AW-FP200 series addressable fire alarm control
panel is designed with 7-inch LCD display touch
screen with button operation, easy to operate,
and nice human-computer interface.
This machine can be connected to 8 loops. Each
loop can be connected to 250 devices, such as
smoke detectors, temperature detectors,
input/output modules, each loop can be
connected to 10 groups of wireless loops, a
group of wireless loops can be connected to 20
devices, such as smoke detector, temperature
detector, input and output module, etc.
Features Installation
7-inch color LCD display, touch screen
operation
All addressable devices use a two-wire
system
A wired loop can connect 250 wired
addressable devices, including 10
groups of wireless loops
One set of wireless loops can connect to
20 devices
Max 8 loop cards can be installed
Up to 999 records of history can be
saved (save when power off)
Multiple access levels can be set
It has a rechargeable backup battery
Can simply judge the running status of
the machine based on the LED lights
Automatic search device
Each of the 8 hosts CAN be controlled
remotely
USB software upper computer to check
and set the device status and fire history
records
It can bind 10 mobile phone numbers to
receive host alarm information (The
GSM module must be added)
ASENWARE LTD
ADDRESS: 6 PROSPECT WAY, ROYAL OAK INDUSTRIAL ESTATE DAVENTRY, NORTHAMPTONSHIRE, ENGLAND, NN118PL
WEBSITE: www.asenware.com EMAIL: [email protected]
AW-FP200 Addressable Fire Alarm Control Panel
Technical Specification
Rated input voltage 85-260VAC 50Hz/60Hz
Standby battery Two 12V/7Ah lead-acid batteries in series
Working environment Relative humidity (<95%) at -10 ~45 ℃, no condensation)
AC power input fuse: 3.15A/250V 5*20mm, Glass tube fuse slowly
Fuse blow
Battery output fuse: 10A/250V 5*20mm, Glass tube fuse, slowly blow
Auxiliary power supply Resettable 24VDC 200mA (Max)
Normal output -12VDC
F.A output
Fire alarm output 24VDC/200mA (Max)
Normal output is 24VDC/200mA (Max), and the fault is output
Fault output
-12VDC
Normal state output - 12VDC
S.C output
Active state output -24VDC/200mA (Max)
Maximum Load Current per
24VDC 1A(Max)
Loop
All terminals rated for 12 to18 AWG (0.75 to 2.5 mm2)
Terminal blocks rating Screened or unscreened twisted-pair,
Transmission distance ≤1000m