Trumeter ADM Series


Graphical Panel Meters
Graphical panel meters with versatile programmable
features and user-configurable alarms ADM100-LN
ADM100-HN
Trumeter's line of graphical panel meters combines the instant visual representa- Negative LCD
tion of an analog meter with the accuracy of a digital meter. Bright digits on
black background
These meters feature a programmable bar graph and alarms to immediately
alert operators when a parameter is out of range. In addition, a four-character
messaging area displays custom messages, alarms and annunciators.
Each meter is configurable to measure voltage, current or frequency. The
ADM100-Lx model is for use with a low voltage power supply, and the ADM100-
Hx is for use with mains power. Both models offer two LCD options – positive
LCD for bright conditions or negative LCD for dark environments.
ADM100-LP
ADM100-HP
Flexible metering solution Positive LCD
• Fully programmable scalable input Black digits on
• User-selectable measurement range (min, max and span) bright background
• Two independent alarm outputs
• A fully scaled analog monitor output
• Programmable backlight automatically changes color or flashes when the input reaches a
certain value or goes outside a specific range
• Configurable via an easy-to-use PC utility UL file # E469787

Programmable Dynamic Warning


Overview
Backlight Color Flash Combined Digital and Measurement
Bar Graph Display
• Voltage: 0-600 AC or DC
• Current: 0-5A direct
Segment Curved 0-9,999A via CT
Bar Graph Display
• Frequency: 2-400 Hz (not
Programmable to recommended for VFD or
measure voltage, non-sinewave sources)
current or frequency
Outputs
Accuracy • 2x digital open collector
User-Configurable • 2x analog 4-20 mA
Alarms Input Power
ADM100-Lx: 12-24 VAC/VDC (+/- 10%)
ADM100-Hx: 100-240 VAC
or 110-300 VDC (+/- 10%)
Programmable
Scale Free Configuration Utility Download
C0-00DD1-D
• PC utility via USB
• Basic configuration without PC
(default setting is volts)
53mm Display Options
[2.09in] Programmable Starburst • Positive LCD (bright environments)
Two digital outputs Deep (14 Segment) Display for
Two analog outputs Alarms and Annunciators • Negative LCD (dark environments)
Programmable
Key features • Scale (offset and gain) and Range
(min and max)
• Large multi-format display • Dynamic backlight color • Four-character starburst for custom
• 40-segment bar graph display • User-adjustable backlight brightness, annunciators
• Large 4-digit display flash and color (red, green, white) • User-selectable backlight color and
• Wide viewing angle (both horizontal intensity
• Separate starburst display area for • Two independent alarm set-points
annunciators, custom message and and vertical)
• Two independent outputs
alarm information • Three-year warranty (with • 4-20 mA analog monitor output
registration at trumeter.com)
tPWP-11 1 - 8 0 0 - 633 - 0 4 0 5
For latest prices, please check AutomationDirect.com.

Trumeter ADM Series


Graphical Panel Meters
Graphical Panel Meters
Part Number Description Price
Graphical Panel Meter. Supply voltage 12-24 VAC/VDC. Positive LCD. Current, voltage or frequency input with two discrete or
ADM100-LP analog configurable outputs.
$70.00

Graphical Panel Meter. Supply voltage 12-24 VAC/VDC. Negative LCD. Current, voltage or frequency input with two discrete or
ADM100-LN analog configurable outputs.
$70.00

Graphical Panel Meter. Supply voltage 100-240 VAC. Positive LCD. Current, voltage or frequency input with two discrete or analog
ADM100-HP configurable outputs.
$77.00

Graphical Panel Meter. Supply voltage 100-240 VAC. Negative LCD. Current, voltage or frequency input with two discrete or analog
ADM100-HN configurable outputs. $77.00

Trumeter ADM Series Graphical Panel Meters


Part Number ADM100-LP ADM100-LN ADM100-HP ADM100-HN
Power Supply
Input 12-24 VAC/VDC +/- 10% 100-240 VAC or 110-300 VDC (+/-10%)
Power Consumption 1.6 W (max) 1.6 W (max)
Supply Frequency 50-400 Hz 47-63 Hz
Measurement Inputs
Voltage 0-600 VAC/VDC RMS
Current (Direct Connection) 0-5A
Current (With Current Transformer) 0-9,999A
Frequency 2-400Hz (not recommended for non-sinewave sources)
Display
User Configurable Backlight Colors Red, Green, White
Positive/Negative LCD Positive Negative Positive Negative
Readout Text Character Size Four-digit display, 0.47 in [12mm]
Message Text Character Size Four-digit display, 0.24 in [6mm]
Bar Graph Character Size 40 segments, 0.24 in [6mm]
Environmental
Operating Temperature 14 to 140°F (-10 to 60°C)
Storage Temperature -40 to 158°F (-40 to 70°C)
IP Rating (from the front) IP65, NEMA type 4 and NEMA type 12
Analog Outputs (2)
Output 4-20 mA
Accuracy 0.50%
Resolution 0.02 mA
Open Collector Outputs (2)
Max Voltage 34VDC
Max Current 500mA
Programming
Programming Port USB 2.0 (requires USB Type A to Type B cable, sold separately – USB-CBL-AB3, AB6, AB10 or AB15)
Agency Approvals
Certification CE, UL (File #E469787)
Mechanical
Wire Connection Type Screw Terminals
Wire Gauge (Solid or Stranded) 18AWG to 12AWG (0.8 mm2 - 3.3 mm2). Torque 0.5-0.6 Nm [4.43-5.31 lb-in]
Weight 6.35 oz (180g)
Mounting Clips Screw Torque <0.4 Nm [3.54 lb-in]

tPWP-12 1 - 8 0 0 - 633 - 0 4 0 5
For latest prices, please check AutomationDirect.com.

Trumeter ADM Series


Graphical Panel Meters
Dimensions
mm [inches]

Wiring Diagrams Rear connections


SingleSingle
phasephase
2-wire 2-wire
(1P2W)(1P2W) Outputs Reset for Peak Hold
N
L1
Voltage CT
Input * Input *

POWER
THD PF
kWVAr
MAX ø Hz
SUPPLY ** THD PF
PSU kWVAr
ø Hz
THD PF
kWVAr
ø Hz

kWh

* Both connection options shown. User must select one (volts, amps or
frequency) to be displayed.
** Dotted lines show 100-240 VAC power option on ADM100-Hx models.
ADM100-Lx units use the 12-24 VAC/VDC PSU connection shown.
COM RST (RESET)

Panel Cutout Dimensions {


POWER PSU -/N SP1{ OUTPUTS
SUPPLY PSU +/N SP2

mm [inches]

USB TYPE B
{
DIP SWITCHES
{ 1
2
3
4
VOLT/FREQ. AMP
INPUT INPUT
CT (CONNECTION)

Note: DIP switch setting is 0 for positions 1, 2, 3 and 4 off. To


change the default setting, visit https://support.automationdirect.
com/downloads.html#tools for free Trumeter ADM configuration
utility download.

Please see our website www.AutomationDirect.com for complete engineering drawings.