SERVICE LEVEL

ECOCONTROL PLUS
FOR COOLING ONLY & HEAT PUMP

R 407C

INTERNATIONAL E
CONTROL USER GUIDE : ECOCONTROL Plus
The microprocessor control YORK, the ECOCONTROL Plus • Maximum compressor starts / hours (1)
has three levels of access ; user level, Factory Level and • Reading of compressor running hours
service level for YORK International engineers only, for • Condensing temperature set point (fan speed control) (1)
• Minimum fan speed (%) (1)
Factory and Service Level contact your YORK agent. The
• Maximum fan speed (%) (1)
microprocessor can control either the leaving or the return • Defrost cycle timing (1)
temperature. The control is compact, fitted on the panel • Defrost cycle start/stop temperature values (1)
without addivite boards. • Fan mode during defrost cycle (1)
The control regulates the fan speed according to the • Anti-freeze cut out (1)
condensing temperature, if the unit is a Cooling Only and to • Anti-freeze differential (1)
the ambient temperature is the unit is a Heat Pump. • Return water high temperature alarm (1)
The control can allow the access to a BMS (option). The • Low pressure alarm delay (1)
• Flow switch alarm delay (1)
control can allow a connection to a remote control (option)
• Stand by pump delay (1)
with on/off function, cooling/heating mode selection and two • Correction of temperature probe readings (1)
leds (on and alarms). • Automatic restart after power down (1)
The control displays the alarms, the set point, the leaving and • Choice of °C or °F (1)
return temperature, the condensing temperature and, only for • Minimum cooling set point allowed to the end user (1)
Heat Pump, the ambient air temperature. • Maximum heating setpoint allowed to the end user (1)
The control allows the modification or the reading of the • Serial N2Open communication address (2)
following : • Analog input mode : temperature sensor/pressure trasducer (2)

• Set point differential (1) (1) the parameters can be changed only at service level
• Control mode (leaving or return water temperature control) (1)
(2) the parameters can be changed only at factory level
• Compressor timer (1)
5 7 6
4

2
3
1- ON/OFF key 5- Led status
The unit will start after pushing the key 1 during more than 3 Led off: chiller is off
seconds Led on: chiller is on
The unit will stop after pushing the key 1 more than 3 seconds Led is blinking: Alarm
2- key enter 6- Led compressor
Allows to enter the user level for modifying the set point or to Led off: compressor is off
the service level giving an access to all the parameters Led on: compressor is on
(service level only for YORK international engineers) Led is blinking: compressor timer is on (compressor off waiting
3- Display for starting)
Will indicates the temperatures, the parameters, alarm codes If you push key 2, more than 3 seconds you can read on the
and setting values display “CLG”, you are at the user level, you are able then to
At the user level it will indicate the leaving and return modify the set point with the up and down arrows.
temperatures, the set point and the condensing temperature, The new value for the set point is entered in the memory
air temperature (only for H model) and the cooling / heating pushing again key 2 (enter)
mode (only for H model). 7- Heating Mode Status (only for YCSA/H)
4- Arrows up and down Led off : unit is in cooling mode
For moving into the program for reading and modifying the Led on : unit is in heating mode
parameters and for the reset of the alarms Led is blinking : unit is in defrost cycle

USER LEVEL
If you push key 2, more than 5 seconds you can read on the • Cooling setpoint CLG
display “CLG” , you are at the user level, you are able then to • Heating setpoint HTG (only for H model)
modify the set point with the up and down arrows the • Functioning Mode Pr0 (0=Cooling; 1=Heating) (only for H model)
following:
Setting variables levels : User level

PARAMETER DESCRIPTION MIN VALUE MAX VALUE DEFAULT TYPE


CLG Cooling set point C01 20 12 ºC
HTG Heating set point 20 H01 40 ºC
Pr0 Functioning Mode 0=Cooling 1=Heating 0 flag

New setting is stored in the memory pushing again key 2 (enter).

2
SERVICE LEVEL

“If you push key 2 more than 20 seconds you can read on the WARNING:
display “DIF”, you are at the service level (only for YORK
SOME PARAMETERS CONCERNS DIRECTLY THE SAFETY
STAFF or authorized engineers)”.
OF THE CHILLER RUNNING LIKE FOR INSTANCE THE
Once “DIF” is displayed, with the two arrows you can go to the ANTI FREEZE ALARM PARAMETER. THE PARAMETER
parameter you want to modify, afterward you press the key CAN BE MODIFY ONLY BY YORK INTERNATIONAL
“enter” (2) and with the arrows you put the value you want to ENGINEERS.
enter in the control and than again press key “enter” (2).

Service level

PARAMETER DESCRIPTION MIN VALUE MAX VALUE DEFAULT TYPE


DIF Set point differential 0,5 10 1 ºC
Pr2 Control Mode 0=leaving 1=return 1 Flag
CP1 Comp running min time 60 180 90 Sec
CP2 max comp starts/hour 6 12 7 N
CP3 total comp running time 0 999 Read only N x 10 h

Tc1 Condensation temp set 30 55 40 (20) ºC


Fn1 min. fan speed 0 100 25 (35) %
Fn2 max fan speed 50 100 85 %
Fn3 min. speed temp. in heating -20 60 15 ºC
Fn4 max. speed temp. in heating -20 60 30 ºC

Df1 Time start defrost 10 99 30 Min


Df2 Max defrost duration 1 99 4 Min
Df3 Temp start defrost -20 40 0.5 °C
Df4 Temp stop defrost -20 40 6 °C
Df5 Fan during defrost 0 = off 1 = cycling 0 (1) Flag

A01 Antifreeze cut out -20 60 4 ºC


A02 Antifreeze differential 0,5 10 2 ºC
A03 on heater differential temp 0 10 0 ºC
A04 Return water high temp alarm 30 70 35 ºC
A05 low pressure alarm delay 0 99 40 Sec
A06 flow switch alarm delay 0 99 2 Sec

P01 stand-by pump stop time 1 24 6 Hour


P02 stand-by pump on time 0 99 60 Sec

S01 ST1 return sensor offset -20 20 0 ºC


S02 ST2 leaving sensor offset -20 20 0 ºC
S03 ST3 coil sensor offset -20 20 0 ºC
S03 ST4 coil sensor offset -20 20 0 °C

r01 re-start after power down 0=auto 1=manual 1 Flag


Un units type ºC ºF ºC Flag
C01 minimum cooling set point -15 20 6 °C
H01 Max heating setpoint 35 50 50 °C

The column Default you have the factory settings for A/C Parameter TC1: setted to 40 for YCSA and setted to 20 for
application, chilled water at 7/12ºC. all YCSA/H
Parameter Fn1: setted to 25 for YCSA 06-18, setted to 35
for YCSA 26-36, to be setted to 10 for all YCSA if LAK is
WARNING/NOTES :
fitted.
Parameter A01 value must always be setted at least 2° Parameter Df5: setted to 0 for YCSA 06-18, setted to 1 for
degrees below the minimum leaving water temperature YCSA 26-36.
that we expect, according with CLG value, control mode, Parameter H01: setted to 50 all YCSA/H, setted to 45 for
temperature drop and the glycol percentage. YCSA/H DUTCH.

3
FACTORY LEVEL

“If you push key 1 and 2 together more than 10 seconds you Once “Pr1” is displayed, with the two arrows you can go to the
can read on the display “Pr1”, you are at the factory level (only parameter you want to modify, afterward you press the key
for YORK STAFF or authorized engineers)” “enter” (2) and again with the arrows you put the value you want
to enter in the control and than again press key “enter” (2).
Factory level

PARAMETER DESCRIPTION MIN VALUE MAX VALUE DEFAULT


Pr1 Unit Set Up 0=Chiller 1=Heat Pump 0
Add N2Open Device Address 1 255 255
Ps ST3 input selection mode 0=temp 1=pressure 0
sensor input converter input

IMPORTANT NOTE:
If LAK is fitted, set Ps to 1.
Use Add to select the unit address if serial communication
accessory is fitted.

ALARM DISPLAY

Priority Type Reset Note Display code


0 Memory fault ------ Control to be replaced EE
1 Reset Manual Timer Power Up Rst*
2 Efficiency Alarm Manual Rotation alarm EFF
3 Leaving sensor failure ST2 Auto Leaving water temperature F2
4 Return sensor failure ST1 Auto Return water temperature F1
5 Anti Freeze Alarm 1 Auto/Manual LWT Cut Out Af
6 High return water temperature Auto Return water temperature Ht
7 Flow/Diff. Pressure switch 3 Auto/Manual Flow switch alarm FS
8 High pressure Manual High pressure alarm/Motor Overload HOL
9 Low pressure 3 Auto/Manual Low pressure alarm LOP
10 Condenser sensor failure ST3 Auto Condenser temperature F3
11 Air sensor failure ST4 Auto Ambient temperature F4

NOTES: The reset is automatic for the first time within one hour. If the
alarm occurs more than 1 time within one hour, the reset must
• The “rst” message is displayed every time we switch on the
be done pressing the two arrows during more than 5 seconds.
unit by the main switch, or after a power down/up if the
parameter r01 is = 1 The alarm “HT” occurs in cooling configuration, if the return
water temperature (RWT) rise above 35°C during more than 60
• “rst” alarm can be resetted by switching on the unit using
seconds. The reset is automatic when return water
the ON/OFF key (1) and not by the arrow keys.
temperature (RWT) fall below 25°C.
• If r01=0 you will never see “rst” displayed
The alarm “FS” (Flow Switch) can be reset by switching off
• The parameter r01, as well as all other listed parameters, and on the unit with the key 1. The pump starts and, if before
can be modified only at the service level 2 seconds the flow switch resets, the alarm is reset. If the
alarms occurs more than 3 times in one hour, to reset the unit
The efficiency alarm “EFF” occurs if the difference entering
must be switch off and on by the main power.
water temperature – leaving water temperature is below 1°C
during more than 1 minute then the unit is stopped. This The alarm High Pressure / Motor OverLoad “HOL” reset is
control is done only for the first start of the compressor after always manual, first you have to reset the high pressure switch
each power on. The reset is done by switching off and on the and then the control pressing the 2 arrows together during
unit or by pressing the two arrows during more than 5 more than 5 seconds.
seconds.
The alarm low pressure “LOP” has got an automatic reset, if
The anti freeze alarm “AF” occurs in standard configuration if the alarm occurs more than 3 times in one hour the reset must
the leaving water temperature goes below 4°C, the be done pressing the 2 arrows together during more than 5
compressor is stopped, the heaters of the heat exchanger seconds.
(and buffer tank for the pack version only ) are switched on.
The anti freeze alarm is reset if leaving temperature goes
above + 6°C (4°C + 2°) (factory setting) and then the unit goes
back to normal operation.

4
BMS COMMUNICATION
N2Open Protocol Serial Communication Card Accessory
General Features Wiring
The N2Open serial card is a plug-in, optional card, that allows The connection to the network is made by means of the 3 pins
the Ecocontrol Plus (031B10078-001) of the YCSA unit to be on the plug-in connector (Figure 3).
connected in a N2Open serial network trough the RS485
standard (figure 1).

1
2
3
Figure 1
Figure 3

Card Insertion The meaning of each pin is as follows:


Remove the plastic door on the back of the controller
031B10078-001 and insert the card until it is fully in and pin RS485
securely locked by the small indentation present on the top of
the plastic box (Figure 2). 1 COM
2 RT-
Indentation to 3 RT+
Figure 4
031B10078-001 lock the card
The network cable must be laid along a low voltage cable
path. It must be placed at least at 30 cm from cables carrying
high voltages or currents (>230V or >30A). If strong
interference fields are expected, the cable must be located at
the greatest distance possible from the source. The
communication line must be laid out on the multi-drop line
principle, i.e. from one controller to the next until the last
controller has been connected. The line must be terminated at
both ends with a 220 Ohm resistor (not included) between
RT+ and RT- (Figure 4).
Figure 2
RS485 line: maximum length without repeater: 1200 mts,
AWG26 twisted pair with shield
RS232C line: maximum length: 10 mts
Devices: maximum of 32 per 1200 mts bus segment

IMPORTANT NOTE:
Enter in Factory Level and select the Device Address
(between 1 and 255).

LOW AMBIENT KIT ACCESSORY


Pressure Transducer plus Input Converter

IMPORTANT NOTE:
if LAK is fitted, be sure to select in Factory Level
parameter Ps from 0 to 1, and in Service Level parameter
Fn1 from 25 (or 35, depending on the sizes) to 10 for all
sizes.
Refer also to instruction you find in the Kit.

5
Manufacturer reserved the rights to change specifications without prior notice

INTERNATIONAL Ref. E-ECO-SL-0701


All rights reserved