0% found this document useful (0 votes)
393 views28 pages

Siemens fc2025 fc2050 ft2050 Fire Alarm Control Panel Installation Instructions 1906532784

Siemens fire control alarm setup
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
393 views28 pages

Siemens fc2025 fc2050 ft2050 Fire Alarm Control Panel Installation Instructions 1906532784

Siemens fire control alarm setup
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

FC2025 / FC2050 / FT2050

FV2025 / FV2050 / VR2005


Fire Alarm Control Panel
Installation Instructions
MP-UL 3.1

A6V10337045_en--_n Siemens Industry, Inc.


Smart Infrastructure

firealarmresources.com
Legal Notice
Technical specifications and availability subject to change without notice.
© 2020 Copyright by Siemens Industry, Inc.
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization
of its contents and communication thereof to others without express authorization are
prohibited. Offenders will be held liable for payment of damages. All rights created by patent
grant or registration of a utility model or design patent are reserved.
Edition: 2020-10-21
Document ID: A6V10337045_en--_n

2
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
Cyber security disclaimer

Siemens provides a portfolio of products, solutions, systems and services that


includes security functions that support the secure operation of plants, systems,
machines and networks. In the field of Building Technologies, this includes building
automation and control, fire safety, security management as well as physical
security systems.

In order to protect plants, systems, machines and networks against cyber threats, it
is necessary to implement – and continuously maintain – a holistic, state-of-the-art
security concept. Siemens’ portfolio only forms one element of such a concept.
You are responsible for preventing unauthorized access to your plants, systems,
machines and networks which should only be connected to an enterprise network
or the internet if and to the extent such a connection is necessary and only when
appropriate security measures (e.g. firewalls and/or network segmentation) are in
place. Additionally, Siemens’ guidance on appropriate security measures should be
taken into account. For additional information, please contact your Siemens sales
representative or visit https://www.siemens.com/global/en/home/company/topicareas/
future-of-manufacturing/industrial-security.html.

Siemens’ portfolio undergoes continuous development to make it more secure.


Siemens strongly recommends that updates are applied as soon as they are
available and that the latest versions are used. Use of versions that are no longer
supported, and failure to apply the latest updates may increase your exposure to
cyber threats. Siemens strongly recommends to comply with security advisories on
the latest security threats, patches and other related measures, published, among
others, under https://www.siemens.com/cert/en/cert-security-advisories.htm.

3
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
Table 1: Limitations and Restrictions per UL864, sec 90.23
Notice to Users, Installers, Authorities Having Jurisdiction (AHJ) and Other Involved Parties

This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL864, certain programming features or options must
be limited to specific value or not used at all as indicated below.
3

Program Feature or Options Permitted in Possible Settings Setting Permitted in UL864


UL864? (Y/N)
Ability to change the volume for Y Adjustment of the sounder volume on Setting of the Sounder Volume must
the sounder on the FACP the Operating Unit Menu ranges from be greater than "Bypassed" setting.
Loud to Max to Low to Min to Default must be set to Max
Bypassed
Global Access Point (GAP) using Y Ability to connect the FACP network When used with DesigoCC
Ethernet connection * using the Ethernet connection on the Management Station, connection
Operating Unit to connect to the must be in the same room within 20
FCNET feet and installed in rigid conduit.
Panel control functions using N Ability to connect the FACP network Not Allowed
"Desigo View" (Remote User using the Ethernet connection on the
Interface) * Operating Unit to permanently connect
to the Desigo View.

Ability to set FDOOT441 and Y FDOOT441 and FDOOTC441 Only the Selectable Alarm Threshold
FDOOTC441 detectors sensitivity detectors can be configured in the Setting Profiles permitted are:
programming tool: 2.50%/ft, 3.00%/ft, 2.50%/ft, 3.00%/ft, 2.50%/ft +
2.50%/ft + Verified, 3.00%/ft + Verified, Verified , 3.00%/ft + Verified
3.5%/ft and 3.5%/ft + Verified
Ability to set the FDOOTC441 Y FDOOTC441 detectors can be Minimum selection for CO level
detectors to CO level limit configured in the programming tool to limits must be 30ppm
define CO level limits in the range of
20ppm – 600ppm (in 10ppm
increments)

Ability to configure the FDCIO422 N FDCIO422 inputs can be configured Not Allowed
for Class A inputs with Open and for Class A with Open and Short circuit
Short circuit supervision supervision.
Ability to set the FDCIO422 device Y FDCIO422 Input Filter Time Setting Acceptable FDCIO422 Input Filter
to multiple Input Filter Time can be configured in the programming Time Setting are:
Setting tool : 0.25s, 0.5s, 1s, 2.5s, 5s, 10s,
0.25s, 0.50s, 1s
20s, 45s, 60s, 90s, 120s, 180s, 210s,
240s
Ability to set the FDCIO422 device Y FDCIO422 OutputPulse Mode Time Acceptable Output Pulse Mode Time
to multiple Output Pulse Mode Setting can be configured in the Setting are: 10s, 20s.
Time Setting programming tool: 1s, 2s, 3s, 5s, 10s,
20s.
Ability to set the FDCIO422 device N FDCIO422 Input Type can be Not Allowed
to Normally Closed inputs for configured to Normally Closed
Class A & Class B wiring

Ability for MNS NACs to be N NACs dedicated for MNS application Acceptable-NACs dedicated for
configured as Silenceable can be configured as Silenceable MNS application must be configured
as Non-Silenceable .
BACnet client Supervision timeout Y Ability for the BACnet supervision Acceptable Range must be between
to delay reporting network timeout to be configured from 1s to 10 1 sec and 85 sec.
supervision. minutes.

4
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
DACT Alarm, Trouble Supervisory DACT retransmission intervals can be DACT retransmission intervals must
Retransmission interval configured up to 24 hours be configured up to 6 hours
Y

Loss of primary power - Door Fire Control can be user defined Fire control to be configured to
unlocking timing accordingly within 10 minutes “unlocking” after
Y loss of primary power

Releasing operation – Door Releasing Control Group can be user Releasing Control Group to be
release operation timing Y defined accordingly configured to 60 secs. Max release

Interconnected/networked panel Interconnected/networked loops could Configuring Class X network loops


loops pathway configuration Y be configured Class X, A or B via the Redundancy management
configuration setting
Alarm verification restart time Alarm verification restart time user Max restart time shall not exceed 30
defined seconds when accomplished on a
Y
multiple circuit (zone) or system
basis

Alarm verification configuration Alarm verification devices in a cross- Alarm verification shall not be used
N zone operation in initiating device circuits intended
for cross-zone operations
CO alarm tone programming CO programming tone user defined CO detector MUST be programmed
Y as Temporal 4

PAD-5 Trouble supervision Trouble supervision setting can be on Error reporting must be “on” and
Y or off activated

PAD-5 Ground Fault monitoring Ground fault supervision for the power Ground fault supervision must be
Y supply can be activated or turned off “on” and activated

Signal Silence Inhibit Feature Signal Silence Inhibit range 0-30 UL minimum is 3 minutes
Y minutes

5
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
Table 2: Limitations and Restrictions per CAN/ULC-S527 3rd Ed. Amd 1 cl. 7
Notice to Users, Installers, Authorities Having Jurisdiction (AHJ) and Other Involved Parties

This product incorporates field-programmable software. In order for the product to comply with the requirements in
CAN/ULC-S527, Standard for Control Units for Fire Alarm Systems, certain programming features or options must be
limited to specific value or not used at all as indicated below.
3

Program Feature or Options Permitted in Possible Settings Setting Permitted in CAN/ULC-


CAN/ULC- S527
S527? (Y/N)

Ability to change the volume for Y Adjustment of the sounder volume on Setting of the Sounder Volume must
the sounder on the FACP the Operating Unit Menu ranges from be greater than "Bypassed" setting.
Loud to Max to Low to Min to Default must be set to Max
Bypassed

Global Access Point (GAP) using Y Ability to connect the FACP network When used with DesigoCC
Ethernet connection * using the Ethernet connection on the Management Station, connection
Operating Unit to connect to the must be in the same room within 20
FCNET feet and installed in rigid conduit.

Panel control functions using N Ability to connect the FACP network Not Allowed
"Desigo View" (Remote User using the Ethernet connection on the
Interface) * Operating Unit to permanently connect
to the Desigo View.

Ability to set FDOOT441 and Y FDOOT441 and FDOOTC441 Only the Selectable Alarm Threshold
FDOOTC441 detectors sensitivity detectors can be configured in the Setting Profiles permitted are:
programming tool: 2.50%/ft, 3.00%/ft, 2.50%/ft, 3.00%/ft, 2.50%/ft +
2.50%/ft + Verified, 3.00%/ft + Verified, Verified , 3.00%/ft + Verified
3.5%/ft and 3.5%/ft + Verified

Ability to set the FDOOTC441 Y FDOOTC441 detectors can be Minimum selection for CO level
detectors to CO level limit configured in the programming tool to limits must be 30ppm
define CO level limits in the range of
20ppm – 600ppm (in 10ppm
increments)

Ability to configure the FDCIO422 N FDCIO422 inputs can be configured Not Allowed
for Class A inputs with Open and for Class A with Open and Short circuit
Short circuit supervision supervision.

Ability to set the FDCIO422 device Y FDCIO422 Input Filter Time Setting Acceptable FDCIO422 Input Filter
to multiple Input Filter Time can be configured in the programming Time Setting are:
Setting tool : 0.25s, 0.5s, 1s, 2.5s, 5s, 10s,
20s, 45s, 60s, 90s, 120s, 180s, 210s, 0.25s, 0.50s, 1s
240s

Ability to set the FDCIO422 device Y FDCIO422 OutputPulse Mode Time Acceptable Output Pulse Mode Time
to multiple Output Pulse Mode Setting can be configured in the Setting are: 10s, 20s.
Time Setting programming tool: 1s, 2s, 3s, 5s, 10s,
20s.

Ability to set the FDCIO422 device N FDCIO422 Input Type can be Not Allowed
to Normally Closed inputs for configured to Normally Closed
Class A & Class B wiring

6
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
Ability for MNS NACs to be N NACs dedicated for MNS application Acceptable-NACs dedicated for
configured as Silenceable can be configured as Silenceable MNS application must be configured
as Non-Silenceable.

BACnet client Supervision timeout Y Ability for the BACnet supervision Acceptable Range must be between
to delay reporting network timeout to be configured from 1s to 10 1 sec and 85 sec.
supervision. minutes.

DACT Alarm, Trouble Supervisory DACT retransmission intervals can be DACT retransmission intervals must
Retransmission interval configured up to 24 hours be configured up to 6 hours
Y

Loss of primary power - Door Fire Control can be user defined Fire control to be configured to
unlocking timing accordingly within 10 minutes “unlocking” after
Y loss of primary power

Releasing operation – Door Releasing Control Group can be user Releasing Control Group to be
Y
release operation timing defined accordingly configured to 60 secs. Max release

Interconnected/networked panel Interconnected/networked loops could Configuring Class X network loops


loops pathway configuration Y be configured Class X, A or B via the Redundancy management
configuration setting

Alarm verification restart time Alarm verification restart time user Max restart time shall not exceed 30
defined seconds when accomplished on a
Y
multiple circuit (zone) or system
basis

Alarm verification configuration Alarm verification devices in a cross- Alarm verification shall not be used
N zone operation in initiating device circuits intended
for cross-zone operations

CO alarm tone programming CO programming tone user defined CO detector MUST be programmed
Y
as Temporal 4

PAD-5 Trouble supervision Trouble supervision setting can be on Error reporting must be “on” and
Y
or off activated

PAD-5 Ground Fault monitoring Ground fault supervision for the power Ground fault supervision must be
Y
supply can be activated or turned off “on” and activated

Signal Silence Inhibit Feature Signal Silence Inhibit range 0-30 ULC minimum is 5 minutes
Y
minutes

7
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
Minimum Requirement to Access FS20 documents
- Computer with high speed internet connection
- Microsoft Explorer 7.0 or higher
- Adobe Reader (http://www.adobe.com/)
If you cannot meet these requirements, please contact Siemens Technical Support at 1-800-248-7976 to request hard
copy of the installation guidelines.

Location of the FS20 User Documentation


To access the FS20 user documentations, go to
https://extranet.w3.siemens.com/buildingtechnologies/partner/FSUSENV3/Pages/default.aspx. Click “Search
Documentation”. Enter the appropriate document number in the “Search for” dialog box to access, and then click “Search”.

Select the appropriate document by double clicking it. It is recommended to save these documents in your computer for
future access. Select the “Save” button to store the document in your computer.

8
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
Table 3: FS20 Document Description
Document Description Doc Number Description
FS20 System Description A6V10315009 Overview of the FS20 system structure and functions
FS20 Planning A6V10315013 Provide information on project planning for the system and the
individual devices.

FS20 Mounting, Installation, A6V10315015 Provide HW reference document. This contains the wiring
Product Data connections, electrical rating, module settings and compatible
accessories for each individual module. Provides detailed
description on how each module is installed in the enclosure and
how internal and external wiring are routed.
FS20 SLC Device Compatibility A6V10326371 Provides the list of compatible devices that can be connected to
List the signaling line circuit (such as detectors, etc.)
FS20 SLC Device Compatibility A6V10399673 Provides the list of compatible devices that can be connected to
List (Canada) the signaling line circuit (such as detectors, etc.)
FS20 Commissioning, A6V10315021 Instructions for commissioning, maintenance and troubleshooting
Maintenance, Troubleshooting of the whole fire detection system

FS20 Configuration A6V10315023 Provides instructions how to use DesigoWorks Configuration Tool
to configure and program the system.
FC20xx / FT2050 Operation A6V10315017 Provides the detailed operating instructions of the system after it
Manual has been configured

FS20 NAC Compatibility List A6V10333530 Provide the list of compatible devices that can be connected to the
Notification Appliance Circuit.
FS20 Desigo Fire System CM10013en0F Describes the FS20 Protection Integration including the
Integration Guide configuration steps of FC20 fire alarm control panels.

9
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
Introduction
The FS20 system is a life safety network that is modular, networkable fire detections system that can consist of FC2025,
FC2050 Fire control panels (250p/500p), and FT2050 Network terminal (8 lines). It comprises of all the components
required for the detection, evaluation and annunciation of life safety event such as fire and smoke conditions. By using
optional modules, copper wiring and/or Fiber Optic cables are used to network the panels together.
The FC2025 panel is capable of supporting up to 252 devices and FC2050 is capable of supporting up to 504 devices.
Both panels have a PMI with optional LED module, 2 Class B or 1 Class A NAC (expandable to 4 Class B, 2 Class A
NACs), 4 control relays, Battery Charger, Aux Power connection and optional capability for connection to Leased Line or
City Tie. Both panels support DACT, connection to Remote Printer / Remote Annunciators and Releasing Application as
optional feature. Both panels use 170W power supply or optional 300W power supply for more power capability.
The PAD-5 is an addressable booster power supply which offers additional NAC expansion with flexible configuration for
each individual circuit. The PAD-5 also includes releasing circuits and conventional zone inputs.
The FV2025 and FV2050 Fire voice control panels have all the capabilities and features of the FC2025 and FC2050 plus
voice evacuation capabilities that support Mass Notification and Emergency evacuation. Both panels have Voice Card
Cage, which, can support up to 3 amplifier circuits which, can be configured as Class A or Class B (3 primary and 1
backup, or 2 primary and 2 backup), connection LED/Switch module and optional capability for connection to remote/local
microphone, remote LED/Switch module and low-level input/output audio. It has the ability to originate and broadcast
voice announcements through connected speakers and transfer voice announcement among interconnected systems.
Both the FV2025 and the FV2050 are powered by either a single or two cascaded 300W power supplies. For Mass
Notification Application, it has the security level stated below:
- Communication Security  Level 1 (Security function not employed)
- Stored Data Security  Level 0 (Passwords are employed)
- Access Control Security  Level 1 (Passwords are employed with programmable time-out feature)
- Physical Security  Level 1 (keylocks are employed to control physical entry to the panel)
The FT2050 panel is a network terminal capable of displaying events for the entire system or can be programmed to
control and display a specific panel.
The VR2005 Remote microphone is a remote voice station that utilizes remote terminal board and can have microphone
and LED/switch modules connected to the FV2025 or FV2050 to enable fire safety personnel to originate voice
announcements remotely. The FV2025/FV2050 can power and control up to four VR2005 remote microphone stations per
node. Refer to the VTA2001-A1 installation instructions, Document ID A6V10405564, for installation information.
The FT2050 panel and remote microphone can be combined in a 2HU enclosure (2HU Remote Station) by utilizing its
respective interface units and remote switch module. Refer to Figure 5 for connection and recommended wiring routes.
The FV2025/FV2050 Voice Systems, when used in conjunction with Siemens Hi-Fidelity speakers, meets the requirement
for low frequency signal tone as described in the section for Determination of Low Frequency Signal Format, in UL464,
Standard Audible Signal Appliance, suitable for sleeping area as required by NFPA 72 Chapter 18.4.5 (2013 Edition).
Refer to Document ID A6V10333530 for compatible speakers.
The FV2025/FV2050 also supports Background music and Convenience paging functionalities using Global analog audio
input that is configured for lowest priority. Refer to the FS20 Configuration manual, Document ID A6V10315023, Section
11.6.5 and the FS20 Operation Manual, Document ID A6V10315017, Section 8.7 for proper configuration and operation.
For a complete FS20 system overview, refer to the FS20 System Description, Document ID A6V10315009.
Legacy Migration
The FC2025/FC2050 fully supports Siemens legacy systems and technology. With the use of the FCL2004-U1 module,
the Desigo Fire Safety panel offers full compatibility with legacy MXL and MXL-IQ system peripheral devices. Each Desigo
system will support up to two FCL2004-U1 modules. Each module has two ALD circuits for a total of 240 MXL compatible
devices (120 per module), in addition to the Desigo Fire Safety peripherals already available. Also available are the MXL-
IQ mechanical migration kits. The kits support existing MXL-IQ backboxes MSE-3L and MSE-3M. Reuse the existing
enclosure and replace the electronics with new Desigo Fire Safety system panel electronics.

10
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
Remote Connectivity
The FC2025/2050 and FV2025/2050 can send events via the Connect X300 gateway for remote diagnostics and
serviceability. The Connect X300 can be installed as a node on the FCnet or FVnet.

Installation
The FC2025, FC2050, FT2050, FV2025, FV2050 and VR2005 panels are installed in dry, protected environments using
different enclosures that consist of backbox, inner door and outer door that is lock-protected and have clear plexiglass
windows. The FV2025 and FV2050 panels use 3-Height enclosure units; the FC2025 and FC2050 panel use 2-Height
enclosure units and the FT2050 and VR2005 use 1-Height enclosure units. All the modules are installed inside the
enclosure backbox and inner doors (refer to Figure 3). An optional DIN Rail Kit is available (PN: S54400-B44-A1) to allow
indirect wiring connection to the PMI and other modules that support low power field wiring. An optional Battery Seismic
Kit is available (PN: S54400-B43-A1 or S54400-B55-A1) to meet the seismic requirement. An optional Battery Disconnect
module (S54400-B145-A1) is available to meet ULC requirements. An optional Ethernet Switch Module (S54400-B152-
A1) is available to allow the FC2025/FC2050/FT2050 panels to be networked with FV2025/FV2050.
To support migration from legacy installations, the use of the FHA2056-U1/-R1 is recommended (PN: S54400-B18-A1
[Black] or S54400-B19-A1 [Red]).
For complete module mounting and installation, please refer to the FS20 Mounting, Installation and Product Data manual,
Document ID A6V10315015.
Wiring
For FS20 System wiring, refer to the applicable module section of the FS20 Mounting, Installation and Product Data
manual, Document ID A6V10315015, and module installation instructions.
External FS20 System Wiring
FCNET – Refers to communication connection between panels using SafeDLink module (S54400-A60-A1) and/or Fiber
network modules (SM/MM) (FN2006-U1 / FN2007-U1). This can be configured as Class A and B and is supervised. Refer
to the FS20 Mounting, Installation and Product Data manual, Document ID A6V10315015, for proper wiring connection.
RS485 Remote Peripheral (UFP) – connection of the FACP to the Remote display (FT2014-U2, FT2014-R2), Remote
terminal (FT2015-U2, FT2015-R2), Remote peripheral module (FCA2018-U1), LED annunciator driver (FT2007-U1),
Tabular annunciator 16 zone (FT2008-U1/FT2008-R1), Tabular annunciator 32 zone (FT2009-U1/FT2009-R1), and
Graphic driver (I/O) (FT2003-U1) through the RS485 class A module (isol.) (FCA2016-A1). This can be configured as
Class A and B and is supervised. Refer to the FS20 Mounting, Installation and Product Data manual, Document ID
A6V10315015, for proper wiring connection.
FDNET – Signaling Line Circuits (SLC) that used P2 proprietary protocol connection of the FACP to the Initiating Devices
such as Detectors, Monitor switches, etc., through the Periphery board (250p/500p) (FCI2016-U1/FCI2017-U1). This can
be configured as Class A, B, or X and is supervised. Refer to the FS20 Mounting, Installation and Product Data manual,
Document ID A6V10315015, Section 25, for proper wiring connection and compatible devices. A full portfolio of peripheral
devices with optional built-in isolation including the PAD-5 is available for use on the FDNET.
Notification Appliance Circuit (NAC) – This is the connection of FACP to the Notification Appliances devices through the
Periphery board (250p/500p) (FCI2016-U1/FCI2017-U1) or optional NAC Module (1A/2B) (FCI2011-U1). This can be
configured as Class A or Class B and is supervised. Refer to the FS20 Mounting, Installation and Product Data manual,
Document ID A6V10315015, for proper wiring connection, and Document ID A6V10333530 for List of Compatible NAC
Devices.
Releasing Circuit – This is the connection of the FACP to releasing devices such as solenoids and squibs through the
optional Releasing module (XCI2001-U1). This is configured as Class B or Class A and is supervised. The releasing
application meets the requirement for the following regulation: NFPA 13, NFPA 750, NFPA 2010, NFPA 2001.
Refer to the FS20 Mounting, Installation and Product Data manual, Document ID A6V10315015, Section 22, for proper
wiring connection. Refer to the Solenoid Compatibility List, Document ID A6V11620059.
VCNet Connections – Refers to the communication connection between Voice panels using Ethernet modules (VN2001-
A1, VN2002-A2, VN2003-A3). This can be configured as Class B or Class X and is supervised. Refer to the FS20
Mounting, Installation and Product Data manual, Document ID A6V10315015, for proper wiring connection.

11
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
CAN Circuits – connection of the Voice panels to remote or local CAN modules (VTO2001-U2, VTO2004-U2, VCI2001-
U1). This can be configured as Class B. Refer to the FS20 Mounting, Installation and Product Data manual, Document ID
A6V10315015, for proper wiring connection.
Ethernet Connections – This is the internal connection of the Card cage (4 amplifiers) (VCA2002-A1) to the Op. unit
bracket UL (option) (FCM2025/2050-A1) and VCNET connection of the FV2025/2050 Control Panel. For inter-connection
between FC2025/FC2050 and FV2025/FV2050, the Ethernet switch (modular) (FN2012-A1, S54400-B152-A1) must be
used. The Ethernet connections can be configured as Class B or Class X and is supervised. For proper wiring connection,
refer to the FN2012-A1 Installation Instructions, Document ID A6V10407862.

Audio Input/Output – This is the internal and external connection of audio inputs from microphones and connected audio
systems. All audio inputs and outputs are Class B and are supervised. Refer to the FS20 Mounting, Installation and
Product Data manual, Document ID A6V10315015, for proper wiring connection.
Speaker Circuits – This is the external connection of amplified audio to the speaker lines. These can be configured as
Class A, Class B or Dual-interleaved Class B and are supervised. Refer to the VCI2001-U1 Voice amplifier c ard (25V)
Installation Instructions, Document ID A6V10370410, for proper wiring connection. Up to 24 HCP intelligent control points
can be used in speaker zones and can be configured as Class A or Class B. Refer to the HCP installation instructions,
P/N 315-034860, for more information.
Compatible Solenoids – Refer to the Solenoid Compatibility List, Document ID A6V11620059.

Note: The Manual Discharge function always overrides the Abort switch function.

Leased Line / City Tie Circuit – This is the connection of FACP to the Leased Line or City Tie through optional LLCT
Module (FCI2020-U1). This is configured as Class B only and is supervised only when configured as City Tie. Refer to the
FS20 Mounting, Installation and Product Data manual, Document ID A6V10315015, Section 23, for proper wiring
connection.
Central/Remote Station – The FACP uses the Dialer module (DACT) (FCA2015-U1) connected to the PSTN to connect to
the central or remote station in the event of life safety situation. Connections to phone lines are supervised. Refer to the
FS20 Mounting, Installation and Product Data manual, Document ID A6V10315015, for proper wiring connection.
For Canadian Installations the following applies:
- Both the Dialer module (DACT) (FCA2015-U1) and the 3rd party communicator must be configured and
connected to the same Central Station.
- One of the User-Defined buttons on the Operating Unit must be programmed as Manual Alarm Signal
(evacuation) Control which is able to initiate alarm signal and resound audible devices after they have been
silenced. The button chosen must be clearly marked on the Inscription Strip.
- The Battery disconnect module (FCA2032-U1) is required to disconnect the battery when voltage drops below 19
VDC while system is on battery power.
- If using a Remote display or Remote Terminal (FT2014-U2 or FT2015-U2) the Inner Door RDT (FHD2012-U1) is
required to meet ULC audible indicator sound output requirements.

12
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
Knockout
#7 Knockout
11 #5 or #6
Knockout
#8
2 3
4
Knockout
1 Knockout #4
#9 5
6

Knockout
Ribbon Cables #3

Module Locations:
1. FCM2018/FCM2019-U2 Operating Unit 7
8
2. FN2001-U1 SafeDLink Module 9
3. FCA2016-A1 RS485 Module Knockout
4. FCI2016/FCI2017-U1 Periphery Board #10 or #11
5. FCI2020-U1 City Tie/Municipal Ckt
6. XCI2001-U1/FCI2011 -U1 Releasing/NAC
7. FN2006/FN2007-U1 Network Module
8. FCA2015-U1 DACT
9. FP2011-U1/FP2012-U1 Power Supply 10 10
10. Battery Set
11. FHA2031-U1 DIN Rail Set

Recommend Wiring Routes: Knockout


Knockouts: 1, 2, 3, 5, 6 are Non-Power Limited wiring only #1 or #2
Knockouts: 4, 7, 8, 9, 10, 11 are for Power Limited only

Notes:
Refer to Table 5 to locate each module wiring diagram.

Figure 1: Module Location in 2HU Enclosure and Recommended Wire Routing

13
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
Figure 2: Module Location in 1HU Enclosure and Recommended Wire Routing
Modules Location in FHB2001-U1/R1 Recommended Wiring Routes:
7 – FN2006 -U1 /FN2007-U1 - Knockouts: 1, 2, 3, 4 are for Power Limited wiring only
11 – FHA2031-U1 Notes: Refer to Table 5 to locate each module wiring
12 – FTI2001-U1 diagram.

14
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
Figure 3: Module Location in 3HU Enclosure and Recommended Wire Routing
Module Locations in FHB2005-U2/R2
Recommended Wiring Routes
1. FCA2015-U1 8. FP2013 -U1
- Knockouts 1 and 6 are for non-power limited
2. FCM2018/FCM2019-U2/U3 9. VCA2002-A1 [contains: VCI2001-U1,
wiring.
3. FCA2016-A1 VCC2001-A1, VCC2002-A1]
- Knockouts 2, 7, 10, 11, 12 are for power limited
4. FHA2031-U1 10. Battery set
wiring.
5. FCI2020-U1 11. VTO2001-U2/U3
6. FCI2016/FCI2017-U1 12. FCM2022-U2/U3
7. FCI2011-U1 or XCI2001 -U1 13. VTO2004-U2/U3
14. FCA2032-U1

15
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
TO FV2025 /2050 FIRE VOICE CONTROL
PANEL OR ADJACENT VR 2005
REMOTE MICROPHONE STATION

TO MUTED SPEAKER

Knockout
#1 4

3
2 2 2

Knockout # 2

POWER LIMITED

TO ADJACENT VR2005 REMOTE


MICROPHONE STATION

Figure 4: Module Location in 1HU Remote Microphone Station and Recommended Wire Routing
Module Locations FHB2001-U2/R2:
1. VTO2004-U2/U3 Recommended Wiring Routes:
2. VTO2001-U2/U3 Any knockouts may be used for the power-limited wiring
3. VTA2001-A1 associated with the Remote Microphone.
4. FHA2031-U1 (optional)

16
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
To FV2025 / FV 2050
1
2
24 VDC

Low Level
3 Audio

CAN Bus

7 7 7

Internal Wiring

External Wiring

Figure 5: Module Location for 2HU Enclosure (Remote Station) and Recommend Wire Routing
Module Locations FHB2002-U2/R2: Recommended Wiring Routes:
1. FCM2018-U2 / FCM2019-U2
Any knockouts may be used for the power-limited wiring
2. FCA2015-U1 (optional)
associated with the 2HU - Remote Station.
3. FTI2001-U1
4. VTA2001-A1
5. FN2012-A1 with VN2001-A1 / VN2002-A1 /
VN2003-A1 Notes:
6. VTO2004-U2/U3 As indicated in Figure 5, FTI2001-U1 and VTA2001-A1 are
7. VTO2002-U2/U3 stacked on top of one another using the standoff provided with
VTA2001-A1. The image is displayed flat to show the wiring
details.

17
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
S54400-A66-A1
TO MXL (BUNDLED CABLE)
DETECTOR FCM2018-U2/-U3
CIRCUITS FCL2004-U1 OR
FCM2019-U2/-U3

1 3

2
S54400-A66-A1
(RIBBON CABLE)

Power-Limited

18-Conductor
Bundled Cable

20-Conductor
Ribbon Cable for
FCL2004-U1 Optional FCL2004
(OPTIONAL)
24V Power

Figure 6: Module Location in MXL-IQ MSE-3L Enclosure and Recommended Wire Routing

Module Locations in MSE-3L Enclosure Notes:


using Adapter Plate (P/N A5Q00075220):
1. FCL2004-U1 To install an FCL2004-U1 module in a MSE-3L enclosure, install a
2. FCL2004-U1 (optional) FHA-MIQKIT-04 (Black) or FHA-MIQKIT-05 (Red).
3. FCI2016/FC2017-U1
4. FCM2018/FCM2019-U2/-U3

18
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
FCI2016-U1
OR
FCM2018-U2/-U3
FCI2017-U1
OR
FCM2019-U2/-U3

1 2

SECOND FCL2004-U1
FIRST FCL2004-U1 (OPTIONAL)

24V Power

18-Conductor
Bundled Cable
2nd FCL2004-U1
20-Conductor
Ribbon Cable for
Optional FCL2004 1st FCL2004-U1

MALE-FEMALE
STANDOFFS

ADAPTER
PLATE

Figure 7: Module Location in 2HU Enclosure and Recommended Wire Routing

Module Locations in 2HU Enclosure using Notes:


Adapter Plate (P/N A5Q00079811):
1. FCL2004-U1 For mounting the FCL2004-U1 module(s) in a 2HU enclosure,
2. FCL2004-U1 (optional) refer to the FCL-MXLPLATE Installation Instructions, Document
3. FCI2016/FC2017-U1 ID A6V11877890.
4. FCM2018/FCM2019-U2/-U3

19
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
FS20 General Electrical Characteristics
Refer to the FS20 Mounting, Installation and Product Data manual, Document ID A6V10315015, for circuit electrical characteristics.

System Power Input  Output:

FP2011-U1: 120 VAC, 60 Hz, 50 Hz, 1.64 A (max); 240 VAC, 50 Hz, 60 Hz, 1.5 A (max)  24 VDC @ 6.5 A (max)

FP2012-U1: 120 VAC, 60 Hz, 50 Hz, 2.77 A (max); 240 VAC, 50 Hz, 60 Hz, 1.37 A (max)  24 VDC @ 11.5 A (max)

FP2013-U1: 120VAC@ 5.0A (max), 240VAC, 2.5A (max)  24VDC @ 20A (max, combined output for both units)

Ground Fault Threshold: 1k Ohms (0.1 Ohm for Leased Line Circuit)

Wire to wire fault impedance threshold = 0 Ohms

Wire to wire open impedance threshold = Infinite impedance

Battery: 24VDC Lead acid batteries only. 100AHr (max), Charge Voltage/Current: 27.5VDC, 6A (max)

Table 4: Battery Sets


Model Number Part Number Description
BP-61 175-387194 24V 18AH (min.) – Battery set
BTX-1 175-083897 24V 33AH (min.) – Battery set
BTX-2 175-350784 24V 55AH (min.) – Battery set
BTX-3 175-034219 24V 100AH (min.) – Battery set
SLC: 35V @ 500mA (max), max line impedance: 180 ohms, Class B, A, X. All SLC are supervised. Refer to Document ID
A6V10326371 (U.S.) or A6V10399673 (Canada) for Compatible devices.

NAC: 24VDC, 0.3A (max) Regulated for Pulsing Loads; 24VDC, 3.0A (max) Special Application for pulsing loads, Regulated for non-
pulsing loads , Class A or Class B, Coded or Non-coded, Synchronized, refer to Document ID A6V10333530 for compatible NAC
devices. Only combination MNS NACs and Fire NACs are allowed.

Relay Contacts: 30VDC, 120ADC, 5A, Common (Alarm, Supervisory, Trouble) and Programmable (User-defined)

Releasing Circuit: 24VDC, 2A(max), Class B or Class A. Refer to the Solenoid Compatibility List, Document ID A6V11620059.

Aux Power: 24VDC, 1.5A (max), Power Limited, Special Application

DC Supervision (optionally selectable): 18VDC max

CAN Bus: max line impedance: 15 ohms, Class B, Supervised.

Speaker Circuit:

Output Voltage: 25Vrms or 70Vrms


Max Power Output: 65W @ 70Vrms, 50W @ 25Vrms (refer to Document ID A6V10370410 for resistance limitations)
Frequency Response: 400 Hz – 4kHz
Total Harmonic Distortion (THD): <0.4% nominal @ 1kHz

Efficiency (under full load): 85% @ 70Vrms, 80% @ 25Vrms

Voice Intelligibility: The FS20 System meets Voice Intelligibility Requirement as defined in Section D of the NFPA 72, 2010 edition,
having a Speech Transmission Index (STI) of 0.50 or greater. Each acoustically distinguished space must be properly evaluated and
tested to ensure compliance.

Pathway Survivability: Each circuit must be evaluated and tested to ensure compliance to the application and area of protection to
meet the criteria of Section 12.4 of NFPA 72, 2010 edition.

All wiring between the releasing device and any other interconnected product shall be monitored for integrity in accordance with the
Common Performance and Monitoring for Integrity – Protected Premises Units/Systems.

20
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
Any SLC pathway shall have the capability, either inherent or by use of external devices, to prevent a wire to wire fault from affecting
the entire pathway.

NOTE 1: Reference to Power Limited is deemed Class 2 for U.S. installation only. Reference to Power Limited 70V speaker circuits is
deemed Class 3 for U.S. installation only. For Canadian installations, the same circuits employed by the product aren’t
deemed Class 2 nor Class 3. Please refer to the appropriate product installations for further details.

NOTE 2: Where power to a device or appliance is supplied over a separate pathway from the initiating device, notification appliance,
and/or signaling-line circuit(s), the operation of the power pathway shall meet the performance requirements of the initiating
device, notification appliance, and/or signaling-line circuit(s) and the power circuit shall be defined by the applicable class in
the product installation wiring diagram/instructions.

21
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
FS20 Module Description -
Table 5: Installation Instruction Part Numbers
Model Number Part Number Description Product Insert Number
FCM2018-U2 S54400-C40-A1 Operating unit A6V10315030
FCM2019-U2 S54400-C41-A1 Operating unit (+ LED) A6V10315030
FCI2016-U1 S54400-A55-A1 Periphery board (250p) A6V10315038
FCI2017-U1 S54400-A56-A1 Periphery board (500p) A6V10315038
FCI2011-U1 S54400-A54-A1 NAC module (1A/2B) A6V10315036
FCI2020-U1 S54400-A57-A1 Leased line / city tie mod. A6V10334256
FTI2001-U1 S54400-A58-A1 Fire terminal board A6V10315040
FP2011-U1 500-450222 Power supply (170W) A6V10333499
FP2012-U1 S54400-Z60-A1 Power supply (300W) A6V10334250
FP2013-U1 S54400-Z61-A1 Power supply set (600W) A6V10436206
FCA2015-U1 S54400-A63-A1 Dialer module (DACT) A6V10334254
FCA2016-A1 S54400-A39-A1 RS485 class A module (iso.) A6V10334252
FCA2018-U1 S54400-A65-A1 Remote peripheral module A6V10315044
FTO2012-U1 500-692407 External parallel printer (PAL-1) A6V10372650
FCA2033-A1 S54400-P154-A1 License key (S1) A6V10350183
FCA2034-A1 S54400-P155-A1 License key (S2) A6V10350183
FCA2035-A1 S54400-P156-A1 License key (S3) A6V10350183
XCI2001-U1 S54400-A69-A1 Releasing module A6V10315050
FN2001-U1 S54400-A60-A1 Network module (SAFEDLINK) A6V10315042
FN2006-U1 S54400-A61-A1 Fiber network module (SM) A6V10315048
FN2007-U1 S54400-A62-A1 Fiber network module (MM) A6V10315048
FT2014-U2 S54400-F67-A1 Remote display (black) A6V10315046
FT2014-R2 S54400-B75-A1 Remote display (red) A6V10315046
FT2015-U2 S54400-F68-A1 Remote terminal (key, bl) A6V10315046
FT2015-R2 S54400-B15-A1 Remote terminal (key, red) A6V10315046
FCM2022-U2 S54400-C44-A1 Option module (blank) A6V10315032
FCM2023-U2 S54400-C45-A1 Option module (LED) A6V10315032
FHD2001-U2 S54400-B49-A1 Outer door (1HU, black) A6V10335926
FHD2001-R2 S54400-B49-A2 Outer door (1HU, red) A6V10335926
FHD2002-U2 S54400-B50-A1 Outer door (2HU, 1 win, bl) A6V10335926
FHD2002-R2 S54400-B50-A2 Outer door (2HU, 1 win, red) A6V10335926
FHD2003-U2 S54400-B51-A1 Outer door (2HU, 2 win, bl) A6V10335926
FHD2003-R2 S54400-B51-A2 Outer door (2HU, 2 win, red) A6V10335926
FHD2006-U1 S54400-C46-A1 Clear window A6V10335926
FHB2001-U1 S54400-B47-A1 Back box (1HU, black) A6V10335922
FHB2001-R1 S54400-B47-A2 Back box (1HU, red) A6V10335922
FHB2002-U1 S54400-B48-A1 Back box (2HU, black) A6V10335922
FHB2002-R1 S54400-B48-A2 Back box (2HU, red) A6V10335922
FHD2004-U1 S54400-B52-A1 Inner door (black) A6V10335929
FHD2005-U1 S54400-B53-A1 Inner door (solid, black) A6V10335929
FHA2031-U1 S54400-B44-A1 DIN rail set A6V10334278
FHA2032-U1 S54400-B43-A1 Battery bracket A6V10334280
FHA2035-U1 S54400-B42-A1 Trim Kit (1HU, Black) A6V10350024
FHA2035-R1 S54400-B44-A2 Trim Kit (1HU, Red) A6V10350024
FHA2036-U1 S54400-B41-A1 Trim Kit (2HU, Black) A6V10350024
FHA2036-R1 S54400-B42-A2 Trim Kit (2HU, Red) A6V10350024
FT2003-U1 S54400-C136-A1 Graphic driver (I/O) A6V10384377
FCA2032-U1 S54400-B145-A1 Battery disconnect module A6V10385200
FHD2012-U1 S54400-C135-A1 Inner door RDT (black) A6V10385202
FCL2004-U1 S54400-A68-A1 MXL Device Interface Module A6V11415283

22
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
Model Number Part Number Description Product Insert Number
FCL-MXLPLATE S54400-B153-A1 Adapter plate to mount the A6V11877890
FCL2004 loop driver
FCM2034-U2 S54400-C137-A1 Option module (LED r/y, y) A6V10315032
FCM2035-U2 S54400-C139-A1 Operating unit (+ LED) A6V10315030
FHA-MIQKIT-04 S54400-C24-A1 MXL-IQ Mechanical Migration Kit A6V11420345
FHA-MIQKIT-05 S54400-C25-A1 MXL-IQ Mechanical Migration Kit A6V11420345
FHA2056-U1 S54400-B18-A1 FS250/MPC Mech Migration Kit A6V101004423
(Black)
FHA2056-R1 S54400-B19-A1 FS250/MPC Mech Migration Kit A6V101004423
(Red)
Connect X300 S55842-Z121-A100 CXG3.X300 Connect X300 A6V11649121
Gateway

Table 6: Fire-Voice Installation Instruction Part Numbers


Model Number Part Number Description Product Insert Number
VCA2002-A1 S54400-A47-A1 Card cage (4 amplifiers) A6V10380472
VCC2002-A1 S54400-A41-A1 Voice I/O card A6V10397774
VCC2001-A1 S54400-A40-A1 Voice CPU card A6V10397772
VCI2001-U1 S54400-A45-A1 Voice amplifier card (25V) A6V10370410
VN2001-A1 S54400-A42-A1 Ethernet Module (electric) A6V10370415
VN2002-A1 S54400-A43-A1 Ethernet Module (MM) A6V10370419
VN2003-A1 S54400-A44-A1 Ethernet Module (SM) A6V10370419
VCI2003-A1 S54400-A141-A1 VoIP module A6V10380474
VTA2001-A1 S54400-F163-A1 Remote terminal board (class B) A6V10405564
VTO2001-U2 S54400-C60-A1 Option module (24 switches) A6V10370342
VTO2004-U2 S54400-C61-A1 Option module (Microphone) A6V10370377
FHB2005-U1 S54400-B110-A1 Back box (3HU, black, deep) A6V10359788
FHB2005-R1 S54400-B110- A2 Back box (3HU, red, deep) A6V10359788
FHD2007-U2 S54400-B111-A1 Outer Door (3HU, 3 win, bl) A6V10359790
FHD2007-R2 S54400-B111-A1 Outer Door (3HU, 3 win, red) A6V10359790
FHA2041-R1 S54400-B93-A1 Enclosure cover A6V10370383
FHA2042-U1 S54400-B55-A1 Battery bracket (33 Ah) A6V10370385
FHA2043-U1 S54400-B56-A1 Trim kit (3HU, black) A6V10370379
FHA2043-R1 S54400-B57-A1 Trim kit (3HU, red) A6V10370379
FHD2009-U1 S54400-B114-A1 Blank plate (black) A6V10359792
FHD2009-R1 S54400-B114-A2 Blank plate (red) A6V10359792
FCA2031-A1 S54400-A153-A1 Connection module (MoNet) A6V10407860
FN2012-A1 S54400-B152-A1 Ethernet switch (modular) A6V10407862
FT2007-U1 S54400-A142-A1 LED annunciator driver A6V10456395
FT2008-U1 S54400-A143-A1 Tabular annunciator (16 z, bl) A6V10456397
FT2008-R1 S54400-A144-A1 Tabular annunciator (16 z, red) A6V10456397
FT2009-U1 S54400-A145-A1 Tabular annunciator (32 z, bl) A6V10456397
FT2009-R1 S54400-A146-A1 Tabular annunciator (32 z, red) A6V10456397
PAD-5 S54339-A5-A1 Power Expander Main Board A6V101030358
PAD-5-CLSA S54339-A6-A1 Class A/B Expansion Board w/ A6V101030359
Releasing
PAD-5-CDC S54339-A7-A1 Conventional Detector Expansion A6V101030366
Board

23
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
Table 7: Battery Calculation Form
Ref. No.
Enter
Submitted By: value
Project Name: Select choice
Project Location: Fixed
Panel Location: Calculated
Node No: Date:

Module Standby Alarm


Module Description Feature Qty Current Current Comments
FCM2018-U2 Operating unit 0.000 0.000 125 mA (standby), 166 mA (alarm) per module
Operating unit 0.000 0.000 130 mA (standby), 170 mA (alarm) per module
FCM2019-U2 (+ LED) LED zones 1 mA per zone (3 LEDs per zone)
FCI2016-U1 Periphery board (250p) 110 mA (standby) , 136 mA (alarm)
0.000 0.000
SLC load Calculated device load from below
NAC load2 NAC alarm current from signals
Aux power
load1 External Aux power for standby & alarm
Bell Follower No 0.000 0.000 4mA if Bell Follower is active
FCI2017-U1 Periphery board (500p) 120 mA (standby), 136 mA (alarm)
0.000 0.000

SLC load Calculated device load from below


NAC load2 NAC alarm current from signals
Aux power
load1 0.000 0.000 External Aux power for standby & alarm
Bell Follower No 0.000 0.000 4mA if Bell Follower is active
FCI2011-U1 NAC module (1A/2B) No 0 0.000 0.000 15 mA (standby), 40 mA (alarm)
NAC load2 NAC alarm current from signals
XCI2001-U1
11 mA (standby), 40 mA (alarm) per module, 1
Releasing module No 0 0.000 0.000 mA per releasing circuit
Releasing
load2 Releasing alarm current from solenoids

27 mA (standby), 40 mA (alarm) for LL;


FCI2020-U1 Leased line/city tie mod. Not Installed 0.000 0.000 2 mA (standby) 13 mA (alarm) for City Tie
FN2001-A1 Network module (SAFEDLINK) 0.000 0.000 35 mA per module
FCA2016-U1 RS485 class A module (isol.) 0.000 0.000 58 mA per module
FN2006-U1 Fiber network module (SM) 0.000 0.000 127 mA per module
FN2007-U1 Fiber network module (MM) 0.000 0.000 132 mA per module
FT2014-xx Remote display (color) 0.000 0.000 34 mA (standby) 55 mA (alarm) per module
FT2015-xx Remote terminal (color) 0.000 0.000 34 mA (standby) 55 mA (alarm) per module
FTI2001-U1 Fire terminal board 0.000 0.000 11 mA per module
FCM2023-U2 Option module (LED) 0.000 0.000 5 mA per module
LED zones 0.000 0.000 1 mA per zone (3 LEDs per zone)
FCA2015-U1 Dialer module (DACT) 0.000 0.000 25 mA (standby), 33 mA (alarm) per module
FCA2018-U1 Remote peripheral module 0.000 0.000 73 mA per module
FT2003-U1 Graphic driver (I/O) 0.000 0.000 19.5 mA (standby) 32 mA (alarm) per module
FCA2032-U1 Battery disconnect module 0.000 0.000 7 mA (standby) 12.6 mA (alarm) per module
VCA2002-A1 Card Cage 0.000 0.000 4 mA (standby) 4 mA (alarm)
VCC2002-A1 Voice I/O module 0.000 0.000 151 mA (standby) 156 mA (alarm) per module
VCC2001-A1 Voice CPU card 0.000 0.000 200 mA (stanby) 210mA(alarm) per module
196 mA(standby) 2.42A @ 25V (alarm) per
VCI2001-U1 Voice amplifier card (25V) 0.000 0.000 module
VN2001-A1 Ethernet Module (electric) 0.000 0.000 7 mA(standby) 7mA (active) per module

24
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
VN2002-A1 Ethernet Module (MM) 0.000 0.000 35 mA(standby) 36mA(active) per module
VN2003-A1 Ethernet Module (SM) 0.000 0.000 35mA(standby) 36 mA(active) per module
VCI2003-A1 VoIP module 0.000 0.000 43 mA (standby), 43 mA (alarm) per module
VTO2001-U2/U3 Option module (24 Switches) 0.000 0.000 16mA (standby) 143mA (active)
VTO2004-U2/U3 Option Module (Microphone) 0.000 0.000 29mA (standby) 54 mA (active)
FCA2031-A1 Connection module (Monet) 0.000 0.000 1 mA (standby), 1 mA (alarm) per module
FN2012-A1 Ethernet switch (modular) 0.000 0.000 340 mA (standby), 340 mA (alarm) per module
FT2007-U1 LED annunciator driver 0.000 0.000 25 mA (standby), 250 mA (max)

Tabular annunciator (16 z,


FT2008-U1/-R1 bl/red) 0.000 0.000 25 mA (standby), 65 mA (max)
Tabular annunciator (32 z,
FT2009-U1/-R1 bl/red) 0.000 0.000 25 mA (standby), 105 mA (max)

FCL2004-U1 MXL Device Interface Module 0.000 0.000 130mA + 1.5mA per device
Connect X300
Gateway CXG3-X300 Connect X300 0.000 0.000 259 mA per module

Current
Devices Description Qty Stdby/Alm Draw
HFP-11 Photo-thermal detector 0.00000 1.4 mA per device
HFPO-11 Photo detector 0.00000 1.4 mA per device
HFPT-11 Thermal detector 0.00000 1.4 mA per device
Dual optical/thermal/CO
FDOOTC441 detector 0.00000 0.75 mA per device
FDOOT441 Dual optical/thermal detector 0.00000 0.68 mA per device
FDOT421 Photo-thermal detector 0.00000 0.28 mA per device
FDO421 Photo detector 0.00000 0.28 mA per device
FDT421 Thermal detector 0.00000 0.28 mA per device
FDCIO422 4-input/4-output module 0.00000 1.0 mA per device
HMS-S/D/M Manual station 0.00000 1.4 mA per device
HTRI-S Single input module 0.00000 1.4 mA per device
HTRI-D Dual input module 0.00000 1.4 mA per device
HTRI-R Singl input/single relay Mod 0.00000 1.4 mA per device
Addressable Switch Interface 0.00000
Mod w/ Dual Isolators (single-
XTRI-S input) 0.65 mA per device
Addressable Switch Interface 0.00000
Mod w/ Dual Isolators (Dual
XTRI-D input) 0.95 mA per device
Addressable Switch Interface 0.00000
XTRI-R Mod w Dual Isolators (w/ relay) 0.75 mA per device
Addressable Switch Interface 0.00000
Mod w/ Dual Isolators (compact
XTRI-M size) 0.65 mA per device
XMS-D Double action pull station 0.00000 0.50 mA per device
XMS-M Single action pull station 0.00000 0.50 mA per device
XMS-S Single action pull station 0.00000 0.50 mA per device
Intelligent Remote Lamp – Wall 0.00000
ILED-XW mount (rectangular plate) 0.50 mA per device
Intelligent Remote Lamp – 0.00000
ILED-XC Ceiling mount (round plate) 0.50 mA per device
Intelligent Test Switch Module 0.00000
TSM-1X with Isolators 0.50 mA per device
HZM Conventional zone module 0.00000 1.4 mA per device
HCP Addressable control point 0.00000 1.4 mA per device
HLIM Loop Isolator Module 0.00000 1.0 mA per device
ILED Intelligent LED 0.00000 1.4 mA per device
1.4mA (standby) ,
ABHW-4B (L dBa) Loop-powered audible base - L 0.00000 75mA (alarm)
1.4mA (standby),
ABHW-4B (H dBa) Loop-powered audible Base - H 0.00000 12mA (alarm)

25
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
PAD-5 Power Expander Main Board 0.00000 0.75 mA per expander
Conventional Detector
PAD-5-CDC Expansion Board 0.00000 0.75 mA per board
Class A/B Expansion Board w/
PAD-5-CLSA Releasing 0.00000 1.25 mA per board
Total 0 0.000 (included above) System OK

Total Current 0.000 0.000 Use 170W power supply

Standby Time
(hrs) 24 0.00

Alarm Time (min) 30* 0.00


AH required (no reserve) 0.00
Battery Reserve 125%

AH Required (with reserve) 0.00 System OK

Note 1: Ensure that the standby Aux power is not entered twice when used as external power source for optional modules.
Note 2: Max Alarm NAC Current = 3A/Circuit, Max Releasing Circuit Current = 2A/Circuit
Note 3: *Alarm time requirements offer multiple selections. Choose the appropriate time based on the requirements of
your application. Options include: 5 minutes, 10 minutes, 15 minutes, 30 minutes, 60 minutes, and 120 minutes.

Battery Calculation
Battery backup is required for compliance to UL864 and ULC-S527. Refer to NFPA 72 and CAN/ULC-S524 for required
standby time. To determine the battery, use Table 7 above and fill-out the required parameters.
1. Record quantities of all required modules and devices per panel.
2. Device Load Calculation: Place the # of devices in the yellow column, multiply with the current draw and place results
in Standby/Alarm column. Add all results in the Standby/Alarm column to determine the total device current draw and
place the result in the appropriate SLC load cell.
3. Module Load Calculation: Place the # of modules and associated functions (e.g., LED zones, Bell Follower, etc) in the
yellow column and multiply with associated current draw and place results in the appropriate column (Standby or
Alarm).
4. Place the NAC load and Releasing load during alarm in the Alarm Column.
5. Add all results in the Standby Column to determine the System Standby Current.
6. Add all results in the Alarm Column to determine the System Alarm Current.
7. Place the required parameters: Standby Time (hr), Required Alarm Time (hr), Minimum Battery Size (AHr), Minimum
Battery Reserve (%)
8. Calculate Battery Requirement for System Standby (AHr) = System Standby Current (A) x Standby Time (hr)
9. Calculate Battery Requirement for System Alarm (Ahr) = System Alarm Current (A) x Alarm Time (hr)
10. Calculate the Battery Reserve (AH) = (Battery Reserve (%) / 100%) x (System Alarm Req + System Standby Req)
11. Calculate the minimum battery Requirement = Battery Reserve + System Alarm Req + System Standby Req.
Select the battery that meets or exceeds the final calculated amp hour rating.

26
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure

firealarmresources.com
THIS PAGE HAS BEEN LEFT INTENTIONALLY BLANK.

27
Siemens Industry, Inc. A6V10337045_en--_ n
Smart Infrastructure

firealarmresources.com
Issued by © 2020 Siemens Industry, Inc.
Siemens Industry, Inc. Technical specifications and availability subject to change without notice.
Smart Infrastructure
8 Fernwood Road
Florham Park, NJ 07932
Tel. +1 973-593-2600
www.downloads.siemens.com/dlc

Document ID A6V10337045_en--_n SAP order no.: A5Q00050986

firealarmresources.com

You might also like