E05-016 - How To Design System Grounding in Low Voltage Electrical Systems - US
E05-016 - How To Design System Grounding in Low Voltage Electrical Systems - US
P: (877) 322-5800
[email protected]
www.cedengineering.com
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
TABLE OF CONTENTS
TABLE OF CONTENTS................................................................................................................................ i
Fire .......................................................................................................................................................... 4
Implementation .................................................................................................................................... 11
Implementation .................................................................................................................................... 13
System grounding confronted with fire and electrical power unavailability hazards .......................... 18
Fire ........................................................................................................................................................ 18
Lightning................................................................................................................................................ 21
i
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
References ............................................................................................................................................ 33
LIST OF FIGURES
Figure 1. Time/current area of AC impact (15 Hz to 100 Hz) on people (defined as per IEC 60449-1) .. 3
Figure 2. Direct and indirect contacts ..................................................................................................... 5
Figure 3. Equi-potentiality inside a building ........................................................................................... 7
Figure 4. Connection arrangement of the neutral at the origin of the installation and of the frames of
the electrical loads .................................................................................................................................. 8
Figure 5. Example of the different system grounding arrangements included in the same LV
installation .............................................................................................................................................. 9
Figure 6. Fault current and voltage in TN grounding arrangement ...................................................... 10
Figure 7. Fault current and voltage in TT grounding arrangement....................................................... 12
Figure 8. First insulation fault current in IT grounded system .............................................................. 15
Figure 9. Second insulation fault current in IT grounding arrangement (distributed neutral) and
feeders with the same cross-section and length .................................................................................. 16
Figure 10. Electrical power availability ................................................................................................. 19
Figure 11. Short-circuit in a network supplied by a diesel standby generator ..................................... 21
Figure 12. Transmission of lighting over-voltages (regardless of the neutral point earthing method,
there are common over-voltages on phases) ....................................................................................... 22
Figure 13. Typical overhead public distribution.................................................................................... 24
Figure 14. RCD functional diagram ....................................................................................................... 26
ii
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
LIST OF TABLES
Table 1. Maximum safe contact voltage times ....................................................................................... 4
Table 2. Breaking time in TN grounded systems .................................................................................. 10
Table 3. Upper limit of the resistance of the frame ground connection not to be surpassed according
to RCD sensitivity and limit voltage ...................................................................................................... 13
Table 4. Maximum breaking times specified in IT grounding arrangement ......................................... 17
Table 5. System earthing characteristics .............................................................................................. 17
Table 6. Maximum resistance of the earth connection of the substation frames depending on the
network system grounding ................................................................................................................... 23
Table 7. LV circuit-breakers tripping current (magnetic or short time delay) ...................................... 25
Table 8. Typical fuse operating threshold limits ................................................................................... 26
Table 9. Circuit breakers according to system grounding..................................................................... 30
iii
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
The objective of these three grounding systems is identical regarding protection of people and
equipment - mastery of insulation fault effects. They are considered to be the same with
respect to safety of people against indirect contacts.
Nevertheless, the same is not necessarily correct for dependability of the low voltage
electrical installation with respect to:
- System availability; and
- Maintenance requirements.
Quantities that can be calculated are subject to increasing requirements in factories and
buildings. Also, the control and monitoring equipment in buildings (electrical power
distribution management systems) has an increasingly crucial role in management and
dependability. These developments in dependability requirements impact the selection and
design of system grounding. It needs to be kept in mind that the issue with service continuity
(keeping a sound network in public distribution by disconnecting consumers with insulation
faults) played a role when system grounding first emerged.
In order to provide staff protection and service continuity, conductors and live elements of
electrical installations are "insulated" from the frames connected to the ground. Insulation is
accomplished by:
- Applying insulating materials; and
- Distancing, which calls for clearances in gases (air, SF6) and creepage distances
(concerning switchgear, for example, an insulator flash over path).
Insulation is described by set voltages which, in line with standards, are applied to new
products and devices with:
1
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
When new equipment is manufactured as per adequate practices with products as specified in
standards, the risk of insulation faults is extremely low. Nevertheless, as the installation ages
this risk increases.
The installation is exposed to different aggressions which increase insulation faults. For
instance:
- During installation:
- Mechanical damage to an underground cable insulator
- During service:
- Conductive dust
- Insulator thermal ageing due to excessive temperature caused by too many cables in
a cable duct, a poorly ventilated cubicle, climate, current or voltage harmonics,
overcurrent, etc.
- The electro-dynamic forces created during a short-circuit which may damage a cable
or decrease a clearance
- The operating and lightning overvoltage
- The 60 Hz return overvoltage, created by an insulation fault in MV
Typically, it is a mix of these primary causes which creates the insulation fault. The latter is:
- Either of differential mode (between energized conductors) and becomes a short-circuit
- Or of common mode (between exposed conductors and frame or ground), a fault current
then flows in the protective conductor (PE).
- LV system grounding is mainly concerned by common mode faults which mainly occur in
loads and cables.
2
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
A person exposed to an electrical voltage is electrified. This person may suffer from:
- muscular contraction;
- discomfort;
- burn; or
- Cardiac arrest (this is Electrocution) .
500
1 2 3 4
100
20
mA
500
Threshold=30mA Current flowing through
the human body
Figure 1. Time/current area of AC impact (15 Hz to 100 Hz) on people (defined as per IEC 60449-1)
Zone 1: Perception
Zone 2: Considerable discomfort
Zone 3: Muscular contractions
Zone 4: Risk of cardiac arrest
3
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
Since the protection of people against electric current lethal effects is a priority, electric
shock is the first and most important hazard that needs to be assessed.
The current strength (expressed in amperes), flowing through the human body (especially the
heart) is the most dangerous and can be fatal. In LV systems, body impedance value (skin
resistance is one of the most important aspects of overall body impedance) changes according
to environment including dry and wet premises and damp premises.
A safety voltage is defined as the maximum acceptable contact voltage for at least 5s and has
been set at 50 V. In this case, there is a risk of contact voltage Uc surpassing 50 V voltage,
which implies that the application time of the voltage needs to be limited and shortened by
using different protection elements as presented in Table 1.
Fire
Once it occurs, fire can have serious consequences for both personnel and property.
Considerable number of fires are caused by localised temperature rises or an electric arc
created by an insulation fault. The danger increases as the fault current rises. It also depends
on the risk of fire or explosion that may happen in the premises.
4
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
This risk must be mastered in process industries, which are lengthy and costly to restart.
Also, if the fault current is high, it will can to:
- Damage that can be significant which increases repair costs and time; and
- Circulation of high fault currents in the common mode (between network and ground)
which may create problem for sensitive equipment, especially if these are part of a "low
current" system geographically distributed with galvanic links.
During de-energising, the occurrence of over-voltages and/or electromagnetic radiation
processes may lead to malfunctioning of sensitive devices.
UC
Id UC
5
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
Contact of personnel with accidentally energised metal frames is known as indirect contact
(as presented in Figure 2 (b)). Accidental energising is caused by an insulation fault. A fault
current travels and creates a potential rise between the frame and the ground, therefore
causing a fault voltage to appear which is dangerous, especially if it surpasses voltage UL.
Installation standards have provided an official status for three grounding methods and
defined the corresponding installation and protection practices. The protection actions against
indirect contacts are based on grounding of the frames of loads and electrical equipment in
order to prevent an insulation fault which actually represents a risk equivalent to direct
contact.
6
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
Individual
protective
conductors
(PE)
Main
Reinforcement
protective
meshing
conductor
Water
Ga
s
Heating
Measuring strip
7
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
3 3
N N
T
T
3 3
N N
N
I
Figure 4. Connection arrangement of the neutral at the origin of the installation and of the frames of the electrical loads
8
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
Figure 5.
3
N
PEN N N
PE PE PE
TN-C TN-S TT IT
Figure 5. Example of the different system grounding arrangements included in the same LV installation
TN grounding system
In the case of TN grounding arrangement, the fault current Id is only limited by the
impedance of the fault loop cables (as shown in the Figure 6):
𝑈0
𝐼𝑑 =
𝑅𝑝ℎ1 + 𝑅𝑑 + 𝑅𝑃𝐸
0.8𝑈0
𝐼𝑑 =
𝑅𝑝ℎ1 + 𝑅𝑃𝐸
Once a short-circuit happens, impedances upstream from the relevant feeder cause a voltage
drop of around 20 % on phase-to-neutral voltage Uo, which is the nominal voltage between
phase and ground.
9
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
A Id
N
D
PE
C B
Rd
Ud
0.8𝑈0
𝑈𝑑 ≈ 𝑖𝑓 𝑅𝑃𝐸 = 𝑅𝑝ℎ 𝑎𝑛𝑑 𝑅𝑑 = 0
2
𝑈0 0.8𝑈0
𝐼𝑑 = →
𝑅𝐴𝐵 + 𝑅𝑑 + 𝑅𝐶𝐷 𝑅𝑝ℎ + 𝑅𝑃𝐸
For LV networks, the voltage of around U0/2 (if RPE=Rph) is dangerous since it surpasses the
limit safety voltage, even in dry atmospheres (UL=50 V). The installation or part of the
installation must then be automatically and instantly disconnected, as shown in Table 2. Since
the insulation fault resembles a phase-neutral short-circuit, breaking is accomplished by the
Short-Circuit Protection Device (SCPD) with a maximum specified breaking time depending
on UL.
10
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
Implementation
To ensure that the protection device has been activated, the current Id must be higher than the
operating threshold of the protection device Ia (Id>Ia) irrespective of the fault location. This
condition must be checked at the installation design stage by assessing the fault currents for
all the distribution circuits.
If the same path is occupied by the protective conductor - PE- and the live conductors,
calculation will be simplified. To guarantee this situation, another approach consists in
defining a maximum impedance value on the fault loops according to the type and rating of
the selected SCPDs. This approach may result in increasing the cross-section of the live
and/or protective conductors. Another method of checking that the element will ensure
protection of personnel is to calculate the maximum length not to be surpassed by each feeder
for a given protection threshold Ia.
To determine Id and Lmax, three techniques can be applied:
- The impedance technique
- The composition technique
- The conventional technique
For the protection element to complete its function properly, Ia must be lower than Id.
Therefore, the expression of Lmax, the maximum length authorised by the protection device
with a threshold Ia is:
0.8𝑈0 𝑆𝑝ℎ
𝐿𝑚𝑎𝑥 =
𝜌(1 + 𝑚)𝐼𝑎
Where:
11
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
- For a fuse, current such that fuse total breaking time (prearcing time + arcing time)
complies with values presented in Table 2.
If the line is longer than Lmax, conductor cross-section must be increased. Alternatively, it
must be protected with a Residual Current Device (RCD).
TT grounding system
When an insulation fault happens, the fault current Id (shown in Figure 7) is limited by the
ground resistances if the ground connection of the frames and the ground connection of the
neutral are not associated. Assuming that Rd=0, the fault current is:
𝑈0
𝐼𝑑 ≈
𝑅𝑎 + 𝑅𝑏
Since ground resistances are typically low and of the same magnitude, voltage of the order of
U0/2 is dangerous. Therefore, the part of the installation affected by the fault must be
automatically disconnected (resistance of the frame earth connection is presented in Table 3).
Id
PE
Id=U0/(Ra+Rb)
Ud=U0Ra/(Ra+Rb)
Ud
Rb Ra
Figure 7. Fault current and voltage in TT grounding arrangement
12
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
Table 3. Upper limit of the resistance of the frame ground connection not to be surpassed according to RCD sensitivity and
limit voltage
Implementation
Since the fault current (beyond which a risk is present (Id=U0RaL)) is far lower than the
settings of the overcurrent protection devices, at least one RCD must be installed at the
supply end of the installation. In order to increase electrical power availability, application of
several RCDs ensures time and current discrimination on tripping. All these RCDs will have
a nominal current threshold lower than Id0.
De-energising by the RCDs must finish in less than 1 s. It is important to note that protection
by RCD does not depend on cable length and authorises several separate Ra ground
connections (which is an unsuitable measure since the PE is no longer a unique potential
reference for the entire installation).
IT grounding system
The neutral is unearthed, i.e. not connected to the ground. The frame’s ground connections
are typically interconnected (just like the TN and TT grounding arrangements).
- In normal service (without insulation fault), the network is grounded by the network leakage
impedance. Natural ground leakage impedance of a three phase 1 km long cable is
characterised by the typical values:
- C = 1 µF / km
- R = 1 MΩ/ km
which give (in 60 Hz):
- Zcf = 1 / j Cω= 2,652 Ω
- Zrf = Rf = 1 MΩ,
Hence, Zf ≈ Zcf = 2,652 Ω
In order to correctly set the potential of a network in IT grounding arrangement with respect
13
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
to the ground, it is suggested that impedance (Zn ≈ 1,500 Ω) between transformer neutral and
the ground is installed. If this is done, IT impedance-earthed system is formed.
1 1
= + 3𝑗𝐶𝑓𝜔
𝑍𝑒𝑒𝑞 𝑍𝑛
The corresponding fault voltage is still low and not dangerous. Installation can be kept in
service. Even though risk-free continuity of service is a huge benefit, it is mandatory:
- to know that fault exists
- to track it and clear it quickly, before a second fault happens
14
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
If
3
2
N 1
N
Surge PE
If If
limiter
Cf Cf Cf Cf
device
Rb
If
V1 V2 IC2
If ICN
V13 V23 IC1
V3
Figure 8. First insulation fault current in IT grounded system
15
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
0.8 U0
Id
3
2
N 1
N
PE
Id
RPE RPh RPE RPh
Ud Ud
Ra
Figure 9. Second insulation fault current in IT grounding arrangement (distributed neutral) and feeders with the same cross-
section and length
0.8 𝑈0 0.8𝑈0
𝐼𝑑 ≈ 𝑈𝑑 =
2(𝑅𝑃𝐸 + 𝑅𝑝ℎ ) 2
0.8𝑈0 √3
𝐼𝑎 ≤
2𝑍
In this case one of the two faults is on the neutral, the fault current and fault voltage are twice
as low as in the TN grounding arrangement. Due to this major manufacturers authorise longer
SCPD operation times (as shown in Table 4). Just as in the TN system grounding, protection
by SCPD is only applicable to maximum cable lengths:
- Distributed neutral:
1 0.8𝑈0 𝑆𝑝ℎ
𝐿𝑚𝑎𝑥 =
2 𝜌(1 + 𝑚)𝐼𝑎
- Non-distributed neutral:
16
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
√3 0.8𝑈0 𝑆𝑝ℎ
𝐿𝑚𝑎𝑥 =
2 𝜌(1 + 𝑚)𝐼𝑎
This is provided that the neutral is protected and its cross-section equal to phase cross-
section. Due to this certain standards advise against distributing the neutral.
-Situation where all frames are not interconnected. For frames grounded individually or in
groups, each circuit or group of circuits must be protected by a RCD.
In the case of an insulation fault in groups connected to two different grounding
arrangements, the protective device's reaction to the insulation fault (Id, Ud) is similar to that
of a TT system (the fault current flows through the ground). Therefore, protection of
personnel against indirect contacts is accomplished in the same way.
𝑈𝐿
𝐼𝛥𝑛 ≤
𝑅𝑎
Continuity of
Id Ud Lmax
operation
0.8𝑈0 𝑆𝑝ℎ 0.8𝑈0 0.8𝑈0 𝑆𝑝ℎ Vertical
TN
𝜌(1 + 𝑚)𝐿 1+𝑚 𝜌(1 + 𝑚)𝐼𝑎 discrimination
17
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
𝑈0 𝑈0 𝑅𝑎 Vertical
TT No constraint
𝑅𝑎 + 𝑅𝑏 𝑅𝑎 + 𝑅𝑏 discrimination
1st fault <1 A <<UL No tripping
Double
1 0.8𝑈0 𝑆𝑝ℎ 𝑚 0.8𝑈0 1 0.8𝑈0 𝑆𝑝ℎ Vertical
fault with
≤ ≤ discrimination
distributed 2 𝜌(1 + 𝑚)𝐿 2 1+𝑚 2 𝜌(1 + 𝑚)𝐼𝑎
and possibility
neutral
IT of horizontal
Double √3 0.8𝑈0 𝑆𝑝ℎ 𝑚√3 0.8𝑈0 √3 0.8𝑈0 𝑆𝑝ℎ
≤ ≤ discrimination
fault with 2 𝜌(1 + 𝑚)𝐿 2 1 + 𝑚 2 𝜌(1 + 𝑚)𝐼𝑎 to the
non-
advantage of
distributed
current feeders
neutral
PE cross-section that is typically equal to phase cross-section, can be half of phase cross-
section when the latter exceeds 35mm2.
Fire
It has been shown, that contact between a live conductor and a metal part can cause fire
especially in vulnerable areas. This can happen when current exceeds 300 mA. These areas
include:
- Premises with risk: Petrochemical factories, farms, etc.; and
- Premises with moderate risks, but where consequences may be extremely serious, e.g. very
high buildings.
In the unearthed neutral grounding arrangement, the risk of "fire":
- is very small on the first fault; and
- is as important as in TN on the second fault.
For the TT and TN grounding arrangements, the fault current is dangerous considering
developed power (P=RdI2):
- In TT = 5A < Id < 50 A
- In TN = 1 kA < Id < 100 kA
The power where the fault has happened is considerable, especially in the TN grounding
18
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
arrangement, and fast action is crucial in order to limit the dissipated energy (∫Rdi2dt).
Protection is provided by an instantaneous RCD with threshold of 300 mA, regardless of the
system earthing arrangement.
𝑀𝑈𝑇
𝐷=
𝑀𝐷𝑇 + 𝑀𝑈𝑇
Time
MUT – Mean Up Time – Mean failure De-enegising De-enegising De-enegising
on fault Restoration on fault Restoration on fault Restoration
free time of voltage of voltage of voltage
MDT – Mean Down Time (detection +
repair + resumption of operation) Failure status Operating status
Figure 10. Electrical power availability
Therefore, system grounding must be examined in terms of electrical power availability, with
special focus on the IT system earthing since it is the only one that authorises non-tripping in
the presence of a fault.
19
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
In order to keep the advantage of IT system earthing, i.e. not interrupting electrical
distribution on the first fault, the second fault must be prevented. Otherwise, it presents the
same high risks as the TN grounding system. Therefore, the first fault must be cleared before
a second fault happens. The use of efficient detection and locating techniques and availability
of a maintenance team considerably decreases the chances for the "double fault". Also,
monitoring devices are available and they monitor processes in insulation of the different
feeders, provide fault prediction and anticipate status of the fault.This ensures maximum
availability with the IT system earthing arrangement.
Note: In order to ensure continuity of operation, installation is equipped with a generator set
or a UPS (Uninterruptible Power Supply). In that case there is a risk of failure to operate or a
risk of delayed operation of the SCPDs. This happens during source changeover (lowest Isc as
shown in Figure 11). In TN and IT earthing arrangements, it is vital to verify that the
protection conditions are always met (operating time and threshold), particularly for very
long feeders. If this is not achieved, RCDs must be used.
20
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
Irms
Sub-transient Transient
state state
In
Generator with
≈0.3In serial
excitation
Occurrence 10 to 0.1 to
of fault 20ms 0.3 s
Figure 11. Short-circuit in a network supplied by a diesel standby generator
Lightning
In the case MV network consists of overhead lines, lightning arresters are installed to limit
the effects of a direct or an indirect lightning stroke. They are installed on the last pylon
before the MV/LV substation and they limit overvoltage and direct lightning current to earth.
However, a lightning wave is transmitted by capacitive effect between the transformer
windings, to the LV live conductors and can rise up to 10 kV. Even though it is progressively
21
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
weakened by the stray capacities of the network, it is suggested to install surge limiters
(lightning arresters) at the origin of the LV network, regardless of the used earthing system
(see Figure 12).
≤125kV ≤10kV
3
N
Short
connections
3 3
Figure 12. Transmission of lighting over-voltages (regardless of the neutral point earthing method, there are common over-
voltages on phases)
Operating over-voltages
Certain MV switchgear types (e.g. vacuum circuit-breakers) cause considerable over-voltages
when operated. Unlike lightning which is a common mode disturbance (between network and
ground), these over-voltages are, in LV, differential mode disturbances (between live
conductors). These disturbances are transmitted to the LV network by capacitive and
magnetic coupling. Just like all differential mode phenomena, operating over-voltages do not
interfere, or only very slightly, with any of the system grounding.
22
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
ground is separate from the substation one). Substation ground and LV neutral connections
are not generally connected. However, if they are, a limit is set to the common ground
connection value to prevent potential rise of the LV network. Typical earth connection values
are presented in Table 6.
Table 6. Maximum resistance of the earth connection of the substation frames depending on the network system grounding
impedance-earthed or
Ih (A) RPAB(Ω) unearthed in IT.
Z 300 3 to 20 IhMV: Maximum strength
1000 1 to 10 of the first earth single-
RPAB
phase fault current of the
high voltage network
Utp: Power frequency
withstand voltage of the
low voltage equipment
TTN or ITN (1)
of the substation.
IhMV (A) RPB(Ω) (1)The third letter of the
Z 300 3 system earthing means:
RPB
1000 1 - All the frames are
RA linked R
- The substation frame is
connected to the neutral
frame: N
- The earth connections
TTS or ITS (1)
Utp
2 4 10 are separated: S
(kV)
IhMV (A) RP(Ω) Note: No values
Z
300 4 8 20 stipulated but these
RP RB 1000 1 3 10 values prevent excessive
RA potential rise of the
assembly
The maximum value allowed for the ground connection resistance depends on the equi-
potentiality conditions of the frames of the LV network (its system grounding).
23
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
IhMVRPAB or IhMVRAB.
In the case this overvoltage surpasses the dielectric withstand of the LV network (in reality
the order of 1,500 V), LV disruptive breakdowns are possible if the equi-potentiality of all
the frames, electrical or not, of the building is not properly done or incomplete.
- In the case of the TT earthing system the load frames are at the potential of the deep ground.
Complete LV network is exposed to IhMVRPB or IhMVRB. There is a risk of disruptive
breakdown "by return" of loads if the voltage generated in RPB or RB surpasses their
dielectric capability.
- In the case of IT system grounding a discharger, short-circuits itself as soon as its arcing
voltage is reached. Consequently, it translates the problem to the level of the TN earthed
network (or TT network in the case there are several ground connections).
In any case, MV/LV disruptive faults can be severe, both for the LV installation and loads,
especially if LV neutral ground connection is not controlled.
N
Metering
Lightning arrester
RCD
≥30m
≥8m ≥8m
PE
Earth trip
24
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
TN grounding system
In TN grounding system the SCPDs (circuit-breaker or fuses) provide protection against
insulation faults, with automatic tripping according to a specified maximum breaking time.
- Circuit-breaker tripping happens at a level defined by the type of the tripping release (as
shown in Table 7).
As soon as the fault current surpasses the threshold of the short-circuit protection trip release
(typically "instantaneous"), opening starts in a time far shorter than defined maximum
breaking time, for example 5 s for distribution circuits and 0.4 s for terminal circuits. When
source and cable impedances are high, low threshold trip releases must be used.
Alternatively, RCDs associated with the SCPDs need to be installed. These RCDs may be
separate residual current elements or be combined with circuit-breakers (residual current
circuit breakers) of low sensitivity. Their threshold needs to be:
0.8𝑈0
𝐼𝛥𝑛 <
𝑅𝑝ℎ + 𝑅𝑝𝑒
25
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
shown in Table 8. Individual validation of the ratings provided for each protection element is
needed to check suitability of the maximum breaking time. If they are not suitable, fault loop
impedance must be decreased (increase cable cross-section). Alternatively, fuse must be
replaced with a low threshold or a residual current circuit-breaker.
Table 8. Typical fuse operating threshold limits
TT grounding system
With TT grounding system, the small value of the fault currents does not allow the SCPDs to
protect people against indirect contacts. RCDs need to be used in a combination with circuit-
breakers or switches. RCD functional diagram is shown in Figure 14.
Output
Time delay
Threshold
Shaping
𝐼Ԧ ≠ 0
IT grounding system
In the case of a double fault, people safety is provided by the SCPDs. When the first
insulation fault happens, the calculation proved there was no risk (contact voltage lower than
limit safety voltage). Therefore, automatic de-energising is mandatory. This is the main
benefit of this grounding system. To keep this advantage, standards suggest the application of
26
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
an Insulation Monitoring Device (IMD) and locating the first fault. In the case a second fault
happens, automatic breaking is important due to the electric shock risk. This is accomplished
by SCPDs backed up by the RCDs if needed. Locating the first fault for repairs is simplified
with the application of a Ground Fault Location Device (GFLD). Predictive maintenance,
based on the monitoring of changes in insulation impedance, is also done. LV networks that
use IT grounding system, which starts at a MV/ LV transformer, must be protected against
risks of insulation faults between MV and LV by installing a "surge limiter".
Finally, to fix the potential of the LV network with respect to the ground (short network
supplied by a MV/LV transformer), impedance can be installed between the transformer
neutral and the ground. Its value of approximately 1,500 Ω (60 Hz) is very high in DC and in
very low frequency so it does not obstruct insulation measurement and fault locating.
- IMD operating principle - A circuit fault results in a drop in insulation, or more precisely in
resistance of the network. Therefore, the purpose of the IMDs is to monitor resistance value.
Typically, they operate by injecting an AC or DC current between the network and the
ground and by measuring the value of this current (as shown in Figure 15).
N Insulation measuring
current (Rd)
Impedance (~100kΩ at
Z
60Hz; low in LF)
Threshold→time
delay→alarm
Measuring
LF current generator
PE
27
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
- GFLD operating method - The most typical approach is to inject an identifiable current
(with a frequency different from the network frequency). The generator can be the IMD.
Then, by means of magnetic current sensors (toroid transformers and/or clamp-on probe)
associated with an amplifier tuned to the injected current frequency, it is possible to trace its
path up to the fault (as shown in Figure 16 ). Alternative solution consists in comparing,
constantly and for each circuit, the value of its resistance with a pre-set or programmable
threshold value.
LF
generator
PE
PE
Figure 16. Locating insulation faults by tracing the path of a low frequency current injected at the installation origin
This approach enables the following actions, both locally and remotely:
- First fault reporting (IMD)
- Locating of this fault (GFLD) in order to fix it (curative maintenance) (as shown in
Figure 17)
- Information about insulation evolution in time, feeder by feeder, to take corrective
action on feeders with abnormal insulation drops (predictive maintenance)
-Surge limiters are connected between a live conductor (neutral or phase) and the ground.
Therefore, their arcing voltage Ue must be adapted to the assembly.
28
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
PE
PE
Figure 17. GFLD operating principle with low frequency impedance measurement
29
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
Table 9 indicates which circuit-breaker types should be used for certain grounding
arrangements. Note that TT and TN grounding arrangements can use the same devices (with
an additional residual current module in TT).
Circuits Diagrams
TN- TN- TT IT
C S
Single phase circuits
Single phase circuits with one protected pole
I>
N No Yes Yes No
Two pole circuit breaker (1-protected pole 2-de-energized
poles)
Phase to neutral circuits with two protected poles
I>
No Yes Yes Yes
N I>
Two pole circuit breaker (with two protected poles)
Three phase circuits without neutral
With three pole protection
1 I>
2 I>
No Yes Yes No
3 I>
N
Four pole circuit breaker with three protected poles
1 I>
30
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
1 I>
31
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
implement and which minimises damage with respect to the TN. The installation of an
additional output is easily accomplished without the necessity of further calculations.
- Continuity of service not vital: it is preferred to use the TN-S (quick repairs and
extensions done according to rules)
- Continuity of service not essential and no maintenance service: Prefer the TT
grounding system
- Fire hazard: IT grounding system if maintenance service and use of
0.5 A RCD or TT grounding system
- Finally, here are the special characteristics of network and loads:
- Very long network or, even more important, leakage current: it is preferred to use
the TN-S grounding system
- Use of replacement or standby power supplies: it is preferred to use the TT
grounding system
- Loads sensitive to high fault currents (motors): it is preferred to use the TT or IT
grounding system
- Loads with low natural insulation (furnaces) or with large HF filter (large
computers): it is preferred to use the TN-S grounding system
- Supply of control and monitoring systems: it is preferred to use the IT grounding
system (continuity of service) or the TT grounding system (enhanced equi-potentiality
of communicating devices)
Since there is no ideal choice with single system grounding, it is suggested to implement
several system grounding techniques in the same installation.
32
How to Design System Grounding in Low Voltage Electrical Systems – E05-016
References
33