Installatie en Onderhouds Manual CPAN XHE 3
Installatie en Onderhouds Manual CPAN XHE 3
Size1 - Size6
MANUEL
Dear Customer,
Clivet has been working for years to offer the market systems able to assure maxi-
mum and long-las ng wellbeing with high reliability, efficiency, quality and safety.
The company aim is that to offer its customers developed systems that assure the
best comfort, reduce energy consump ons and installa on and maintenance costs
for the en re life-span of the system.
With this manual, we intend giving informa on useful throughout all phases: from
recep on, to installa on, to use and even disposal, so that such a developed system
meets the best installa on and use methods.
CLIVET Spa
TABLE OF CONTENTS
1 Generality ......................................... 4
2 Receipt .............................................. 6
3 Positioning ....................................... 7
7 Start-up ............................................ 19
8 Control ..................................... 28
9 Maintenance ................................... 39
11 Disposal .......................................... 46
The data contained in this manual is not binding and may be changed
by the manufacturer without prior notice.
Reproduction, even is part, is FORBIDDEN © Copyright - CLIVET
S.p.A. - Feltre (BL) - Italia
3
1 - GENERALITY
4
1 - GENERALITY
Range
Size E
D
Serial number
B A
Year of manufacture
C
Wiring diagram
CESTD Standard exchanger on outdoor air std E Variable air flow fan on supply air
EVE Electronic expansion valves std F Variable air flow fan on exhaust air
CPHGM Hot gas re-heating coil with capacity modulation G Exhaust air exchanger
std
AIR SIDE FEATURES
PCOSME Air flow constant in delivery and expulsion std
PVARC Variable air flow on supply and exhaust with CO2
probe
PVARCV Variable air flow on supply and exhaust with
CO2+VOC probe
FG4EE G4 class air filters on outdoor and exhaust air std
PSTAF Filters dirty differential pressure switch on extract
and delivery std
MHSEX Immersed electrodes steam humidifying module
5
2 - RECEIPT
2.3 Storage
Respect the indications on the outside of the pack.
Size3....size6
lifting bracket
6
3 - POSITIONING
The functional spaces have the aim of: positioning underneath the ground level, near very
high walls, underneath roofs or in corners (can give
guarantee good operation of the unit
rise to stratification or recirculation phenomena).
allow maintenance operations Neglecting the previous indications can lead to:
protect the authorised operators and exposed worsening of the energy efficiency.
persons.
blocks due to HIGH PRESSURE (in summer) or LOW
Respect the functional spaces indicated in the TECHNICAL
PRESSURE (in winter).
INFORMATION chapter
Avoid snow and ice accumulation in front of the external air
Double the functional spaces if more units are aligned.
outlets and of the exhaust air ejection.
3.3 Positioning
Positioning on concrete floor
The units have been designed to be installed :
OUTDOORS
INDOORS (OPTION)
in permanent position.
Choose the place of installation depending on the following
criteria:
level of sound emissions admitted by the local
standards
Customer approval
safely accessible position
technical spaces requested by the unit
maximum distance admitted from the electric 1 strisce in neoprene di spessore 2 cm
connections 2 platea in calcestruzzo
support points with adequate capacity for the unit 3 solaio
weight
spaces for air ejection and suction
disposal of condensate water
Prefer places where the unit does not disturb neighbours. Positioning on steel structure
Avoid snow accumulating obstructing the coils
Avoid places that may be subject to floodings
Install the unit lifted from the ground.
Protect the unit with suitable fence in order to avoid
access to unauthorised personnel (children, vandals, etc.)
Limit the transmission of vibrations:
use anti-vibration devices or neoprene strips on the
unit support points
install flexible joints on the hydraulic connections
install flexible joints on the aeraulic connections.
A correct air circulation on the coil is essential to guarantee the
good operation of the machine.
Avoid:
1 anti-vibration devices
obstacles to air flow (strong prevailing winds, hedges,
2 steel structure
fences, etc.)
3 steel structure
7
3 - POSITIONING
Avoid snow and ice accumulating in front of the exhaust air 3.6 STEAM HUMIDIFICATION MODULE - OPTION
ejection.
IMMERSED ELECTRODE STEAM HUMIDIFICATION
MODULE
This accessory requires connection to a water supply network
and discharge water circuit with adeguate frost protection.
Requires its own power supply and have to be connected to
the unit. Installation and wiring to customer care.
CENTRALISED STEAM HUMIDIFICATION MODULE
A shut-off valve in the unit’s steam input line is to be provided
(responsibility of the customer). Install the steam line in a
position higher to the unit.
If the available steam supply exceeds the pressure operating
range indicated, the required de-pressurization must take
place outside the unit (responsibility of the customer).
Operating pressure: 1 bar
3.4 INDOOR INSTALLATION SET-UP Risk of freezing: see par. 4.2
A Rain-proof protection
B Safety and anti-intrusion for small animals grille
C Rain drain
D Condensate drain
8
4 - HYDRAULIC CONNECTIONS
A. vent
B. filling glycol
C. water filling tap
Example :
P = 300 Pa = 30 mm
T = 2P = 60 mm
S = T/2 = 30 mm
9
4 - HYDRAULIC CONNECTIONS
4.4 Immersed electrodes humidifier - option Limit values for the supply water with medium-high conductivity in an
immersed electrode humidifier
SUPPLY WATER min max
The humidifier must be supplied with mains water having the Hydrogen ions pH 7 8,5
following features:
Specific conductivity at 20°C μS/cm 300 1250
pressure between 0.1 and 0.8 Mpa (1 – 8 bar)
(1) (1)
Total dissolved solids TDS mg/l
temperature between 1 and 40°C
(1) (1)
Do not use : Dry residue at 180°C R 180 mg/l
water treated with softeners: it can corrode the Total hardness TH mg/l CaCO3 100 (2) 400
electrodes and form foam with possible faults/ (3)
Temporary hardness mg/l CaCO3 60 300
malfunctionings
Iron + Manganese mg/l Fe+Mn 0 0,2
pit, industrial or potentially polluted (chemically or
bacteriologically) water Chlorides ppm Cl 0 30
Chlorides ppm Cl 0 20
(2) not lower than 200% of the chloride content in mg/l of Cl-
(3) not lower than 300% of the chloride content in mg/l of Cl-
10
5 - AERAULIC CONNECTIONS
The dimensioning and correct execution of the aeraulic The internal surface of the channel must be smooth, enable
connections are fundamental to guarantee good unit operation its washing and must not contaminate the air
and adequate level of silence in the room. Thermally isolate the channels and the flanges to avoid
When designing and manufacturing the channels, consider energy losses and forming of condensation
LOAD LOSSES, AIR FLOW AND SPEED that must be DIFFUSERS INLETS GRILLES
consistent with the unit features. A correct diffusion of the air in the room is determining for the
Particularly consider that load losses higher than the unit level of comfort.
useful prevalence, lead to reduction in flow rate, with When choosing and positioning the grilles, inlets and
consequent unit blocks. diffusers, avoid:
the weight of the channels must not burden on the excessive air speed
connection flanges
forming of stagnant and stratification areas
place anti-vibration joints between channels and unit
cold air delivery in room
connection to the flanges and between the various
sections of the channels must guarantee air seal, avoiding
forming of localised currents (also due to uneven
distribution of air)
dispersions penalising the overall efficiency of the system
limit the load losses by optimising the path, the type and excessive room temperature variations, vertically and
horizontally
number of bends and junctions
Thermally isolate the channels and the flanges to avoid energy losses and forming of condensation
11
5 - AERAULIC CONNECTIONS
1 2
12
6 - ELECTRIC CONNECTIONS
Matriculation
plate
VOLTAGE
FLA (A)
FLI (kW)
6.3 Connections
Refer to the wiring diagram of the unit (the number of the
wiring diagram is indicated in the matriculation plate)
Check the mains have features conform with the data reported
on the matriculation plate
Before starting work, check the isolation device at unit power
supply line start is open, blocked and provided with sign
First carry out the earth connection
Protect the cables using adequately sized cable glands
Before electrically powering the unit, ensure all protections QS1 main isolator
removed during electric connection are restored. AUX Customer connections terminal box
13
6 - ELECTRIC CONNECTIONS
14
6 - ELECTRIC CONNECTIONS
15
6 - ELECTRIC CONNECTIONS
Distance up to 700 mt
A user interface
B = B1 KNX bus, max 350 mt
twisted pair with shield, Ø 0,8 mm
EIB/KNX cable marking recommended
C power supply unit N125/11 5WG1 125-1AB11
C1 AC 120...230 V, 50...60 Hz
16
6 - ELECTRIC CONNECTIONS
ENC2: from 0 to 7
address of the units connected to the same port, max 8
Baudrate = 9600
Parity = none
Stop bit = 1
Address = 1 ~ 63
1 .. 15 1 .. F OFF OFF
16 .. 31 1 .. F ON OFF
32 .. 47 1 .. F OFF ON
48 .. 63 1 .. F ON ON
17
6 - ELECTRIC CONNECTIONS
green communication ok
yellow startup / channel not communicating
red communication down
A metal conduit
B metal septums
C metal-lined sheath (sleeve)
D unit
18
6 - ELECTRIC CONNECTIONS
LED BSP communication with AP1 module LED BSP communication with AP1 module
green communication ok green communication ok
yellow software ok but communication with AP1 yellow software ok but communication with AP1
down down
red flashing : software error red flashing : software error
fixed : hardware error fixed : hardware error
LED BUS communication with BACNET LED BUS communication with LONWORK
green ready for communication green communication ok
yellow startup yellow startup
red BACnet server down flashing: communicating not possible
restart after 3 sec. red communication down
19
7 - START-UP
unit powered by fixed network or by electrogen group treated air flow rate measurement
electric connections by customer supply, return and outdoor air temperature measurement
* only if present
20
7 - START-UP
The indicated operations must be carried out by qualified Check the unit is connected to the earth system. Check
technicians and specifically trained on the product. fastening of the conductors: the vibrations caused by handling
and transport may cause loosening.
Upon request, the after-sales assistance centres execute start-
up. Power the unit by closing the isolation device but leave in
OFF.
The electric, hydraulic connections and the other work of the
system are the responsibility of the installer. Check the network frequency and voltage values, that are
within the limits:
Agree the start-up date with the after-sales assistance centre
with sufficient advance 400/3/50 +/- 10%
Check the unbalancing of the phases:
7.4 Hydraulic circuit Operation outside the limits can entail irreversible damages.
21
7 - START-UP
22
7 - START-UP
In this operating mode, the supply air temperature (T_SA) can vary in accordance with the temperature of the air extracted from the
room (T_RA) and their deviation from the set value.
Therefore, there is feedback from the room.
In cooling mode the humidity control of the supply air is standard and a priority.
Type of adjustment
Main index \ Parameter machine \ Plant config
set P0032 X2Config = None (Main index \ Parameter machine \ configure machine)
set rated air flow rate P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config)
Variable air flow rate, CO2 probe connected to the X2 input:
set P0032 X2Config = CO2 (Main index \ Parameter machine \ configure machine)
set air flow rate with quality NOT met: P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config)
set air flow rate with quality met: P0004SetQAirCO2Ok (P0004<P0002) (Main index \ Parameter machine \ Plant config)
Constant supply pressure, pressure detector connected to the X2 input:
set P0032 X2Config = Supply (Main index \ Parameter machine \ configure machine)
set the supply pressure setpoint: P0003 SetPSupplyPlant (Main index \ Parameter machine \ Plant config)
Temperature setpoint
Set the values related to the SPR return air setpoint in relation to the T_OA external temperature:
(Main index \ Parameter machine \ plant config)
P0005 SetCool
P0006 SetHeat
P0008 MC_TExtCool
P0009 MC_TExtHeat
23
7 - START-UP
The T_SA supply setpoint is calculated in relation to the SPR return setpoint.
Set the values related to the T_SA supply air setpoint in relation to the T_RA return temperature:
Main index \ Parameter machine \ Thermoregulator
P0070 LimMinSupplyT
P0071 LimMaxSupplyT
P0072 MC_BandPr
P0073 MC_DeadBand
Humidity setpoint
Main index \ Parameter machine \ Plant config
set the specific supply humidity setpoint in cooling mode: P0017 SetXSA
set the specific return humidity setpoint in heating mode: P0018 SetXSR
Confirm configuration
Main index \ Parameter machine \ Plant config
24
7 - START-UP
with two fixed seasonal setpoints, for operation in cooling and heating mode
with two dynamic seasonal setpoints, in which the supply temperature is offset automatically in accordance with the external dry
bulb temperature T_OA, with climatic regulation.
There is no feedback from the room.
In cooling mode the humidity control of the supply air is standard and a priority.
Type of adjustment
Main index \ Parameter machine \ Plant config
set P0032 X2Config = None (Main index \ Parameter machine \ configure machine)
set rated air flow rate P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config)
Variable air flow rate, CO2 probe connected to the X2 input:
set P0032 X2Config = CO2 (Main index \ Parameter machine \ configure machine)
set air flow rate with quality NOT met: P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config)
set air flow rate with quality met: P0004SetQAirCO2Ok (P0004<P0002) (Main index \ Parameter machine \ Plant config)
Constant supply pressure, pressure detector connected to the X2 input:
set P0032 X2Config = Supply (Main index \ Parameter machine \ configure machine)
set the supply pressure setpoint: P0003 SetPSupplyPlant (Main index \ Parameter machine \ Plant config)
25
7 - START-UP
Temperature setpoint
Set the values related to the T_SA supply air setpoint in relation to the T_OA external temperature:
(Main index \ Parameter machine \ plant config)
P0005 SetCool
P0006 SetHeat
P0010 CS_TExtCool
P0011 CS_TExtHeat
Humidity setpoint
Main index \ Parameter machine \ Plant config
set the specific supply humidity setpoint in cooling mode: P0017 SetXSA
set the specific return humidity setpoint in heating mode: P0018 SetXSR
Confirm configuration
Main index \ Parameter machine \ Plant config
26
7 - START-UP
In this operating mode the external air T_OA is treated until it reaches the value of the supply air temperature T_SA).
There is no feedback from the room.
The humidity control of the supply air is running only in heating mode.
Type of adjustment
Main index \ Parameter machine \ Plant config
set P0032 X2Config = None (Main index \ Parameter machine \ configure machine)
set rated air flow rate P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config)
Variable air flow rate, CO2 probe connected to the X2 input:
set P0032 X2Config = CO2 (Main index \ Parameter machine \ configure machine)
set air flow rate with quality NOT met: P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config)
set air flow rate with quality met: P0004SetQAirCO2Ok (P0004<P0002) (Main index \ Parameter machine \ Plant
config)
Constant supply pressure, pressure detector connected to the X2 input:
set P0032 X2Config = Supply (Main index \ Parameter machine \ configure machine)
set the supply pressure setpoint: P0003 SetPSupplyPlant (Main index \ Parameter machine \ Plant config)
Temperature setpoint
Set the values related to the T_SA supply setpoint in relation to the T_OA external temperature:
(Main index \ Parameter machine \ Plant config)
P0014 HA_SetHeat
P0015 HA_TExtLg
27
7 - START-UP
Humidity setpoint
Main index \ Parameter machine \ Plant config
set the specific return humidity setpoint in heating mode: P0018 SetXSR
Confirm configuration
Main index \ Parameter machine \ Plant config
28
8 - CONTROL
change of status:
OFF, ON, FAN
Symbols
ON / OFF
OFF status. On the top field of the thermostat, the Humidifier / Dehumidifier mode
temperature and OFF indication are alternated The Humidifier mode is active
every 2 seconds. If flashing, it means the Dehumidifier mode is
When the status is OFF, changes to the active
SETPOINT and schedule are blocked.
29
8 - CONTROL
press
16.3 C°
the access by password is reserved to
qualified personnel, the parameters
17:00
changes can cause malfunctions.
COD
confirm 47
P1
1
confirm the new value
select
to enable the new value and exit ESC
30
8 - CONTROL
Press
16.3 C°
17:00
Code Description
1 Outdoor temperature
2 Supply temperature
31
8 - CONTROL
16.3 C° 16.3 C°
17:00 17:00
select to confirm
ESC
exit
Key-code table
16.3 C°
n. key key n. key key
17:00
T0 T5
T1 T6
T2 T7
T4
32
8 - CONTROL
press
only if the ALARM symbol is flashing 16.3 C°
17:00
press
007
7 days since the alarm was 17:00
triggered
17:00 alarm time
previous menu
ee
0030
scroll the alarms
33
8 - CONTROL
3
Time Event 1 2 Wedne-
4 5 6 7 12
Monday Tuesday Thursday Friday Saturday Sunday
sday
15:00 4 ON - ON ON - - -
press 1 3
18:00 5 ECO - ECO ECO - - -
The most recent schedule saved overrides the existing one. For 1 3 4 starts flashing
instance, if a day is included in two different schedules, the most
recent one saved prevails.
press 1 34
press
(ref. A)
-- starts flashing
000
--:--
1 34
set
- time of the event
000
05:--
press
1 34
34
8 - CONTROL
press 3
example: 5:30 o'clock unit in FAN mode
(3 stays steady)
(003)
press
003 7 starts flashing
press
05:30
to set altri the events 2,3,…..6
press
1 34
to confirm selected days 3 7
Ripeat from (ref. A)
press
press 3 times
starts flashing 003 (= FAN)
002
P flashing, active scheduling
press 13:00
P 3
16.3 C° set
- desired event 002 (= ON)
17:00
4
press
16.3 C°
17:00
35
8 - CONTROL
Function keys
Main menu
1/7
Confirm
Password
main menu
main menu
main menu
→ setpoint
36
8 - CONTROL
It is possible to set 6 events (Off, Eco, On, Recirculating) for Press 3 sec
each week day.
Scheduler must be enabled: HMI settings
display : actual value = On Select
Confirm
37
8 - CONTROL
8.11 ALARMS
1 Critico (A)
14.02.2012 11.30.10
select
EXECUTED
38
8 - CONTROL
ALARMS - Tab 1
ee006 PlantConfig Absence of a configuration of the type of unit operation upon starting
EE010 High Temp. Integration Protection of maximum temperature on the auxiliary heater
ee051 H2O freeze temp Heating water coil temperature probe fault
ee068 ExhaustPDiff 2nd Differential pressure trasducer exaust 2nd fan fault
ee069 Exhaust Fan 2nd Intervention of the protections of return / exaust 2nd fan
39
8 - CONTROL
ALARMS - Tab 2
ee201 Timoeout comm. Module circuit Control circuit board not responding
ee202 Timeout comm. Driver Expansion valve control board not responding
ff055 Room condition Heat mode Heat mode - room temperature too low (outside operating limits).
ff056 Outdoor condition Heat mode Heat mode - outdoor temperature too low (outside operating limits).
ff057 Room condition Cool mode Cool mode - room temperature too high (outside operating limits)
ff058 Outdoor condition Cool mode Cool mode - Outdoor temperature too high (outside operating limits)
40
8 - CONTROL
ALARMS - Tab 3
FF238 Alarm missing comunication inv1 - C2 Missing comunication compressor 1 inverter - circuit 2
FF241 Alarm missing comunication inv2 - C2 Missing comunication compressor 2 inverter - circuit 2
FF244 Alarm missing comunication inv3 - C2 Missing comunication compressor 3 inverter - circuit 2
41
8 - CONTROL
P.C. CONNECTION
9 confirm (OK)
15 Userid = WEB
16 Password = SBTAdmin!
42
9 - MAINTENANCE
□ presence corrosion
□ panel fixing
□ fans fixing
□ coil cleaning
□ outflow test
□ leaks control *
□ safety valves *
□ protective equipment test: pressure switches, thermostats, flow meters, etc.
□ protective equipment test: setpoint, climatic compensations, power slicing, air flow rate variations
□ control devices test: alarms signal, thermometers, probes, pressure gauges, etc.
43
9 - MAINTENANCE
reduce deterioration speed to which each equipment Operation with clogged filters leads to a reduction in the air
is subject in time flow rate with malfunctionings and block, up to possible breaks
in the unit.
collect information and data to understand the
The frequency with which the filters must be checked depends
efficiency state of the unit and prevent possible faults
on the quality of the outdoor air, the unit operation hours, the
dustiness and crowding of rooms.
9.3 Frequency of interventions Frequency can indicatively vary from WEEKLY to MONTHLY.
It is advised to start with frequent checks, subsequently
Frequency of the inspections must be at least six-monthly
adjusting frequency to degree of detected dirt.
However, frequency depends on the type of use.
1. Remove the closing panels
heavy (continuous or highly intermittent, near to 2. Delicately remove the filter avoiding dirtying the area
operation limits, etc.) below
critical (essential service). 3. Wash the filtering jacket in warm water with common
detergent
4. Accurately rinse in running water avoiding spilling in
9.4 Machine schedule the room
Foresee a machine schedule to keep trace of the 5. Dry the filter
interventions made on the unit. 6. Insert it back in its seat
In this way, it will be easier to adequately schedule the various 7. Remount the closing panels
interventions and facilitate any troubleshooting. Old filters, washing wastewater and residues must be
On the schedule note: disposed of according to the current standards.
date
description of intervention
9.5 Stand-by
If foreseen a long period of inactivity:
9.6 Structure
Check the state of the parts constituting the structure.
Treat those parts of the unit subject to oxidation, with paints
act at eliminating or reducing the oxidation phenomena.
Check fastening of the unit external panelling.
Bad fastening give rise to anomalous noises and vibrations.
44
9 - MAINTENANCE
9.8 Filtri elettronici - opzione Remove the pre-filter by lifting it of about 1 cm and remove it
as shown in figure.
750
750
310
45
9 - MAINTENANCE
46
9 - MAINTENANCE
9.11 Immerged electrodes humidifier- option check the seal gasket between the cylinder and the drain
unit
Do not use solvents or detergents to clean the plastic compo-
nents. remount the cylinder repeating the operations in reverse
order
For descaling use a vinegar or acetic acid solution at 20%,
subsequently rinsing with water
PERIODICAL CHECKS
Cylinder:
15
not over 300 hours of work
days
checking operation, general state, no leaks
Cylinder:
90 not over 1000 hours of work
days checking operation, general state, no leaks, any
replacement
Cylinder:
not over 2500 hours of work (disposable cylinders)
Load solenoid valve replacement: disconnect
electric power supply, dismantle valve, clean the
1 year drain solenoid valve filter:
disconnect electric power supply, remove reel and
dismantle valve body and any impurity and rinse
the power supply bowl, piping:
check they are free and without impurities
Cylinder:
not over 10000 hours of work (inspectional
5 years
cylinders)
replacement
47
10 - RESIDUE RISKS
Generality Carry out all work on the electric system with reference to the wiring
The most common situations, as they cannot be controlled by the diagram and this manual, assuring use of a dedicated system.
manufacturer, that may give rise to risk situations for things or persons An incorrect fastening of the lid of the electric components can favour
are found in this section. entry of dust, water, etc. inside and consequently cause electric shocks,
Dangerous area damages to the unit or fires.
It is the area in which only an authorised operator can act. The Always securely fasten the lid to the unit.
dangerous area is the area inside the unit, accessible only via removal of The metal masses of the unit, when powered and not correctly
the cowling or parts of it. connected to the earth system, can cause electric shocks or death for
Handling electrocution.
The handling operations, if carried out without all the necessary safety Carefully execute connection to the earth system.
devices and without the due caution, can cause the falling or overturning Contact with the accessible powered parts inside the unit after the
of the unit with consequent damages, even serious, to things, persons removal of guards can cause electric shocks, burns or death for
and the unit itself. electrocution.
Handle the unit following the instructions on the packaging, in this Open and padlock the main isolator before removing the guards and
manual and according to the local standards in force. signal the works in progress with relative sign.
In case of coolant gas leak, refer to the coolant "Safety sheet". Contact with parts that may power due to unit start-up, can cause electric
Installation shocks, burns or death for electrocution.
An incorrect installation of the unit can cause water leaks, condense When not necessary.
storage coolant leaks, electric shocks, fires, malfunctioning or damages Moving parts
to the unit itself. Contact with the transmissions or suction of the fans can cause injuries.
Check installation is carried out only by qualified technical personnel and Before accessing inside the unit, open the isolator on the unit connection
that the instructions in this manual and the local standards in force are line, padlock it and expose appropriate sign.
complied with. Contact with the fans can cause injuries.
The unit installation in a place where, even occasionally, the flammable Before removing the protective grilles or fans, open the isolator on the
gas leaks and consequent storage of these gases in the area around the unit connection line, padlock it and expose relative sign.
unit itself, can cause explosions and fires.
Coolant
Installation of the unit in an unsuitable place to support the weight and/or
The intervention of the safety valves and the consequent coolant gas
guarantee an adequate anchoring, can cause the falling and/or
expulsion can cause injuries and intoxication. Always wear adequate
overturning, with consequent damages to things, persons or the unit
clothing and protective goggles for operations inside the dangerous area.
itself.
In case of coolant gas leak, refer to the coolant "Safety sheet".
Carefully check positioning and anchoring of the unit.
Contact between naked flames or sources of heat with coolant, or the
The easy access to the unit by children, unauthorised persons or
heating of the pressurised gas circuit (e.g. during welding), can cause
animals, may give rise to accidents and injuries, even serious.
explosions or fires.
Install the unit in places accessible only by authorised personnel and/or
Do not place any source of heat inside the dangerous area.
foresee protections against intrusions in the dangerous area.
The maintenance or repair interventions requiring welding must be done
General risks
with system drained.
Burnt odour, smoke or other signs of serious anomalies may show the
Hydraulic part
arising of situations that can cause damages to things, persons or the
unit itself. Defects in the piping, in the connections or in the shut-off parts, can
cause water leaks or projections, with consequent damages to things or
Electrically isolate the unit (yellow-red isolator).
short circuits of the unit.
Contact the after-sales authorised assistance centre to identify and
resolve the problem at origin of the anomaly.
The accidental contact with exchange coils, compressors, supply piping
or other components can cause injuries and/or burns.
Always wear adequate clothing that includes protective gloves for
operations inside the dangerous area.
Maintenance and repair operations carried out by unqualified personnel
can cause damages to things, persons or the unit itself.
Always contact a qualified after-sales assistance centre.
The lack in closing the unit panels, or lack in checking the correct
fastening of all fastening screws of the panelling, can cause damages to
things, persons or the unit itself.
Periodically check closing of all panels and their correct fastening.
In the event of fire, the coolant temperature can reach values such to
bring the pressure over the safety value, with consequent possible
projection of coolant or explosions of the circuit that remain isolated from
closure of the cocks.
Do not stand near the safety valve and never leave the cooling system
cocks closed.
Electrical part
An incomplete connection line to the electric mains and/or with
incorrectly dimensioned cables, and/or with inadequate protective
equipment, can cause electric shocks, intoxication, damages to the unit
or fires.
48
11 - DISPOSAL
11.2 Dismantling
FOR DISMANTLING AND DISPOSING THE UNIT MUST
ALWAYS BE DELIVERED TO AUTHORISED CENTRES.
During dismantling, the fan, the motor and the coil, if working,
may be recovered by the specialised centres for an eventual
reuse.
All materials must be recovered or disposed or in compliance
with the relative national standards in force.
For further information on the dismissal of the unit, contact the
manufacturing company.
49
Page intentionally left blank
50
Page intentionally left blank
51
FOR OVER 30 YEARS, WE HAVE BEEN
OFFERING SOLUTIONS TO ENSURE
SUSTAINABLE COMFORT AND THE
WELL-BEING OF PEOPLE AND THE
ENVIRONMENT
M05G40L12-76– 23/01/2020
CLIVET SPA
Via Camp Lonc 25, Z.I. Villapaiera
32032 Feltre (BL) ‐ Italy
Tel. +39 0439 3131 ‐ Fax +39 0439 313300
[email protected]