Chapter 04-Analysis and Design of Rectangular Footing
Chapter 04-Analysis and Design of Rectangular Footing
Column
Footing
CHAPTER O4
CHAPTER O4
0.35 m 0.65 m
with 20 mm ø. The footing width is limited to a r s
te
1.00 m
maximum of 3 m. Use f’c = 21 MPa and fy = 275 e
3m
MPa 23.6 kN/m3
CHAPTER O4
0.35 m 0.65 m
P = PDL + PLL qnet = qallow − γshs − γchc r s
te
1.00 m
e
= 250 + 390 = 75 − 19.2(0.65) − 23.6(0.35) 3m
23.6 kN/m3
P = 640 kN qnet = 54.26 kPa
640 640
A= L(3) = L = 3.932 m
54.26 54.26
Say, use Minimum Footing Size: 3.00 m x 4.0 m L
CHAPTER O4
0.35 m 0.65 m
= 1.2(250) + 1.6(390) 4.0 ter s
1.00 m
e
3m
wu = 231 kN/m
Pu = 924 kN d
d = hc − Cc − 0.5db
0.075m
= 350 − 75 − 0.5(20) wu = 231 kN/m
d = 265 mm 4.0 m
CHAPTER O4
0.35 m 0.65 m
Overhang Overhang
1.00 m
1.25 m
3.0 m
3.0 m
1.75 m 1.75 m d = 0.265 m
1.25 m
0.075m
wu = 231 kN/m
4.0 m 4.0 m
CHAPTER O4
0.35 m 0.65 m
1.00 m
ϕ = 0.75 for shear Vu d
Vu = wu × l d = 0.265 m
= 231(1.485)
wu = 231 kN/m 0.075m
Vu = 343.035 kN wu = 231 kN/m
Shear Section
4.0 m
CHAPTER O4
0.35 m 0.65 m
ϕVc = ϕ λ f′c bwd
1.00 m
6 Vu d
1
= (0.75) (1.0) 21(3,000)(265) d = 0.265 m
6
ϕVc = 455.393 kN
wu = 231 kN/m 0.075m
455.393 kN > 343.035 kN wu = 231 kN/m
Shear Section
Therefore, SAFE FOR SHEAR 4.0 m
CHAPTER O4
422.6.4.1.1
For square or rectangular columns, concentred loads, or reaction areas, critical sections for two-way
shear in accordance with Section 422.6.4.1 (a) and (b) shall be permitted to be de ned assuming
straight sides.
CHAPTER O4
fi
SITUATION NO. 01
SOLUTION:
Critical Sections for Two-way Members
P
Longer d d Longer
Overhang 2 2 Overhang
d d
2 2
0.35 m 0.65 m
1.00 m
422.6.2 E ective Depth
422.6.2.1 For calculation of Vc and Vs for two-way
d
shear, d shall be the average of the e ective depths
in two orthogonal directions.
0.075m quNET = 77 kPa
d = dave = hc − Cc − db = 350 − 75 − 20
d = 255 mm 4.0 m
CHAPTER O4
0.35 m 0.65 m
Shear d d
1.00 m
Section 2 2
0.3
5m d = 255 mm
500 + d = 755 mm
d d bo 1.75 m 1.75 m
0.35 m 0.65 m
Pu = 924 kN 2 0.50 m 2
d d
1.00 m
quNET = 77 kPa 2 2
6( β)
Least of (a), 1 2
(a) 422.6.5.2 (b), and (c):
1+ λ f′c (b)
(b) Section 422.5.5, if the conditions of Section
422.6.5.4 are satis ed
12 ( bo )
1 asd
422.6.5.2 vc shall be calculated in accordance 2+ λ f′c (c)
with Table 422.6.5.2.
CHAPTER O4
6( β)
1 2 Compute only
β is the ratio of long side to short side of the
1+ λ f′c (b) column, concentrated load, or reaction area.
when β > 2
12 ( bo )
1 asd Compute only as is 40 for interior columns, 30 for edge
2+ λ f′c (c) a d
when s
<2 columns, and 20 for corner columns.
bo
CHAPTER O4
bo
as = 40 as = 30 as = 20
CHAPTER O4
500 + d = 755 mm
bo
vc = λ f′c 1.75 m 1.75 m
0.35 m 0.65 m
3 d d
1.00 m
2 2
6( β)
1 2 β>2
vc = 1+ λ f′c d = 0.255 m
1.00 < 2
asd 0.075m
12 ( bo )
1 asd <2 500 + d quNET = 77 kPa
vc = 2+ λ f′c bo 755 mm
3.377 > 2 Plan 4.0 m
CHAPTER O4
500 + d = 755 mm
bo
3 1.75 m 1.75 m
0.35 m 0.65 m
d d
1
1.00 m
2 2
ϕVc = ϕ λ f′c bod
3
d = 0.255 m
1
= (0.75) (1.0) 21(3020)(255)
3 0.075m
500 + d quNET = 77 kPa
ϕVc = 882.260 kN 755 mm
Plan 4.0 m
CHAPTER O4
0.35 m 0.65 m
5 m
. 7
Mu 1
1.00 m
0.3 5 m
5m 1.7
d = 0.265 m
0.075m
3.0 0 m wu = 231 kN/m
m 4.
4.0 m
CHAPTER O4
0.35 m 0.65 m
Moment, Mu
1.00 m
wul 2 Mu
Mu = d = 0.265 m
2
2
231(1.75)
= wu = 231 kN/m 0.075m
wu = 231 kN/m
2
Mu = 353.719 kN ∙ m Bending Section 4.0 m
CHAPTER O4
0.35 m 0.65 m
Rn = = = 1.866 MPa
ϕbd 2 0.90(3000)(265)2
1.00 m
0.85 f′c 2Rn
ρ= 1− 1− d = 0.265 m
fy 0.85 f′c
0.075m
0.85(21) 2(1.866) wu = 231 kN/m
ρ= 1− 1− ρ = 0.00718
275 0.85 (21) 4.0 m
CHAPTER O4
0.35 m 0.65 m
1.4 1.4 2
As,min = bwd = 275 (3000)(265) = 4,047.27 mm
1.00 m
fy
d = 0.265 m
f′c 21 2
As,min = bwd = 4(275) (3000)(265) = 3,311.95 mm
4fy 0.075m
wu = 231 kN/m
2
As,min = 0.002Ag = 0.002(350 × 3000) = 2,100 mm 4.0 m
CHAPTER O4
0.35 m 0.65 m
1.00 m
5,708.1
= d = 0.265 m
314
N = 18.179 Provide: 19 - 20 mm ø Bars 0.075m
wu = 231 kN/m
4.0 m
CHAPTER O4
0.35 m 0.65 m
5m
Mu
1.00 m
1.2
0.3 5m
5m
d = 0.245 m
0.075m
3.0 0 m wu = 308 kN/m
m 4.
3.0 m
CHAPTER O4
0.35 m 0.65 m
Moment, Mu
1.00 m
wul 2 Mu
Mu = d = 0.245 m
2
2
308(1.25)
= wu = 308 kN/m 0.075m
wu = 308 kN/m
2
Mu = 240.625 kN ∙ m Bending Section 3.0 m
CHAPTER O4
Mu 6
240.625 × 10 1.25 m 1.25 m
Rn = = = 1.114 MPa
0.35 m 0.65 m
ϕbd 2 0.90(4000)(245)2
1.00 m
0.85 f′c 2Rn
ρ= 1− 1− d = 0.245 m
fy 0.85 f′c
0.075m
0.85(21) 2(1.114) wu = 308 kN/m
ρ= 1− 1− ρ = 0.00419
275 0.85 (21) 3.0 m
CHAPTER O4
0.35 m 0.65 m
1.4 1.4 2
As,min = bwd = 275 (4000)(245) = 4,989.09 mm
1.00 m
fy
d = 0.245 m
f′c 21 2
As,min = bwd = 4(275) (4000)(245) = 4,082.658 mm
4fy 0.075m
wu = 308 kN/m
2
As,min = 0.002Ag = 0.002(350 × 4000) = 2,800 mm 3.0 m
CHAPTER O4
0.35 m 0.65 m
1.00 m
4,107
= d = 0.245 m
314
N = 13.08 Provide: 14 - 20 mm ø Bars 0.075m
wu = 308 kN/m
3.0 m
CHAPTER O4
0.35 m 0.65 m
distributed in accordance with (a) and (b).
1.00 m
(a) reinforcement in long direction shall be
distributed uniformly across entire width of
footing.
3.0 m
CHAPTER O4
3.0 m
0.35 m
s s s s s s s s s s s s s s s s s s
4.0 m
A 3.0 m
PLAN SECTION THRU A-A
CHAPTER O4
0.35 m
reinforcement along long direction.
A s s s s s s s s s s s s s s s s s s
4.0 m
3.0 m
SECTION THRU A-A
Spacing, s
B = 2Cc + 19(db) + 18(s)
3.0 m
3.0 m
3000 = 2(75) + 19(20) + 18(s)
s = 137.222 mm ≈ 130 mm
4.0 m s = 130 mm < 450 mm
A
PLAN Therefore s = 130 mm
CHAPTER O4
(b) For reinforcement in the short direction, a portion of the total reinforcement, γsAs, shall
be distributed uniformly over a band width equal to the length of short side of footing,
centered on the centerline of column or pedestal. Remainder of reinforcement required in
the short direction, (1 - γs)As, shall be distributed uniformly outside the center band width
of footing, where is calculated by:
2
γs = where β is the ratio of long to short side of footing.
β+1
CHAPTER O4
4.0 m
14 - 20 mm ø Bars
3.0 m
3.0 m
0.35 m
s s s s s s s s s s s
B B
3.0 m 3.0 m
PLAN SECTION THRU B-B
CHAPTER O4
0.35 m
required inside the band width B of
the short direction. s s s s s s s s s s s
4.0 m
3.0 m
SECTION THRU B-B
Check maximum spacing for main bars as per
3.0 m
3.0 m
NSCP 2015 Section 407.2.2.3:
Maximum spacing s of deformed reinforcement
B B shall be the lesser of:
3.0 m a. Smax = 3h = 3(350) = 1050 mm
PLAN b. Smax = 450 mm
CHAPTER O4
0.35 m
required inside the band width B of
the short direction. s s s s s s s s s s s
4.0 m
3.0 m
SECTION THRU B-B
Spacing, s
B = 12(db) + 11(s)
3.0 m
3.0 m
3000 = 12(20) + 11(s)
s = 250.909 mm ≈ 250 mm
B B
s = 250 mm < 450 mm
3.0 m
PLAN Therefore s = 250 mm
CHAPTER O4
0.35 m
required outside the band width B
of the short direction. s s
4.0 m
0.50 m 3.0 m 0.50 m
SECTION THRU B-B
Check maximum spacing for main bars as per
3.0 m
3.0 m
NSCP 2015 Section 407.2.2.3:
Maximum spacing s of deformed reinforcement
B B shall be the lesser of:
3.0 m a. Smax = 3h = 3(350) = 1050 mm
PLAN b. Smax = 450 mm
CHAPTER O4
0.35 m
required outside the band width B
of the short direction. s s
4.0 m
0.50 m 3.0 m 0.50 m
SECTION THRU B-B
Spacing, s
500 = Cc + db + s
3.0 m
3.0 m
500 = 75 + 20 + s
s = 405 mm ≈ 400 mm
B B
s = 400 mm < 450 mm
3.0 m
PLAN Therefore s = 400 mm
CHAPTER O4
CHAPTER O4