Controlcable 16C 1.5sqmm
Controlcable 16C 1.5sqmm
3 TWISTED PAIRS/ OVER LAY >10 twists or more per Meter / yes
4 CABLE O.D. 21 mm
5 INDIVIDUAL PAIR SHIELDING/ MATL. NOT APPLICABLE
6 OVERALL SHIELD / MATL. YES / AL. MYLAR TAPE
7 TYPE OF SCREENING 100% COVERAGE WITH 25%OVERLAP
8 CONDUCTOR MATL. / TYPE TINNED COPPER / Stranded
9 CONDUCTOR STANDARD IS- 8130
Conductor
4) ALL CABLES SHALL WATER, OIL & SUNLIGHT RESISTANT, GAS & VAPOUR TIGHT.
THE DRAIN WIRE RESISTANCE INCLUDING SHIELD SHALL NOT EXCEED 30 OHMS/ KM. THE DRAIN WIRE
5)
SHALL BE IN CONTINEOUS CONTACT WITH THE SIDE OF THE SHIELD.
EMBOSSING MARKING PER METER OF THE CABLE SHALL BE CLEAR & PROMINENT.RUNNING LENGTH OF
6)
CABLE SHALL BE PRINTED AT LEAST EVERY 5 METER INTERVAL.