Switches &MODs
Switches &MODs
Disconnect switches
Allow disconnection of major substation equipment
o Transformers
o Circuit breakers
o Lines & Busses
Allow for maintenance and testing
Provide a physical and visual disconnect to ensure separation of energized equipment
from de-energized equipment
Switch types
Single phase – switch connected to bus by insulators, connection broken by pulling on
ring at the top connection with an insulated hook stick.
Three phase – Gang or group operated switch, three switches simultaneously operated
by a single mechanism (handle or crank)
Motor operated switch – 3 phase simultaneous disconnect powered by the operation of
a motor.
Voltage Rating
Nominal rated voltage
o The voltage value that the system will typically operate at. The switch will be
able to withstand this voltage level continuously.
Preferred Ratings
o IEEE standard C37.32 specifies the preferred voltages levels for switch
construction.
o These KV ratings are as follows; 8.3, 15.5, 27, 38, 48.3, 72.5, 123, 145, 170, 245,
362, 550, 800.
o A switch constructed at a specific rating will withstand all operating voltages
below that rating. This allows utilities that have unique operating voltages to
select a switch from an existing standard selection as opposed to having a costly
custom switch constructed.
Impulse voltage
o This is the rating of the switches capability to withstand a voltage much higher
than the nominal voltage. Referred to as BIL, basic impulse level or basic
insulation level.
o 3-10 times the rated nominal voltage, duration is very small in the order of
milliseconds.
o Can be caused by lightning, switching or fault.
o Opening and closing of switches develops a large voltage stress across the switch
and its insulators.
o The BIL indicates the strength of the insulation during voltage surges caused
from high voltage events.
o As the nominal voltage increases the insulation level, BIL, should be increased as
well. A higher nominal voltage will also have higher voltage surges.
o Higher insulation levels will increase the reliability of the equipment while also
increasing cost. This is a trade-off that engineers must contend with when sizing
equipment.
o Inside of the substation, all equipment operating at the same nominal voltage
will need to have the same BIL, this is an intuitive concept as a specific nominal
voltage will necessitate a certain BIL.
o BIL requirements can also be found in IEEE C37.32. In this standard BIL is
referred to as “Lightning Impulse”.
o When referencing the high voltage levels on IEEE C37.32, you can see there is
more than one BIL. This is due to cost differences in insulation and
improvements in surge arrestor technologies that have developed over time.
Current Ratings
Continuous
o Load current rating
o Standard ratings; 600, 1200, 1600, 2000, 3000, 4000, 5000, 6000. These values
pulled from IEEE standard
Short time (1 to 3 seconds)
o Fault current rating
o Required so that contacts do not heat up weld themselves closed during high
current faults
Peak (10 cycles)
o Fault current rating
o Required so that magnetic forces do not cause the switch to mis-operate.
o Most important rating, required so the switch does not open unintentionally
during fault conditions as this can cause another fault that may switch the entire
substation out of service.
o Design features that address mis-operation.
Spring loaded contacts: springs load the contact with a constant force dis-
allowing unwanted contact movement.
Current Interruption
A switch must have additional hardware for it to be able to safely break load current.
They are used to prevent arching damage to the main contacts of the switch during
current interruption.
These types of hardware include;
o Arching Horns – this is the simplest form of current interruption on a disconnect
switch. It consists of a horn on the stationary contacts of the switch that makes
contact to the horn attached to the blade as the switch opens. Load is carried by
the contacts of the switch during typical operation, once the switch commences
an open cycle the horns then make contact as the switch contacts separate. At
that time, load is transferred to the horns. This type of interruption can break
the magnetizing current of small transformers, as well as charging current on
small transmission lines and substation busses.
o Aching whips – A tapered this rod that has a high elasticity attached to the blade
fits into a latch on the stationary contact of the switch. As the switch opens the
rod/whip is latched to the stationary contact until the blade clear the contact.
Then the latch releases and the whip will deflect back toward the blade causing
an arc that will dissipate as distance between the whip and the contact
increases. These can break magnetizing current on medium sized transformers,
as well as bus and medium distance line charging currents.
o Vacuum and SF6 interrupters – as the switch opens, the blade swings away from
the stationary contacts and creates a circuit through contact with the actuating
arm of the interrupter. This circuit is maintained until the blade is clear of the
stationary contacts. As the actuating arm is lifted it sends a trip to the contacts
inside of the interrupter bottle. This will break the circuit and the arc is
established inside of the bottle that is either under vacuum or contains SF6 gas,
both of which assist in arc extinguishing. As the blade fully opens the actuating
arm is reset allowing the contacts inside of the interruption bottle to reset.
Interrupter applications include load dropping capabilities.
Switch Movement
Vertical breaking switches – Allows closer horizontal spacing between each phase
switch. They also require greater vertical clearance because of the direction of the
switch blade.
Side breaking switches – Requires less vertical clearance, making it great for low-profile
substations. This set-up will require a greater horizontal spacing between phase
switches.
Double side breaking switches – The switch blade rotates on the center insulator of the
switch. This has the advantage of both of the previous switch designs discussed with the
draw back of greater complexity because you are doubling the amount of contacts that
must be aligned.
Center break switches – The device has two blades that disconnect at the center of the
switch. These require a smaller profile vertically and horizontally between phase but
come with more complexity being that the blades must be aligned properly to connect
at the center.
Grounding Switches
Used to ground live parts of substation equipment, lines, and busses.
They are required for safety during maintenance when conventional grounding cables
can not be used.
They can be single pole or gang operated switches depending on design constraints.
Shunt Tripping
o Circuit switchers can come with a shunt tripping device
o The shunt trip is a high-speed current breaking device that acts more quickly
than traditional tripping of the motor operator.
o Maximum interruption time is 8 cycles.
o Shunt tripping operated independently of the motor operator. It is achieved
through the shunt trip solenoid which trips the contacts in the interrupter.
S&C Series 2000 Circuit Switcher
o Can be used for transformer protection.
o Can be sized up to 25 kA current interruption.
o Utilizes SF6 interrupter.
S&C Mark V Circuit Switcher
o Versatile application (transformer, line, capacitor bank protection).
o Up to 80 kA current interruption.
o Utilizes SF6 interrupter.
o Can include shunt tripping for very fast isolation.
Metal-Clad Switchgear
When working with switchgear that can potentially expose workers to arc flashing, extra
precautions must be adhered to for safe working conditions to be established. These are
the boundary definitions of each zone of an arc flash as described by OSHA;
o Flash Protection Boundary (outer boundary): The flash boundary is the farthest
established boundary from the energy source. If an arc flash occurred, this
boundary is where an employee would be exposed to a curable second-degree
burn (1.2 calories/cm2). The issue here is the heat generated from a flash that
results in burns. Personnel are required to wear protective equipment if working
within this zone.
o Limited Approach: An approach limit at a distance from an exposed live part
where a shock hazard exists. This zone requires all personnel must be specially
trained or escorted by a specially trained person to perform work in this area, in
addition to having all required PPE.
o Restricted Approach: An approach limit at a distance from an exposed live part
which there is an increased risk of shock. Only specially trained individuals
should enter this zone with all required PPE.
o Prohibited Approach (inner boundary): A distance from an exposed part which is
considered the same as making contact with the live part. This zone should not
be occupied at all when the equipment is energized.
o This distance is not common between equipment. Some equipment will have a
greater flash protection boundary while other equipment will have a lesser
boundary.