Adex TXR Test Guide
Adex TXR Test Guide
The test 05
Glossary 07
Routine tests
Special tests
Quality system
All Adex-transfo transformers are manufactured in accor-
dance with a procedural quality system certified to be in con-
formity with international standard ISO 9001.
03
Definition
A static electrical energy transducer intended to transform an alternat-
ing current system into one or several alternating current systems of
the same frequency, but generally of different current and voltage.
The transformer receives a primary current I1 at a primary voltage U1,
and transforms it to a secondary current 12, different from the primary
current, at a secondary voltage U2.
O operating principle
"A winding subject to a variable flux, generated by a variable voltage
via cross section of a given magnetic core, induces an electromotive
force across its terminals proportional to the number of turns in the
winding".
This electromotive force determines the voltage across the terminals
of the transformer according to the Boucherot equation :
U = 4,44 Bmax x N x S x f
with U = Voltage across the terminals of the primary or secondary winding
Bmax = the maximum value of the magnetic field in the magnetic core
N = the number of turns in the primary or secondary winding
S = magnetic core cross-sectional area
f = supply frequency of the transformer expressed in Hertz
i1 R1 L1 i2 R2 L2
k
U1 (RF) LF U2
(supply) (output)
i1 R1+R2 k2 L1+L2 k2 i2
k
U1 (RF) LF U2
(supply) (output)
U1 N1 I2
k= = =
U2 N2 I1
II
III
III II III II
I I I
II II II
III III III
The connection of the highest voltage (MV) is in upper case and that
of the lowest voltage in lower case (LV). If there is a neutral terminal,
we have : YN or yn,
ZN or zn
The clock-hour index allows us to express the phase displacement, al
a multiple of 30°, between the MV winding and the LV winding.
E.g. : Dyn 11 = Delta connected MV (D) and star connected LV (y)
with a neutral output. The clock-hour index shows a phase displace-
ment of 30o between the MV and LV voltage vectors in an anti-
clockwise direction.
O Adex-transfo windings :
The technologies used in the copper or aluminium windings give the
transformer its short-circuit strength in accordance with current
standards. In addition :
- autoclave vacuum drying eliminates all traced of humidity from the
active part of the winding
- vacuum filling impregnates the windings and eliminates any air
from the tank.
These two procedures give the transformer excellent performance
levels (lightning impulse withstand).
05
O dielectric liquids :
The most commonly used dielectric liquids at Adex-transfo are of
mineral oil type (O1). The PCB1), and FCBT2) contents are guaran-
teed to be less than or equal to the minimum limit for measurement
of 2 ppm (parts per million)
1) (Polychloro Biphenyls contained in Askarels)
2) (Polychloro Benzyl Toluenes, contained in Ugilec)Transformers are
Visitors may only enter these areas under the supervision of autho-
rised testing department personnel, after having first been informed
of the inherent dangers in the installation, when no test sequence is
taking place.
06
Glossary
Reference Symbols Units
1) Rating plate
Rated power Sn Volt Ampere (VA) or kilo Volt Ampere (kVA) or
Mega Volt Ampere (MVA)
Rated frequency Fn Hertz or kilo Hertz (Hz or kHz)
High voltage MV kilo Volt (kV)
Low voltage LV Volt or kilo Volt (V or kV)
Temperature °C degrees Celsius (°C)
Temperature rise K Kelvin
No-load losses Po Watt or kilo Watt (W or kW)
Load losses Pcc Watt or kilo Watt (W or kW)
No-load current lo Ampere (A)
Rated current IN Ampere (A)
Short circuit current Icc Ampere (A)
Impedance voltage Ucc Volt (V)
Power factor Cosϕ percentage (%)
Magnetic field B Tesla (T)
Number of turns N
2) Routine tests
• Measurement of no-load losses
Corrected no-load losses Po Watt (VV)
First wattmeter reading dW1 Watt (W)
Second wattmeter reading dW2 Watt (VV)
Constant Cte
Power correction k Watt (VV)
Approximation ∆ percentage (%)
• Measurement of load losses
Currents in the 3 windings I1, I2, I3 Ampere (A)
Measured power Pmeas Watt (W)
Special losses = additional losses Ps Watt (W)
• Resistance of windings
Resistance of MV and LV RMV, RLV ohm (Ω)
Joules losses ΣRI2 Watt (W)
3) Type tests
• Temperature rise tests
Total losses Pt Watt (W)
Average current lave Ampere (A)
Ambient temperature T°amb °Celsius (°C)
• Lightning impulse tests
Sweep time microsecond (*s)
4) Special tests
• Partial discharge level measurement
Transformer voltage class Um Kilo Volt (kV)
Apparent charge q pico Coulomb (pC)
• Noise level measurement
Background noise decibel (dB)
Weighted (A) acoustic pressure level Lp (A) decibel (A)
Weighted (A) acoustic power level Lw (A) decibel (A)
07
Induced Voltage dielectric test
Induced over voltage test
The standard
This standard is taken from IEC standard 60076-3 (1980)
Definitions
Test description
The type of induced voltage test used, depends on the type of trans-
former winding.
When the test frequency exceeds twice the rated frequency, the test
duration should be:
09
Applied voltage dielectric test
Special source power transformer test
The standard
This summary of the test standard is taken from the IEC publication
on dielectric testing IEC 60076-3 (1988)
Definition
Applied voltage : this is the single phase voltage that is applied to
one of a transformer's windings, whilst the others are earthed.
The full test voltage must be applied for 60 seconds between the
winding under test and all the terminals of the other windings, the
magnetic core, the frame and the tank or enclosure of the trans-
former, connected together to earth.
o 1.1 3
3.6 10
7.2 20
12.0 28
17.5 38
24.0 50
36.0 70
10
Test objective Test rig diagram
Testing the dielectric strength of the trans-
former (insulating properties of the oil and the
windings) at the power frequency (50 Hz), and
that of the winding relative to both earth and to
the other windings. V
R1 L1 R2 L2
(RF)
Voltage transformer
U1 tank
11
Measurement of no load losses and
no load current
The standard
This measurement procedure is described in standard IEC 60076-1
(1993)
All the values measured during this test are expressed for the princi-
pal tapping unless otherwise specified by the customer, with the
transformer initially at ambient temperature.
Definitions
O no load losses: this is the active power absorbed by the trans-
former when the rated voltage at the rated frequency is applied to
the terminals of one of the windings with the other windings open-
circuited
O no load current: this is the effective value of current required to
magnetise the magnetic core.
Test description
Tolerances
Values Tolerances
1. No load losses +15% of the declared
values on condition that
tolerances on total losses
are complied with
2. No load current +30% of the value declared
by the manufacturer
3.Total losses (Po + Pcc) +10% of the declared
values
12
Test objective Phase 1 I1
0 1200 V TI1 a A
- Characterising the no load losses and no load V
KI1
k V
n
Test rig contol desk Transformer being
tested e.g. Dyn 11
R1 L1 R2 L2
k
13
Measurement of the resistance of
MV and LV windings
The standard
The following details are taken from IEC standard 60076-1 (1993)
Definition
MV and LV resistances are internal transformer resistances from the
MV and LV sides that generate Joule losses proportionally to the
square of the current.
Test description
The resistance of each winding is measured and the temperature is
recorded ; the test is performed with direct current.
The effects of self-induction must be reduced to a minimum in all
resistance measurements.
For oil immersed transformers, the test starts once the transformer's
dielectric fluid has been left to rest ; the average oil temperature is
then determined by considering it to be equal to that of the winding.
14
Test objective A
R3 R1
To measure the resistance in ohms of each of R4
the windings of the transformer. Trans- G
6V
Theses resistances are shown within the dotted former
terminals
R5
lines in the following diagram: RT R2
with
if R1 = R4 and R2 = R5
15
Measurement of the impedance voltage and load
losses
The standard
This measurement procedure is described in IEC standard 60076-1 (1993)
Definitions
O The impedance voltage : is the voltage that must be applied to the line terminals of a winding
in order to give the rated current when the terminals of the other windings are short-circuited.
It is given in percentage of the rated voltage.
O Load losses : these correspond to the absorbed active power (ings, if there are any are open-
circuited. These losses are also called short-circuit losses (= Joule losses + special losses)
Test description
Impedance voltages and load losses must be measured with a supply current of at least 50% of
the tapping's rated current.
The measured value of these losses must be multiplied by the square of the ratio between the
rated current of the tapping and the current used for the test.
The measurement must be made quickly to avoid temperature rises introducing any significant
errors ; the temperature difference of the oil from top to bottom must be sufficiently low to
enable determination of the average temperature with the required accuracy.
For transformers with a tapped winding whose tapping range is greater than +/-5%, the imped-
ance voltage must be measured across the principal tapping and the two end tappings.
Tolerances
Tolerances are taken from the standard, unless otherwise specified by the customer.
Values Tolerances
1. b) Partial losses: ± 15 % of each of the partial
(No-load or load losses) losses, on a condition that the tolerance on
the total losses is complied with (+10 %
of the declared values)
3. Short circuit voltage ± 7.5 % of the value declared by
a) on the principal tapping the manufacturer if the impedance
voltage value (Ucc) is M 10%
± 10 % of the value declared by the
manufacturer if Ucc is <10%
b) on the other tappings ± 10% of the value declared by the
manufacturer if Ucc is M10%
± 15 % of the value declared by
the manufacturer if Ucc is <10%
16
Test objective Calculation of load losses
- Measurement of the transformer’s load losses (Pcc) - at ambient temperature (20oC on average)
- Measurement of the impedance voltage (Ucc)
Pcc = PjoulesMV + PjoulesLV + Pspecial
Equivalent circuit: = [(3/2) x RMVx I2] + [ (3/2) x RLV x I2] + Pspecial
A A W
Phase 3
C c
0 1200 V
A A
Neutral
n
Test rig contol desk Transformer being
tested e.g. Dyn 11
17
Measurement of the impedance voltage
and load losses (cont.)
The standard
O Standard values for impedance voltage in Europe, according to harmonisa-tion
document H 428.S1.
50 m Sn m 630 4
630 m Sn m 2500 6
In accordance with IEC publication 76-5 (1982), the impedance voltage applied
to a tested transformer is deduced from the following table :
Sn m 630 4
630 < Sn m 1250 5
1250 < Sn m 3150 6.25
3150 < Sn m 6300 7.15
18
The impedance voltage Ucc
The impedance voltage comprises a reactive
component, Ux, and Ur, which unlike Ux is
dependent on temperature.
Uc
c 75
(Ucc%)2 = (Ux%)2 + (Ur%)2 Ux
Uc
oC
cT
o am
with Ur% = (Pcc x 100) / Sn
Ucc% = (Ucc x 100) / Un
b.
Ur To amb. Ur 75oC
E.g. : at ambient temperature of 20oC , and at a
reference temperature of 75oC, we have, always
given in percentage:
(Ucc75oC)2 - (Ur75oC)2
= (Ucc20oC)2 - (Ur20oC)2
( ) ( ) ( )
Ucc75oC =100 x E Ucc20oC 2 - Pcc20oC 2 + Pcc75oC 2
Un Sn Sn
19
Measurement of the transformation
ratio and verification of the vector
group
The standard
The following information is taken from IEC standard 60076-1
(1993)
Definitions
O phase displacement in a three phase winding: this is the
phase angle between the vectors representing the MV and LV volt-
ages across the corresponding terminals of a pair of windings.
The vectors are considered to turn counter-clockwise.
The vector of the MV winding, which 1st phase is oriented at 12
o'clock on the clock face, is used as a reference, and the phase
displacement between all the other win-dings is usually expressed
relative to this using a clock-hour figure.
Description of measurements
The transformation ratio is measured on each transformer tapping.
The vector group of three phase transformers, as well as the polarity
of single phase transformers must be checked.
Tolerances
Values Tolerances
b) ± 10 % of the real
percentage of the impedance
voltage
20
Test objectives The calculations
- To check the conformity of the transformer Calculation of the rated transformation ratio for
connection arrangement with that stated each tapping :
- To check the conformity of the transformation This ratio is only valid for the same reference
ratio, k, on each tapping compared with the voltage.
guaranteed values.
Example :
The part of the transformer studied during this Simple or complex ratios of MV/LV voltages
test lies within the dotted line on the following
diagram : To obtain the rated transformation ratio for Yd
or Dy connections, the values must be multi-
k
R1 L1 R2 L2 plied or divided by E3 depending on whether
U1 (RF) U2 the voltages measured are simple or complex.
For Yy or Dd connections, the rated transforma-
U1
tion ratio is not modified.
ex : k = = 50
U2
Test procedure
Usual connections
The vector group is checked and the trans-
former ratio is measured on each tapping with a The most common connections in Europe are :
voltage of 110 or 220 V applied on the MV side.
b C c B
n
E
D
c
n
for f = 50 x 4 = 200 Hz
the PD level in dB at 200 Hz
= 6 dB + PD level at 50 Hz
23
Measurement of sound level
The standard
The test procedure is described in IEC standard 551 (1987)
Definitions
- the sound pressure level, Lp : this is the value expressed in decibels (dB), equal
to 20 times the decimal logarithm of the given acoustic pressure and the refer-
ence acoustic pressure; the reference acoustic pressure being 20 µPascals.
- the sound power level, Lw: this value is expressed in dB, equal to 10 times the
decimal logarithm of the ration of the given acoustic power being 1 picoWatt.
- the ambient noise level: this is the weighted level (A) of the acoustic pressure
when the transformer is de-energised.
Measuring devices
Measurements must be performed using a class 1 sound level meter. In addition,
the background noise level must be measured immediately before and after the
measurement is performed on the transformer.
If the difference between the Lp of the background noise and the sum of the levels
resulting from the background noise and the transformer is M 10 dB, the back-
ground noise levels may only be measured from one measurement position with-
out it being necessary to apply any correction to the noise level measured for the
device.
It the difference is between 3 and 10 dB, the corrections in the table below must
be applied.
Moreover, if the difference is less than 3 dB the test will not be accepted unless the
level resulting from the background noise and the noise of the transformer are less
than the guaranteed values.
Should this be the case, a lower value will be taken for this difference and a total
level reduced by 3 dB could be considered as the upper limit of the acoustic pres-
sure level in this position.
3 3
4 or 5 2
6 or 8 1
9 or 10 0.5
24
Test objective O in terms of the device's (A) weighted sound
power level, Lw, calculated from the sound
Comparing the noise generated by the trans- pressure using the following equation
former with that set in the standard.
Lw (A) = Lp (A) + 10 log S - X
Test procedure
Lw (A) = the weighted acoustic power level in dB (A)
The noise is caused by magnetostriction of the Lp (A) = the sound pressure in dB (A)
X = correction for background noise (see previous page)
core, the reactors and their associated cooling S = the equivalent surface area in m2, defined by the
devices. equation: S= 1.25 x H x P
with H = the transformer height in metres
Once the background noise has been measured, P = the length of the measuring perimeter at a distance
of max. 30 cm, in meters
power is supplied to the transformer under no 1.25 = empirical factor designed to take account of the
load, at the rated voltage and frequency, with acoustic energy radiated by the top of the
the tapping selector on the principal tapping. transformer or the coolers.
0.3 m mini
6 measuring prescribed
points mini contour
1 m maxi
Layout of measuring points