Stock # : 560247 SPEC 46311

AL Compact 15kV NLEPR Insulation 133% IL Black SIM-PVC Jacket.


MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial
Type MV-105 Single Conductor Aluminum, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level,
Tape Shield, SIMpull Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA.

Image not to scale. See Table 1 for dimensions.

CONSTRUCTION:
1. Conductor: Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
2. Conductor Shield: Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or
equal to 500 Kcmil
3. Insulation: 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level,
4. Insulation Shield: Strippable semi-conducting cross-linked copolymer
5. Copper Tape Shield: Helically wrapped 5 mil copper tape with 25% overlap
6. Overall Jacket: Polyvinyl Chloride (PVC)

APPLICATIONS AND FEATURES:


Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed
with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior
electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in
excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C
for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual
UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in
conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

SPECIFICATIONS:
• ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
• ASTM B836 Compact Rounded Stranded Aluminum Conductors
• UL 1072 Medium-Voltage Power Cables
• UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
• CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
• CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
• CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
• ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
• ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
• IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
• AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test
Requirements)

Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com


Copyright © 2024 Southwire Company, LLC. All Rights Reserved UPDATED: 11 de Diciembre de 2023 a las 21:29UTC REVISION: 1.000.001
Stock # : 560247 SPEC 46311
• Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and
the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

SAMPLE PRINT LEGEND:


SOUTHWIRE [SYMBOL - LIGHTING BOLT] #P# (UL/CSA) 1/C [#AWG or #kcmil] AL 220 MILS NL-EPR 15KV 133% INS LEVEL
25% TS MV-105 FOR CT USE SUN. RES. TC-ER(CSA 1/0 LARGER) FOR DIRECT BURIAL FT4 - YEAR (NESC) [SEQUENTIAL FEET
MARKS]

Table 1 – Weights and Measurements


Stock Cond. Strand Diameter Diameter Diameter Over Jacket Approx. Copper Approx. Max Pull Min Conduit
Number Size Count Over Over Insulation Thickness OD Weight Weight Tension Bending Size*
Conductor Insulation Shield Radius
AWG/ No. of inch inch inch mil inch lb/1000ft lb/1000ft lb inch inch
Kcmil Strands
560247 250 22 0.520 1.006 1.066 80 1.246 86 839 1500 14.9 3.5
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM

Table 2 – Electrical and Engineering Data


DC AC Capacitive Inductive Zero Positive Shield Short Allowable Allowable
Cond. Resistance @ Resistance @ Reactance @ Reactance @ Sequence Sequence Circuit Ampacity In Ampacity In Air
Size 25°C 90°C 60Hz 60Hz Impedance Impedance Current 6 Duct 90/105°C 90/105°C
Cycles
AWG/ Ω/1000ft Ω/1000ft MΩ*1000ft Ω/1000ft Ω/1000ft Ω/1000ft Amp Amp Amp
Kcmil
250 0.071 0.090 0.034 0.042 0.447 + j0.321 0.091 + j0.04 3333 250/270 345/385
* Ampacities are based on:
* For Duct: Table 310.60(C)(78) Detail 1.
* For Free Air: Table 310.60(C)(70).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
* Capacitive Reactance is between Phase-to-Shield.