Mar2 Led
Mar2 Led
A
Linear LED Lighting for Hazardous Locations
R
• Class I, Division 2, Groups A, B, C & D
• UL 844 Hazardous Locations
2
L
• UL 1598A Marine Outside Type
• UL 1598 Wet Locations
• UL 8750 LED Safety E
• CSA C22.2 #250.0-08
• CSA C22.2 #137-M1981
D
• NEMA 4X
• IP66
• 55°C Ambient Temperature
• Tested to LM 79 & LM 80
713.943.0340 | azz.com/rigalite
MAR2 LED
Linear LED Lighting for Hazardous Locations
Key Features:
1 Heavy-duty .094” thick extruded housing
2 Permanent safety cable attachment points
3 Two ¾” NPT conduit hubs
2 4
4 360º mounting flexibility
5 Field-replaceable LED circuit boards and drivers with quick 7 3
disconnects
6 Toolless entry via twist-lock latches
7 Watershed design
5
MAR2 07 - L2 - 4 - U - XX
1 2 3 4 5 6
1Mounting Hardware not included. Please see accessories for mounting selec-
tions.
2Specify voltage when option F is needed. When option F is selected, one fuse
is provided for 120 and 277V. Two fuses are provided for 220-240V. Fuse
option not available for marine listed fixtures, or for fixtures listed for use in
Canada.
Catalog logic is for explaining catalog number structure only. Not all combinations are possible; consult factory for catalog numbers not listed in charts.
LED
MAR2 LED
Linear LED Lighting for Hazardous Locations
Certification Guide
Supply Wire
Lumen Class I, Div. 2,
Total Suitable
Model Length Wattage Operating Voltage per CRI CCT Ambient Temperature Group Hub Size
Lumens Temperature,
Watt A, B, C & D
°C
MAR206L22U 2 ft 56W 120V - 277V 50/60 Hz 5476 98 85 4062 -20°C < Tamb < 55°C T6 90°C 3/4 in. NPT
MAR207L24U 4 ft 74W 120V - 277V 50/60 Hz 7660 103 82 4071 -20°C < Tamb < 55°C T6 90°C 3/4 in. NPT
MAR207L24U
Coefficients of Utilization Candlepower Distribution Photometric Data
% Effective Ceiling
Cavity Reflectance rcc 80 50 10 Deg. Parl. 22.5 45 67.5 Norm
% Wall Reflectance rw 50 30 10 50 30 10 50 30 10 0 2760 2760 2760 2760 2760
Room Cavity Ratio
RCR Effective Floor Cavity Reflectance 20% 15 2680 2666 2675 2676 2669
0 119 119 119 111 111 111 102 102 102 25 2513 2495 2516 2522 2519
1 106 102 98 99 96 94 92 90 88 35 2261 2248 2286 2295 2285
2 93 86 81 87 82 78 81 78 75 45 1925 1921 1960 1938 1921
3 82 74 68 77 71 66 72 67 64 55 1495 1516 1511 1459 1444
4 72 64 57 69 62 56 64 59 55 65 978 1004 953 941 928
5 65 56 49 61 54 49 58 52 48 75 409 399 344 17 15
6 58 49 43 55 48 42 52 46 42 85 34 5 4 4 4
7 53 44 38 50 43 38 48 42 37 90 0 0 0 0 0
8 48 40 34 46 39 33 44 38 33
9 44 36 30 42 35 30 40 34 30
10 41 33 27 39 32 27 37 31 27
MAR206L22U
Coefficients of Utilization Candlepower Distribution Photometric Data
% Effective Ceiling
Cavity Reflectance rcc 80 50 10 Deg. Parl. 22.5 45 67.5 Norm
% Wall Reflectance rw 50 30 10 50 30 10 50 30 10 0 2068 2068 2068 2068 2068
Room Cavity Ratio
RCR Effective Floor Cavity Reflectance 20% 15 1999 1996 1995 1998 2002
0 119 119 119 111 111 111 102 102 102 25 1962 1834 1867 1869 1876
1 106 102 99 99 97 94 92 90 89 35 1661 1666 1673 1669 1669
2 93 87 82 88 83 79 82 78 75 45 1396 1405 1407 1384 1379
3 82 75 69 78 72 67 73 68 65 55 1068 1087 1063 1052 1051
4 73 65 58 69 66 57 65 60 56 65 677 691 682 362 348
5 65 57 50 62 55 50 59 53 49 75 267 270 142 127 29
6 59 50 44 56 49 44 53 47 43 85 15 3 4 4 4
7 53 45 39 51 44 39 48 43 38 90 0 0 0 0 0
8 49 40 35 47 40 34 44 38 34
9 45 37 31 43 36 31 41 35 31
10 41 34 28 40 33 28 38 32 28
LED
MAR2 LED
Linear LED Lighting for Hazardous Locations
Accessories