Quickie Load Form Blank

The document provides a quick load estimate form for calculating cooling loads, including sections for room design conditions, load density, air distribution, ventilation, humidification, and individual load components like windows, walls, ceilings, floors, people, lights, and computers.

Uploaded by

Franky Ken
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Quickie Load Estimate Form

Project Name:
Rules of Thumb for Cooling Load Estimates Table 1
Computer & Equipment Load
Room Design Conditions Quantity Model BTU/Hr Total BTU
Temperature 72F +/- 1F 1 Ricoh 0
Humidity 50% +/- 1% RH 1 0

Sensible Heat Ratio


Sensible Heat Gain 0.90 to 0.95
Total Heat Gain

Load Density
sq ft/Ton 50 to 100
(Total heat gain / 12000)

Preferred Air Distribution


Underfloor/overhead Underfloor

Ventilation Rate
CFM/person 10-15 Maximum

Humidificaiton Total BTU/HR 0


Lbs Moisture/100 CFM 3 NOTE: If BTU is not available, get total wattage input mult. X
of outside air 3.4 = BTU/Hr
Factor
Outside Design Temp BTU/HR
Item Quantity 95º F
1 Windows Exposed to sun South sq ft 70
East, West, Southeast sq ft 92
(Use only one exposure: Select the one
that gives the largest result)
Northwest sq ft X 72 =
(If no venetian or shading device is Northeast sq ft 75
available, mult. X 1.4) North sq ft 10
2 All windows not included in item 1 sq ft X 26 =
3 Wall Exposed to sun Light construction linear ft 75
(Use only the wall with the Heavy construction X =
linear ft 55
exposure used in item 1) (12" masonry or insulation)
4 Shade walls not included in item 3 linear ft X 40 =
5 Partitions All interior walls adjacent to linear ft X 35 =
an unconditioned space
6 Ceiling or roof Ceiling with unconditioned,
sq ft 5
occupied space above
Ceiling w/attic above No Insulation sq ft 12
X =
2" or more insulation sq ft 5
Flat roof w/ceiling below No Insulation sq ft 10
2" or more insulation sq ft 5
7 Floor Over unconditioned space
or vented crawlspace sq ft X 5 =
(Do not figure heat gain for floor directly
on ground or over unheated basement)
8 People Number of people
X 750 =
(includes allowance for ventilation)
9 Lights
Watts X 3.4 =
(if not available, use 3 watts/sq ft of floor area)
10 Computer Load Total BTU/Hr
From Table 1 0 =
(if not available in BTU, mult total watts x 3.4)
Total BTU Cooling Load: 0