Romblon State University Rubrics and Rating:

Completeness ……………………………………….(35%): ________


College of Engineering and Technology Accuracy ……………………………………………..(35%): ________
Timeliness……………………………………………(10%): ________
MECHANICAL ENGINEERING DEPARTMENT Neatness/Orderliness……………………………….(20%): ________
School Year 2023-2024 | 2nd Semester Total ________

INDUSTRIAL PLANT ENGINEERING Problem Set No.:


Topic: Date Submitted:
Name: Year:
Instructor:
Course:
Learning Objectives (3):

Problem: Detailed Solution:


(6) An R-12 standard refrigeration cycle operates at an
evaporating pressure of 386 kPa and a condensing pressure of
1009 kPa. Show the effects of decreasing the vaporizing (8) A refrigerant 12 refrigeration system requires a load of
pressure to 270 kPa on the following: For a unit mass, (a) 54 kW at an evaporator pressure of 270 kPa and a
refrigerating effect, (b) COP, and (c) work. For a refrigerating condenser pressure of 1009 kPa. The refrigerant is
capacity of 1 kW, (d) power, (e) mass flow rate, (f) heat rejected, subcooled 10 degrees before entering the expansion
and (g) volume flow rate. valve and vapor is superheated 14 degrees before
entering the compressor. A twin-cylinder compressor
with stroke equal to 1.25 times the bore is to be used at a
speed of 27 r/s. The volumetric efficiency is 84 per cent.
Determine (a) the quantity of cooling water in the
condenser for an 11-degree increase in temperature, (b)
the bore and stroke, and (c) the compressor power.

Working formulas:

Illustrations: (with complete labels and given) (9) A refrigerant 22 refrigeration system carries a load of
Schematic Diagram
82 kW at an evaporator pressure of 354 kPa and a
condenser pressure of 1460 kPa. The liquid refrigerant is
subcooled by 4 degrees before entering the expansion
valve and the vapor is superheated by 5 degrees before
entering the compressor. The compressor operates at 28
r/s. The stroke-to-bore ratio of the twin-cylinder
compressor is 1.20 and the actual volumetric efficiency is
82 per cent. Determine (a) mass flow rate of refrigerant,
(b) mass flow rate of cooling water in the condenser for a
7-degree change in temperature, and (c) the bore and
stroke.
Problem: Detailed Solution:

(7) An industrial plant has available a 4-cylinder, 76-mm bore by


102-mm stroke, 800 rpm, single-acting compressor for use with
Refrigerant 12. Proposed operating conditions for the (10) A refrigerant 22 refrigerating system is operating with a
compressor are 38°C condensing temperature and 5°C condenser temperature of 42°C and an evaporating temperature
evaporating temperature. It is estimated that the refrigerant will of 0°C. (a) If the liquid line from the condenser is soldered to the
enter the expansion valve as a saturated liquid, that the vapor suction line from the evaporator to form a simple heat exchanger
will leave the evaporator at a temperature of 7°C, and will enter and if as a result of this the saturated vapor leaving the
the compressor at a temperature of 13°C. Assume a compressor evaporator is superheated 10 degrees, how many degrees will
volumetric efficiency of 70 per cent. Assume frictionless flow. the saturates liquid leaving the condenser be subcooled?
Calculate the refrigerating capacity in kW for a system equipped Determine (b) the volume flow rate, and (c) the compressor work.
with this compressor.

(11) In a conventional refrigeration cycle which uses Freon- 12


as the refrigerant, the temperature of the evaporating fluid is -
20°C. It leaves the evaporator as saturated vapor at -20°C and
enters the compressor. The pressure in the condenser is 1.30
MPa. The liquid leaves the condenser and enters the expansion
valve at 40°C. It is proposed to modify this cycle by adding a
heat exchanger that would superheat the suction vapor to 25°C.
Compare the coefficient of performance of these two cycles.
What is the temperature of the refrigerant entering the expansion
Given Working formulas valve with the heat exchanger? For a load of 50kW, determine
the volume flow rate for both cycles.

Illustrations: (with complete labels and given)


Schematic Diagram

Continuation of the previous problem (if need extra page)