IRIS Programmer-Manual EN 022012
IRIS Programmer-Manual EN 022012
SensoIRIS Programmer
Programming Unit for SensoIRIS Devices
ATTENTION: This document is subject to change without notice!
Technical Specifications
Connection Diagram
(Example for connecting to SensoIRIS MC-D addressable base)
You can find a detailed connection diagram for every one SensoIRIS device (modules, detectors, call
points or sounders) in its individual installation manual.
1
SensoIRIS Programmer - Operation Manual
Operating Menus
Button Set Check Read Save Function
Main Language
address address parameters parameters
Rejects the settings.
Exit to the main operating
menu.
Esc 9 9 9 9 9 9
Shows the current software
version of the programmer and
the logo of the manufacturer.
Scroll up to the previous
Up 9 9 9 9
menu or parameter.
Increase the numeric digit
Modify 9 9
with one unit.
Scroll down to the next menu
Down 9 9 9 9
or parameter.
Move the cursor with one
Right 9 9
step on the right.
Confirm the settings. Start
Enter 9 9 9 9 9 9 reading/ writing address and
configuring parameters.
NOTE: The buttons and have a different functionality according the entered operating menu. The
“9” mark shows the menus for which the button is active and operates with the described functionality.
NOTE: If you connect by mistake or other reasons more than one device to the SensoIRIS Programmer,
the unit will alert with an error message when you start writing and reading address function.
Messages
2
SensoIRIS Programmer - Operation Manual
♦ Press the (Esc) button several times to exit back to the main programming menu in case
you have entered other menus earlier.
♦ Use the (Up) and (Down) buttons to choose the “Set Address” menu.
Set address
Check address
Read parameters
Save parameters
♦ Use the (Modify) and (Right) buttons to set address for the device displayed on the
first row of the screen:
• Press the (Right) button to move the cursor on the right. When is reached the last
position of the address, the cursor will move automatically to the first digit of the address.
• Press the (Modify) button to increase the digit with one unit. You can increase the digit
when the cursor is blinking over it. When the cursor is over the least significant digit (the
last right digit) the increasing is done with transfer to the next two most significant digits.
Examples:
1. The displayed address is 009 and the next pressing of the (Modify) button will
increase the address to 010.
2. The displayed address is 099 and the next pressing of the (Modify) button will
increase the address to 100.
3. The displayed address is 099 and the next pressing of the (Modify) button will
change the address to 009. In that case, there is no transfer to the most significant
digit because the cursor is under the middle digit of the address.
♦ Press the (Enter) button to start the writing procedure. While the addressing procedure is
running the screen displays:
New Address 001
Wait please
3
SensoIRIS Programmer - Operation Manual
Set address
Check address Choose the “Set address” start menu – scroll with “UP” and “Down”
Read parameters buttons if necessary.
Save parameters
New Address 001 “New address” setting screen. The setting always starts from the least
Enter Address significant digit of the address.
(Right) Press “Right” button to move to the first digit of the address.
(Modify) Press “Modify” button to increase the digit with one unit.
(Right) Press “Right” button to move to the next digit of the address.
(Modify) Press “Modify” button to increase the digit with one unit.
4x (Modify) Press “Modify” button 4 times to increase the digit with four units.
New Address 115
The address is set.
Enter Address
(Enter) Press the “Enter” button to write the address to the connected device.
(Esc) Press “Esc” button several times to return to the main menu.
4
SensoIRIS Programmer - Operation Manual
♦ Press the (Esc) button several times to exit back to the main programming menu in case
you have entered other menus earlier.
♦ Use the (Up) and (Down) buttons to choose the “Check address” menu.
Set address
Check address
Read parameters
Save parameters
♦ After the reading is over the programmer displays on the right up corner the address of the
device.
5
SensoIRIS Programmer - Operation Manual
3. Reading Parameters
Here in this menu, the installer can review the set parameters of SensoIRIS series addressable detectors:
T110, T110IS, S130, S130IS, M140 and M140140IS.
The parameters differ according the type of the detector. The parameters available for reading are listed
in the table below:
* Class according EN54-5: A1R/ A2R/ BR/ CR/ A1S/ A2S/ BS/ CS
** Sensitivity level according EN54-7: Low/ Middle/ Normal/ High
Note: At SensoRIS M140 and SensoRS M140IS detectors, class A1R is factory set for the heat part and
could not be changed.
♦ Press (Enter) button. The message “Read parameters. Wait, please...” is on the screen
while reading the detector parameters, and after that is displayed the type of the detector and
the respective parameters accessible for viewing.
The blinking arrow “x” pointing to the right, means that the programmer is reading
parameters. On the same row is displayed and the type of the detector.
♦ The parameters differ according the type of the detector:
o Address – Shows the current address of the detector.
o Day – Shows the current set day alarm level - for the heat detectors the class
according EN-54, and for the optical-smoke detectors – the level of sensitivity of
the smoke chamber according EN-54.
o Night - Shows the current set night alarm level - for the heat detectors the class
according EN-54, and for the optical-smoke detectors – the level of sensitivity of
the smoke chamber according EN-54.
o OPTOFFSET, OPTGAIN, CALIBRATION, CONGIF – specialized parameters
configured from the manufacturer.
o Version – Shows the current software revision.
Note: To review all parameters of SensoIRIS S130(IS) and M140(IS) use the (Down) button
one more time.
6
SensoIRIS Programmer - Operation Manual
4. Saving of parameters
Here in this menu, the installer can enter and save new parameters for SensoIRIS series addressable
detectors: T110, T110IS, S130, S130IS, M140 and M140140IS.
The programming options are: changing the address of the detector and setting of new parameters for
day and night alarm levels.
ATTENTION: To ensure correct parameters setting, it is obligatory first to read the current set
parameters and then to enter the “Save parameters” menu!
♦ Use the (Up) and (Down) buttons to choose the “Save parameters” menu:
Set address
Check address
Read parameters
Save parameters
♦ Configuration and saving of parameters. Use the (Up) and (Down) to scroll over the
different parameters.
o Day level – Shows the current set day alarm level - for the heat detectors the class
according EN-54, and for the optical-smoke detectors – the level of sensitivity of the
smoke chamber according EN-54.
To enter new Day level, press the (Enter) button. The programmer enters in
settings mode – the edited parameter is blinking. Press the (Down) button until
you reach the desired class or sensitivity level. Confirm the new entered parameter
with (Enter) button. Press the (Down) button to move to the next parameter.
o Night level - Shows the current set night alarm level - for the heat detectors the class
according EN-54, and for the optical-smoke detectors – the level of sensitivity of the
smoke chamber according EN-54.
To enter new Night level, press the (Enter) button. The programmer enters in
settings mode – the edited parameter is blinking. Press the (Down) button until
you reach the desired class or sensitivity level. Confirm the new entered parameter
with (Enter) button. Press the (Down) button to move to the next parameter.
o Save – Saving of the new set address and/ or parameters to the detector. Press the
(Enter) button to start. For a while the message “Wait, please...” is displayed. The
message “Successfully” means that the new address and/ or parameters are
successfully configured to the detector.
7
SensoIRIS Programmer - Operation Manual
5. Choosing language
♦ Press the (Esc) button several times to exit back to the main programming menu in case
you have entered other menus earlier.
♦ Use the (Up) and (Down) buttons to choose the “Language” menu.
Check address
Read parameters
Save parameters
Language
♦ Use the (Up) and (Down) buttons to select the desired language:
English
Български
Turkce
Espanol
♦ Press the (Enter) button to confirm your choice or (Esc) button to cancel the
operation.
♦ The programmer will automatically load the new language and exit to the main menu:
Check address
Read parameters
Save parameters
Language
♦ The language settings will be saved even if the programmer is switched off.