Regime R
Regime R
NEUTRAL REGIME
• Know the different earth connection schemes defined by the NF-C-1500 standard
CLASSES
GOALS
I. GENERAL:
Electrical energy, although useful, is dangerous for humans. If a current passes through the human body, there is a risk of
lesions or even death. It is therefore necessary to protect people against such dangers (see § on primary safety).
Distribution networks are essentially characterized by the nature of the current and the number of active conductors,
as well as by the connection to earth or neutral regimes.
The safety of people and equipment is ensured differently depending on the neutral system used in a
Electrical Installation.
Distribution systems are characterized by the nature of the current and the number of wires.
- NOT
+ Ph1
M
- Ph2
The NF C 15.100 standard defines three neutral systems which are characterized by two letters:
Page 1 / 4
Machine Translated by Google
C. TT diet:
PE
Earth connection
As soon as an insulation fault occurs,
installation Ground connection there must be a cut-off: This is the cut-off at the
first fault.
D. TN neutralization:
Ph1
Ph2
Ph3
PE
PEN NOT
NOT
PE PE
1. TN-C scheme
The neutral and the protective conductor are COMBINED. This type of diagram is prohibited for conductor sections less
than 10 mm2 ; Downstream of the TN-S diagram, three-pole switchgear is used.
2. TN-S scheme
The neutral and the protective conductor are SEPARATE. Three-pole + neutral devices must be used .
In both cases, protection must be ensured by cutting at the first fault.
E. Isolated neutral: IT
symbolization of a
The neutral is isolated or connected to earth
transformer by a fairly high impedance (1500 to 2000 V).
Ph1
Ph2 The first fault does not present any danger.
Ph3 The phase-to-ground current is very low and no
NOT dangerous voltage is to be feared.
Impedance
But it must be reported and researched to be
possible Surge limiter
eliminated. Cutoff is mandatory at the second fault.
PE
Page 2 / 4
Machine Translated by Google
II. TT REGIME:
The TT distribution system is the neutral system used by EDF for all public energy distribution in the
low voltage network.
A. Principle:
Ph1
Ph2
Ph3
NOT
220V
Earth connection of
neutral
Uc
RN AR
ID
When a phase touches the mass, there is an increase in the potential of this mass.
Let RD : The fault resistance = 0 ÿ; RN: the resistance of the neutral earth connection = 10 ÿ; RA: the resistance of the earth
connection = 20 ÿ;
This voltage is fatal. (see § first class: the dangers of electric current)
When an insulation fault occurs in a TT network, there is a dangerous rise in the ground potential
metallic. (Which usually are at 0V potential).
B. Rules to observe:
1st
rule: All the masses of equipment protected by the same protection device must be interconnected
and connected by a protective conductor (PE) to the same earth connection.
2nd rule: The protection condition must satisfy the following relationship: RAA
*I<UC
- IA : Operating current of the protection device; resistance of
- - UC : the earth connection of the masses; - RA :
- limit contact voltage: UC = 50V, 25V depending on the premises.
3rd rule: In TT schemes, protection will be ensured by a residual current differential device. In this case, the current IA is equal
to the residual differential current of the circuit breaker.
The sensitivity of a residual current circuit breaker is indicated by the symbol IÿN, which indicates the protection system, which
can be a switch or a circuit breaker.
Page 3 / 4
Machine Translated by Google
C. Sensitivity of differentials:
III. EXERCISE :
An electrical installation is made up of a three-phase heating resistor and a three-phase asynchronous motor. The assembly diagram is this:
km1
Data Rn =10 V, Ra = 10 V, Rc = 4 V, T1 20 kV / 240/400 V.
D2
F2
Page 4 / 4