CTOReport ISX0002337300-0004 UPS

This document is a CTO report for a DC power solution containing details about the design, UPS, batteries, services, and accessories. The solution contains Galaxy VL UPS systems in a parallel redundant configuration with lithium-ion battery cabinets to provide over 15 minutes of backup power.

Uploaded by

goldin1936
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views3 pages

CTOReport ISX0002337300-0004 UPS

This document is a CTO report for a DC power solution containing details about the design, UPS, batteries, services, and accessories. The solution contains Galaxy VL UPS systems in a parallel redundant configuration with lithium-ion battery cabinets to provide over 15 minutes of backup power.

Uploaded by

goldin1936
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

CTO Report

Solution Name : DC_DataPower_UPS_My Solution 2337300


Solution Number : ISX0002337300-0004
Design Name : Design 1
Status : Open
Opportunity # : OP-231214-13840162
BOM Type : 3P GVL

Design Notes for Design 1 :


1. BOM has been modified manually after Design/Configuration Save
2. No standard Parallel Maintenance Bypass is available to meet the requirements! The solution contains one or more Parallel-capacity
UPS systems (N) or Parallel-redundant UPS systems (N+1) which requires a Custom Parallel Maintenance Bypass Panel. Please work
with your Schneider Electric contact.
3. The solution contains Galaxy VL. A review by a Schneider Electric certified solution approver is required after the solution is
submitted for approval.
4. Battery runtime is based on specified conditions at 25 °C (77 °F) ambient temperature and +/- 10% of the resultant runtime.

* *If a report extends to more than one page, there is a possibility of a SKU getting displayed more than once. This is to enhance user
readability.

Details

Design Name: Design 1


Type: 3-Phase UPS Configurator

SKU Type Quantity Item Description

PTO 2 GVL200K500DS Galaxy VL UPS 200 scalable to 500kW, 400/480V, Start-up 5x8

FG 1 GVSOPT006 Parallel Communications Kit for Galaxy VS/VL

PTO 4 LIBSESMG16UL Galaxy Lithium-ion Battery Cabinet UL with 16 x 2.04 kWh battery modules

NOTES:
*= Unreleased part number or the part number is being phased out. Please see the Part Number Status report for details of all the
SKUs in this solution. Each Design in Solution is Approved Independently.

Page 1 of 3
System Name - System 1

Model : null
Description : Galaxy VL UPS 200 scalable to 500kW, 400/480V, Start-up 5x8

Technical Specification

UPS Details

Number of UPS : 2
UPS Configuration Type : Parallel redundancy UPS system (N+1)
UPS Input and Output voltage : 480 V Input,480 V Output
Load Power Factor : 1.0

Battery Details

Battery Solution : Lithium-Ion Batteries


Strings per UPS : 2
Number of blocks per string : 40
Technology : Li-ion
Requested Battery runtime (minutes)
: 15
Actual Battery runtime (minutes) at
200.0 kW Unit load: 17.5
Actual Battery runtime (minutes) at
200 kW Unit load
(Load Power Factor 1.0 and 100 %
Load) 17.5
DC Load : 209000 Watts

UPS

Qty Part Number Description

2 GVL200K500DS Galaxy VL UPS 200 scalable to 500kW, 400/480V, Start-up 5x8

Batteries

Qty Part Number Description

4 LIBSESMG16UL Galaxy Li-Ion Battery Cabinet UL with 16 x 2.04 kWh battery modules

Services

Qty Part Number Description

1 WSTRTUP-LB-04 (1) Startup Service for (4) Cabinets Li-Ion Battery solution

Accessories

Qty Part Number Description

1 GVSOPT006 Parallel Communications Kit for Galaxy VS/VL