z A scale of 10 means that the register contains the value multiplied by 10. The actual value is
therefore the value of the register divided by 10.
z A scale of 0.1 means that the register contains the value multiplied by 0.1. The actual value is
therefore the value of the register multiplied by 10.
Unit Information unit of measurement:
z “–”: no unit corresponding to the value expressed.
z “h”: hours
z “D”: the unit depends on the connected device.

Type Coding data type (see "Data type" table later in this topic).
Range Range of permitted values for the variable, usually a subset of what the format allows. For BITMAP
type data, the content of this domain is “–”.
Default value Default value for the variable
Svd Saving the value in the event of a power failure:
z “Y”: the value of the register is saved in the event of a power failure.
z “N”: the value is lost in the event of a power failure.

NOTE: On start-up or reset, the available values are retrieved.


Function Code of functions that can be used in the register.
code
Description Information about the register and the restrictions that apply.

Data Types
The following data types appear in the tables of Modbus registers:

Name Description Range


UINT 16-bit unsigned integer (1 word) 0...65535
INT 16-bit signed integer (1 word) -32768...+32767
UINT32 32-bit unsigned integer (2 words) 0...4 294 967 295
INT32 32-bit signed integer (2 words) -2 147 483 648...+2 147 483 647
Float32 32-bit value (2 words) -3.4028E+38... +3.4028E+38
ASCII 8-bit alphanumeric character Table of ASCII Characters
BITMAP 16-bit field (1 word) –
DATE See “Date” table later in this topic –

NOTE:
Float32 type data: Single precision float with sign bit, 8 bits exponent, 23 bits mantissa (positive and
negative normalized real)

76 DOCA0004EN 05/2015
Tables of Modbus Registers

For ASCII type data, the order of transmission of characters in words (16-bit registers) is as follows:
z Character n as least significant
z Character n + 1 as most significant

All registers (16-bit or 2 bytes) are transmitted with Big Endian coding:
z The most significant byte is transmitted first
z The least significant byte is transmitted second

32-bit variables saved on two 16-bit words (e.g. consumption meters) are in Big Endian format:
z The most significant word is transmitted first, then the least significant.

64-bit variables saved on four 16-bit words (e.g. dates) are in Big Endian format:
z The most significant word is transmitted first, and so on.

DATE
DATE format in accordance with TI081 standard:

Word Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1 Reserved (0) R4 (0) Year (0...127)
2 0 Month (1...12) WD (0) Day (1...31)
3 SU (0) 0 Hour (0...23) iV 0 Minute (0...59)
4 Millisecond (0...59,999)
R4: Bit reserved
Year: 7 bits (year starting at 2000)
Month: 4 bits
Day: 5 bits
Hour: 5 bits
Minute: 6 bits
Millisecond: 16 bits
WD (day of the week) : Bit at 0 if this parameter is not used.
SU (summertime): Bit at 1 for summertime, bit at 0 if this parameter is not used.
iV (validity of the information received): Bit at 1 if the information is not valid, bit at 0 if this parameter is not
used.

Direct Bit Addressing


Addressing is permitted for BITMAP type zones with functions 1, 2, 5 and 15.
The address of the first bit is constructed as follows: (register address x 16) + bit number.
This addressing mode is specific to Schneider Electric.
Example: For functions 1, 2, 5 and 15, bit 3 of register 0x0078 should be addressed; the bit address is
therefore 0x0783.
NOTE: The register whose bit needs to be addressed should have an address ≤ 0x0FFF.

DOCA0004EN 05/2015 77
Tables of Modbus Registers

Example of Modbus Frames


Request

Definition Number of Bytes Value Comment


Slave number 1 byte 0x05 Acti 9 Smartlink Modbus Address
Function code 1 byte 0x03 Reads n output or internal words
Address 2 bytes 0x36E2 Address of a consumption meter whose address
is 14050 in decimal notation.
Number of words 2 bytes 0x002C Reads 44 16-bit registers.
CRC 2 bytes xxxx Value of CRC16.

Response

Definition Number of Bytes Value Comment


Slave number 1 byte 0x05 Acti 9 Smartlink Modbus Address
Function code 1 byte 0x03 Reads n output or internal words
Number of Bytes 2 bytes 0x0058 Number of bytes read
Value of words read 88 bytes – Reads 44 16-bit registers
CRC 2 bytes xxxx Value of CRC16.

Modbus Address
The list of Modbus addresses, defined by the protocol, starts at 0. The detailed tables in subsequent
chapters of this manual give the addresses.
If the programmable controller (Modbus master) refers to the data model addresses, the addresses to be
supplied to this controller must meet the following rule: Data model address = address + 1.
If the programmable controller (Modbus master) refers to the procotol addresses, the addresses to be
supplied to this controller must be the addresses.

78 DOCA0004EN 05/2015
Tables of Modbus Registers

Global Modbus Address Table


Description Address No. of Type RW
Words
System
Identification 100 11 ASCII R
Status 112 1 BITMAP R
Date and Time 115 4 DATE RW
Summary of channels 1 to 11
Status 120 2 BITMAP R
Orders 130 4 BITMAP RW
Power or flow indicators 14000 44 Float32 R
Consumption meters 14050 44 UINT32 R
Operation counters 14100 44 UINT32 RW
Running hour counters 14144 22 UINT32 RW
Detail of channel 1
Status 14200 1 BITMAP R
Orders 14201 2 BITMAP RW
Output status 14203 1 BITMAP R
Power or flow indicators 14204 4 Float32 R
Consumption meters 14208 4 UINT32 R
Operation counters 14212 4 UINT32 RW
Running hour counters 14216 2 UINT32 RW
Setting date of operation counters 14218 12 DATE R
Pulse weight settings (meters) 14230 2 UNIT RW
Detail of channels 2 to 11

Channel 2(1) 14240 40 – –

Channel 3 (1) 14280 40 – –

Channel 4(1) 14320 40 – –

Channel 5(1) 14360 40 – –

Channel 6(1) 14400 40 – –

Channel 7(1) 14440 40 – –

Channel 8(1) 14480 40 – –

Channel 9(1) 14520 40 – –

Channel 10(1) 14560 40 – –

Channel 11(1) 14600 40 – –

(1)The
detailed information for channels 2 to 11 has the same structure as the detailed information for
channel 1. To address the channel N (1 ≤ N ≤ 11) registers, add 40 × (N - 1) to the channel 1 registers.

Modbus Address
The list of Modbus addresses, defined by the Modbus protocol, starts at 0. The detailed tables in
subsequent chapters of this manual give the Modbus addresses.
If the programmable controller (Modbus master) refers to the data model addresses, the addresses to be
supplied to this controller must meet the following rule: Data model address = Modbus address + 1.
If the programmable controller (Modbus master) refers to the procotol addresses, the addresses to be
supplied to this controller must be the Modbus addresses.

DOCA0004EN 05/2015 79
Tables of Modbus Registers

Section 10.2
Summary and Detailed Modbus Tables

Summary and Detailed Modbus Tables

What Is in This Section?


This section contains the following topics:
Topic Page
System 81
Summary of Channels 1 to 11 83
Details of Channels 1 to 11 86

80 DOCA0004EN 05/2015
Tables of Modbus Registers

System

Identification

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
100 6 R – – ASCII – N/A N 03, Serial number on
100–4 12 ASCII characters;
11 alphanumeric digits
maximum [SN] or [S/N]:
PP YY WW [D[nnnn]]
z PP: SAP Bridge plant
number
z YY: Year in decimal
notation [05...99]
z WW: Week in decimal
notation [1...53]
z D: Day of the week in
decimal notation [1...7]
z nnnn: Sequence of
numbers
[0001...10.000–1]
109 3 R – – ASCII – N/A N 03, Software version on 6
100–4 ASCII characters.
Example: “V0.0.1”

Status

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
112 1 R – – BITMAP – 0x0000 N 01, 02, 03, Acti 9 Smartlink device
100–4 status and diagnostic
register
Bit 0 = 1: start-up phase
Bit 1 = 1: operating phase
Bit 2 = 1: downgraded
mode(1)
Bit 3 = 1: failure mode
Bit 4: not used
Bit 5: not used
Bit 6 = 1: invalid data
Bit 7 = 1: invalid 24 V I/O
Bit 8: not used
Bit 9: not used
Bit 10: not used
Bit 11: not used
Bit 12: not used
Bit 13: E2PROM error
Bit 14: RAM error
Bit 15: FLASH error
NOTE: Bits 0 to 3 are
exclusive: only one mode
is used at any given time.

(1)Downgraded mode comes into effect:


z When the power supply is cut or less than 16 V DC.
z In the event of overcurrent (overload or short-circuit) on the Ti24 I/O.
If a short-circuit on an output has caused a change to downgraded mode, at the end of the short-circuit,
the output is reset to 0 by the electronics: the Modbus master system sends a Modbus message to reset
the output to 1 if it was at 1, before the short-circuit.
Failure mode intervenes if there is an FLASH and/or RAM and/or E2PROM error.

DOCA0004EN 05/2015 81
Tables of Modbus Registers

The data is invalid in the start-up phase, downgraded and failure modes. Invalid data include
inputs 1 and 2, the power or flow indicator, the operation and running hours counter.
z The E2PROM error bit is activated during the operating phase when a checksum error is detected in an
E2PROM page.
z The RAM error bit is activated during the product initialization phase when an error is detected during a
test of the RAM.
z The FLASH error bit is activated during the start-up phase when a checksum error is detected on the
FLASH memory.

Date and Time

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
115 4 RW – – DATE (1) N/A N 03, 16 Indicates the year, month,
100–4 day, hour, minute and
millisecond on the
Acti 9 Smartlink device.

(1)
See description of the DATE type (see page 77).

82 DOCA0004EN 05/2015
Tables of Modbus Registers

Summary of Channels 1 to 11

Status

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
120 1 R – – BITMAP – 0x0000 N 01, 02, 03, Electrical status on
100–4 input 1 of all channels(1).
121 1 R – – BITMAP – 0x0000 N 01, 02, 03, Electrical status on
100–4 input 2 of all channels(1).

(1)
z Bit 0 to 10: channel 1 to 11
z Bits 11 to 15: reserved
Each bit gives the electrical level of input 1 and 2:
z 0 = no current
z 1 = input current

Reserved bits do not mean anything.

Orders

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
130 1 RW – – BITMAP – 0x0000 N 01, 02, 03, Open order for Acti 9
05, 06, 15, product(1).
16,
100–4
131 1 RW – – BITMAP – 0x0000 N 01, 02, 03, Close order for Acti 9
05, 06, 15, product(1).
16,
100–4
132 1 RW – – BITMAP – 0x0000 N 01, 02, 03, Deactivation order for
05, 06, 15, product not in the Acti 9
16, range(1).
100–4
133 1 RW – – BITMAP – 0x0000 N 01, 02, 03, Activation order for
05, 06, 15, product not in the Acti 9
16, range(1).
100–4

(1)
z Bit 0 to 10: channel 1 to 11
z Bits 11 to 15: reserved
NOTE:
z Each bit corresponds to an open order (activated when the bit is at 1).
z The open order on several channels is possible.
z The Acti 9 Smartlink device resets the bit to state 0 when the order is taken into account (unless no
product is connected to the channel).
z If a reserved bit is at 1, the Acti 9 Smartlink device resets it to 0.

z “No meaning” indicates that the bits are fixed at 0 or 1 and do not affect the system.
z If bits 0 and 1 are at 1, there is no effect on the system.

DOCA0004EN 05/2015 83
Tables of Modbus Registers

Power or Flow Indicators

Channels
1 2 3 4 5 6 7 8 9 10 11
Input I1 14000 14002 14004 14006 14008 14010 14012 14014 14016 14018 14020
Input I2 14022 14024 14026 14028 14030 14032 14034 14036 14038 14040 14042

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14000 2 R X1 D Float32 – 0 N 03, Power or flow indicator for
100–4 channel 1/input 1(1).

(1)
z When the impulse counter (the unit depends on the connected device: energy, gas, water, etc.) is
connected to input 1 or 2 of channel 1, the register contains the flow value. This is calculated as follows:
z (3600 x pulse weight)/t, t representing the time in seconds between 2 pulses. The result is expressed
for one hour.
z The pulse weight is 10 by default and can be configured by the Modbus command.
Example: This register indicates the active power between the last 2 pulses if an iEM2000T device is
connected to the channel 1/input 1 (Pulse weight = 10 Wh).
NOTE:
This register is reset to 0:
z After a duration d = 3 x t (t being the time in seconds between the last 2 pulses), if 3 x t is less than
5 seconds, the duration d equals 5 seconds
z After 24 hours without a pulse
z After loss of the 24 Vdc input/output voltage

The accuracy of the power or flow indication is:


z 5% if the pulse frequency is 5 Hertz or less
z 17% if the pulse frequency equals the maximum frequency of 17 Hertz

Consumption Meters
The consumption meters in this Modbus table indicate the consumption from meters connected to each
Acti 9 Smartlink channel (1 to 11).
The consumption value (associated with a channel) is obtained by multiplying the number of pulses
(received by inputs I1 and I2 of this channel) by the pulse weight.

Channels
1 2 3 4 5 6 7 8 9 10 11
Input I1 14050 14052 14054 14056 14058 14060 14062 14064 14066 14068 14070
Input I2 14072 14074 14076 14078 14080 14082 14084 14086 14088 14090 14092

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14050 2 R X1 – UINT32 – 0 Y 03, Consumption meter on
100–4 channel 1/input I1.

NOTE:
z The number of pulses from inputs I1 and I2 of each channel (1 to 11) are available in registers 14212
(channel 1) to 14614 (channel 11). The number of pulses can be preset by writing to the impulse counter
register. See the Operation Counters chapter.
z The pulse weights of inputs I1 and I2 of each channel (1 to 11) are available and can be set in registers
14230 (channel 1) to 14631 (channel 11). The pulse weight is 10 by default. See the Parameter Settings
chapter.

84 DOCA0004EN 05/2015
Tables of Modbus Registers

Operation Counters

Channels
1 2 3 4 5 6 7 8 9 10 11
Input I1 14100 14102 14104 14106 14108 14110 14112 14114 14116 14118 14120
Input I2 14122 14124 14126 14128 14130 14132 14134 14136 14138 14140 14142

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14100 2 RW X1 – UINT32 – 0 Y 03, 16, Operation counter for
100–4 channel 1/input 1:
changes from state 1 to
state 0.

Running Hour Counters

Channels
1 2 3 4 5 6 7 8 9 10 11
Input I1 14144 14146 14148 14150 14152 14154 14156 14158 14160 14162 14164

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14144 2 RW X1 h UINT32 – 0 Y 03, 16, Running hours counter
100–4 for channel 1/input 1.
Counting starts when the
input is activated.

DOCA0004EN 05/2015 85
Tables of Modbus Registers

Details of Channels 1 to 11

Channels 1 to 11 Overview

Channels
1 2 3 4 5 6 7 8 9 10 11
Status
Input I1 (bit 0) 14200 14240 14280 14320 14360 14400 14440 14480 14520 14560 14600
Input I2 (bit 1) 14200 14240 14280 14320 14360 14400 14440 14480 14520 14560 14600
Orders
Commands output Q (bit 0 14201 14241 14281 14321 14361 14401 14441 14481 14521 14561 14601
and bit 1): Acti 9 product
Commands output Q (bit 0 14202 14242 14282 14322 14362 14402 14442 14482 14522 14562 14602
and bit 1): non-Acti 9
product
State of output Q (bit 0) 14203 14243 14283 14323 14363 14403 14443 14483 14523 14563 14603
Counters
Input I1 power or flow 14204 14244 14284 14324 14364 14404 14444 14484 14524 14564 14604
indicator(2)
Input I2 power or flow 14206 14246 14286 14326 14366 14406 14446 14486 14526 14566 14606
indicator(2)
Input I1 consumption 14208 14248 14288 14328 14368 14408 14448 14488 14528 14568 14608
meter(1)(2)
Input I2 consumption meter 14210 14250 14290 14330 14370 14410 14450 14490 14530 14570 14610
(1)(2)

Operation and Running Hours Counters

I1 operation counter(1) 14212 14252 14292 14332 14372 14412 14452 14492 14532 14572 14612

I2 operation counter(1) 14214 14254 14294 14334 14374 14414 14454 14494 14534 14574 14614

I1 input running hours(1) 14216 14256 14296 14336 14376 14416 14456 14496 14536 14576 14616

Setting Date of Operation Counters


Input I1 date 14218 14258 14298 14338 14378 14418 14458 14498 14538 14578 14618
Input I2 date 14222 14262 14302 14342 14382 14422 14462 14502 14542 14582 14622
Running hours parameter 14226 14266 14306 14346 14386 14426 14466 14506 14546 14586 14626
setting date on input I1
Pulse Weight Settings (Meters)

Pulse weight for input I1(2) 14230 14270 14310 14350 14390 14430 14470 14510 14550 14590 14630

Pulse weight for input I2(2) 14231 14271 14311 14351 14391 14431 14471 14511 14551 14591 14631

(1) Data type: UINT32


(2)
Information specific to Meter type devices

86 DOCA0004EN 05/2015
Tables of Modbus Registers

Modbus Address
The list of Modbus addresses, defined by the Modbus protocol, starts at 0. The detailed tables in
subsequent chapters of this manual give the Modbus addresses.
If the programmable controller (Modbus master) refers to the data model addresses, the addresses to be
supplied to this controller must meet the following rule: Data model address = Modbus address + 1.
If the programmable controller (Modbus master) refers to the procotol addresses, the addresses to be
supplied to this controller must be the Modbus addresses.

Reminder: The following figure shows the terminals for each channel.

A Channels from 1 to 11

Description of Terminals for Each Channel (Ti24 Interface):

Terminal Description
24 V 24 V of the 24 Vdc power supply
Q Control output
I2 Input number 2
I1 Input number 1
0V 0 V of the 24 Vdc power supply

Status

Channels
1 2 3 4 5 6 7 8 9 10 11
Input I1 (bit 0) 14200 14240 14280 14320 14360 14400 14440 14480 14520 14560 14600
Input I2 (bit 1) 14200 14240 14280 14320 14360 14400 14440 14480 14520 14560 14600

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14200 1 R – – BITMAP – 0x0000 N 03, Electrical status of
100–4 inputs 1 and 2 of all
connected devices(1).

(1)
z Bit 0 = electrical level of input 1
z Bit 1 = electrical level of input 2
z Bits 2 to 15 = reserved
NOTE: “Reserved” means that the bits are fixed at 0 and do not mean anything.
Meaning of bits for inputs I1 and I2:
z 0 = no current
z 1 = input current

DOCA0004EN 05/2015 87
Tables of Modbus Registers

Orders

Channels
1 2 3 4 5 6 7 8 9 10 11
Output Q (bit 0 14201 14241 14281 14321 14361 14401 14441 14481 14521 14561 14601
and bit 1):
Acti 9 product

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14201 1 RW – – BITMAP – 0x0000 N 03, 06, 16, Close and open order for
100–4 products in the Acti 9
range(1).

Channels
1 2 3 4 5 6 7 8 9 10 11
Output Q (bit 0 14202 14242 14282 14322 14362 14402 14442 14482 14522 14562 14602
and bit 1): non-
Acti 9 product

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14202 1 RW – – BITMAP – 0x0000 N 03, 06, 16, Deactivation and
100–4 activation order for
product not in the Acti 9
range(2).

(1)
z Bit 0 = close order
z Bit 1 = open order
z Bits 2 to 15 = no meaning
(2)
z Bit 0 = deactivation order
z Bit 1 = activation order
z Bits 2 to 15 = no meaning
NOTE:
z The Acti 9 Smartlink device resets the bit to state 0 when the order is taken into account (unless no
product is connected to the channel).
z If a reserved bit is at 1, the Acti 9 Smartlink device resets it to 0.

z “No meaning” indicates that the bits are fixed at 0 or 1 and do not affect the system.
z If bits 0 and 1 are at 1, there is no effect on the system.

88 DOCA0004EN 05/2015
Tables of Modbus Registers

Power or Flow Indicators

Channels
1 2 3 4 5 6 7 8 9 10 11
Input I1 power or flow 14204 14244 14284 14324 14364 14404 14444 14484 14524 14564 14604
indicator(6)
Input I2 power or flow 14206 14246 14286 14326 14366 14406 14446 14486 14526 14566 14606
indicator(6)

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14204 2 R X1 D Float32 – 0 N 03, Power or flow indicator
100–4 for input 1(1).
14206 2 R X1 D Float32 – 0 N 03, Power or flow indicator
100–4 for input 2(1).

(1)
The same channel (Ti24 interface) on the Acti 9 Smartlink can take account of 2 counters:
z One counter connected to input I1
z One counter connected to input I2

Consumption Meters

Channels
1 2 3 4 5 6 7 8 9 10 11
Input I1 consumption 14208 14248 14288 14328 14368 14408 14448 14488 14528 14568 14608
meter(1)
Input I2 consumption 14210 14250 14290 14330 14370 14410 14450 14490 14530 14570 14610
meter(1)

(1) The same channel (Ti24 interface) on the Acti 9 Smartlink can take account of 2 meters:
z One meter connected to input I1
z One meter connected to input I2

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14208 2 R X1 – UINT32 – 0 Y 03, Consumption meter on
100–4 input 1.
14210 2 R X1 – UINT32 – 0 Y 03, Consumption meter on
100–4 input 2.

Operation Counters

Channels
1 2 3 4 5 6 7 8 9 10 11
I1 operation counter 14212 14252 14292 14332 14372 14412 14452 14492 14532 14572 14612
I2 operation counter 14214 14254 14294 14334 14374 14414 14454 14494 14534 14574 14614

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14212 2 RW X1 – UINT32 – 0 Y 03, 16 Operation counter for
100–4 channel 1/input 1.
This register indicates the
number of changes of
state of input 1 from
state 1 to state 0.

DOCA0004EN 05/2015 89
Tables of Modbus Registers

Running Hour Counters

Channels
1 2 3 4 5 6 7 8 9 10 11
I1 input running time 14216 14256 14296 14336 14376 14416 14456 14496 14536 14576 14616

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14216 2 RW X1 h UINT32 – 0 Y 03, 16 Running hours counter
100–4 for channel 1/input 1.
Counting starts when the
input is activated.

Setting Date of Operation Counters

Channels
1 2 3 4 5 6 7 8 9 10 11
Input I1 date 14218 14258 14298 14338 14378 14418 14458 14498 14538 14578 14618
Input I2 date 14222 14262 14302 14342 14382 14422 14462 14502 14542 14582 14622
Running hours 14226 14266 14306 14346 14386 14426 14466 14506 14546 14586 14626
parameter setting
date on input I1

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14218 4 R – – DATE (1) (1) Y 03, Date when the operation
100–4 counter parameter was
last set.
This register indicates the
date and time when the
operation counter
parameter was last set on
input 1.
14222 4 R – – DATE (1) (1) Y 03, Date when the operation
100–4 counter parameter was
last set.
This register indicates the
date and time when the
operation counter
parameter was last set on
input 2.
14226 4 R – – DATE (1) (1) Y 03, Date when the running
100–4 hours counter parameter
was last set.
This register indicates the
date and time when the
running hours counter
parameter was last set on
input 1.

(1)
See description of the DATE type (see page 77).

90 DOCA0004EN 05/2015
Tables of Modbus Registers

Pulse Weight Settings (Meters)

Channels
1 2 3 4 5 6 7 8 9 10 11
Pulse weight I1 14230 14270 14310 14350 14390 14430 14470 14510 14550 14590 14630

Pulse weight I2 (1) 14231 14271 14311 14351 14391 14431 14471 14511 14551 14591 14631

Address No. RW X Unit Type Range Default Svd Function Description


Value Code
14230 1 RW X1 D UNIT 0...65,535 10 Y 03, 06, 16 Pulse weight: this
100–4 register can be used to
set the value of the pulse
weight for the meter
connected to input 1 of
channel 1.
14231 1 RW X1 D UNIT 0...65,535 10 Y 03, 06, 16 Pulse weight: this
100–4 register can be used to
set the value of the pulse
weight for the meter
connected to input 2 of
channel 1.

(1)
The same channel (Ti24 interface) on the Acti 9 Smartlink can take account of 2 meters:
z One meter connected to input I1
z One meter connected to input I2

DOCA0004EN 05/2015 91
Tables of Modbus Registers

Section 10.3
Modbus Tables for Connected Products

Modbus Tables for Connected Products

What Is in This Section?


This section contains the following topics:
Topic Page
iOF+SD24 Indication Auxiliary 93
OF+SD24 Indication Auxiliary 94
iEM2000T, iEM3110, iEM3155, iEM3210, iEM3255 Meters or Meter with Pulse Output (Standard CEI 95
62053-31)
iACT24 Auxiliary for iCT Contactor 96
iATL24 Auxiliary for iTL Impulse Relay 97
Contactor and Relay (Not in the Acti 9 Range) 98
Acti 9 RCA iC60 Remote Control with Ti24 Interface 99
Acti 9 Reflex iC60 Integrated Control Circuit Breaker With Ti24 Interface 100

92 DOCA0004EN 05/2015
Tables of Modbus Registers

iOF+SD24 Indication Auxiliary

Overview
The iOF+SD24 indication auxiliary is used to find out the status of the following devices:
z iC60 and iC65 circuit breaker (OF and states)
z iID residual current circuit breaker (OF and states)
z iSW-NA switch (OF status)
z iDPN circuit breaker (sold in China)

The Modbus information in the following table is given for an iOF+SD24 auxiliary connected to channel 1.

Description Address(1) No. of Type Action Values and Meanings


Register(s)
Status
OF status 14200 1 BITMAP R bit 0 = 0: circuit breaker
open
bit 0 = 1: circuit breaker
closed
14200 1 BITMAP R bit 1 = 0: device tripped
status
(fault present)
bit 1 = 1: device not tripped
Counters
Number of circuit breaker 14212 2 UINT32 RW –
opening/closing cycles
Number of trippings 14214 2 UINT32 RW –
Load running time 14216 2 UINT32 RW in hours

(1)
To address the channel N (1≤ N ≤ 11) registers, add 40 × (N – 1) to the channel 1 registers.

DOCA0004EN 05/2015 93
Tables of Modbus Registers

OF+SD24 Indication Auxiliary

Overview
The OF+SD24 indication auxiliary is used to find out the status of the following devices:
z C60 or C120 circuit breaker (OF and states)
z DPN residual current circuit breaker (OF and states)
z DPN switch (OF status)
z C60H-DC circuit breaker (OF and states)
z iDPN circuit breaker (sold in every country except China)

The Modbus information in the following table is given for an OF+SD24 auxiliary connected to channel 1.

Description Address(1) No. of Type Action Values and Meanings


Register(s)
Status
OF status 14200 1 BITMAP R bit 0 = 0: circuit breaker open
bit 0 = 1: circuit breaker
closed
14200 1 BITMAP R bit 1 = 0: device tripped (fault
status
present)
bit 1 = 1: device not tripped
Counters
Number of circuit breaker 14212 2 UINT32 RW –
opening/closing cycles
Number of trippings 14214 2 UINT32 RW –
Load running time 14216 2 UINT32 RW in hours

(1)
To address the channel N (1≤ N ≤ 11) registers, add 40 × (N – 1) to the channel 1 registers.

94 DOCA0004EN 05/2015
Tables of Modbus Registers

iEM2000T, iEM3110, iEM3155, iEM3210, iEM3255 Meters or Meter with Pulse Output (Standard CEI
62053-31)

Overview
The meter delivers a pulse output.
The Modbus information in the following table is given for a meter connected to channel 1.
The same channel (Ti24 interface) on the Acti 9 Smartlink can take account of 2 meters:
z One meter connected to input I1
z One meter connected to input I2

Description Address(1) No. of Type Action Values and Meanings


Register(s)
Status
Pulse output (meter 1) 14200 1 BITMAP R bit 0
Pulse output (meter 2) 14200 1 BITMAP R bit 1
Counters
Power or flow indicator (meter 1) 14204 2 Float32 R (2)

Power or flow indicator (meter 2) 14206 2 Float32 R (2)

Consumption meter (meter 1) 14208 2 UINT32 R (3)

Consumption meter (meter 2) 14210 2 UINT32 R (3)

Settings
Pulse weight (meter 1) 14230 1 UINT RW (2)

Pulse weight (meter 2) 14231 1 UINT RW (2)

(1)
To address the channel N (1≤ N ≤ 11) registers, add 40 × (N – 1) to the channel 1 registers.
(2) The register contains the flow value.
z The flow is: (3600 x pulse weight)/t, with t representing the time in seconds between two pulses. The
result is expressed for one hour.
z The pulse weight is 10 by default. The unit depends on the connected device: energy, gas, water, etc.
(3) The consumption value (associated with a channel) is obtained by multiplying the number of pulses

(received by inputs I1 and I2 of this channel) by the pulse weight.

DOCA0004EN 05/2015 95
Tables of Modbus Registers

iACT24 Auxiliary for iCT Contactor

Overview
The iACT24 auxiliary:
z Can be used to control an iCT contactor rated 25 A or higher via its Y1, Y2 and Y3 inputs.
The Y3 (24 Vdc) input can be controlled by one of the Acti 9 Smartlink device channels.
z Is used to find out the contactor status (O/C status: open/closed status)

The Modbus information in the following table is given for an iACT24 auxiliary connected to channel 1.

Description Address(1) No. of Type Action Values and Meanings


Register(s)
Status
O/C status: open/closed status 14200 1 BITMAP R bit 0 = 0: contactor open
bit 0 = 1: contactor closed
Device present 14200 1 BITMAP R bit 1 = 0: connection fault or
no connected device
bit 1 = 1: connected device
Orders
Deactivate contactor coil 14201 1 BITMAP RW bit 0 = 1: deactivate coil(2)
Activate contactor coil 14201 1 BITMAP RW bit 1 = 1: activate coil(2)
Counters
Number of contactor open/close 14212 2 UINT32 RW –
cycles
Load running time for an NO 14216 2 UINT32 RW in hours
contactor

(1)
To address the channel N (1≤ N ≤ 11) registers, add 40 × (N – 1) to the channel 1 registers.
(2) The Acti 9 Smartlink device resets the bit to state 0 when the order is taken into account (unless no

product is connected to the channel). If bits 0 and 1 of address 14201 are activated simultaneously, the
Acti 9 Smartlink device does nothing.

96 DOCA0004EN 05/2015
Tables of Modbus Registers

iATL24 Auxiliary for iTL Impulse Relay

Overview
The iATL24 auxiliary:
z Can be used to control an iTL impulse relay via its Y1, Y2 and Y3 inputs
The Y3 (24 Vdc) input can be controlled by one of the Acti 9 Smartlink device channels.
z Can be used to find out the impulse relay status (O/C status open/closed status).

The Modbus information in the following table is given for an iATL24 auxiliary connected to channel 1.

Description Address(1) No. of Type Action Values and Meanings


Register(s)
Status
O/C status: open/closed status 14200 1 BITMAP R bit 0 = 0: impulse relay open
bit 0 = 1: impulse relay closed
Device present 14200 1 BITMAP R bit 1 = 0: connection fault or
no connected device
bit 1 = 1: connected device
Orders
Impulse relay contact opening 14201 1 BITMAP RW bit 0 = 1: Impulse relay
contact opening(2)
Impulse relay contact closing 14201 1 BITMAP RW bit 1 = 1: Impulse relay
contact closing(2)
Counters
Number of impulse relay 14212 2 UINT32 RW –
opening/closing cycles
Load running time 14216 2 UINT32 RW in hours

(1)
To address the channel N (1≤ N ≤ 11) registers, add 40 × (N – 1) to the channel 1 registers.
(2)The Acti 9 Smartlink device resets the bit to state 0 when the order is taken into account (unless no
product is connected to the channel). If bits 0 and 1 of address 14201 are activated simultaneously, the
Acti 9 Smartlink device does nothing.

DOCA0004EN 05/2015 97
Tables of Modbus Registers

Contactor and Relay (Not in the Acti 9 Range)

Overview
A contactor or relay powered with 24 Vdc can be connected to Acti 9 Smartlink. This should have the
following characteristics:
z The contactor or relay coil must not draw more than 100 mA
z The indication contact must be low level type

Only contactors in the Acti 9 range can be connected to Acti 9 Smartlink using the iATL24 auxiliary.
The contactor can be controlled by one of the Acti 9 Smartlink device channels.
The Modbus information in the following table is given for a contactor connected to channel 1.

Description Address(1) No. of Type Action Values and Meanings


Register(s)
Status
OF status 14200 1 BITMAP R bit 0 = 0: contactor open
bit 0 = 1: contactor closed
Orders
Deactivate contactor coil 14202 1 BITMAP RW bit 0 = 1: deactivate coil(2)
Activate contactor coil 14202 1 BITMAP RW bit 1 = 1: activate coil(2)
Counters
Number of contactor 14212 2 UINT32 RW –
open/close cycles
Load running time for an NO 14216 2 UINT32 RW in hours
contactor

(1)
To address the channel N (1≤ N ≤ 11) registers, add 40 × (N – 1) to the channel 1 registers.
(2) The Acti 9 Smartlink device resets the bit to state 0 when the order is taken into account (unless no

product is connected to the channel). If bits 0 and 1 of address 14202 are activated simultaneously, the
Acti 9 Smartlink device does nothing.

98 DOCA0004EN 05/2015
Tables of Modbus Registers

Acti 9 RCA iC60 Remote Control with Ti24 Interface

Overview
The Acti 9 RCA iC60 remote control:
z Should have a Ti24 interface (with product references A9C70122 and A9C70124)
z Can be used to control a iC60 circuit breaker via input Y3 of its Ti24 interface.
The Y3 (24 Vdc) input can be controlled by one of the Acti 9 Smartlink device channels
z Can be used to find out the OF and states of the circuit breaker associated with the Acti 9
RCA iC60 remote control
The Modbus information in the following table is given for an Acti 9 RCA iC60 remote control connected to
channel 1.

Description Address(1) No. of Type Action Values and Meanings


Register(s)
Status
OF status 14200 1 BITMAP R bit 0 = 0: circuit breaker open
bit 0 = 1: circuit breaker closed
14200 1 BITMAP R bit 1 = 0: device tripped (fault
status
present)
bit 1 = 1: device not tripped
Orders
Activation of the open order 14201 1 BITMAP RW bit 0 = 1: activation of the open
order(2)
Activation of the close order 14201 1 BITMAP RW bit 1 = 1: activation of the close
order(2)
Counters
Number of circuit breaker 14212 2 UINT32 RW –
open/close cycles
Number of trippings 14214 2 UINT32 RW –
Load running time 14216 2 UINT32 RW in hours

(1)
To address the channel N (1≤ N ≤ 11) registers, add 40 × (N – 1) to the channel 1 registers.
(2)The Acti 9 Smartlink device resets the bit to state 0 when the order is taken into account (unless no
product is connected to the channel). If bits 0 and 1 of address 14201 are activated simultaneously, the
Acti 9 Smartlink device does nothing.

DOCA0004EN 05/2015 99
Tables of Modbus Registers

Acti 9 Reflex iC60 Integrated Control Circuit Breaker With Ti24 Interface

Overview
The Acti 9 Reflex iC60 integrated control circuit breaker:
z Should have a Ti24 interface (with product references A9C6••••).
z Can allow the device to be controlled via input Y3 of its Ti24 interface
The Y3 (24 Vdc) input can be controlled by one of the Acti 9 Smartlink device channels.
z Can be used to communicate its O/C and auto/OFF status

The Modbus information in the following table is given for an Acti 9 Reflex iC60 integrated control circuit
breaker connected to channel 1.

Description Address(1) No. of Type Action Values and Meanings


Register(s)
Status
O/C status: open/closed status 14200 1 BITMAP R bit 0 = 0: circuit breaker
open
bit 0 = 1: circuit breaker
closed
auto/OFF status: handle position 14200 1 BITMAP R bit 1 = 0: handle in OFF
position (device open)
bit 1 = 1: handle in upper
position: auto
Orders
Activation of the open order 14201 1 BITMAP RW bit 0 = 1: activation of the
open order(2)
Activation of the close order 14201 1 BITMAP RW bit 1 = 1: activation of the
close order(2)
Counters
Number of circuit breaker 14212 2 UINT32 RW –
open/close cycles
Number of trippings 14214 2 UINT32 RW –
Load running time 14216 2 UINT32 RW in hours

(1)
To address the channel N (1≤ N ≤ 11) registers, add 40 × (N – 1) to the channel 1 registers.
(2)The Acti 9 Smartlink device resets the bit to state 0 when the order is taken into account (unless no
product is connected to the channel). If bits 0 and 1 of address 14201 are activated simultaneously, the
Acti 9 Smartlink device does nothing.

100 DOCA0004EN 05/2015


Acti 9 Smartlink Modbus Communication System
Integration of Acti 9 Smartlink in an EGX System
DOCA0004EN 05/2015

Chapter 11
Integration of Acti 9 Smartlink in an EGX System

Integration of Acti 9 Smartlink in an EGX System

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Introduction to the EGX System 102
Connection 103
Configuration 105
Control 109
Monitoring 111
Diagnostics 114

DOCA0004EN 05/2015 101


Integration of Acti 9 Smartlink in an EGX System

Introduction to the EGX System

Overview
For Acti 9 Smartlink, the EGX300 gateway (version 4.200 or later) can be used in two different ways:
z Standard gateway function (see document EGX 63230-319-216B2 dated 11/2011)
z Function with Web Server page embedded in EGX300 and adapted for Acti 9 Smartlink

With the embedded Web Server page function, you can:


z View the discrete I/O status
z Set the energy meter parameters
z View energy consumption in the form of a graph (curves)
z Export the consumption data stored in the EGX300 in .csv format
z View the Modbus registers of Acti 9 Smartlink devices

The following chapters describe configuration and the functions accessible in the embedded Web Server
for Acti 9 Smartlink.
After configuring the EGX300 gateway Ethernet parameters, you can access the EGX300 gateway on a
local area network, using a standard Web browser.
The following diagram shows the home page:

To close the EGX300 session, click Logout.


We recommend that you log out when you no longer need to access the EGX300 gateway.

102 DOCA0004EN 05/2015


Integration of Acti 9 Smartlink in an EGX System

Connection

Possible Connections
The first operation consists of connecting the Acti 9 Smartlink device(s) to the EGX gateway.
The following figure shows the options for connecting devices on EGX:

The Acti 9 Smartlink device can be connected as a serial slave device or as a remote slave device.

Selector Switch Position


The EGX gateway selector switches must be configured for operation on a two-wire network.
The following figure shows the required selector switch configuration:

DOCA0004EN 05/2015 103


Integration of Acti 9 Smartlink in an EGX System

Wiring
The link used between the EGX gateway and the Acti 9 Smartlink device(s) is a two-wire link plus an
earthing braid.
The physical connection between the EGX connector and the Modbus connectors on Acti 9 Smartlink
devices must be made as follows:

104 DOCA0004EN 05/2015


Integration of Acti 9 Smartlink in an EGX System

Configuration

Device List
The Device List page can be used to detect and configure devices connected to the EGX300 gateway.
To go to this page, select the Configuration tab, then click on Device List on the left of the screen.
The following illustration shows the Device List page:

Automatic Detection
From the Device List page, click the Detection button.
The following page will appear:

The table describes the automatic detection procedure:

Step Action
1 Select the Start Address box.
2 Enter the Modbus address where detection is to start.
3 Select the End Address box.
4 Enter the Modbus address up to which detection is to be performed.
5 Click the Start Detection button.
6 If necessary, repeat step 5.

NOTE:
z The automatic detection process can be interrupted at any time by clicking the Stop Detection button.
z The device names should be configured manually. Perform steps 1 and 3 of manual configuration.

DOCA0004EN 05/2015 105


Integration of Acti 9 Smartlink in an EGX System

Manual Configuration

The procedure for manually configuring devices connected to the EGX300 gateway is as follows:

Step Action
1 Select the Device List page.
2 In the Assigned drop-down menu, select Acti 9 Smartlink.
3 If necessary, in the Name box, type in a name.
4 If necessary, fill in the Local ID field.

Device Logging
The Device Logging page is used to configure energy meters connected to the Acti 9 Smartlink device
and the file storage and sending parameters.
To go to this page, select the Configuration tab, then click on Device Logging on the left of the screen.
The following illustration shows the Device Logging page:

On this page you need to declare the time interval between 2 recordings. The desired interval is selected
from the drop-down list of Recording Interval options.

106 DOCA0004EN 05/2015


Integration of Acti 9 Smartlink in an EGX System

Energy Meter Declarations


From the Device Logging page, click on values.
The following page will appear:

The procedure for assigning impulse counters to the channels of an Acti 9 Smartlink device is as follows:

Step Action
1 Check the desired box(es) opposite the Channel x Input y identification.
2 Use the vertical scroll bar to go to the bottom of the page.
3 Click on the Apply button.

NOTE:
For each channel, it is possible to select the type of information required:
z Real energy
z Real power

DOCA0004EN 05/2015 107


Integration of Acti 9 Smartlink in an EGX System

Declaration of the Device Log Export Type


From the declarations assigning the impulse counter to channels on the Acti 9 Smartlink device, the
EGX300 gateway stores each measurement point at the selected frequency and offers the option of
exporting the backup files via email or via FTP server.
To define these parameters, in the Configuration page, click on Device Log Export.
The following page will appear:

108 DOCA0004EN 05/2015


Integration of Acti 9 Smartlink in an EGX System

Control

Overview
The Control page allows the user to change the Acti 9 Smartlink internal parameters:
z Energy meter pulse weight
z Energy meters

Interface
To access the Control page, proceed as follows:

Step Action
1 Click on the Control tab.
2 Click Acti 9 Smartlink on the left of the screen.
3 The following page displays all the channels and inputs to which an impulse counter is connected.

Pulse Weight Parameter Setting


If impulse counters have been assigned to the I/O of an Acti 9 Smartlink device, it is possible (or even
essential) to configure the counter pulse weight to be able to calculate the real energy and real power.
The table shows how to assign the pulse weight:

Step Action
1 Check the box opposite the desired channels to change their weight.
2 Check the desired box in the Pulse Weight column.
3 Type in the value of the desired pulse weight.
4 Repeat steps 2 and 3 for each value to be changed.
5 Click the Reset button.

NOTE: If no energy meter has been assigned to a channel of the Acti 9 Smartlink device, we recommend
setting the pulse weight to 0.

DOCA0004EN 05/2015 109


Integration of Acti 9 Smartlink in an EGX System

Resetting Meters
It is possible, if the application requires it, to reset the values of the Acti 9 Smartlink device energy meters.
The table shows how to reset the meters:

Step Action
1 Check the box opposite the desired channels to change their weight.
2 Check the desired box in the Preset Value column.
3 Type in the new value you wish to assign to the impulse counter concerned.
4 Repeat steps 2 and 3 for each value to be changed.
5 Click the Reset button.

110 DOCA0004EN 05/2015


Integration of Acti 9 Smartlink in an EGX System

Monitoring

Interface
To display the status of the Acti 9 Smartlink device I/O, go to the Monitoring page:

Viewing the I/O


The table describes the procedure for accessing the Acti 9 Smartlink device I/O data:

Step Action
1 Click on Real Time Data in the left-hand panel.
2 Click on Single Device Pages in the left-hand panel.
3 Click on Acti 9 Smartlink in the left-hand panel.
4 The I/O data (basic readings) screen is displayed.

DOCA0004EN 05/2015 111


Integration of Acti 9 Smartlink in an EGX System

Assigning Channel Names


A specific name can be assigned to each channel. The procedure is as follows:

Step Action
1 On the I/O data (basic readings) screen, click on Channel Names.
2 Click on the channel name to be changed.
3 Type in the new channel name.
The number of characters is limited to 10.
4 Repeat steps 2 and 3 for all the channel names to be changed.
5 Click on the Apply button.

The following illustration gives an example of changed channel names:

Graphic Representation of Consumption


If impulse counters have been configured, consumption can be displayed in graphic form. The procedure
is as follows:

Step Action
1 In the Monitoring page, click on Device Logging.
2 In the Device drop-down menu, select Acti 9 Smartlink.
3 To select the values to be displayed, press the New Value(s) button.
4 Choose the values to be displayed and press the Apply button.
5 Use the mouse to select an area to be enlarged.

The following illustration gives an example of graphic representation of the meter consumption:

NOTE: By default, only the first channel declared is represented. To display other channels, repeat steps
3 to 5.

112 DOCA0004EN 05/2015


Integration of Acti 9 Smartlink in an EGX System

Viewing Data
The data is displayed, according to the type of channel and data selected:
z Either discrepancies in total energy between 2 successive recordings
z Or the active power of each recording.

To display these stored values since commissioning, click on the Access Data button.
The following page will appear:

DOCA0004EN 05/2015 113


Integration of Acti 9 Smartlink in an EGX System

Diagnostics

Interface
From the EGX300 gateway, diagnostics can be performed on all connected devices.
To do this, go to the Diagnostics page.

Reading Registers
On the Diagnostics page, click on Read Device Registers.
The following page will appear:

The table describes the procedure for reading registers:

Step Action
1 In the Device Name drop-down menu, select the desired device.
2 Select the Starting Register field.
3 Enter the address of the first register to be read.
4 Select the Number of Registers field.
5 Enter the number of registers to be read.
6 Click on the Read button.

114 DOCA0004EN 05/2015


Acti 9 Smartlink Modbus Communication System

DOCA0004EN 05/2015

Appendices

What Is in This Appendix?


The appendix contains the following chapters:
Chapter Chapter Name Page
A Details of Modbus Functions 117
B Connecting Acti 9 Devices Directly to a PLC 125

DOCA0004EN 05/2015 115


116 DOCA0004EN 05/2015
Acti 9 Smartlink Modbus Communication System
Appendix A: Details of Modbus Functions
DOCA0004EN 05/2015

Appendix A
Details of Modbus Functions

Details of Modbus Functions

Overview
This appendix describes Modbus functions supported by the Acti 9 Smartlink device that are not available
on the www.modbus.org website. It is not attempting to describe the whole protocol.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Function 8: Modbus Diagnostics 118
Function 43-14: Read Acti 9 Smartlink ID 119
Function 43–15: Read Date and Time 121
Function 43-16: Write Date and Time 122
Function 100–4: Read n Non-Adjacent Words 123

DOCA0004EN 05/2015 117


Appendix A: Details of Modbus Functions

Function 8: Modbus Diagnostics

Structure of Modbus Messages Concerning Acti 9 Smartlink Diagnostic Counter Management


Request

Definition Number of Bytes Value


Slave number 1 byte 0x00 to 0x63
Function code 1 byte 0x08
Sub-function code 1 byte See the table “Sub-function codes” later in
this topic
Reserved 2 bytes 0x0000

Sub-function codes

Sub-function Description
Codes (Decimal)
10 Resets all the diagnostic counters
11 Reads the correct bus messages managed by the slave counter
12 Reads the incorrect bus messages managed by the slave counter
13 Reads the exception responses managed by the slave counter
14 Reads the messages sent to the slave counter
15 Reads the broadcast message counter
17 Reads the messages sent to the slave counter sent to the slave but without a response because
of exception code 06: slave device busy
18 Reads the incorrect bus messages due to overload errors counter

Response

Definition Number of Bytes Value


Slave number 1 byte 0x00 to 0x63
Function code 1 byte 0x08
Sub-function code 1 byte See the preceding list
Diagnostic counter 2 bytes Value of diagnostic counter corresponding
to the sub-function code

Resetting Counters
The counters are reset to 0:
z When they reach the maximum value 65535.
z When they are reset by a Modbus command (function code 8, sub-function code 10).
z When the power is cut off, or
z When the communication parameters are modified.

118 DOCA0004EN 05/2015


Appendix A: Details of Modbus Functions

Function 43-14: Read Acti 9 Smartlink ID

Structure of Modbus Read Acti 9 Smartlink ID Messages


The ID consists of ASCII characters called objects.
Request for basic information

Definition Number of Bytes Value


Slave number 1 byte 0x00...0x63
Function code 1 byte 0x2B
Sub-function code 1 byte 0x0E
Product ID 1 byte 0x01
Object identifier 1 byte 0x00

Response with basic information

Definition Number Value


of Bytes
Slave number 1 byte 0x00...0x63
Function code 1 byte 0x2B
Sub-function code 1 byte 0x0E
Product ID 1 byte 0x01
Conformity level 1 byte 0x01
Reserved 1 byte 0x00
Reserved 1 byte 0x00
Number of objects 1 byte 0x03
Object 0: manufacturer name Object number 1 byte 0x00
Object length 1 byte 0x12
Object content 18 bytes Schneider Electric
Object 1: product code Object number 1 byte 0x01
Object length 1 byte 0x08
Object content 8 bytes “A9XMSB11”
Object 2: version number Object number 1 byte 0x02
Object length 1 byte 0x06 (minimum)
Object content 6 bytes “Vx.y.z”
minimum

Request for complete information

Definition Number of Bytes Value


Slave number 1 byte 0x00...0x63
Function code 1 byte 0x2B
Sub-function code 1 byte 0x0E
Product ID 1 byte 0x02
Object identifier 1 byte 0x00

DOCA0004EN 05/2015 119


Appendix A: Details of Modbus Functions

Response with complete information

Definition Number Value


of Bytes
Slave number 1 byte 0x00...0x63
Function code 1 byte 0x2B
Sub-function code 1 byte 0x0E
Product ID 1 byte 0x02
Conformity level 1 byte 0x02
Reserved 1 byte 0x00
Reserved 1 byte 0x00
Number of objects 1 byte 0x05
Object 0: manufacturer name Object number 1 byte 0x00
Object length 1 byte 0x12
Object content 18 bytes “Schneider Electric”
Object 1: product code Object number 1 byte 0x01
Object length 1 byte 0x08
Object content 8 bytes “A9XMSB11”
Object 2: version number Object number 1 byte 0x02
Object length 1 byte 0x06 (minimum)
Object content 6 bytes “Vx.y.z”
minimum
Object 3: manufacturer URL Object number 1 byte 0x03
Object length 1 byte 0x1A
Object content 26 bytes “www.schneider-electric.com”
Object 4: product name Object number 1 byte 0x04
Object length 1 byte 0x12
Object content 18 byte “Acti 9 Smartlink”

NOTE: The preceding table describes how to read the ID of a Modbus Acti 9 Smartlink slave.

120 DOCA0004EN 05/2015


Appendix A: Details of Modbus Functions

Function 43–15: Read Date and Time

Structure of Modbus Read Date and Time Messages


Request

Definition Number of Bytes Value Example


Slave number 1 byte 0x2F 47
Function code 1 byte 0x2B 43
Sub-function code 1 byte 0x0F 15
Reserved 1 byte 0x00 Reserved

Response

Definition Number of Value Example


Bytes
Slave number 1 byte 0x2F 47
Function code 1 byte 0x2B 43
Sub-function code 1 byte 0x0F 15
Reserved 1 byte 0x00 Reserved

Date and time(1) byte 1 Not used 1 byte 0x00 Not used
byte 2 Year 1 byte 0x0A Year 2010
byte 3 Month 1 byte 0x0B Month of November
byte 4 Day of the month 1 byte 0x02 Second day of the
month
byte 5 Hour 1 byte 0x0E 14 hours
byte 6 Minute 1 byte 0x20 32 minutes
byte 7 and byte 8 Millisecond 2 bytes 0x0DAC 3.5 seconds
(1) See description of the DATE type (see page 76).

DOCA0004EN 05/2015 121


Appendix A: Details of Modbus Functions

Function 43-16: Write Date and Time

Structure of Modbus Write Date and Time Messages


Request

Definition Number of Value Example


Bytes
Slave number 1 byte 0x2F 47
Function code 1 byte 0x2B 43
Sub-function code 1 byte 0x10 16
Reserved 1 byte 0x00 Reserved

Date and time (1) byte 1 not used 1 byte 0x00 Not used
byte 2 Year 1 byte 0x0A Year 2010
byte 3 Month 1 byte 0x0B Month of November
byte 4 Day of the month 1 byte 0x02 Second day of the
month
byte 5 Hour 1 byte 0x0E 14 hours
byte 6 Minute 1 byte 0x20 32 minutes
byte 7 and byte 8 Millisecond 2 bytes 0x0DAC 3.5 seconds
(1) See description of the DATE type (see page 76).

Response

Definition Number of Value Example


Bytes
Slave number 1 byte 0x2F 47
Function code 1 byte 0x2B 43
Sub-function code 1 byte 0x10 15
Reserved 1 byte 0x00 Reserved

Date and time (1) byte 1 Not used 1 byte 0x00 Not used
byte 2 Year 1 byte 0x0A Year 2010
byte 3 Month 1 byte 0x0B Month of November
byte 4 Day of the month 1 byte 0x02 Second day of the
month
byte 5 Hour 1 byte 0x0E 14 hours
byte 6 Minute 1 byte 0x20 32 minutes
byte 7 and byte 8 Millisecond 2 bytes 0x0DAE 3.502 seconds
(1) See description of the DATE type (see page 76).

122 DOCA0004EN 05/2015


Appendix A: Details of Modbus Functions

Function 100–4: Read n Non-Adjacent Words

Structure of Modbus Read n Non-Adjacent Words Messages Where n ≤ 100


Request

Definition Number of Bytes Value


Modbus slave number 1 byte 0x2F
Function code 1 byte 0x64
Length of data in bytes 1 byte 0x06
Sub-function code 1 byte 0x04

Transmission number(1) 1 byte 0xXX

Address of the first word to be read 1 byte 0x00


(MSB)
Address of the first word to be read 1 byte 0x65
(LSB)
Address of the second word to be read 1 byte 0x00
(MSB)
Address of the second word to be read 1 byte 0x67
(LSB)
(1) The master gives the transmission number in the request.

NOTE: The preceding table describes how to read addresses 101 = 0x65 and 103 = 0x67 of a Modbus
slave. The Modbus slave number is 47 = 0x2F.
Response

Definition Number of Bytes Value


Modbus slave number 1 byte 0x2F
Function code 1 byte 0x64
Length of data in bytes 1 byte 0x06
Sub-function code 1 byte 0x04

Transmission number (1) 1 byte 0xXX

First word read (MSB) 1 byte 0x12


First word read (LSB) 1 byte 0x0A
Second word read (MSB) 1 byte 0x74
Second word read (LSB) 1 byte 0x0C
(1) The slave sends back the same number in the response.

NOTE: The preceding table describes how to read addresses 101 = 0x65 and 103 = 0x67 of a Modbus
slave. The Modbus slave number is 47 = 0x2F.

DOCA0004EN 05/2015 123


Appendix A: Details of Modbus Functions

124 DOCA0004EN 05/2015


Acti 9 Smartlink Modbus Communication System
Appendix B: Connecting Acti 9 Devices Directly to a PLC
DOCA0004EN 05/2015

Appendix B
Connecting Acti 9 Devices Directly to a PLC

Connecting Acti 9 Devices Directly to a PLC

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
iACT24 Auxiliary for iCT Contactor 126
iATL24 Auxiliary for iTL Impulse Relay 127
iOF+SD24 Indication Auxiliary 128
OF+SD24 Indication Auxiliary 129
Acti 9 RCA iC60 Remote Control with Ti24 Interface 130
Acti 9 Reflex iC60 Integrated Control Circuit Breaker With Ti24 Interface 131

DOCA0004EN 05/2015 125


Appendix B: Connecting Acti 9 Devices Directly to a PLC

iACT24 Auxiliary for iCT Contactor

Description
The iACT24 auxiliary:
z Can be used to control an iCT contactor rated 25 A or higher via its Y1, Y2 and Y3 inputs.
The Y3 (24 Vdc) input can be directly controlled by a PLC (Programmable Logic Controller).
z Is used to find out the contactor status (O/C status: open/closed status)

An iACT24 auxiliary for iCT contactor can also be connected with an A9XCAU06 or A9XCAC01 pre-wired
cable: molded connector (at iACT24 end), and with 5 wires (at PLC end).

Description of Ti24 Connector at iACT24 End (Using an A9XCAU06 or A9XCAC01 Cable)


Terminal Description
24 V 24 V of the 24 Vdc power supply
Y3 Control input
Unused terminal –
O/C Open/closed contactor state
0V 0 V of the 24 Vdc power supply

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

126 DOCA0004EN 05/2015


Appendix B: Connecting Acti 9 Devices Directly to a PLC

iATL24 Auxiliary for iTL Impulse Relay

Description
The iATL24 auxiliary:
z Can be used to control an iTL impulse relay via its Y1, Y2 and Y3 inputs
The Y3 (24 Vdc) input can be directly controlled by a PLC.
z Is used to find out the impulse relay status (O/C status: open/closed status)

An iATL24 auxiliary for iTL impulse relay can also be connected with an A9XCAU06 or A9XCAC01
pre-wired cable: molded connector (at iATL24 end), and with 5 wires (at PLC end).

Description of Ti24 Connector at iATL24 End (Using an A9XCAU06 or A9XCAC01 Cable)


Terminal Description
24 V 24 V of the 24 Vdc power supply
Y3 Control input
Unused terminal –
O/C Open/closed impulse relay status
0V 0 V of the 24 Vdc power supply

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

DOCA0004EN 05/2015 127


Appendix B: Connecting Acti 9 Devices Directly to a PLC

iOF+SD24 Indication Auxiliary

Description
The iOF+SD24 indication auxiliary is used to find out the status of the following devices:
z iC60 and iC65 circuit breaker (OF and states)
z iID residual current circuit breaker (OF and states)
z iSW-NA switch (OF status)
z iDPN circuit breaker (sold in China)

The iOF+SD24 indication auxiliary for iC60 circuit breaker can also be connected with an A9XCAU06 or
A9XCAC01 pre-wired cable: molded connector (at iOF+SD24 end), and with 5 wires (at PLC end).

Description of Ti24 Connector at iOF+SD24 End (Using an A9XCAU06 or A9XCAC01 Cable)


Terminal Description
24 V 24 V of the 24 Vdc power supply
Unused terminal –
Fault indication

OF Open/closed circuit breaker status


0V 0 V of the 24 Vdc power supply

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

128 DOCA0004EN 05/2015


Appendix B: Connecting Acti 9 Devices Directly to a PLC

OF+SD24 Indication Auxiliary

Description
The OF+SD24 indication auxiliary is used to find out the status of the following devices:
z C60 or C120 circuit breaker (OF and states)
z DPN residual current circuit breaker (OF and states)
z DPN switch (OF status)
z C60H-DC circuit breaker (OF and states)
z iDPN circuit breaker (sold in every country except China)

The OF+SD24 indication auxiliary for C60 and C120 circuit breakers can also be connected with an
A9XCAU06 or A9XCAC01 pre-wired cable: molded connector (at OF+SD24 end), and with 5 wires (at PLC
end).

Description of Ti24 Connector at OF+SD24 End (Using an A9XCAU06 or A9XCAC01 Cable)


Terminal Description
24 V 24 V of the 24 Vdc power supply
Unused terminal –
Fault indication

OF Open/closed circuit breaker status


0V 0 V of the 24 Vdc power supply

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

DOCA0004EN 05/2015 129


Appendix B: Connecting Acti 9 Devices Directly to a PLC

Acti 9 RCA iC60 Remote Control with Ti24 Interface

Description
The Acti 9 RCA iC60 remote control:
z Should have a Ti24 interface (product references A9C70122 and A9C70124)
z Can be used to control a iC60 circuit breaker via input Y3 of its Ti24 interface.
The Y3 (24 Vdc) input can be directly controlled by a PLC.
z Can be used to find out the OF and states of the circuit breaker associated with the Acti 9
RCA iC60 remote control
An RCA iC60 remote control with Ti24 interface can also be connected with an A9XCAU06 or A9XCAC01
pre-wired cable: molded connector (at RCA iC60 end with Ti24 interface), and with 5 wires (at PLC end).

Description of Ti24 Connector at Acti 9 RCA iC60 End with Ti24 Interface (Using an A9XCAU06 Cor A9XCAC01
Cable)
Terminal Description
24 V 24 V of the 24 Vdc power supply
Y3 Control input
Fault indication

OF Open/closed status of the RCA iC60 with Ti24 interface


0V 0 V of the 24 Vdc power supply

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

130 DOCA0004EN 05/2015


Appendix B: Connecting Acti 9 Devices Directly to a PLC

Acti 9 Reflex iC60 Integrated Control Circuit Breaker With Ti24 Interface

Description
The Acti 9 Reflex iC60 integrated control circuit breaker:
z Should have a Ti24 interface (with product references A9C6••••)
z Can allow the device to be controlled via input Y3 of its Ti24 interface.
The Y3 (24 Vdc) input can be directly controlled by a PLC.
z Can be used to communicate its O/C and auto/OFF status

An Acti 9 Reflex iC60 integrated control circuit breaker with Ti24 interface can also be connected with an
A9XCAU06 or A9XCAC01 pre-wired cable: molded connector (at Reflex iC60 end with Ti24 interface), and
with 5 wires (at PLC end).

Description of Ti24 Connector at Acti 9 Reflex iC60 End With Ti24 Interface (Using an A9XCAU06 or
A9XCAC01 Cable)
Terminal Description
24 V 24 V of the 24 Vdc power supply
Y3 Control input
auto/OFF Handle position (upper position: auto; lower position: OFF)
O/C Open/closed status of the Reflex iC60 with Ti24 interface
0V 0 V of the 24 Vdc power supply

NOTE:
z Do not connect 2 wires in each of the Ti24 connector terminals (A9XC2412).
z Do not connect a wire with cable end in each of the Ti24 connector terminals.

DOCA0004EN 05/2015 131


Appendix B: Connecting Acti 9 Devices Directly to a PLC

132 DOCA0004EN 05/2015


DOCA0004EN-05

Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35, rue Joseph Monier of the information given in this publication.
CS30323
F - 92506 Rueil Malmaison Cedex

www.schneider-electric.com 05/2015