Nalayag Visitor Center PVSYS JKM260 - SM200-2pcs - MS45amp - 1kWp Off Grid

This document provides the simulation parameters for a stand-alone photovoltaic system in Lobo, Batangas, Philippines using a 1 kW PV array and battery storage. It details the PV module characteristics, losses, controller, battery, and the daily household energy needs of 3.5 kWh.

Uploaded by

Jimmy Asuncion
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
20 views5 pages

Nalayag Visitor Center PVSYS JKM260 - SM200-2pcs - MS45amp - 1kWp Off Grid

This document provides the simulation parameters for a stand-alone photovoltaic system in Lobo, Batangas, Philippines using a 1 kW PV array and battery storage. It details the PV module characteristics, losses, controller, battery, and the daily household energy needs of 3.5 kWh.

Uploaded by

Jimmy Asuncion
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

PVSYST V6.

41 31/01/19 Page 1/5

Stand Alone System: Simulation parameters

Project : Nalayag Visitor Center


Geographical Site Lobo, Batangas Country Philippines
Situation Latitude 13.7°N Longitude 121.2°E
Time defined as Legal Time Time zone UT+8 Altitude 72 m
Albedo 0.20
Meteo data: Lobo, Batangas MeteoNorm 7.1 - Synthetic

Simulation variant : JKM260_SM200-2pcs_MS45amp_1kWp


Simulation date 31/01/19 13h31

Simulation parameters
Collector Plane Orientation Tilt 15° Azimuth 0°
Models used Transposition Perez Diffuse Perez, Meteonorm

PV Array Characteristics
PV module Si-poly Model JKM 260P-60
Original PVsyst database Manufacturer Jinkosolar
Number of PV modules In series 2 modules In parallel 2 strings
Total number of PV modules Nb. modules 4 Unit Nom. Power 260 Wp
Array global power Nominal (STC) 1040 Wp At operating cond. 929 Wp (50°C)
Array operating characteristics (50°C) U mpp 55 V I mpp 17 A
Total area Module area 6.5 m² Cell area 5.8 m²

PV Array loss factors


Array Soiling Losses Loss Fraction 3.0 %
Thermal Loss factor Uc (const) 20.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
Wiring Ohmic Loss Global array res. 55 mOhm Loss Fraction 1.5 % at STC
Serie Diode Loss Voltage Drop 0.7 V Loss Fraction 1.1 % at STC
Module Quality Loss Loss Fraction -0.8 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Incidence effect, ASHRAE parametrization IAM = 1 - bo (1/cos i - 1) bo Param. 0.05

System Parameter System type Stand Alone System


Battery Model SM200
Manufacturer Motolite
Battery Pack Characteristics Voltage 24 V Nominal Capacity 200 Ah
Nb. of units 2 in series
Temperature Fixed (20°C)
Controller Model Tristar TS MPPT 45 - 24V
Manufacturer Morningstar
Technology MPPT converter Temp coeff. -5.0 mV/°C/elem.
Converter Maxi and EURO efficiencies 99.0/97.0 %
Battery management control Treshold commands as Battery voltage
Charging 0.0/0.0 V Corresp. SOC 0.24/0.53
Discharging 0.0/0.0 V Corresp. SOC 0.57/0.53

PVsyst Licensed to ADTEL Inc (Philippines)


PVSYST V6.41 31/01/19 Page 2/5

Stand Alone System: Simulation parameters (continued)

System Parameter System type Stand Alone System


Battery Model SM200
Manufacturer Motolite
Battery Pack Characteristics Voltage 24 V Nominal Capacity 200 Ah
Nb. of units 2 in series
Temperature Fixed (20°C)
Controller Model Tristar TS MPPT 45 - 24V
Manufacturer Morningstar
Technology MPPT converter Temp coeff. -5.0 mV/°C/elem.
Converter Maxi and EURO efficiencies 99.0/97.0 %
Battery management control Treshold commands as Battery voltage
Charging 0.0/0.0 V Corresp. SOC 0.24/0.53
Discharging 0.0/0.0 V Corresp. SOC 0.57/0.53

User's needs : Daily household consumers Constant over the year


average 3.5 kWh/Day

PVsyst Licensed to ADTEL Inc (Philippines)


PVSYST V6.41 31/01/19 Page 3/5

Stand Alone System: Detailed User's needs


Project : Nalayag Visitor Center
Simulation variant : JKM260_SM200-2pcs_MS45amp_1kWp

Main system parameters System type Stand alone


PV Field Orientation tilt 15° azimuth 0°
PV modules Model JKM 260P-60 Pnom 260 Wp
PV Array Nb. of modules 4 Pnom total 1040 Wp
Battery Model SM200 Technology general
battery Pack Nb. of units 2 Voltage / Capacity 24 V / 200 Ah
User's needs Daily household consumers Constant over the year global 1292 kWh/year

Daily household consumers, Constant over the year, average = 3.5 kWh/day

Annual values

Number Power Use Energy


Lamps (LED or fluo) 6 7 W/lamp 12 h/day 504 Wh/day
TV / PC / Mobile 1 70 W/app 6 h/day 420 Wh/day
Electric Fans 3 60 W/app 12 h/day 2160 Wh/day
Lamps (LED or fluo) 4 9 W tot 12 h/day 432 Wh/day
Stand-by consumers 24 h/day 24 Wh/day
Total daily energy 3540 Wh/day

Hourly profile
350
Fraction of daily enegy [%]

300
250
200
150
100
50
0
0 3 6 9 12 15 18 21 24

PVsyst Licensed to ADTEL Inc (Philippines)


PVSYST V6.41 31/01/19 Page 4/5

Stand Alone System: Main results


Project : Nalayag Visitor Center
Simulation variant : JKM260_SM200-2pcs_MS45amp_1kWp

Main system parameters System type Stand alone


PV Field Orientation tilt 15° azimuth 0°
PV modules Model JKM 260P-60 Pnom 260 Wp
PV Array Nb. of modules 4 Pnom total 1040 Wp
Battery Model SM200 Technology general
battery Pack Nb. of units 2 Voltage / Capacity 24 V / 200 Ah
User's needs Daily household consumers Constant over the year global 1292 kWh/year

Main simulation results


System Production Available Energy 1498 kWh/year Specific prod. 1440 kWh/kWp/year
Used Energy 1292 kWh/year Excess (unused) 1498 kWh/year
Performance Ratio PR 69.2 % Solar Fraction SF 100.0 %
Loss of Load Time Fraction 0.0 % Missing Energy 0 kWh/year

Normalized productions (per installed kWp): Nominal power 1040 Wp Performance Ratio PR and Solar Fraction SF
12 1.2
Lu : Unused energy (full battery) 3.95 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.692
Lc : Collection Loss (PV-array losses) 0.97 kWh/kWp/day SF : Solar Fraction (ESol / ELoad) : 1.000
Ls : System losses and battery charging -3.4 kWh/kWp/day
10 Yf : Energy supplied to the user 3.4 kWh/kWp/day 1.0
Normalized Energy [kWh/kWp/day]

8 0.8
Performance Ratio PR

6 0.6

4 0.4

2 0.2

0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

JKM260_SM200-2pcs_MS45amp_1kWp
Balances and main results

GlobHor GlobEff E Avail EUnused E Miss E User E Load SolFrac


kWh/m² kWh/m² kWh kWh kWh kWh kWh
January 126.3 132.7 119.2 119.2 0.000 109.7 109.7 1.000
February 135.1 138.5 122.8 122.8 0.000 99.1 99.1 1.000
March 181.8 177.5 154.5 154.5 0.000 109.7 109.7 1.000
April 188.2 173.1 151.3 151.3 0.000 106.2 106.2 1.000
May 169.2 148.7 132.5 132.5 0.000 109.7 109.7 1.000
June 155.1 134.0 120.3 120.3 0.000 106.2 106.2 1.000
July 149.3 130.2 117.7 117.7 0.000 109.7 109.7 1.000
August 136.6 122.9 110.5 110.5 0.000 109.7 109.7 1.000
September 137.9 129.7 115.7 115.7 0.000 106.2 106.2 1.000
October 130.1 129.4 114.9 114.9 0.000 109.7 109.7 1.000
November 128.4 134.1 119.8 119.8 0.000 106.2 106.2 1.000
December 124.0 132.9 118.9 118.9 0.000 109.7 109.7 1.000

Year 1762.0 1683.7 1498.1 1498.1 0.000 1292.1 1292.1 1.000

Legends: GlobHor Horizontal global irradiation E Miss Missing energy


GlobEff Effective Global, corr. for IAM and shadings E User Energy supplied to the user
E Avail Available Solar Energy E Load Energy need of the user (Load)
EUnused Unused energy (full battery) loss SolFrac Solar fraction (EUsed / ELoad)

PVsyst Licensed to ADTEL Inc (Philippines)


PVSYST V6.41 31/01/19 Page 5/5

Stand Alone System: Loss diagram


Project : Nalayag Visitor Center
Simulation variant : JKM260_SM200-2pcs_MS45amp_1kWp

Main system parameters System type Stand alone


PV Field Orientation tilt 15° azimuth 0°
PV modules Model JKM 260P-60 Pnom 260 Wp
PV Array Nb. of modules 4 Pnom total 1040 Wp
Battery Model SM200 Technology general
battery Pack Nb. of units 2 Voltage / Capacity 24 V / 200 Ah
User's needs Daily household consumers Constant over the year global 1292 kWh/year

Loss diagram over the whole year

1762 kWh/m² Horizontal global irradiation


+1.9%
+1.9% Global
Global incident
incident in
in coll.
coll. plane
plane

-3.3% IAM factor on global


-3.3% IAM factor on global
-3.0% Soiling loss factor
-3.0% Soiling loss factor
1684 kWh/m² * 7 m² coll. Effective irradiance on collectors
1684 kWh/m²
efficiency * 7=m²
at STC coll.
15.91% Effective irradiance on collectors
PV conversion
efficiency1754 kWh= 15.91%0.0%
at STC Array
Energynominal
Battery
Charge/Disch.
Gassing
PV conversion energy
Self-discharge
supplied
CurrentCurrent (at STC
(electrolyte
to the
Current
Efficiency
user effic.)
dissociation)
Loss
-0.4% PV loss due to irradiance level
1754 kWh Array nominal energy (at STC effic.)
-12.0%
-12.0% PV
PV loss due to temperature
-0.4% PV loss
loss due
due to
to temperature
irradiance level
+0.8%
+0.8% Module
Module quality
quality loss
loss
-12.0% PV loss due to temperature
-1.0%
-1.0% Module
Module array mismatch loss
array mismatch loss
-2.3%
-2.3%
+0.8% Ohmic
Modulewiring
Ohmic qualityloss
wiring loss
loss

-1.0% Module array mismatch loss


-2.3% Ohmic wiring loss

-100.0%
-100.0% Unused
Unused energy
energy (full
(full battery)
battery) loss
loss

-100.0% Unused energy (full battery) loss


0 kWh Effective energy at the output of the array
0 kWh Effective energy at the output of the array
+100.0% Converter Loss during operation (efficiency)
+100.0% Converter Loss during operation (efficiency)
+100.0% Converter Loss due to power threshold
+100.0% Converter Loss due to power threshold
+100.0% Converter Loss over nominal conv. voltage
+100.0% Converter Loss over nominal conv. voltage
Missing energy +100.0% Converter Loss due to voltage threshold
Missing energy
0 kWh +100.0% Converter
ConverterLoss due(effic,
losses to voltage threshold
overload)
0.0% 0 kWh Converter
Effective lossesat(effic,
energy overload)
the output of the array
Direct
0.0%
0.0 kWh Stored
use Battery Storage
Direct
0.0 kWh Stored
use
100.0%
0.0% Battery Storage
0.0% -3307.1%
100.0%-3307.1%
Battery Stored Energy balance
Battery Stored
+100.0% Converter LossEnergy balance (efficiency)
during operation
+100.0% Converter Loss due to power threshold
+100.0% Converter Loss over nominal conv. voltage
+100.0% Converter Loss due to voltage threshold
Missing energy
0 kWh +100.0% Battery efficiency
Converter lossesloss
(effic, overload)
0.0% +100.0% Battery efficiency loss
Direct
0.0 kWh Stored
use Battery Storage
Energy need of the user (Load)
100.0%
0.0% -3307.1% Battery Stored Energy balance

0.0% Charge/Disch. Current Efficiency Loss


0.0% Charge/Disch.
Gassing Current Current Efficiency
(electrolyte Loss
dissociation)
0.0% GassingSelf-discharge
Battery Current (electrolyte
Currentdissociation)
1292 kWh 0.0% Battery Self-discharge
Energy efficiency
supplied loss
to theCurrent
user
+100.0% Battery
1292 kWh Energy supplied to the user
1292 kWh Energy need of the user (Load)
1292 kWh Energy need of the user (Load)
1292 kWh
PVsyst Licensed to ADTEL Inc (Philippines)

You might also like