Nalayag Visitor Center PVSYS JKM260 - SM200-2pcs - MS45amp - 1kWp Off Grid
Nalayag Visitor Center PVSYS JKM260 - SM200-2pcs - MS45amp - 1kWp Off Grid
Simulation parameters
Collector Plane Orientation Tilt 15° Azimuth 0°
Models used Transposition Perez Diffuse Perez, Meteonorm
PV Array Characteristics
PV module Si-poly Model JKM 260P-60
Original PVsyst database Manufacturer Jinkosolar
Number of PV modules In series 2 modules In parallel 2 strings
Total number of PV modules Nb. modules 4 Unit Nom. Power 260 Wp
Array global power Nominal (STC) 1040 Wp At operating cond. 929 Wp (50°C)
Array operating characteristics (50°C) U mpp 55 V I mpp 17 A
Total area Module area 6.5 m² Cell area 5.8 m²
Daily household consumers, Constant over the year, average = 3.5 kWh/day
Annual values
Hourly profile
350
Fraction of daily enegy [%]
300
250
200
150
100
50
0
0 3 6 9 12 15 18 21 24
Normalized productions (per installed kWp): Nominal power 1040 Wp Performance Ratio PR and Solar Fraction SF
12 1.2
Lu : Unused energy (full battery) 3.95 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.692
Lc : Collection Loss (PV-array losses) 0.97 kWh/kWp/day SF : Solar Fraction (ESol / ELoad) : 1.000
Ls : System losses and battery charging -3.4 kWh/kWp/day
10 Yf : Energy supplied to the user 3.4 kWh/kWp/day 1.0
Normalized Energy [kWh/kWp/day]
8 0.8
Performance Ratio PR
6 0.6
4 0.4
2 0.2
0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
JKM260_SM200-2pcs_MS45amp_1kWp
Balances and main results
-100.0%
-100.0% Unused
Unused energy
energy (full
(full battery)
battery) loss
loss