1 APPLICATION/ PART NO.

CONTROL as per IS - 1554


2 NO. OF PAIRS/Core 8 PAIR / 16 core
General

3 TWISTED PAIRS/ OVER LAY >10 twists or more per Meter / yes
4 CABLE O.D. 21 mm
5 INDIVIDUAL PAIR SHIELDING/ MATL. NOT APPLICABLE
6 OVERALL SHIELD / MATL. YES / AL. MYLAR TAPE
7 TYPE OF SCREENING 100% COVERAGE WITH 25%OVERLAP
8 CONDUCTOR MATL. / TYPE TINNED COPPER / Stranded
9 CONDUCTOR STANDARD IS- 8130
Conductor

10 CONSTRUCTION STRANDED 7 X 0.53 mm DIA


11 CONDUCTOR CROSS SECTION 1.5 mm2
12 CONDUCTOR INSULATION / STANDARD LDPE / IS 6474
13 INSULATION COLOR BLACK (+ve) & LIGHT BLUE(-ve)
14 INNER SHEATH / COLOUR (ST2 - IS5831) FRLS PVC / BLACK(ST-2-IS5831/IEC-502)
Construction

15 OUTER SHEATH / COLOUR FRLS PVC 1.6 mm THK * / GREY(ST-2-IS5831/IEC-502)


16 DRAIN WIRE MATL. & SIZE TINNED COPPER 7 X 0.3 mm DIA
17 RIP CORD REQUIRED BELOW INNER SHEATH
18 ARMOUR TYPE IS - 3975 GALVANISED STEEL WIRE 1.6mm DIA.
19 CORE IDENTIFICATION / NUMBERING PAIR NO. ON EACH CORE AT EVERY 50mm
20 INSULATION RESISTANCE OHM/Km >5000 MEGA OHM /KM at 20 Deg C. AS PER BS-5308
21 FLAME RETARDANCE IEC 332 PART III TYPE A
22 VOLTAGE GRADE (Volts) 600 V / 1100 V
23 ELECTROSTATIC NOISE REJECTION
24 CONDUCTOR RESISTANCE Ohm / Km @ 20 C 12.3 OHMS / KM
25 MUTUAL CAPACITANCE max.
(a) BETWEEN CORE TO CORE
(b) BETWEEN CORE TO SCREEN
26 INDUCTANCE AT 1 kHz mH/Km max. 1.2
Testing

27 L / R RATIO μH / OHM max 40


28 DIELECTRIC TEST VOLTAGE Tests as per IS- 1554 Part I
(a) CORE TO CORE **
(b) CORE TO SHIELD
(c) ARMOUR TO SHIELD
(d) SHIELD TO SHIELD
(e) SPARK TEST DURING PRODUCTION
29 OXYGEN INDEX (%) >29 AS PER ASTM D 2863
30 TEMPERATURE INDEX (OC) AS PER ASTM D 2863
31 ACID GAS EMISSION (%) AS PER IEC- 754 - 1
32 SMOKE INDEX (% ABSORBANCE) AS PER ASTM D 2843
33 OVERALL OUTER DIAMETER (mm) ± 1 mm *
34 DIAMETER BELOW ARMOUR (mm) ± 1 mm *
35 DIAMETER ABOVE ARMOUR (mm) ± 1 mm *
36 NET WEIGHT OF CABLE PER KM *
1) * Manuf. To specify.
NOTES
2) THE SUPPLIED CABLE SHALL NOT HAVE VARIATION IN DIAMETER FROM PLACE TO PLACE MORE THAN ±0.
3) NEGATIVE TOLERANCE IN LENGTH IS NOT ACCEPTABLE.
NOTES

4) ALL CABLES SHALL WATER, OIL & SUNLIGHT RESISTANT, GAS & VAPOUR TIGHT.

THE DRAIN WIRE RESISTANCE INCLUDING SHIELD SHALL NOT EXCEED 30 OHMS/ KM. THE DRAIN WIRE
5)
SHALL BE IN CONTINEOUS CONTACT WITH THE SIDE OF THE SHIELD.

EMBOSSING MARKING PER METER OF THE CABLE SHALL BE CLEAR & PROMINENT.RUNNING LENGTH OF
6)
CABLE SHALL BE PRINTED AT LEAST EVERY 5 METER INTERVAL.