On-Site: Irae Cucu LC Ae
On-Site: Irae Cucu LC Ae
~ ON-SITE
mee)To BS 7671 : 2001 (2004)
mM eras eee ny
irae CUCU LC ae
No1:2002
and No 2: rt Aes
Ms
ae = -
ig -*
= rd
3 5
a (Pe
eae,
2r ay wy
= 7 Peas =,
re en mn
|
i
IAMwT!
HAR Lor
os
Wak,
3 ; =
Weeyeurviil.
at LAID
WWI
Published by: The IEE, LONDON, UK
This publication is copyright under the Berne Convention 2003 and the Universal
Copyright Convention. All rights reserved. Apart from any fair dealing for the purposes
of research or private study, or criticism or review, as permitted under the Copyright,
Designs and Patents Act, 1988, this publication may be reproduced, stored or
transmitted, in any form or by any means, only with the prior permission in writing of
the publishers, or in the case of reprographic reproduction in accordance with the terms
of licences issued by the Copyright Licensing Agency. Inquiries concerning reproduction
outside those terms should be sent to the publishers at the undermentioned address:
The IEE, Michael Faraday House, Six Hills Way, STEVENAGE, SG1 2AY, United Kingdom
While the publisher and contributors believe that the information and
guidance given in this work is correct, all parties must rely upon their
own skill and judgement when making use of it. Neither the publisher
nor any contributor assume any liability to anyone for any loss or
damage caused by any error or omission in the work, whether such
error or omission is the result of negligence or any other cause. Where
reference is made to legislation it is not to be considered as legal
advice. Any and all such liability is disclaimed.
2
CONTENTS
Page
PREFACE
FOREWORD
SECTION 1. INTRODUCTION 11
Scope 11
i Basic Information Required 13
APPENDICES
INDEXES
BS 7671 and the On-Site Guide are not design guides. It is essential to
prepare a schedule of the work to be done prior to commencement
or alteration of an electrical installation and to provide all necessary
information and operational manuals of any equipment supplied to
the user on completion.
Any specification should set out the detailed design and provide
sufficient information to enable competent persons to carry out the
installation and to commission it. The specification must include a
description of how the system is to operate and all of the design and
operational parameters.
The Designer(s)
The Installer(s)
The Electricity Distributor
The Installation Owner and/or User
The Architect
The Fire Prevention Officer
The Planning Supervisor
All Regulatory Authorities
Any Licensing Authority
The Health and Safety Executive
In producing the specification advice should be sought from the
installation owner and/or user as to the intended use. Often, such
as in a speculative building, the detailed intended use is unknown. In
those circumstances the specification and/or the operational manual
must set out the basis of use for which the installation is suitable.
10
ON-SITE GUIDE
SECTION 1. INTRODUCTION
pat Scope
11
Sec 1
This Guide contains information which may be required in
general installation work, e.g. conduit and trunking capacities,
bending radii of cables.
12
Sec 1
Part 3
{2 Basic Information Required
(viii) the arrangements for the incoming cable and metering. 3130101)
13
Sec 1
SECTION 2. THE SERVICE POSITION
Where the meter tails are protected against fault current 473-02-04(v)
by the distributor’s cut-out the method of installation,
maximum length and minimum cross-sectional area
must comply with the requirements of the distributor.
14
Sec 2
Fig 2a: Layout when the supplier does not provide a main switch
Note: Earthing arrangements have been omitted for clarity. Tails between the
meter and the consumer’s installation are provided by the consumer
meter consumer's
installation
ee ne supplier’s
ine:
terminals
distributor's
cut-out
Fig 2b: Layout when the supplier does provide a main switch
Note: Earthing arrangements have been omitted for clarity. Tails between any
main switch provided by the supplier and the consumer's installation are
provided by the consumer
consumer’s
installation
consumer's
tails
ee supplier's
main switch terminals
distributor's
cut-out
15
Sec 2
(iv) Supplier’s Switch
16
Sec 2
SECTION 3. PROTECTION
Functions (i) and (ii) are carried out usually by one device, a fuse
or circuit-breaker.
17
Sec 3
trunking or be within a suitable enclosure. A 30 mA
RCD may be provided to give supplementary protection 412-06
against direct contact, but must not be relied upon for
primary protection.
SELV 411-02
Separated extra-low voltage (SELV) systems
PELV. 471-14-01
Protective extra-low (PELV) systems must meet all the 471-14-02
requirements for SELV, except that the circuits are not
electrically separated from earth.
18
Sec 3
For SELV and PELV systems protection against direct 411-02-09
contact need not be provided if voltages do not exceed 471-14-02
the following:
19
Sec 3
(i) where the earth fault loop impedance is too high to 413-02-19
provide the required disconnection time e.g. where the
distributor does not provide an earth - TT systems
(ii) on socket-outlet circuits in TT systems 471-08-06
20
Sec 3
Fig 3a: Installing RCDs in a TT installation
note 1
labelled
“main
switch”
note 1
labelled
“main
switch’
21
Sec 3
Fig 3a cont'd: Installing RCDs in a TT installation
lAn 2 100 mA
note 4
labelled
“main
switch’
22
Sec 3
Fig 3b: Installing RCDs in a TN-S or TN-C-S installation
note 1 The 30 mA RCD and associated cbs may be replaced by residual current breakers with
overcurrent protection (RCBOs) on the main switch busbar rail
2 Circuits to lights, cooker, water heating, smoke alarms
3 Circuits to portable equipment outdoors and socket-outlets that may reasonably supply
equipment outdoors
23
Sec 3
SECTION 4. BONDING AND EARTHING
Note that:
(i) only copper conductors should be used; copper covered 542-03-03
aluminium conductors or aluminium conductors or
structural steel can only be used if special precautions
outside the scope of this Guide are taken
(ii) bonding connections to incoming metal services should 547-02-02
be as near as possible to the point of entry of the
services to the premises, but on the consumer's side of
any insulating section
(iii) the connection to the gas, water, oil, etc service should 5547-02-02
be within 600 mm of the service meter, or at the point
of entry to the building if the service meter is external,
24
Sec 4
and must be on the consumer’s side before any branch
pipework and after any insulating section in the service.
The connection must be made to hard pipe, not to soft
or flexible meter connections
(iv) | the connection must be made using clamps (to BS 951) —542-03-03
which will not be subject to corrosion at the point of
contact
(v) if incoming gas and water services are of plastic, main
bonding connections are to be made to metal
installation pipes only.
4.4 Earthing
25
Sec 4
(ii) metal central heating pipes and air conditioning systems
(iii) | accessible metal structural parts of the building (metal
door architraves, metal handrails, window frames and
similar parts are not considered to be extraneous-
conductive-parts unless they are connected to metallic
structural parts of the building)
(iv) metal baths and metal shower basins.
26
Sec 4
Hi4 :ep jedidA, Hulypyelsa sjusWAaHUe.e
puke 3AI}39}01d 40}9NPUOD
&S>
- S-NL
Ja}9W
Ja}aWsje}GZ ZU
A2UINsSUOD
uN
UO!}NqLJ}sIp
paeog
10
Bulyyes
Jeq
14dV1
387
| OL! ZU (a7
|| }UI! ae | (73a¥7
Hulyyes
JaY}O
je}oW
149V11 gk
sebadid
ule JEUILUI9}
sued
ulew
ulew
-SNOSUPIIXO
Joy
-3AIPNpuUuod
Hulyyes
Npuod
:S-NL payyeyZ
O} INOW
AO I1]/e}9W Y}eaYsS
yyea
Hulpuog
Ajddns
:a720/V(i uieyy jeljuaj}odinba
Hulpuog s1O}INPUOD
AeWaq a}e1edas
se) (UMOYs
Jo Paedoo]YIM UBHOIQUN *$JOJINPUOD
$40}INpuod
jelzuazodinba
(!! | -[TFGVT
Ajayes Je914999/3 UO!PaUUOD
- O JON ‘AAOWAY
ae
Sec 4
N
00
Sec 4
614 :qy jerIdA, Hulyzies s}yuswWabH
pue uewe 3AI}39}01d 40}9NPUOdD
&S2
- S-“D-NL
Ja}
Ja}OWsje}GZ ZWIW
|
| sauinsuod
lun
JO Uuol}Nq!}sS
paeog
Ip
138V1 bulyyes
Jeq
aye}UI [1387] [138
OL WW C+ 14aV1 a
OL ZUW
| J9UO
'
ule ulew JeUa}odinba -
Bbulyyes Hulpuog S10}NPUOD -
Ajddns yea JEUIWI9} sued
oud jejow jezowW oy)
UO!}DaUUOD Jayem seb
adid adid
:S-D-NLFINd Yes
:a20//(| uleyy jeuaiodinba
HuIpUuog s10JINpUOD
Ae aq a}eJedas
se) (UMoYs
Jo padoo|YIM USYOIGUN "SJOJINPUOD
(I [207 Ayid144D9]a UO!INGIYSIP
y4OMJaU suol}IPUOd
AewW a4inbas JabHJe] "sJOPNPUOD
(1! 1) -[FAGVT
Aayes 231499919 UO!}DBUUOD
- O JON "BAOWAY
614 :>p jeriIdAy Buiypes s}UaWabUeWe
pue 3AI}39}01d 10}9NPUOD
&S)
- LL
49}9W
GZ
7WW
sjle}
Ja}9W
}IUN
p1eogJeq
JaUINsSUOD
JO Bulyyes
UO!}NqLIA}sSIp
ulew
ZW 9 T349V1
Hulyyes
JO}NpuOD
DOL a1Ge1 Bas [138V7 |
[av]
148V1
uleuw
je}OW
jeyou
BGs rUy
seb
JayeM
yee
apoupaja adid BAid ee.
-SNOdUPI}XA
-LL YW UAN}94
SIA YPWeS 8pO1}D9]9 -89AIINPUOD
:a2ZO/y(| uley~y jeljuajodinba
Hulpuog ssO}DNPUOD
AeWaq a}eJedas
Se) (UMOYS
JO padoo|YIM UBYOIQUN “SJOJNPUOD syed
"BAOWAY JON O - UO!}D9UUOD JeI1I9/9 Ayayes -| TIGVT | (1!
N
si
uy
75,
(III
aas
a
‘OL'y
Yea
Sec 4
apOUpaja
‘pauinsai
aduejsIsad
Hulpaaaxa
UdeuBesed
“SJOJPINPUOI ‘
“SQUOZ dU} OPISINO Iv ‘[OO} B JO ASN oY} YA ATUO sIqQISsadoR “IWR ay) JapuN seoeds
BHuipuog Aieyuawajddns ‘J00] B JO ISN JY} INOYIIM o]qGIssadov st aovds ay] Jf | WUOZ, ,
:
se pasn aq Aew siojonpuod *
BAIPDI9}OId YINDIID. 7
sulseq ve aysem jejaw
Jamoyus je}yaw pue syjyeq
fll Ld ofiii Ud
je}oOW pue ‘sadid buleay LLL” Y;—;QQutaaeeEEEEELLLdddd ddd
jesjUa> pue Ja}eM ‘ajsem .
jeyaw Bulpnyou! ‘seuoz ne ||
ay} Ul Sued-aAl}2NpuOod ‘ sadid jeyau OS
-snoauedj}xa ||e 0} papuog pes
Aueyuaweajddns ag ysnw —
SOUOZ 94} UIY}IM s}UIod
Huljy61| pue samod je 4o
SJOPNPUOD dAI}D9}0OId SUL “1
‘SOLON ,
UW 6Z'Z ¥ € QUOZ yun zouoz ss [| oUOZ we
SoUOZ apisingQ.:
: Janeys =
:
KR
@
p10 ay
: a
ASS
JaMous
€ QU0Z, Z Uu0Z
gq
souoZ apIsInC, Janne eS
sieate ap= wn aiene'= Deeeeeeaciocses
adid
Eee YD}IMs pod Te jeyow
aseUIWUN|
SS
Zi
SUH! Mee MCC
uol}E]]e}SUI adid jeyaw - WoosY}eq & Ul HUIpUOg AueyUaWa|ddns :pr BIJ
Sec 4
mo
614 707 Aue}UsWwajddns
Hulpuog
Ul e WoOo1Yy}eq
- 31}Sse;dadid uol}e]]/e}sul
UU
CO
suo
a1yse\d UDUMs P4od ||Nd
adid
3
&
ee
ee
eb
ede
ee
ewe
wee
y Y YyY y y
weet
eee
eee
SOuO7Z,
Z OUOZ, € QUOZ
SpisynO
y
VY
y
U
couse tardeeeJamoyusSac
‘
eee ete meee eR en RECUR
Uc otaSulese Ween tc iaac Raveltsb
Y JueIPeY
diy
UIMS
YD :.
G Te a e ----|------+
fein a
y YyY
YA : :
U 13 = ; us
Jane
y —::
i:
yun
U0Z
Y .
;
‘Sa1ON
ra
woe
Y ;
¢QUOZ,
|SOUOZ
UniCE
ZTWUO0Z
9pIsINgQ
y Ao “| aU, BAIPa}OId SJO
YA
y 4o je samodpue Hulj
] Ss}UIOd UIYLIM
JU} SQUOZ
y }snuwaq Asey
y al
ay
;
0}
aq
34}
Sedid
—=
Aew
opsejd
eyo
‘papuogq
Hulpuog
ajsem
d14se|d
yes
OS
410
Wpaims
j YYY Y Yy y
oat(eeta ef eq@ LLL. Uddddddddeddddddddddddddddddddddddddddddlddddbflef
dd "juowd inba
jeuIW23
uol~aUUOD
Pe
eee
*[00}
JO
st
ajqissaoor
Jl
ay}
5|9UOZ,
Bayy
asn
aouds
sadeds JopuN
dy) ‘YR IQISsador
ATUO YIM dy} ASN JOB ‘JOO]div OPIsINO
IU} “SQUOZ
BHulpuog
31
Sec 4
"$10}DNPUODd
Aueyuawayddns
4.8 Earth Electrode (Fig 4c)
Metal gas or water or other metal service pipes are not to be 542-02-04
used as the earth electrode, although they must be bonded as
paragraph 4.1.
(vi) lead sheaths and metal coverings of cables, which must 542-02-05
meet the following conditions:
(a) the sheath or covering shall be in effective contact —542-02-05(ii)
with earth,
(b) the consent of the owner of the cable shall be 5A2-02-05\ii)
obtained, and
(c) arrangements shall be made for the owner of 542-02-05(\v)
the cable to warn the owner of the electrical
installation of any proposed change to the cable
or its method of installation which might affect
its suitability as an earth electrode.
32
Sec 4
4.10 Typical Earthing Arrangements
for Various Types of Earthing System (Figs 4a, 4b, 4c)
The protective conductor sizes shown in Figures refer to copper Table 54G
conductors and are related to 25 mmé2 supply tails from the Table 54H
meter. 547-02-01
33
Sec 4
SECTION 5. ISOLATION AND SWITCHING
Sal Isolation
(ii) other than at the origin of the installation every circuit, 476-01-02
or group of circuits, which may have to be isolated
without interrupting the supply to other circuits should
be provided with its own isolating device, which must —537-02-01
switch all live conductors in a TT system and all phase
conductors in a TN system
34
Sec 5
5.2. Functional Switching 537-05
35
Sec 5
A plug and socket-outlet or similar device shall not be selected 537-04-02
as a device for emergency switching.
36
Sec5
SECTION 6. LABELLING
37
Sec 6
(v) Purpose of switchgear and controlgear 514-01-01
IMPORTANT
38
Sec 6
verification must complete the notice, and it must be
updated after each periodic inspection.
(x) Diagrams 514-09
CAUTION
39
Sec 6
SECTION 7. FINAL CIRCUITS
230
where:
40
Sec 7
insulating wall, or single-core thermoplastic (pvc)
insulated cables enclosed in conduit in a thermally
insulating wall (Method 15).
(iv) the ambient temperature throughout the length of the Table 4c1
circuit does not exceed 30 °C
(i) In domestic premises, except for heating cables, the Table 4B1
conventional circuit design permits any number of
single-layer circuits when the spacing between
adjacent surfaces of the cables exceeds one cable
diameter, and, for other than semi-enclosed fuses,
(BS 3036) up to 5 touching, single-layer, circuits, when
clipped to a non-metallic surface (Installation Method 1)
41
Sec 7
SS
WYO GE'0 5 °Z
(BE
S-D-NL
Hua}
y
Ul
LWUNWIXe|/]
sojjoW
|
|UOID@UUODSIp
UO!}DBUUODSIP
|UO!}D@UUODSIP
UO!PaUUODSIP
(11106
LN
Buljjas
3|qe>
-OWJ9U}
uol}ze}|e3SU|
314e>
8}0u)
(!
poyjaw
984’
(and)
d13se|d
-OWJ9U}
398 984
SPINIAID
4’€’'Z‘L
JEUOIBUSAUOD
43 389 a3 38 '€'7'‘L
‘1 ‘7
BAIYE}OJg
| € 1 €
edAL
adhqd
edkl
ed, ed adAl edAL edAL
O9DY/G2
Ogd4/92
adf}
OGDU/G2Ogdu/q?
OgDu/G2 OgDU/G2 OMDHY/G2O9DH/92
ad1Aap
88
Sd
azisajqe>
Sa q>
9E0E
Zadh, qo
zadh,
|
2UuW
|°/
JIGVL
adIN0q
|
SHINDIID SHINDIID
Huizes jeipey
Bury
Ze
ad>/aseyud
2}0uU)
(A
Vv OE
Sa
LOEL S
SA
‘LOEL
Sa
QE0E S
SE
‘LOEL
SA
9E0E Sdsre
988
42
Sec 7
F1GV1L
[7 PaNU!}UOD JEUOHUBAU
S}INIAID
OD
adIAaq
| AazIsajqeD
| BAI2}OJg a1qeD wnwixeyy
y}6ua]
ul saJjew
Burjes
|} zwiw ad!Aapadi} uoljze}/2}su|
Vv dd>jaseud
| (Aajou) pouyew 57= 80 Igo 22 SEO
9}0u)
(] S-NL S-D-NL
-OWJ2Y} -OWJ2Y} S$
Bulas | (2nd) a1se\d UoPaUUODSIP |UOIPEUUOISIp |UOHaUUODsIP |UOPEUUODsIP|
ajqe> aiqe>
leipey
9 Sd 88
OgDuU/q>
adAL ’€'Z‘L D4
s}INI4ID
Ogdu/q?
edf)
gd
OL 88S
OGDy/G2
edAL
‘L ‘7 ’€ 384
Ogdy/q?
edfj
ad
OL Sq 88
OgDuU/G>
adAL
‘L ‘7 ’€ 324
O9dy/q>
edA,
g
Sl SA 9E0E
OGDyY/G2
adAL
‘tL Z
OGDY/G>
dA]
€ g@
a8
)
Sl SA 9E0E
Sa LOEL OGDW/9?
edALZ‘L 48
OgDU/q>
edA)
€ 28
91 aL/Si Sa 88
SA LOEL OgOU/G?
edAL
‘L 2 8 ig
OgDU/G>?
edAl
€ 28
O9p4/q?
ed,
a
43
Sec 7
(16 I qd edA| Ogdu/G?
€€ I! I! 9g € edAL OgDU/G?
€€ 9972 ‘L edAL OgDU/q>
€€ 88 Sd Sz
ZL qd adh} OgdH/9?
(WZ I > 3 ¢ adk, ODU/G>?
ev Z adh, q>
€v g 91 adh, OgDuU/G?
€v LOEL Sd ‘88S
ev 9E0E SA 0z
(OL I d edt Ogd4/9?
LZ I! I 398 ¢€ adkl OGDU/G>?
LZ 992 ‘L edAL OgDH/G?
€N 9E0E SA
12 LOEL Sa ‘'88sa 0z
(1!1)0Z (11)0Z a edAj Ogdu/9?
()9P (1)9S I I > 3 € adh, OgDH/G?
9S 9S 987 ‘L edAL O9DU/G2
9S 9S 88 Sq ol
S}INIIID
jeipey
3jqeo
UOIPsUUODSIP UOIP9UUODSIP UOIPSUUODSIP UO!P2UUODSIP Buijjas
SS -OWJ9U}
S-D-NL ((] 2}0U)
WYO SE°0 > °Z pouj}aw (Aajou) | sd>/eseyd Vv
uolze}|e}SuU| adf} ad1Aap zu Buljes
saijaw ul y}Hua] WNWwixe/\| 21Ge> 9AI}D2}01d azis ajqeD> | a21Aeq
S}INIAID FLUOMUGAUOD Peanul}uod |°/ FEVL
Sec 7
J1gVL
17 PANU!}UOD [EUOIJUBAUOD
S}IND4ID
adINagG
| AZISajged
| BAIP2}OJg ajqe> Wnwixeyy
yyHus;
Ul seujewW
Buljzes zwiw a21Aapadf} uol}e}/e}Su|
Vv >d>/eseyd
| (Aajou) poyjew °Z> GEO WYO
. 910u)
(| S-D-NL
-OWJ2U} -OWJ9Y} ; SG
aIAse}d(2d)
| —Huljas |UOMP@UUODsIP| |UOPEUUOIsIp |UOIPaUUOdSIP UO!PSUUODSIp
ajqe> ajqe
leipey
S}INDUID
SZ ; Sd 88
Ogdy/G>
adAl
| a8
q> adA|
z
OgDy/q>
adA|
€ 8>
Ogdy/92
adhqd
O€ SE 9E0E
S@ L9EL
OgDu/G>
edAl
1 a8
q> adh,
Zz
OGDY/G>
adh|
€ 8>
O€ 0'v/0'0L SA 9E0E
SA LOEL
OgDy/G2
adAl
| a8
q> adh,
Zz
OMDU/G>
adk|
€ 28
z€ Sq 88
OgDyY/G>
adAL
| 49
qo adh,
Zz
OgDU/G>?
adh]
€ 38
Ogdy/q>
edA,
gd
45
Sec 7
(EZ 38 € edAL O@DH/G>
60 60 z adh gD
6t 60 g adh, OgDU/9?
6t 6v a9 1 edAL OgDU/q>
6v (WE 9E0E SA
60 (W)ZE LOEL Sd Sv
(6 (W617 > 8 € adAL OGDH/9?
88 88 Z adh, q>
88 g adh Ogdu/9>
88 , adh, qo
88 88 Sd 0°9/0°91 Ov
(W)ZE > 3 € edAL O9DU/9?
€S z adh q>
€S g adAl OgDu/9>
€S | edAy qo
€S 88 Sq 0'v/0'0L Ov
(N)LS > 3 € adAL OGDH/G?
69 z edAy qo
69 a3 | edAL OgDU/9>
69 88 Sd 0'v/0'0L ze
S}INIIID
jeipey
3|qe>
Huljjes
-OWJ9Y}
UONDEUUODSIP |UOIDBUUODsIP |UOID@ULODSIP |UO!BUUODSIP
SNL (] 9}0U)
WYO 8'0 5 °Z pouyew (Aajou) | do/aseyd Vv
uo!}e}/E}SU| adh} ad1Aap zu Bulzed
sasjaw Ul yyHus] WNWwIxXe//\| 3)qeD 8A1}D9}O1d azIs ajqe> | adIAeq
S}INDAID JEUOIZUBAUOD Panu!}UOD |°/ F1GVL
Sec 7
46
Notes to Table 7.1
All the circuits are limited by voltage drop other than those marked
as below:
47
Sec 7
Table 4A2
7.2.2 Thermosetting cables (e.g. to BS 5467 or BS 7211)
7.2.3 Checklist
(i) what is the load current and can the distribution board
and supply arrangements accommodate it? (See
Appendix 1 for guidance on assessing load currents)
48
Sec 7
7.2.4 TT Systems
49
Sec 7
TABLE 7.2A
Circuit-breakers to BS 3871
(replaced by BS EN 60898)
50
Sec 7
(ii) circuit load characteristics
TABLE 7.2B
Instantaneous Application
trip current
51
Sec 7
(iii) | cable current-carrying capacities
greater than
50 mm joists
Notes:
52
Sec 7
7.3.2. Walls
no protection
required
wall
Note:
A Zone formed on one side of a partition wall of 100 mm or less thickness 522-06-06
extends to the reverse side only if the location of the accessory can be
determined from the reverse side.
53
Sec 7
TABLE 7.3A External Cables
Minimum separation distances between external low voltage
electricity supply cables operating in excess of 50 V a.c. or 120 V d.c.
to earth, but not exceeding 600 V a.c. or 900 V d.c. to earth (Band II),
and Telecommunications cables (Band 1).
il. Where the LV cables share the same tray then the normal
separation should be met.
Zs Where LV and telecommunications cables are obliged to cross
additional insulation should be provided at the crossing point;
this is not necessary if either cable is armoured.
54
Sec 7
7.3.4 Proximity to Other Systems 528-02
Electrical and all other services must be protected from any
harmful mutual effects foreseen as likely under conditions of
normal service. For example, cables should not be in contact 528-02-02
with or run alongside hot pipes.
switch
feed
neutral
2 way switch
common
3 cores
grouped
together
pee
strappers
2 way switch
55
Sec7
7.3.5 Height of switches, sockets etc
56
Sec 7
The cable for the power supply to each self-contained unit and
for the interconnections need have no fire retardant
properties, and needs no special segregation. Otherwise, fire 528-01-04
alarm system cables generally are required to be segregated as
per BS 5839-1 and BS 5839-6, see Table 7.4.
57
Sec 7
SECTION 8. SPECIAL LOCATIONS GIVING RISE TO INCREASED
RISK OF ELECTRIC SHOCK
58
Sec 8
d18Vl
8
syUaWasINbay
4104 JUadINb~a
}UasIN>)
Huisnpuke (SalJOSsa22e
Ul suO!}ed0] Hulule}UOd
& y}eq40 4aMoys
s}uaWasINnbay
10} JUaLUdINba
Ul 3y} S2UO0Z
winwiiull,Al uaesindBusy (sodueljddy) 1e3a6yr}IMsS
pue SalIOssad>.y
avaibap
jo
uo1}39}0:1d
L0-80-L09
AJUO A195 paxit JUaLUCINb~a
}eU} JoUUeD
8q pa}ed0] YyMasja
‘ee| SUON ‘PaMo||e L0-60-L09
A745 }uawdinba‘pamoyjje AjUOZ| A “d°e Pue OE A *D°P SAYIUMS
JO TAS S}INDIIDL0-80-L09
e/\\193 ‘sia}eay
L0-
‘siaMous samous ‘sduind ‘pamoj|e ‘pamoyye
au} a2iNos Bulag apis}noSaUOZ
‘9| pue‘Z
AYO pexi} JUaWiNbea
Jey} JOUUeD Aj\qeuoseai
aq pazed0|
aiaymasyjapamojje
41 papajoud
Aqe OE VW Gou
A745 }uawdinba‘pemoyje /A71FS SayIUMS
pue s}ayd0s ‘paMmo}|e
ay} 841NOs Hulaq
413}e/\/\ ‘sia}eay ‘siamous Jamous ‘sduund ‘sasieuiun|
‘suey apisynosauoz
‘9| pue‘Z pue saneys Ajddnssyiun
0}
Huijesy ‘sadueljdde
syiunJo} jOod|4IyM
syzeq ‘pamoyje SA Na ZPZ09
UDZ 28S| Pamoje
AJUO
4! paxi} aJayM
; a1 Aeids WO} s4aMoUs
si ‘Aja1]UN
L0-80-109
siaymasja‘pamoj|e
A745 puawdinba“‘pamoyjje saliossay
pamoyjje Jdadxa
10} “S}8]JNO-18905s
B1BU|
SI
€
ON
»
OU
Aq
o}|
Jo}
e
‘pue
IsnWW
OE
‘pax
Aq
OF
Sd
NJ
ssajuN
L0-80-L09
pue
Z|
"adu
ag 13S
SHUN
ajqeyiod
77409
UOIsIAoId
pas
Janeys
P2}22I0Jd
s}a30s
deyd
sa2ue!|ddY]
Gul3298uUOd
Uauasinbau
“Juadinba
ON
‘pamoyle
|
0}
Sg
NJ
JdadxKB
Z|
pue
apisino
pamojle pamoyje
pamoj|e
A795
syiun
sauoz
ZvZ09
Pas
janeys
Ajddns JO} Ajddns
deyd
Vw sadueiddy
sjaxI0s
a10/V
:/ B1aU/\
e JaMmoys 3j2IGNI
Ss! Paj|je}SU!
U! & WOOL J8Y4}O UY}
& WOOJY}e
10 JaMoYs ‘WOO APIs}NOSAUOZ
saluossaddV
‘0 ‘| Z JO € & -J9N0S
‘}a]]NO 1830 UCU}
& A7J¥S 38]}NO-Ja4D0s
JO Janeys Ajddns‘yun |jeysaq payda}0Id
Aqe
‘pamole
Jenpisos BuleiadoJUaIIND
(4V}) JOU Hulpeaedxe
QE YWU!
“\uawasinbai
adUePIODIe
YM UO!E|NBay
py ‘90-ZL
aloyy
:z aas SauNHl4
PH pUe dp JO} “SQUOZ
€0-60-L09 LO-80-L09 c0-80-109
90-CLV
ao
Sec 8
8.2. Shower Cubicles in a Room used for Other Purposes _—_601-08-02
Equipment
Equipment having a protective conductor current exceeding 607-02-02
3.5 mA shall be either permanently connected to the fixed
wiring or connected by means of an industrial plug and socket
to BS EN 60309-2.
a
Ny
separate
connections °
a
61
Sec 8
SECTION 9. INSPECTION AND TESTING Part 7
9.2 Inspection
62
Sec 9
(vi) correct connection of accessories and equipment
(including polarity)
- SELV
- limitation of discharge of energy
63
Sec 9
Band | and Band II circuit cables may not be present in 528-01-02
the same enclosure or wiring system unless they are
either separated by an effective barrier or wired with
cables suited to the highest voltage present. Where 528-01-07
common boxes are used for Band | and Band II circuits,
the circuits must be segregated by an insulating or
earthed partition.
Band |circuit:
Band II circuit:
64
Sec 9
(xvii) presence of diagrams, instructions and similar 514-09
information
65
Sec 9
SECTION 10. GUIDANCE NOTES ON INITIAL TESTING OF
INSTALLATIONS
Note: The advice given does not preclude other test methods.
66
Sec 10
(v) earth electrode resistance, when using an earth
electrode resistance tester (see also vii).
Test Method 1 can only be used to measure (Ri + R2) for an ‘all
insulated’ installation. Installations incorporating steel conduit,
steel trunking, micc and pvc/swa cables will produce parallel
paths to protective conductors. Such installations should be
inspected for soundness of construction and Test Method 1 or
2 used to prove continuity.
67
Sec 10
Jy ssayeaug |e
JO JNO sasnj {je
pseog Uol}Nq!3sIp $yO YOUMs Ue JUSWNJYsUl
$9}
UO UDd1IMs 4
Oo
poaowsal
sdwe|
ull
Asesodwia}
}INDID
‘ Jo pua je
asoJ Bulla.
-
L POUzaIA] $10}2NPUOD 3AI}39}0.1d yo A}INUIZUOD
Buljsa} 10} SUO!}DBUUOD :L'OL Bi
Sec 10
68
10.3.1(i) To test the continuity of protective conductors 713-02-01
Test Method 1
Test Method 2
Step 1:
The phase, neutral and protective conductors are identified
and the end-to-end resistance of each is measured separately
(see Fig10.2a). These resistances are r1, fn and r2 respectively. A
finite reading confirms that there is no open circuit on the ring
conductors under test. The resistance values obtained should
be the same (within 0.05 ohm) if the conductors are the same
69
Sec 10
size. If the protective conductor has a reduced csa the
resistance 12 of the protective conductor loop will be
proportionally higher than that of the phase and neutral loops
e.g. 1.67 times for 2.5/1.5 mm cable. If these relationships are
not achieved then either the conductors are incorrectly
identified or there is something wrong at one or more of the
accessories.
Step 2:
The phase and neutral conductors are then connected together
so that the outgoing phase conductor is connected to the
returning neutral conductor and vice-versa (see Fig 10.2b). The
resistance between phase and neutral conductors is measured
at each socket-outlet. The readings at each of the sockets
wired into the ring will be substantially the same and the value
will be approximately one quarter of the resistance of the
phase plus the neutral loop resistances, i.e. (r1 + rn)/4. Any
sockets wired as spurs will have a higher resistance value due
to the resistance of the spur conductors.
Note: Where single-core cables are used, care should be taken to verify that the phase and
neutral conductors of opposite ends of the ring circuit are connected together. An error
in this respect will be apparent from the readings taken at the socket-outlets,
progressively increasing in value as readings are taken towards the midpoint of the
ring, then decreasing again towards the other end of the ring.
Step 3:
The above step is then repeated, this time with the phase and
cpc cross-connected (see Fig 10.2c). The resistance between
phase and earth is measured at each socket. The readings
obtained at each of the sockets wired into the ring will be
substantially the same and the value will be approximately one
quarter of the resistance of the phase plus cpc loop resistances,
i.e. (r1 + 12)/4. As before, a higher resistance value will be
recorded at any sockets wired as spurs. The highest value
recorded represents the maximum (Ri + R2) of the circuit and is
recorded on Form F4. The value can be used to determine the
earth loop impedance (Zs) of the circuit to verify compliance with
the loop impedance requirements of BS 7671 (see Appendix 9).
70
Sec 10
Fig 10.2: Connections for testing continuity of ring final circuit conductors
10.2a
L N
EB
test
instrument
10.2¢
10.2b
N Laer N Le
connection for
taking readings of R1 + R2
at sockets
71
Sec 10
10.3.3 Insulation resistance 713-04
Pre-test checks
10.3.3(i)
10.3.3(ii)
Tests should be carried out using the appropriate d.c. test
voltage specified in Table 10.1.
The tests should be made at each distribution with the main
switch off, all fuses in place, switches and _ circuit-breakers
closed, lamps removed and other current-using equipment
disconnected. Where the removal of lamps and/or the
disconnection of current-using equipment is impracticable, the
local switches controlling such lamps and/or equipment should
be open.
72
Sec 10
Where any circuits contain two-way switching the two-way
switches must be operated one at a time and further
insulation resistance tests carried out to ensure that all the
circuit wiring is tested.
Test between all the live (phase and neutral) conductors at the
distribution board (see Fig 10.3).
73
Sec 10
74
Sec 10
B14 :¢"OL UOI}LINSU] BdDUL}SISA1
S}Sa} UBIM}9q
AAI] $10}INPUOD
JO© }INIAID
£i_|S \
LAY ee
Buljia2 Bulla.
asol asol
Ge (B) | A
Banoo, Aem-om} sayrzimMs sdwe|
paAowad
we,
3]
eee eereer PP
ule UDd}IMs
$40 . Coe Voce
asnj-}INIIID
3NO uolynq!sjs!
Jeoq
JO suayxeasg
$jO
3}OU
=], 3AI}99}01d S$410}INPUOD
O} S9YI}IMS
SACY
uaaq pa}}Iwo
10} Aj}l4e]>
a}OU
:7 }So}
3y} sa} pynoys Ajjeiziul
aq palsed
}NO UO
jUawn}sul
ay}
uo}
e]]e}SU!
3}a;dWI0
Resistance readings obtained should be not less than the
minimum values referred to in Table 10.1.
Single-phase
Test between the live conductors (phase and neutral) and the
circuit protective conductors at the distribution board
(see Fig 10.4).
Three-phase
Test between SELV and PELV circuits and live parts of other
circuits at 500 V d.c.
75
Sec 10
HI4 :y"OL UOI}EINSU] d2uUe}SISA1
S}S9}
O} Yes
Sec 10
ae }---
r a | ae ease
i
ee jit i
vf
Do Ks K
BS fea asol
Buia.
Bsa
Buijia.
A
|
sdwe|
paaowsas
ial
sauryums
Aem-om}
pavowa
3}0U
:1 9AI}I9}01d S10}INPUOD
O} S29YI}IMS
BALY
uaeq pazzIwo
40} Ajlie]> }S9}
a}OU
:7 9y} Sa} pynoys AjjeiIUu!
aq palsies
}NO UO jUaUUNI}sSUI
ay} 3}a;dWI0>d UO!}L]]/e}SUI
uosipZ
8€Z09
*P2IJLIBA
SAapjoyduie;
yo Ly pue £7]
O} Sd NJ
uo!3Nq!3sSIp
O} 3q
pieog
Ayiiejod
BAeY
suayeaug
JO
Ul]
S280p}OU
maids
Asesodwa}
Stel
18h
Ts]
18)
ie
U8
IS
Tsls
= ay}
40}INPUOD
YdIMs
sasnj
:a}0u
|e
ule
JNO
$40
BAI}I9}O1d {je
JO
:310N
iND419
0} 40}
payiwo
ugaqAjse}9
Y}IMS
sey
Hurzyb1
e
Uo
3s9}
zu
Ayejod
:¢°OL }S9}
USIP
M2J9S
Japjoudwe|
jUauNIysuUl
B14
77
Sec 10
10.3.4 Polarity 713-09
The measured resistance should meet the following criteria and 542-02-02
those of 10.3.6 but in any case should not exceed 200 ohms:
For TT systems, the value of the earth electrode resistance Rain 413-02-20
ohms multiplied by the operating current in amperes of the
protective device IAn shall not exceed 50 V e.g. if Ra = 200 Q, then
the maximum RCD operating current should not exceed 250 mA.
78
Sec 10
10.3.6 Earth Fault Loop Impedance 713-11
The values of Z; determined should be less than the value given 413-02-08
in Appendix 2 for the particular overcurrent device and cable. 543-01-03
79
Sec 10
10.3.7 Measurement of prospective fault current 713-12-01
80
Sec 10
SECTION 11. OPERATION OF RESIDUAL CURRENT OPERATED DEVICES
(RCDs) AND RESIDUAL CURRENT BREAKERS WITH
OVERCURRENT PROTECTION (RCBOs) 713-13-01
The tests are made on the load side of the RCD, as near as
practicable to its point of installation, and between the phase
conductor of the protected circuit and the associated circuit
protective conductor. The load supplied should be disconnected
during the test.
81
Sec 11
11.5 Additional Requirement for Supplementary Protection 412-06-02
The test button will only operate the RCD if the RCD is
energised.
Confirm that the notice to test RCDs quarterly (by pressing the 514-12-02
test button) is fixed in a prominent position ((see 6.1(xi)).
82
Sec 11
APPENDICES
CONTENTS
Appendix Page
1 Maximum demand and diversity 84
83
APPENDIX 1
84
Appx 1
be chosen being the responsibility of the designer of the
installation.
TABLE 1A
Current demand to be assumed for points of utilisation and
current-using equipment
Point of utilisation or current-using Current demand to be assumed
equipment
Note 1: See Appendix 8 for the design of standard circuits using socket-
outlets to BS 1363-2 and BS 4343.
Note 2: Final circuits for discharge lighting must be arranged so as to be
capable of carrying the total steady current, viz. that of the lamp(s)
and any associated gear and also their harmonic currents. Where
more exact information is not available, the demand in volt-amperes
is taken as the rated lamp watts multiplied by not less than 1.8. This
multiplier is based upon the assumption that the circuit is corrected
to a power factor of not less than 0.85 lagging, and takes into
account control gear losses and harmonic current.
85
Appx 1
TABLE 1B
Allowances for diversity
86
Appx 1
TABLE 1B continued Allowances for diversity
6. Water-heaters
(thermostatically no diversity allowablet
controlled)
7. Floor warming
installations no diversity allowablet
8. Thermal
storage space no diversity allowablet
heating
installations
87
Appx 1
APPENDIX 2
88
Appx 2
Note: The impedances tabulated in this Appendix are lower than those in
Table 41B1, Table 41B2 and Table 41D of BS 7671 as these are measured
values at an assumed conductor temperature of 10 °C, whilst those in
BS 7671 are design figures at the conductor normal operating temperature.
1.0
1:5 8.00 2.14 1.48 0.91 NP
2.5 to 16.0 1.48
1.0
des NP
2 1.20
4.0 to 16.0
Note: A value of k of 115 from Table 54C of BS 7671 is used. This is suitable for Table 54C
pvc insulated and sheathed cables to Tables 4, 7 or 8 of BS 6004 and for
Isf insulated and sheathed cables to Tables 3, 5, 6 or 7 of BS 7211. The k
value is based on both the thermoplastic (pvc) and thermosetting (Isf)
cables operating at a maximum temperature of 70 °C.
89
Appx 2
TABLE 2B BS 88 fuses
Maximum measured earth fault loop impedance (in ohms) when
overcurrent protective device is a fuse to BS 88
A : (see Note)
(i) 0.4 second disconnection 413-02-05
Table 41B1
; . 543-01-03
Protective Fuse rating (amperes)
conductor
6.0 to 16.0
Note: A value of k of 115 from Table 54C of BS 7671 is used. This is suitable for Table 54C
pvc insulated and sheathed cables to Tables 4, 7 or 8 of BS 6004 and for
Isf insulated and sheathed cables to Tables 3, 5, 6 or 7 of BS 7211. The k
value is based on both the thermoplastic (pvc) and thermosetting (Isf)
cables operating at a maximum temperature of 70 °C.
90
Appx 2
TABLE 2C
Maximum measured earth fault loop impedance (in ohms) when
overcurrent protective device is a fuse to BS 1361
: see Note
(i) 0.4 second disconnection ( 413-02-05
Table 41B1
6.0 to 16.0
Note: A value of k of 115 from Table 54C of BS 7671 is used. This is suitable for Table 54C
pvc insulated and sheathed cables to Tables 4, 7 or 8 of BS 6004 and for
Isf insulated and sheathed cables to Tables 3, 5, 6 or 7 of BS 7211. The k
value is based on both the thermoplastic (pvc) and thermosetting (Isf)
cables operating at a maximum temperature of 70 °C.
91
Appx 2
92
Appx 2
F1EVL
dé eI9GeL CaLy
WuNWIXeEY peunseaw
YES 3jNe} doo] a2Uepaduu!
Ul) (SUYO UDYM JUSLINI4aAOBAI}39}01d
B21ABpP
St & 499C94G-}1NI419
0}
Sa L-LZ8E
AO Sd NA 86809
40 & OdDH
Lv S0-Z0-€
9} Sd NI 600L9
1)( 4IOq70 pue
¢ Spuodas UOI}DBUUODS
S@UI1}IP
-VINDID
ad}
Jayeaigq
(Seuedwe)
J9C31G-INDIID
:azloy anjeny
Jo4 Jo SLL WO4} 1421DyG40 Sd L/9/ SI “Pasn SIU]
SI ajqeyins
JOJ IAd pajze/nsu!
pue payyeays
saiqe>
0} $O
PUB
/8JO}
Sd
7009
410
S9|qe1
v7'
4s| pajejnsul
pue payjyeaus
sajqe>
0} S9/qe]
‘¢ 4109's4O SG “LLZZ AUL¥ ANjeA
si paseq
UO YOG ay} 313se|dowUay}
(rAd) pue Bulneso
(S|)
sajqed Huljeiado
je e WnuwIxew Bunjzesadwa}
$O OL ‘Do
TABLE 2E
Notes:
1 - The correction factor is given by: {1 + 0.004 (Ambient temp - 10} where
0.004 is the simplified resistance coefficient per °C at 20 °C given by BS 6360
for both copper and aluminium conductors
93
Appx 2
APPENDIX 3
TABLE 3A
Applications of cables for fixed wiring
Flat thermoplastic (i) general indoor use in dry (i) additional protection may be
(pvc) or or damp locations. May necessary where exposed to
thermosetting, be embedded in plaster mechanical stresses
insulated and (ii) on exterior surface walls, (ii) protection from direct sunlight may
sheathed boundary walls and the be necessary. Black sheath colour is
like better for cables in sunlight
(iii)overhead wiring (iii)see Note (4)
between buildings (6) (iv) unsuitable for embedding directly
(iv) underground in conduits in concrete
or pipes (v) may need to be hard drawn (HD)
(v) in building voids or ducts copper conductors for overhead
formed in situ wiring (Note 6)
94
Appx 3
TABLE 3A continued
Applications of cables for fixed wiring
95
Appx 3
6 - Cables for overhead wiring between buildings must be able to support their own
weight and any imposed wind or ice/snow loading. A catenary support is usual
but hard drawn copper types may be used.
Thermal insulation
Cable clips
Grommets
Wood preservatives
Creosote
96
Appx 3
TABLE 3B
Applications of flexible cables and cords to BS 6500 : 2000 and BS 7919 : 2001 generally
85 °C heat resisting thermoplastic General, including hot situations, e.g. for pendant
(pvc) insulated and sheathed luminaires
185 °C glass fibre insulated For internal wiring of luminaires only and then
single-core twisted twin and only where permitted by BS 4533
three-core
185 °C glass fibre insulated braided (i) dry situations at high ambient temperatures
circular and not subject to abrasions or undue flexing
(ii) wiring of luminaires
Notes:
1 - Cables and cords having thermoplastic (pvc) insulation or sheath should preferably
not be used where the ambient temperature is consistently below 0 °C. Where
they are to be installed during a period of low temperature, precautions should
be taken to avoid risk of mechanical damage during handling.
97
Appx 3
2 - Cables and cords shall be suitable for the maximum ambient temperature, and
shall be protected from any excess heat produced by other equipment, including
other cables.
3 - For flexible cords and cables to BS 6007, BS 6141 and BS 6500 further guidance may
be obtained from those standards, or from BS 7540 : 1994 "Guide to use of cables
with a rated voltage not exceeding 450/750 V".
4 - When used as connections to equipment flexible cables and cords should be of the
minimum practical length to minimise danger and in any case of such a length
that allows the protective device to operate correctly.
5 - When attached to equipment flexible cables and cords should be protected against
tension, crushing, abrasion, torsion and kinking particularly at the inlet point to
the electrical equipment. At such inlet points it may be necessary to use a device
which ensures that the cable is not bent to an internal radius below that given in
the appropriate part of Table 4 of BS 6700. Strain relief, clamping devices or cord
guards should not damage the cord.
6 - Flexible cables and cords should not be used under carpets or other floor
coverings, or where furniture or other equipment may rest on them. Flexible
cables and cords should not be placed where there is a risk of damage from traffic
passing over them.
7 - Flexible cables and cords should not be used in contact with or close to heated
surfaces, especially if the surface approaches the upper thermal limit of the cable
or cord.
98
Appx 3
Application of suitable coatings before erection, or prevention
of contact by separation with plastics, are recognized as
effective precautions against corrosion.
Special care is required in the choice of materials for clips and 522-05-02
other fittings for bare aluminium sheathed cables and for 522-05-03
aluminium conduit, to avoid risk of local corrosion in damp
situations. Examples of suitable materials for this purpose are
the following:
- porcelain,
- plastics,
- aluminium,
99
Appx 3
APPENDIX 4 522-08
Cables generally
Items 1 to 8 below are generally applicable to supports on
structures which are subject only to vibration of low severity
and a low risk of mechanical impact.
100
Appx 4
For sheathed cables without armour in vertical runs
which are inaccessible and unlikely to be disturbed,
supported by the method described in Item 6 above;
the length of run without intermediate support not
exceeding 2 m for a lead sheathed cable or 5 m for a
thermosetting or thermoplastic sheathed cable.
Overhead wiring
101
Appx 4
14. Support by a catenary wire incorporated in the cable
during manufacture, the spacings between supports
not exceeding those stated by the manufacturer and
the minimum height above ground being in accordance
with Table 4B.
102
Appx 4
avi
Vb
sbuideds
jo syioddns
10} Sajqe>
Ul a/qISsad.e SUO!}ISOd
winwixey| sbuldeds
Jo sdij>
sajqe
payzeays
|yjeyUuOZIIOYH
— yjerxue,
| [yjequoziuoH
= yjeraueA
| fJWUOZOH
wniuiwnye
iG € v S 9
pIe2!19A 8
6
glee
4/&}U0ZLOH
WWW
Jon Bulpaa.xa
6 008
2x3 Bulpsa
6
pue jou BHulpasoxea
GL 0SZ 00” 0021
JO)|je (SAZIS
| 404)||P (SEZIS
Bulpsaax3
G|
pue jou Hulpaadxa
OZ 0002
Bulpaaaxy
0z@
pue jou Hulpaasxa
Ov
103
Appx 4
TABLE 4B
Maximum lengths of span and minimum heights above ground for overhead
wiring between buildings etc
In positions
accessible
to vehicular In positions
Maximum traffic, inaccessible
length of At road | other than to vehicular
Type of system span crossings] crossings traffic*
1 2 3 4 5
¥ i‘
104
Appx 4
TABLE 4B continued
Maximum lengths of span and minimum heights above ground for overhead
wiring between buildings etc
In positions
accessible
to vehicular | In positions
Maximum traffic, inaccessible
length of At road | otherthan | to vehicular
Type of system span crossings| crossings traffic *
1
Note: In some special cases, such as in yacht marinas or where large cranes are present,
it will be necessary to increase the minimum height of span above ground given
in Table 4B. It is preferable to use underground cables in such locations.
105
Appx 4
“LINPUOD aU} JO Ja}@WEIP apIs}NO ay} Saw} G°Z UEY} $S2] JOU aq PjNoys puaq }NPUOd e 4O sniped JSUU! aul
‘und sy ul payoddns aq 0} paau jou saop }! Jey} Y}HuUa] YINs Jo aq PINOYs HNPUOD 9/q!xe}} VE
“sBUITY JO spUag JO WLU QOE UIYIM PauO!}isod aq pynoys syuoddns ‘uni s} ul payuoddns
aq 0} pasinbad AjjewsOU JOU SI }INPUOD a/qIxXEI} VY ‘pasn ae s4ajdnod Huluay}Huaijs jeisads a18yM JO ‘pamo)|O}
ay ‘7
ag snw suOo!NJYsU! SJaun}eynueW ay} asayM ‘Hulyunsy uolsuadsns 6ulzy61| 0 Ajdde you op sasnbiy aroge
U!
"ssd.1]S JEDIUCYIOWW 19Y}O 0} pasodxe Jou Ss! HupyjuNds} JO JINPUOD 84} 3e4} eluNsse Aaul ‘spaepueys ysiziig JUeAS|a1 34}
ay]*|
paipoeds s}iwl| jewUJay} ay} pue suo!}zejnBay au Aq payqiwuad sajqed 40 [ly wWinwIxeW Jo} Moje pazejnge} sbuldeds
'Sa10N
OL Ov Dulpaasx3
30 Ot Hulpea sxe jou pue Gz Bulpee dx
90 Gz Bulpeedxe JOU pue 9| Hulpee 2x4
S‘0 9| Bulpae axe JON
WWW
fs 9 S v € ¢c
jedV2/\ je}UOZIIOH jeriwa/ je}UOZIIOH jera/ je}UOZIIOH
UINpuUOd JO azis |eUILION
a!G2lld Burejnsur pibry jeyows pibiy
suioddns uaamjaq a2uejsIp WNWIXe|\
s}iInpuOd 410} sjioddns jo shuldeds
ov 1dVL
Appx 4
106
Appx 4
107
‘sBulnqly JO spuagq Jo WW OE UUM pauOl}sod aq pjnoys syioddns “uni s} ul peyoddns
aq 0} pauinbas AjjeWOU }OU SI }INPUOD a|qIXaI} V ‘Pasn aie siajdnod Buluay}buaijs jeIdeds a194yM 10 ‘pamo}|O}
JaunpeynueW ay} aiaym ‘Hulyuns} uoisuadsns Huljy61| 0} Ajdde you op sainbiy aroge au *Z
ag ysnw suoINJysU! S$
"§S}S |EDIUPYIOW J9Y}O O} pasodxa }OU Ss! HulyUNJ} JO JINPUOD ay} Fey} atuNsse ABY] “spsepueys Ysiiig JUeAS|94 34} U!
paijioads sjiwl| eWay} ay} pue suo!}e;nBay au} Aq payjiwuad sajqed Jo ||lJ WNWIXeW 104 Mo||e pazeinge} sbuldeds ay] “|
‘S810
07 0005 BHulpaaax
072 0005 Bulpaaaxea jou pue 90¢z Hulpsedx3
GOL 00SZ BHulpaesxe you pue QOS] Hulpas 2x3
S‘0 00S| Buipeasxe jou pue 99/ +Hulpeedx3
00Z S5uipeasxe jou pue 99¢ Hulpaedx3
v € ¢c
S
Bulzeynsul
suioddns usamjeq a duejsip WNwIxey\|
BHuiyjuns} ajqe> 103 syioddns jo shulseds
ar J1aVL
TABLE 4E
Minimum internal radii of bends in cables for fixed wiring
Not exceeding
Thermosetting or 10 mm
thermoplastic (pvc) Non-armoured
(circular, or circular Exceeding 10 mm
stranded copper or but not 4(3)t
aluminium exceeding 25 mm
conductors)
exceeding 25 mm 6
Thermosetting or Armoured or
thermoplastic (pvc) non-armoured
(solid aluminium or
shaped copper
conductors)
108
Appx 4
APPENDIX 5
109
Appx 5
For cables and/or conduits, not covered by this Appendix advice
on the number of cables which can be drawn in should be
obtained from the manufacturers.
Add the cable factors together and compare the total with the
conduit factors given in Table 5B.
TABLE 5A TABLE 5B
Cable factors for use Conduit factors for use
in conduit in in
short straight runs short straight runs
Conductor Conduit
Type of cross-sectional diameter | Conduit
conductor area mm? mm factor
16 290
20 460
25 800
32 1400
Stranded . 38 | 1900
50 3500
63 5600
110
Appx 5
Single-core thermoplastic (pvc)-insulated cables in straight
runs of conduit exceeding 3 m in length or in runs of any
length incorporating bends or sets.
Add the cable factors together and compare the total with the
conduit factors given in Table 5D, taking into account the
length of run it is intended to use and the number of bends
and sets in that run.
TABLE 5C
Solid 16
or 22
Stranded
The inner radius of a conduit bend should be not less than 2.5
times the outside diameter of the conduit.
111
Appx 5
(40}De} WW ZE) XZ BSN Jay@WeIP WLU EQ JOJ
(40}9e4 WwW ZE€) X: ONC te aia osn J9}IWEeIpP WW Qs 404
(40pe} WLW ZE) X pL °° BSN Ja}OWeIP WWW BE 1O4 s10Pe4 [EUOIIPPY
OL
ce v Sv S 9 l 8 6
g pue Vv €
Sc
c69009 vLV
09c_ ~=oiLHL 98
sajqgel a
6¢S
c6~ Ss OSL 16
c€€ BL LLL cL
88E ELC O€L Aq pasenoD L
spueq Jno4 spueg ses, spueg OML puagq aud qyb1e135 WW
jo und
ce Sc 0c QL SZ Oza OL CGM OCEEEOL SZ 0c GZ 0Z~—OPLs Huy
Ww ‘Ja}aWeIp JINPUOD
sun }461e13s Huo] pue spuaq Hulzesodooul suns 104 s10}zDe4 B]qQeD
as a1aVl
Appx 5
112
Single-core thermoplastic (pvc)-insulated cables in
trunking
Add all the cable factors so obtained and compare with the
factors for trunking given in Table 5F.
TABLE 5E
Cable factors for trunking
Stranded
Note:
(i) These factors are for metal trunking and may be optimistic for
plastic trunking where the cross-sectional area available may be
significantly reduced from the nominal by the thickness of the wall
material.
113
Appx 5
TABLE 5F
Factors for trunking
Dimensions of Dimensions of
trunking trunking Factor
mm xmm mm
x mm
Ea
50 x 38 200 x 100
50 x 50 200 x 150 13001
75x25 200 x 200 17429
75 x 38 225 x 38 3474
75x50 225 x 50 4671
7 Xa 225x75 7167
100 x 25 225 x 100 9662
100 x 38 225 x 150 14652
100 x 50 225 x 200 19643
100 x 75 225 x 225 22138
100 x 100 300 x 38 4648
150 x 38 300 x 50 6251
150 x 50 300 x 75 9590
150x 75 300x 100 12929
150 x 100 300 x 150 19607
150 x 150 300 x 200 26285
200 x 38 300 x 225 29624
200 x 50 300 x 300 39428
200 x 75
For sizes and types of cable trunking other than those given in
Tables 5E and 5F, the number of cables installed should be such
that the resulting space factor does not exceed 45 % of the
net internal cross-sectional area.
114
Appx 5
APPENDIX 6 Ch 52
Current-carrying Capacity
Procedure
In = Ib
Ik> Bide
C3 Cj Cg Cr
Where :
Ca _ is the correction factor for ambient temperature, App 4,4
see Tables 6A1 and 6A2
CG is the correction factor for thermal insulation,
see Table 6B
Cg is the correction factor for grouping,
see Table 6C
Cr isthe correction factor 0.725 for semi-enclosed fuses 433-02-03
to BS 3036
115
Appx 6
Voltage Drop
Ambient temperature °C
Type of Operating
insulation temperature 5)SOR|ES5 Als || 5X0) |] (S55 65
Thermoplastic
(general
purpose pvc)
le adel é.
Note: Where the device is a semi-enclosed fuse to BS 3036 the table only
applies where the device is intended to provide short-circuit protection only.
Ambient temperature °C
Type of Operating
insulation temperature | 25 | 30 | 35 | 40] 45] 50] 55 65
Thermoplastic
(general
purpose pvc)
116
Appx 6
Thermal Insulation 523-04
50
100 0.81
200 0.68
400 0.55
500 and over
117
Appx 6
(EL pours) suoddns
=> LL0 | 8£0 | 8Z:0 | 8Z°0 | 6Z'0 | 08'0 | Z8'0 | 98°0 Jappe| Uo Buly ano} a40313;NW Jahe| ajHuls
jedII9/\ (LL pouraw)
S30
Hulyono} ‘Aes} ajqed
je}owW pa}esojied e
s8'0 jejuozOH| uo a109-a/buys 4ahe| aj6uls
xpareds (LL Pour)
oa
So
JEJUOZIIOY JO |edIJ8A
Res} ajqed je}awW pa}esojed
Hulysnol| e uo a709/7/NW JaKe| ajHuls
co :
De
Xe)
So
o
xpeoeds
So
or
=
(L Pour)
ade LNs 51|)/e}@W-UOU
BulysnoL 2 0} paddy) saAe] ajbuis
co
So
a)
(L Pours)
80 | 6E'0 | Lv'0 | Ev'0 | Sv’'0 | 8r'0 | 050 | Z5°0 | 7S'0 | Z9°0 S90 | 0Z'0 | 080 e0} Paulp paddl|>
adepns d1|]2}aWW-UOU
pue paysung JO (710 € POUJsI/|) Peso}>uy
S8|qeD B4OIII|NW JO S}INIIID JO JAQUINN
(8) 40392} UO!}D9II0D
xx 2]/Qe) 341031}/NW SUO UCU} sJOW JO ‘sojqe> 3109-a]6uis JO }INDAID BUO ULY} DIOW JO sdnoib AO} S10}IE} UOIPIIAIOD
Lay age siopey Buldnos5 59 31EVL
Appx 6
118
Appx 6
119
* pajejnge} jou 10e} UO!}DIIIOD
‘LZ9L SG 40 ZAP BIGeL Bas sajqe> pazejnsul jesaUuIW 104
"$2|GeD (W-N) 0} Hulpuodsas0d 1039e4 Huljzes dnoib ay} Bulsn Aq pazis aq ued sajqed 19430 34}
saiaduue 455 ¢'9 Ue} Ja}2016 JOU aJe YDIYM speo| Aed dnosb ay} Ul Sajqe> [I 4! ‘JAABMOH “4 payejnqe} ay}
0} patjdde ®> yo 10;9e} UOIINpas dnoJb e auinbas AjjewsOU pjnom sajqe) pepeo| N Jo dnoJb e ‘ajdwexa 104
‘dnoi6 au} 40 3sa4 ay} JO} Jopey Hulzes ay} Hurureygo yo asodind ay} Joy pasoubl aq Aew 7! ‘burjes
padnoib sil Jo % OF UeY} a10W JOU AuJed 0} payadxea SI ajqed e ‘suo!}puo? Hul}e4ado UMOUY 0} Buimo ‘}}
‘dnoib
ay} ul sajqe> ay} $o Aue Aq pale aq 0} JUaIIND WINWIXeWW a4} SI S1O}Ie} ayelidoudde ay} 4o uoljed1|dde
WOJJ PAALAP }UIIUND JO aNjeA BY] “aZIs BUO Jo |]e Sa}qe>d Jo sdnoJb 0} ajqedijdde ae 9/qe} ay} U! SOP! BYL
‘dnos6 au} ul ajqed Aue jo asnzesadua} Buljzesado ysamo| ay} UOdN paseq aq |jeys
Burzes JUaLND ay} 494}960} pednosb ase sainjesadiua} Hulyesado 10JNpuOD Hulayjip Huirey sajqed Usy
‘paijdde aq paau 1032} UO!}DI1I09 OU ®qZ Spaedxa sajqed Juare[pe UBaMjeq sadUeJeAa|>
j2JUOZOY ay} aay “2q Ja}@WeIP a]/GeD aUO jsea] Je JO SadeJUNs JUaDe[pe UBaMjeq adUeJea]9 e Aq pardeds
‘D9 ATAVL OL SALON
LL OL
‘ye aseud | d°e aseyd } |!0j,01] 10 }!0494} 10
-334Y} -3ajy} | Buryonoy | Hurysno} | Burysno} | Hurydno}
sa}qe> € JO]sajqed € 10] pue ie} pue pue je}, | pue .ej}
‘ye aseyd | “dp Jo *2°e | ‘d"p Jo “d"e| “d"e ase |e] “D"p 40] “d°e aseyd | “d"p JO “D°e| ‘De aseud |‘D"p Jo ‘3"e} ‘d"e aseud | *d"p 40 “d°e
-334Y} aseud aseud -901y} | ‘de aseyd| -aa1y} aseud -33JU} aseud -991U} aseud
“10421 -3|6uls -3|6uls ‘sajqeo -3|Huls ‘sajqeo -9|6uls ‘sa|qe> -9|/6uls ‘sajqeo -9|/Huls
sajqed¢€ | ‘sajqedz | ‘sajqed 7 pjioe ‘sa|qed Z p4jioe ‘Sa|qed Z p4joe ‘Sa|qed Z p4jioe ‘Sa|qed Z
paseds podeas (JEd!SA JO (918 bulyunsy (a3 [Jem Huljzeynsul eve
el} +e|} jezuozioy Aes} ajqed Ul JO [JEM e UO Ajjeway} ul Jeuolpes
Lopes jedwap |je}UOZIOH po}eJOjJad e uo) (Wes1p paddy) }INPUOD UI paso|dUe) }INPUOD UI Paso|dUa) -SSOJD
(ule 8844) ZL POUJSI) BDUDIIJOY LL pou BuaJajoy | POU] BDUSIBJaY | € POYJS/\| BdUSIBJOyY p Pou BuUdJeJay |40}DNpUOD
7009 S@ (Sesedwy) ALIDWdVD ONIAYYVD-LNIYYND
J. OL iaunjzessdwa} Huljzesado 10]9NPuUOD ‘dD, OF :eunjyesodwa} JusIquy
(SHOLDNGNOD YAddOD)
yzeays }NoYM JO YM ‘pasnowue-uOU ‘(| 3}0U) UORe]NSU! HUIZZaSOWIAY} JO (2d) 21)se]dou494} Bulaey sajqe> 2402-2/6uls
aigeL VLOr Lqg9
414aVL
Appx 6
120
Appx 6
121
“suolze}je}sul
paXl} Ul pasn ase sajqed ay} Baym 6 pure g Saige] LEZI Sg O} Sajqed IAd BHuljsisas Jeay D, 06 O} pue
(2)L PIG2L pO09 Sg 0} Sajqed a/q!xa]} 0} ajqerijdde osje ase g 0} Z SUUNIOD UI Sai}19eded HulAsed-JUaIND BYyL
‘xipueddy
SIU} O} UOIPNPOJ}U! BY} as ‘9EOE Sg O} ASN} pasojrua-ias e Aq pa}da}01d aq O} S| JOJINPUOD ay} B19Y/\\
“LLOL SE $9 VLAV PIGeL 92S -
Vat
siqel
dn
ae
sainjessdwa}
0}
Buljyesado
10}9nNpuod
JUIN.
06
D,
ajqeydade
ay}
Huljes
S|
paseaidul
JIU "D. OL Hulpaaoxa jou aunzesadua} e }e UNI YDdIYM Sajqe> YIM a}e1ado 0} paubisap saliossaq7e
JO JUaWAINba 0} payeUUOD sajqed JO} ajqedi|dde ase uO!}eiNsul HulZesOWaY} YIM sajqed oJ sHuljes BY
‘149 HIE VL OL SALON
“LLOL Sd 40 v XIpueddy aas JUaW}eaJ} JA}/N}
2 104 “AYID1|AWIs 404 pa}!WoO SI ‘8ZIS JOJINpUOD aAoge pue ,WW GZ JO} papiAold Ajjensn dosp aberOA jo JUawaja 9AI}De9J BY] :@JON 4
‘doip a6ei0A sa61e] Ul 3)NSad [IM (D9 ajqe| 0} sajoU das) Z| POU BDUaIJAJayY UI Palji9ads asou} UeY} JabHie; sHuldeds :a}0N x
v
(JJeM e UO JO (Buryono} (J2EM e& UO JO uae
(6ulysno} (10243 Ul) Ul *D}9 JINPUOD ‘sKe1} UO O | Ul D}9 JINPUOD as
aseud-ajbuls
(,pareds 7e}}) pue 3e}}) ZL U! paso|>ua) (xpareds) =| Paulp padd)|>) | ul pasojdua) -SSOJD
aiadweaseyd-aaiy}
ZL POY =| LLB L SPOUISI PS LL ‘L SPOYISIN] 78 € SPOYISII CL POUIPIN, | LLB L SPOUIN] 78 ESPOUIPIN| 2°P | 4039Np
adudIajay aduaIajay aduasajoy adudJaoy adudJajay aduaJajay aouasiajay = |S9/Ge2 Z| -yo>
:aunyesodwa}
abeijoa
:(84}aW
doip
Jad)
Jad
Do.
OL ‘sajqed
‘sajqe>
JOJNPUOD
7€pD"e
Hulzesado ‘de
JO
aLar aiqeL cd9 41gVL
Appx 6
122
Appx 6
123
JES|ABAO SOJON 99S
‘de aseud de aseud ‘de aseud ‘ye aseud
-aaiyy ‘ajqe> | “2p4o‘re | -aeiy} ‘ajqed | ‘D2 p4ode | -sesy}‘aj]GQe> | “Dp4so‘ve | -9e14} ‘sjqQe> | "Pp JO “2'e
3109-INO} aseyd-ajbuis 9409-INOJ aseyd-ajbuls 94109-INOJ aseyd-ajbuls 9109-INOJ aseyd-a|buls
| 10 xajqe> | ‘ya]qe> e102 | 1 Jo yajqed | ‘yajqed e109 | 140 xa|qQe> | ‘ya/Ge> 910 | | JO x9/Ge> | “~2/Ge2 2109
9409-994} | -OM} | 9109-991} | -OM} | 9109-3914} | -OM} | 9109-391U} | -OM} |
(4le Ba44) EL POUR (Burjunsy ul so
QDUdIBJ9yY 1O ‘Huljlad JO [jem e UO (D}9 “|JeM pezejnsul ease
(Aes} 8]qe) pazesOjjed e uo) (as1p peddi)>) }INPUOD UI paeso|>dUs) ue Ul paso|duUe) jeUOI}DAS-sso1D
LL pou Ls edusiefay | pou sdUsIaJ9y € POUJ2/\| BDUSIBJ9Y py POUJS B2Us19}9y Jo}DNpuoD
6Z9ZL SE ‘7009 Sa :(Sesedwiy) ALIDVdVD ONIAYYVI-LNAYYND
>, OL aunyesadwa} Buljesado J0JNPUOD *D, OE :eun}pesodwWea} Jusiquiy
(SHOLDNGNOD YaddOD) ‘P24noue-uoU ‘(| a}0U) UOHZe]NSU! HUI}}aSOUI9Y} 40 (20d) 2143se}dow4eY} Buiaey sajqe> 2410913/nNWI
Ved 9|GeL 149 F1aVL
124
Appx 6
SHLON
OL HIEAVL
-TH9
=“ BYL sHulyes
40} SajqerYUM HulyWasOWaY}
uo!}e|Nsu!
ase ajqedi|dde
4104 sajqed pa}aUUOD
0} JUaWAINb~a
JO
saiiossanzepaubisap
0} a}e1ado
YIM Sajqe> YDIYMUNI 7e e aiN}esadW9}
OU Hulpaeadxa
OL D. JOUM
paseasoul si Huljes }UaIIND 9} ajqeydadde ae Dd, YG 0} dn saunjesadwia} Huljzesado 10}9Npuod ye
“LLOL SE 40 VAP PIGe] Ves -
SI
°Z
0}
O}
O}
Sg
9q
ss
Aq
Bas
BY}
BY}
S14}
BSN}
‘QEOE
DIBUN
“Ex YUMJO JNOYUM 9AI}D9}OJd “1OJINPUOD
JE|NIIID $10JINPUOD
a4e pawinsse
10, sazisdn 0} pue Bulpnj>u!
9} ‘pw
pa}da}01d
JOPNPUOD
sanje/A
10} 1a6se]sazis a}ejai
0} padeys siopNpuoOd
pue Aew Ajayesaq patjdde
0} JE|NIIID "SJOPNPUOD
*‘xipueddy
UOIJINPOJ}U!
PasojUa-IWas
TABLE 6E2 Table 4D2B
Voltage drop: Conductor operating
(per ampere per metre): temperature: 70 °C
Note: The reactive element of voltage drop usually provided for 25 mm?
and above conductor sizes is omitted for simplicity. For a fuller
treatment see Appendix 4 of BS 7671.
125
Appx 6
TABLE 6F Table 4D5A
70 °C thermoplastic (pvc) insulated and sheathed flat cable
with protective conductor
(COPPER CONDUCTORS)
BS 6004 Table 8
CURRENT-CARRYING CAPACITY Ambient temperature: 30 °C
(amperes): Conductor operating temperature: 70 °C
(mV/A/m)
1 44
1.5 29
2.5 18
4 11
6 78
10 4.4
2.8
Notes:
126
Appx 6
APPENDIX 7 App 6
CERTIFICATION AND REPORTING
The certificates are used with the kind permission of the BSI.
The introduction to Appendix 6 of BS 7671 : 2001 (Model forms for certification and
reporting) is reproduced on this page.
Introduction
(i) The Electrical Installation Certificate required by Part 7 of BS 7671 shall be made out
and signed or otherwise authenticated by a competent persons or persons in respect
of the design, construction, inspection and testing of the work.
(ii) | The Minor Works Certificate required by Part 7 of BS 7671 shall be made out and
signed or otherwise authenticated by a competent person in respect of the
inspection and testing of an installation.
(iii) |The Periodic Inspection Report required by Part 7 of BS 7671 shall be made out and
signed or otherwise authenticated by a competent persons in respect of the
inspection and testing of an installation.
(iv) Competent persons will, as appropriate to their function under (i) (ii) and (iii) above,
have a sound knowledge and experience relevant to the nature of the work
undertaken and to the technical standards set down in this British Standard, be fully
versed in the inspection and testing procedures contained in this Standard and
employ adequate testing equipment.
(v) Electrical Installation Certificates will indicate the responsibility for design,
construction, inspection and testing, whether in relation to new work or further
work on an existing installation.
Where design, construction and inspection and testing is the responsibility of one person a
Certificate with a single signature declaration in the form shown below may replace the
multiple signatures section of the model form.
FOR DESIGN, CONSTRUCTION, INSPECTION & TESTING.
| being the person responsible for the Design, Construction, Inspection & Testing
of the electrical installation (as indicated by my signature below), particulars of
which are described above, having exercised reasonable skill and care when
carrying out the Design, Construction, Inspection & Testing, hereby CERTIFY that
the said work for which | have been responsible is to the best of my knowledge
and belief in accordance with BS 7671: ............ , amended to ...........+ (date)
except for the departures, if any, detailed as follows.
(vi) A Minor Works Certificate will indicate the responsibility for design, construction,
inspection and testing of the work described in Part 4 of the certificate.
(vii) A Periodic Inspection Report will indicate the responsibility for the inspection and
testing of an installation within the extent and limitations specified on the form
report.
(viii) A Schedule of Inspections and a Schedule of Test Results as required by Part 7 shall be
issued with the associated Electrical Installation Certificate or Periodic Inspection Report.
(ix) When making out and signing a form on behalf of a company or other business
entity, individuals shall state for whom they are acting.
(x) | Additional forms may be required as clarification, if needed by non-technical
persons, or in expansion, for larger or more complex installations.
on
(xi) The IEE Guidance Note 3 provides further information on inspection and testing
completion and for periodic inspections.
127
Appx 7
ELECTRICAL INSTALLATION CERTIFICATES
NOTES FOR SHORT FORM F1 AND STANDARD FORM F2:
The page numbers for each of the Schedules of Test Results should be
indicated, together with the total number of sheets involved.
The maximum prospective fault current recorded should be the greater
of either the short-circuit current or the earth fault current.
The proposed date for the next inspection should take into
consideration the frequency and quality of maintenance that the
installation can reasonably be expected to receive during its intended
life, and the period should be agreed between the designer, installer
and other relevant parties.
128
Appx 7
Form Fl Form No 123/1
ELECTRICAL INSTALLATION CERTIFICATE (notes 1 and 2)
(REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS 7671 [IEE WIRING REGULATIONS])
None
The extent of liability of the signatory is limited to the work described above as the subject of this Certificate.
129
Appx 7
PARTICULARS OF INSTALLATION REFERRED TO IN THE CERTIFICATE '* Boxesjand ertor oetate 25 Peo
Means of Earthing Maximum Demand
Distributor’s facility uy Maximum demand (load) .............:0.. 60. Amps per phase
Earthing conductor: material --- Copper eae CSA) oo... f Gr mm2 connection verified My
BS, Type
yl BS EN 60439-3 No. of poles oie Current rating ........ S0...A Voltage rating ......230...V
SCHEDULES (note 2)
The attached Schedules are part of this document and this Certificate is valid only when they are attached to it.
ie ecu Schedule(s) of Inspections and ......... Schedule(s) of Test Results are attached.
(Enter quantities of schedules attached).
Page 2 of 4 (note 5)
You should have received an original Certificate and the contractor should have retained a duplicate Certificate. If you were the
person ordering the work, but not the user of the installation, you should pass this Certificate, or a full copy of it including the
schedules, immediately to the user.
The "original" Certificate should be retained in a safe place and be shown to any person inspecting or undertaking further work
on the electrical installation in the future. If you later vacate the property, this Certificate will demonstrate to the new owner that
the electrical installation complied with the requirements of British Standard 7671 at the time the Certificate was issued. The
Construction (Design and Management) Regulations require that for a project covered by those Regulations, a copy of this
Certificate, together with schedules is included in the project health and safety documentation.
For safety reasons, the electrical installation will need to be inspected at appropriate intervals by a competent person. The
maximum time interval recommended before the next inspection is stated on Page 1 under "Next Inspection”.
This Certificate is intended to be issued only for a new electrical installation or for new work associated with an alteration or
addition to an existing installation. It should not have been issued for the inspection of an existing electrical installation. A
"Periodic Inspection Report" should be issued for such a periodic inspection.
The Certificate is only valid if a Schedule of Inspections and a Schedule of Test Results is appended.
130
Appx 7
Form F3 Form No123 /3
SCHEDULE OF INSPECTIONS
Methods of protection against electric shock Prevention of mutual detrimental influence
(a) Protection against both direct and indirect (a) Proximity of non-electrical services and other influences
contact: (b) Segregation of band I and band II circuits or band II
N
insulation used
(i) SELV (note 1)
WZal (ii) Limitation of discharge of energy
(c) Segregation of safety circuits
NNNN
(c) Labelling of protective devices, switches and terminals
(iv) Placing out of reach (note 4)
(d) Identification of conductors
NSSISINS
(Vv) PEEV:
Cables and conductors
(vi) Presence of RCD for supplementary
protection = Routing of cables in prescribed zones or within
mechanical protection
(c) Protection against indirect contact:
S Connection of conductors
(i) | EEBAD including: Erection methods
Presence of earthing conductor
CO Selection of conductors for current-carrying capacity and
AN
NAN
N
Presence of circuit protective conductors voltage drop
Presence of main equipotential bonding (e) Presence of fire barriers, suitable seals and protection
conductors against thermal effects
Bl
NINN
N
bonding conductors
(a) Presence and correct location of appropriate devices for
Presence of earthing arrangements for isolation and switching
combined protective and functional
(b) Adequacy of access to switchgear and other equipment
purposes
\ (c) Particular protective measures for special installations
eS Presence of adequate arrangements for
and locations
alternative source(s), where applicable
(d) Connection of single-pole devices for protection or
Presence of residual current device(s)
switching in phase conductors only
L (il) | Use of Class I! equipment or equivalent
(e) Correct connection of accessories and equipment
insulation (note 5)
(f) | Presence of undervoltage protective devices
hal (iii) Non-conducting location: (note 6)
Absence of protective conductors (g) Choice and setting of protective and monitoring devices
for protection against indirect contact and/or overcurrent
(iv) Earth-free equipotential bonding: (note 7)
Presence of earth-free equipotential (h) Selection of equipment and protective measures
AN
AN
N
NsIN
NN
bonding conductors appropriate to external influences
\ (v) Electrical separation (note 8) (i) Selection of appropriate functional switching devices
Page 3 of 4
131
Appx 7
O ,o5R,
paopeoe d 5]|NsaJ 4S9} $O BjNPays UO $a}0U Bas x
aud
:sejou jeloeds pue suonejnBey Burs wos suoiyeineq
iz eee aaa ses
| aes [ome ae Bou: 5
GL L|_ 00% | #0F p| 0 — 7 ; 2 D
50 as: Ov — fm fi D 4amoys
IMoHITL SE 00c
Os i a f D 4ayooD
Yi 50 Ta OF
y
‘GM Vu 00c 60 - O€ — €0 i ‘ i D umop s7ayI0S
Agua,
ee HO) Cm Oa ea. #0 GATOS, ae G dn s1ayo0S
Lou, f,i= De ZS Oca as = Lies Orbe \isar or & unop sy
A es nO: os = = re Gitano or D dn syybiT
tL ar ra 1 re 6» gx | Lx 9% S v € z 1
St OW | 6 Oo Oo gui | 7Wwu Vv
sui oO AK OW
+ u
awl} ! yyeqz | any \ 4
4ayuyO | Gdy SZ i Jeary | aan uy zy} @y+ ty od> any | Burney | adAy
aoue e
Busey -paduu} | a2ueysisay s40}NpuoD wg
syseway jeuonoun4 dooq ° uolje|nsu| AyinuryuoD Buin :Ayoedes
yyeq ‘al PINDIID-OYS , uoljdidsag WNUID
a0lneq
syjnsay JsoL JUALINDBAO,
Jif; PHON\ 40 uonduoseq
seseereerereneseeseneeaeeenenneriyig tit ous 14 mdi jiassaiont pin TaIuIp F pub 7 syina1is SIG Kil OE Buse} 0} ajqesoujna juewdinbS
‘i 98]U09 JOAJIPU! JsuLeBe UONDa}Od jo poay
‘Cope 40180 GO" wy aunyeuBbis
ee ore uoleinsul
pee oe :Aynuluod suo ep cituoye 97, BP: Ss Y
e0uepeduut doo} eb/S-O-NL/Sehit Adding jo edAl , FOOT t/0d 2a sel
TIDE
S]UaUINASU] aaa 0 Sua ie 110}0B4JU0D,
SLINSAY LS3L AO AINGAHIS
v/ exp ON WHOA p WLIO4
Appx 7
132
NOTES ON SCHEDULE OF TEST RESULTS
* Type of supply is ascertained from the distributor or by inspection.
* Ze at origin. When the maximum value declared by the distributor is used, the effectiveness of the earth must be confirmed by a
test. If measured the main bonding will need to be disconnected for the duration of the test.
* Short-circuit capacity of the device is noted, see Table 7.2A of the On-Site Guide or 2.7.15 of GN3
* Prospective fault current (PFC). The value recorded is the greater of either the short-circuit current or the earth fault current.
Preferably determined by enquiry of the distributor.
The following tests, where relevant, shall be carried out in the following sequence:
*6 Continuity
Where Test Method 1 is used, enter the measured resistance of the phase conductor plus the circuit protective conductor (R1+ R2).
See 10.3.1 of the On-Site Guide or 2.7.5 of GN3.
During the continuity testing (Test Method 1) the following polarity checks are to be carried out:
(a) every fuse and single-pole control and protective device is connected in the phase conductor only
(b) centre-contact bayonet and Edison screw lampholders have outer contact connected to the neutral conductor
(.) _ wiring is correctly connected to socket-outlets and similar accessories.
Compliance is to be indicated by a tick in polarity column 11.
All the preceding tests should be carried out before the installation is energised.
*11 Polarity
A satisfactory polarity test may be indicated bya tick in column 11.
polarity.
Only in a Schedule of Test Results associated with a Periodic Inspection Report is it acceptable to record incorrect
*12 Earth fault loop impedance Zs
column 6 to
This may be determined either by direct measurement at the furthest point of a live circuit or by adding (Ri + R2) of
used.
Ze. Ze is determined by measurement at the origin of the installation or preferably the value declared by the distributor
or App 2 of GN3.
Z, = Ze + (R1 + R2). Zs should be less than the values given in Appendix 2 of the On-Site Guide
*13 Functional testing
in the device.
The operation of RCDs (including RCBOs) shall be tested by simulating a fault condition, independent of any test facility
Record operating time in column 13. Effectiveness of the test button must be confirmed.
See Section 11 of the On-Site Guide or 2.7.16 of GN3.
that they are properly
*14 All switchgear and controlgear assemblies, drives, control and interlocks, etc must be operated to ensure
mounted, adjusted, and installed.
Satisfactory operation is indicated bya tick in column 14.
;
Earth electrode resistance
required.
The earth electrode resistance of TT installations must be measured, and normally an RCD is
value on Forms 1, 2 or 6 as
For reliability in service the resistance of any earth electrode should be below 200 2. Record the
appropriate. See 10.3.5 of the On-Site Guide or 2.7.13 of GN3.
133
Appx 7
Form F 2 Form No124 /2
ELECTRICAL INSTALLATION CERTIFICATE (notes 1 and 2)
(REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS 7671 [IEE WIRING REGULATIONS])
DETAILS OF THE CLIENT (note1) 7 /,,,
dev loper Ltd.
ei
INSTALLATION ADDRESS
Description of installation:
Warehouse/factory with
Extent of installation covered by this Ce: Addition to an
existing installation
Alteration to an
existing installation
FOR DESIGN
of which are described
\We being the person(s) responsible for the design of the electrical installation (as indicated by my/our signatures below), particulars
have been responsible is to
above, having exercised reasonable skill and care when carrying out the design hereby CERTIFY that the design work for which I/we
the best of my/our knowledge and belief in accordance with BS 7671 : 4 .., amended to. 201 (date) except for the departures, if any, detailed
as follows:
None
The extent of liability of the signatory or the signatories is limited to the work described above as the subject of this Certificate.
For the DESIGN oftheinstallation: **(Where there is mutual responsibility for the design)
C Me
Signature: ...S OU pate.2/4/2004 Name (BLOCK LETTERS): ......../ B BR . Designer No 1
FOR CONSTRUCTION
are de-
We being the person(s) responsible for the construction of the electrical installation (as indicated by my/our signatures below), particulars of which
scribed above, having exercised reasonable skill and care when carrying out the construction her CERTIFY that theconsitugion work for which I/we have
responsible is to the best of my/our knowledge and belief in accordance with BS 7671: amended to (date) except for the
been
departures, if any, detailed as follows:
. None
The extent of liability of the signatory is limited to the work described above as the subject of this Certificate.
W White 6/4/2004
For CONSTRUCTION ofthe installation:
Signature... -0...c.2
2 Date.....
Details
of departures from BS 7671 (Regulations 120-01-03, 120-02):
None
The extent of liability of the signatory is limited to the work described above as the subject of this Certificate.
For INSPECTION AND TEST of the installation:
Signature:..
Name (BLOCK LETTERS): .
NEXT INSPECTION (notes 4 and 7) 3
\We the designer(s), recommend that this installation is further inspected and tested after an interval of not more than years/inions.
Page | of 4
134
Appx 7
PARTICULARS OF SIGNATORIES TO THE ELECTRICAL INSTALLATION CERTIFICATE
Designer (No 1)
Name: BBrown. t Company:
AddressC )
ee County...
Designer (No 2)
(if applicable)
. Postcode:
Constructor
Company: ...
. Postcode:
Inspector
Name: eS Company:
. Postcode:
SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS (~<0%°° 20 onler detail, a5 sppropral
Earthing arrangements Number and Type of Live Nature of Supply Parameters Supply
Conductors Protective Device
TN-C O ro ae Characteristics
TN-S oO ae; dc. (© | Nominal voltage, U/Us"” 400230V ee
TN-C-S cg eC] Type: BS 1361
tt oO 1-phase, 2-wire 2-pole(1]_ | Nominal frequency, f ........-..- 30 uz Fuse
IT ; (note 6) ’
O 1-phase, 3-wireL] 3-pole F] Nominal current
‘ source O
Alternative 2-phase, 3-wireL] other 1 Prospective
Pp fault current, pf
lpr ..£9 ka ting ...L00...A
rating
of supply (to be detailed 0.2
on attached schedules) | 3.phase, 3-wire L] External loop impedance, Ze 0/5.
A (Note: (1) by enquiry, (2) by enquiry or bymeasurement)
3-phase, 4-wire
PARTICULARS OF INSTALLATION REFERRED TO IN THE CERTIFICATE “00s S77ene"SIs. @8 appropriate
Means of Earthing Maximum Demand
pe b a me - 40
Distributor’s facility Maximum demand (load) .....-....-.sesseeneo Amps per phase
Details of Installation Earth Electrode (where applicable)
Installation oO Type Location Electrode resistance to earth
earth electrode e.g. rod(s), tape
ae
etc
— DE ae Thet ns
SCHEDULES (note 2)
when they are attached to it.
The attached Schedules are part of this document and this Certificate is valid only
sattnelace Schedule(s) of Inspections and ...-L...... Schedule(s) of Test Results are attached.
(Enter quantities of sct Ss attached).
alae le
Page 2 of 4
135
Appx 7
ELECTRICAL INSTALLATION CERTIFICATE
GUIDANCE FOR RECIPIENTS (to be appended to the Certificate)
This safety Certificate has been issued to confirm that the electrical installation
work to which it relates has been designed, constructed and inspected and tested
in accordance with British Standard 7671 (the IEE Wiring Regulations).
You should have received an original Certificate and the contractor should have
retained a duplicate Certificate. If you were the person ordering the work, but
not the user of the installation, you should pass this Certificate, or a full copy of
it including the schedules, immediately to the user.
The "original" Certificate should be retained in a safe place and be shown to any
person inspecting or undertaking further work on the electrical installation in
the future. If you later vacate the property, this Certificate will demonstrate to
the new owner that the electrical installation complied with the requirements of
British Standard 7671 at the time the Certificate was issued. The Construction
(Design and Management) Regulations require that for a project covered by
those Regulations, a copy of this Certificate, together with schedules is included
in the project health and safety documentation.
The Certificate is only valid if a Schedule of Inspections and a Schedule of Test Results
is appended .
136
Appx 7
Form F3 Form No 124/3
SCHEDULE OF INSPECTIONS
Methods of protection against electric shock Prevention of mutual detrimental influence
(a) Protection against both direct and indirect [Vv] (a) Proximity of non-electrical services and other influences
contact: v ] (b) Segregation of band I and band II circuits or band II
insulation used
[NZA (i) SELV (note 1)
Vv (c) Segregation of safety circuits
(ii) Limitation of discharge of energy
Identification
(b) Protection against direct contact: (note 2)
[Vv] (a) Presence of diagrams, instructions, circuit charts and
v1 (i) Insulation of live parts similar information
Vv] (ii) | Barriers or enclosures [Vv (b) Presence of danger notices and other warming notices
[NZA| (iii) Obstacles (note 3) Vv (c) Labelling of protective devices, switches and terminals
A (iv) Placing out of reach (note 4) Vv ] (d) Identification of conductors
(v) PELV Cables and conductors
(vi) Presence of RCD for supplementary
protection Vv ] (a) Routing of cables in prescribed zones or within
mechanical protection
(c) Protection against indirect contact:
Vv (b) Connection of conductors
(i) | EEBAD including: (c) Erection methods
Presence of earthing conductor Vv] (d) Selection of conductors for current-carrying capacity and
Presence of circuit protective conductors voltage drop
Presence of main equipotential bonding (e) Presence of fire barriers, suitable seals and protection
conductors against thermal effects
Presence of supplementary equipotential General
SSS
SN
E
bonding conductors (a) Presence and correct location of appropriate devices for
Presence of earthing arrangements for isolation and switching
combined protective and functional
(b) Adequacy of access to switchgear and other equipment
purposes
(c) Particular protective measures for special installations
Presence of adequate arrangements for
and locations
alternative source(s), where applicable
(d) Connection of single-pole devices for protection or
&
EE
Presence of residual current device(s)
switching in phase conductors only
(ii) Use of Class Il equipment or equivalent
(e) Correct connection of accessories and equipment
insulation (note 5)
(f) |Presence of undervoltage protective devices
(iii) |Non-conducting location: (note 6)
Absence of protective conductors (g) Choice and setting of protective and monitoring devices
for protection against indirect contact and/or overcurrent
(iv) Earth-free equipotential bonding: (note 7)
Presence of earth-free equipotential (h) Selection of equipment and protective measures
S
SSIS
RSS
NS
bonding conductors appropriate to external influences
(v) Electrical separation (note 8) (i) Selection of appropriate functional switching devices
10/4/2004
Inspected by Snes ceca caotldepicese
Notes:
Y toindicate an inspection has been carried out and the result is satisfactory
X to indicate an inspection has been carried out and the result was unsatisfactory
N/A _ to indicate the inspection is not applicable
the work prevented the inspection or test
LIM _ to indicate that, exceptionally, a limitation agreed with the person ordering
being carried out.
5. Use of Class II equipment - infrequently adopted and only
as SELV An extra-low voltage system which is electrically
when the installation is to be supervised
separate from earth and from other systems. The
particular requirements of the Regulations must be (see Regulations 413-03 and 471-09)
checked (see Regulations 411-02 and 471-02) 6. Non-conducting locations - not applicable in domestic
premises and requiring special precautions
2. Method of protection against direct contact - will include
measurement of distances where appropriate (see Regulations 413-04 and 471-10)
te Earth-free local equipotential bonding - not applicable in
3. Obstacles - only adopted in special circumstances domestic premises, only used in special circumstances
(see Regulations 412-04 and 471-06)
(see Regulations 413-05 and 471-14)
4, Placing out of reach - only adopted in special
8. Electrical separation (see Regulations 413-06 and 471-12)
circumstances (see Regulations 412-05 and 471-07)
Page 3 of 4
137
Appx 7
f JOp ase S}]NSBJ }S9} JO B/NPEs UO SB}OU 99S x
aUuONG
:sajou jejoeds pue suojejnbey Buys wos suojjeiAaeq
agony,
yueg | aay
SHIeW3Y jean | jean any | Buney
92ue
Buljsal -padwy a2uP}sIisoy ss0}Npuoy
uoljze|nsu| Ayinuiuo> Budi :Aywedes
JUBNDIBAOC
Jeuonpuny doo
yueq pindsid-WWo0Yys , uoldis9sag WNUID
a01Aeq
s}|NsoyY Jsol]
ase ceeeecenscceseacccesesccsenes . ep UD Pi “sHopaliy, OM JO uonduoseq
Ess eeeecae cee seoreaty anaes
anova sea np reenereanasskeocgtaz cent rnc aa ITD wey aa TIO LTO Sepp OS Oona Ltn EAT aT :Bunjse} 0} a|qeseujnn juawidinb3
Dk :48188} GOY “OU DD Dr Oe \u0o yoo pu! ysurebe uoyjoajo1d jo pouyeyy
Vi Sunes
~ gunyeuBis
Dis suoweinsut
no :Aynulyuoo swyo' ‘(7 :ulBUO ye 87 ,
sgouepedw! doo} —~—tL/S-O-NLG-NL :Alddngs jo adfy , emeoremseneree HOQC/H/OT :818C SOL
Sjueunysuy jg. I RSOSHORREHISIB-FO-HEHESOT/SSOIPPY PVT SIIDNUOY IAT, 40\eUOD,
S11NSAY LSAL JO FINGSHDS
p WO
b/PeT ON UO{
Appx 7
138
NOTES ON SCHEDULE OF TEST RESULTS
* Type of supply is ascertained from the distributor or by inspection.
* Ze at origin. When the maximum value declared by the distributor is used, the effectiveness of the earth must be confirmed by a
test. If measured the main bonding will need to be disconnected for the duration of the test.
* Short-circuit capacity of the device is noted, see Table 7.2A of the On-Site Guide or 2.7.15 of GN3
* Prospective fault current (PFC). The value recorded is the greater of either the short-circuit current or the earth fault current.
Preferably determined by enquiry of the distributor.
The following tests, where relevant, shall be carried out in the following sequence:
*6 Continuity
Where Test Method 1 is used, enter the measured resistance of the phase conductor plus the circuit protective conductor (R4+ R2).
See 10.3.1 of the On-Site Guide or 2.7.5 of GN3.
During the continuity testing (Test Method 1) the following polarity checks are to be carried out:
(a) every fuse and single-pole control and protective device is connected in the phase conductor only
(b) centre-contact bayonet and Edison screw lampholders have outer contact connected to the neutral conductor
(a) wiring is correctly connected to socket-outlets and similar accessories.
Compliance is to be indicated by a tick in polarity column 11.
All the preceding tests should be carried out before the installation is energised.
*11 Polarity
A satisfactory polarity test may be indicated bya tick in column 11.
incorrect polarity.
Only in a Schedule of Test Results associated with a Periodic Inspection Report is it acceptable to record
*12 Earth fault loop impedance Zs
+ R2) of column 6 to
This may be determined either by direct measurement at the furthest point of a live circuit or by adding (Ri
the distributor used.
Ze. Ze is determined by measurement at the origin of the installation or preferably the value declared by
in Appendix 2 of the On-Site Guide or App 2 of GN3.
Z; = Ze + (R1 + R2). Zs should be less than the values given
*13 Functional testing
of any test facility in the device.
The operation of RCDs (including RCBOs) shall be tested by simulating a fault condition, independent
Record operating time in column 13. Effectiveness of the test button must be confirmed.
See Section 11 of the On-Site Guide or 2.7.16 of GN3.
to ensure that they are properly
*14 All switchgear and controlgear assemblies, drives, control and interlocks, etc must be operated
mounted, adjusted, and installed.
Satisfactory operation is indicated by a tick in column 14.
Earth electrode resistance
RCD is required.
The earth electrode resistance of TT installations must be measured, and normally an
value on Forms 1, 2 or 6 as
For reliability in service the resistance of any earth electrode should be below 200 Q. Record the
appropriate. See 10.3.5 of the On-Site Guide or 2.7.13 of GN3.
139
Appx 7
NOTES ON COMPLETION OF MINOR ELECTRICAL INSTALLATION WORKS
CERTIFICATE
Scope
The Minor Works Certificate is intended to be used for additions and alterations to an
installation that do not extend to the provision of a new circuit. Examples include the addition
of a socket-outlet or lighting point to an existing circuit, the relocation of a light switch etc.
This Certificate may also be used for the replacement of equipment such as accessories or
luminaires, but not for the replacement of distribution boards or similar items. Appropriate
inspection and testing, however, should always be carried out irrespective of the extent of the
work undertaken.
1,2 The minor works must be so described that the work that is the subject of the certification
can be readily identified.
4 See Regulations 120-01-03 and 120-02. No departures are to be expected except in most
unusual circumstances. See also Regulation 743-01-03.
2 The method of protection against indirect contact shock must be clearly identified e.g.
earthed equipotential bonding and automatic disconnection of supply using fuse/circuit
breaker/RCD
4 If the existing installation lacks either an effective means of earthing or adequate main
equipotential bonding conductors, this must be clearly stated. See Regulation 743-01-02.
Recorded departures from BS 7671 may constitute non-compliance with the Electricity
Supply Regulations 1988 as amended or the Electricity at Work Regulations 1989. It is
important that the client is advised immediately in writing.
The relevant provisions of Part 7 (Inspection and Testing) of the BS 7671 must be applied in full
to all minor works. For example where a socket-outlet is added to an existing circuit it is
necessary to:
1 establish that the earthing contact of the socket-outlet is connected to the main earthing
terminal
2 measure the insulation resistance of the circuit that has been added to, and establish that
it complies with Table 71A of BS 7671
3 measure the earth fault impedance to establish that the maximum permitted
disconnection time is not exceeded
4 check that the polarity of e.g. the socket-outlet, is correct
5 (if the work is protected by an RCD) verify the effectiveness of the RCD.
Part 4 Declaration
1,3 The Certificate shall be made out and signed by a competent person in respect of the
design, construction, inspection and testing of the work.
1,3. The competent person will have a sound knowledge and experience relevant to the
nature of the installation undertaken and to the technical standards set down in BS 7671,
be fully versed in the inspection and testing procedures contained in the Regulations and
employ adequate testing equipment.
2 When making out and signing a form on behalf of a company other business entity,
individuals shall state for whom they are acting.
140
Appx 7
Form 5 Form No ..125./5
MINOR ELECTRICAL INSTALLATION WORKS CERTIFICATE
(REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS 7671 [IEE WIRING REGULATIONS])
To be used only for minor electrical work which does not include the provision of a new circuit
. Location/Address :
. Comments on existing installation, including adequacy of earthing and bonding arrangements : (See Regulation 130-07)
me Insulation resistance:
Phase/neutral
Phase/earth
Neutral/earth
. Polarity : satisfactory re
. RCD operation (if applicable) : Rated residual operating current lan ens and operating time of ms (at lan)
PART 4: Declaration
have been
i We CERTIFY that the said works do not impair the safety of the existing installation, that the said works
designed, constructed, inspected and tested in accordance with BS 7671 : .2QQJ. (IEE Wiring Regulations),
of
amended to .........-+ ADA. .coseceese and that the said works, to the best of my/our knowledge and belief, at the time
my/our inspection, complied with BS 7671 except as detailed in Part 1.
Names CUAIVHECE:
For and on behalf of: .COUstY. FLCCEICS. scence Position... FLCCHUCUAM .eeesssessnescnneesneeene
Address: ..... 182. Industrial
Lane
Date: 1042004...
141
Appx 7
MINOR ELECTRICAL INSTALLATION WORKS CERTIFICATE
GUIDANCE FOR RECIPIENTS (to be appended to the Certificate)
This Certificate has been issued to confirm that the electrical installation work to
which it relates has been designed, constructed and inspected and tested in
accordance with British Standard 7671, (the IEE Wiring Regulations.)
You should have received an ‘original’ Certificate and the contractor should have
retained a duplicate. If you were the person ordering the work, but not the owner
of the installation, you should pass this Certificate, or a copy of it, to the owner. A
separate Certificate should have been received for each existing circuit on which
minor works have been carried out. This Certificate is not appropriate if you
requested the contractor to undertake more extensive installation work, for which
you should have received an Electrical Installation Certificate.
The Certificate should be retained in a safe place and be shown to any person
inspecting or undertaking further work on the electrical installation in the future. If
you later vacate the property, this Certificate will demonstrate to the new owner
that the minor electrical installation work carried out complied with the
requirements of British Standard 7671 at the time the Certificate was issued.
142
Appx 7
PERIODIC INSPECTION REPORT
NOTES:
1. This Periodic Inspection Report form shall only be used for the reporting on the
condition of an existing installation.
2. The Report, normally comprising at least four pages, shall include schedules of
both the inspection and the test results. Additional sheets of test results may be
necessary for other than a simple installation. The page numbers of each sheet
shall be indicated, together with the total number of sheets involved. The
Report is only valid if a Schedule of Inspections and a Schedule of Test Results
are appended.
3. The intended purpose of the Periodic Inspection Report shall be identified,
together with the recipient's details in the appropriate boxes.
4. The maximum prospective fault current recorded should be the greater of
either the short-circuit current or the earth fault current.
5. The ‘Extent and Limitations’ box shall fully identify the elements of the
installation that are covered by the report and those that are not; this aspect
having been agreed with the client and other interested parties before the
inspection and testing is carried out.
7. The ‘Summary of the Inspection’ box shall clearly identify the condition of the
installation in terms of safety.
8. Where the periodic inspection and testing has resulted in a satisfactory overall
assessment, the time interval for the next periodic inspection and testing shall
be given. The IEE Guidance Note 3 provides guidance on the maximum interval
between inspections for various types of buildings. If the inspection and testing
reveal that parts of the installation require urgent attention, it would be
appropriate to state an earlier re-inspection date having due regard to the
degree of urgency and extent of the necessary remedial work.
9. If the space available on the model form for information on recommendations
is insufficient, additional pages shall be provided as necessary.
143
Appx 7
Form F 6 FormNo 126/6
This inspection has been carried out in accordance with BS 7671: 2001 (IEE Wiring Regulations), amended to 2004
Cables concealed within trunking and conduits, or cables and conduits concealed under floors, in roof spaces and
generally within the fabric of the building or underground have not been inspected.
NEXT INSPECTION (note 8)
We recommend that this installation is further inspected and tested after an interval of not more than 20... THortns/years,
provided that any observations ‘requiring urgent attention’ are attended to without delay.
DECLARATION
INSPECTED AND TESTED BY
Naricaen) (aViltc eee en eee tereeener
eine Signature: ......... UME Cee
For and on behalf of: .......cowmty, Flectrics ......... Position: ........ SEIT ONEN oot cccroseereereeteasotereeee
Address: .....287, Udustrigl Lane os cccssssssee
AA Re
cL OUTS An A Wa! Jabber os connve ter atee ASS cn eG UO ccoconeoececectcorcomonpmmmmmeesnens
Page lof 4
144
Appx 7
SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS 1% ?0%29 and enter details, as appropriate
Earthing arrangements Number and Type of Live Nature of Supply Parameters Supply
Conductors Protective Device
Characteristics
TN-C Oo alc. Mac Nominal voltage, U/Up!”) ........230......V
TN-S Ot j Nominal frequency, f"” .. Type: BS.1361......
TN-C-S 1-phase, 2-wire %2-pole oO Prospective fault current, lp‘? ...4:4%...kKA |... SM 6 ee
TT oO (note 4)
IT O
1-phase, 3 wire [] 3-pol
nese) Sewltenial}Si0o.e! ia) External loop impedance, Z, ...0.24.0 Nominal current
2-phase, 3-wire [Jother C] rating ...200......A
Alternative source [] (Note: (1) by enquiry, (2) by enquiry or by
of supply (to be detailed 3-phase, 3-wire [] measurement)
on attached schedules)
3-phase, 4-wire O
LLATION REFERRED TO IN THE REPORT Tick boxes and enter details, as appropriate
PARTICULARS OF INSTA
Means of Earthing Details of Installation Earth Electrode (where applicable)
Distributor's facility Type Location Electrode resistance
Installation oO (e.g. rod(s), tape etc) to earth
earthelectrode | nsssane SES Renee eee PeaSaRTT reese Beene nane ee eTeee Q
Main Protective Conductors
Earthing conductor: material von COPPET.... connection verified eh
Main equipotential bonding conductors material von COPPEM.... connection verified
To incoming water service wy To incoming gas service wy To incoming oil service al To structural steel ]
Tolightning protection (1 To other incoming service(s)L_] (state details... ec-ceeesesessieseseerersereteeeeeney )
Main Switch or Circuit-breaker
BS,Type.. 0486. seca ai se Pend neces ay No. of poles Meee Current rating 80...A Voltage rating ....... 240.N
Location... Meter.cupboard. Sorep ere Peco UceecLERCCCAER EceReO=tn Fuse rating or setting .===....
Rated residual operating current lan = . a
OBSERVATIONS AND RECOMMENDATIONS 119%? 2° approprisie ; Recommendations as
(note 9) detailed below
Referring to the attached Schedule(s) of Inspection and Test Results, and subject to the limitations specified at | note 6
the Extent and Limitations of the Inspection sgction
LINo remedial work is required The following observations are made:
conductors sizedper 15 editi
One of the following numbers, as appropriate, is to be allocated to each of the observations made above to indicate to the person(s)
responsible for the installation the action recommended.
requires urgent attention requires improvement requires further investigation
does not comply with BS 7671: 2001 amended to 4204 This does not imply that the electrical installation inspected is unsafe.
SUMMARY OF THE INSPECTION E004
Date(s) of the inspection: ...... 28/6/2.00: geese arenes wepapndtieisnehcidsalnsaonxees pars
General condition of the installation: .... le urgent repairs and improve
Page 2of 4
145
Appx 7
PERIODIC INSPECTION REPORT
GUIDANCE FOR RECIPIENTS (to be appended to the Report)
This Periodic Inspection Report form is intended for reporting on the condition of an
existing electrical installation.
You should have received an original Report and the contractor should have retained
a duplicate. If you were the person ordering this Report, but not the owner of the
installation, you should pass this Report, or a copy of it, immediately to the owner.
The original Report is to be retained in a safe place and be shown to any person
inspecting or undertaking work on the electrical installation in the future. If you later
vacate the property, this Report will provide the new owner with details of the
condition of the electrical installation at the time the Report was issued.
The ‘Extent and Limitations’ box should fully identify the extent of the installation
covered by this Report and any limitations on the inspection and tests. The contractor
should have agreed these aspects with you and with any other interested parties
(Licensing Authority, Insurance Company, Building Society etc) before the
inspection was carried out.
The Report will usually contain a list of recommended actions necessary to bring the
installation up to the current standard. For items classified as ‘requires urgent
attention’, the safety of those using the installation may be at risk, and it is
recommended that a competent person undertakes the necessary remedial work
without delay.
The Report is only valid if a Schedule of Inspections and a Schedule of Test Results
is appended.
146
Appx 7
Form F3 Form No 126/3
SCHEDULE OF INSPECTIONS
Methods of protection against electric shock Prevention of mutual detrimental influence
(a) Protection against both direct and indirect [Vv] (a) Proximity of non-electrical services and other influences
contact: [Vv] (b) Segregation of band | and band II circuits or band
insulation used
(i) SELV (note1)
Vv] (c) Segregation of safety circuits
(il) Limitation of discharge of energy
Identification
(b) Protection against direct contact: (note 2)
7] Presence of main equipotential bonding (e) Presence of fire barriers, suitable seals and protection
conductors against thermal effects
Ss
& Presence of residual current device(s)
(d) Connection of single-pole devices for protection or
switching in phase conductors only
(ii) Use of Class Il equipment or equivalent
(e) Correct connection of accessories and equipment
insulation (note 5)
(f) | Presence of undervoltage protective devices
(iii) Non-conducting location: (note 6)
Absence of protective conductors (g) Choice and setting of protective and monitoring devices
for protection against indirect contact and/or overcurrent
(iv) Earth-free equipotential bonding: (note 7)
Presence of earth-free equipotential (h) Selection of equipment and protective measures
A
BN
N
NaN
N&
bonding conductors appropriate to external influences
(v) Electrical separation (note 8) (i) Selection of appropriate functional switching devices
Notes:
v to indicate an inspection has been carried out and the result is satisfactory
x to indicate an inspection has been carried out and the result was unsatisfactory
NN to indicate the inspection is not applicable
LIM to indicate that, exceptionally, a limitation agreed with the person ordering the work prevented the inspection or test
being carried out.
SELV An extra-low voltage system which is electrically 5: Use of Class I] equipment - infrequently adopted and only
separate from earth and from other systems. The when the installation is to be supervised
particular requirements of the Regulations must be (see Regulations 413-03 and 471-09)
checked (see Regulations 411-02 and 471-02) 6. Non-conducting locations - not applicable in domestic
Method of protection against direct contact - will include premises and requiring special precautions
measurement of distances where appropriate (see Regulations 413-04 and 471-10)
Obstacles - only adopted in special circumstances re Earth-free local equipotential bonding - not applicable in
(see Regulations 412-04 and 471-06) domestic premises, only used in special circumstances
(see Regulations 413-05 and 471-14)
Placing out of reach - only adopted in special
circumstances (see Regulations 412-05 and 471-07) 8. Electrical separation (see Regulations 413-06 and 471-12)
Page 3of 4
147
Appx 7
p JOp,aseg $}|NSaJ 4S} JO ajNPays UO Sa}OU aa x
Fiurrydas paou sunpuad unyby
sydyaos Loo punowl of GX ou
suoonpog 07 Furpuog hivyuamaddns ou
qos 00} sajquo Fuspuog uy; :sajou jejoeds pue suojenBoy Burs, wos suoyeiAoq
=a mal
——-
— £0 ST (ce aa = SL sz |09 oF i samoys
a v0 ST OC |)comemsl| es ws ST |Ss ST " Ol HA
Ws 70 Aes fh Ses Wu sz |09 0 u 4ayoo)
GX ou Sig #0 ci ra — Tr ican ||Shas og i umop Fux
spuoptiad fayrof — 20 ST ST _— scgTam |aes 0E f dn fury
spuepuadfara = er Z | | |S or |st § \ umopsrybiT
sneoputad fyyrof —l| ¢f Le |g Or OL NST Ss asf dn sryPrT
vis |e kan tbs | Obx 6x Ba | Le oe S v € 2 t
‘I zw | 7ww Vv
su o A OW OW | 6 wo wo
} u
awl} 1 | yuez | aan | | yy
4ayio | addy sZ 4 JRA | /2AIT fy] tytty ad> any | Buney | adAy
aoue e i
Burjsay -peduyj | a2uejsisay s10}Npuod wg
syseway jeuolpun4 dooq ° uoljejnsu} Ayinuijuo> Buin :Aypeded
yyeq d pind412-Yoys , uo} dis2seq PND
901Aeq
JUBIINIIBAC
sUNsoy jsoL
Pays pia wiiwh “Asidjg ~~ VOM 30 uondiuoseq
Aesauien casoscgnp taguabicon suvanehs wochiips GuniesmaAcnsmaW sm bacioxesea -Bunse} 0} e|qeloujna juewidinb3
Rea ceasaxsnsasecoeviceeseapcerentenys eneamae OT WT 381891 GOW
PT WT ‘uoneinsuy
TT WT ~ :Aynuluod tuiBlo ye 87 ,
So yy E79 aranenveet sayeq sel
+1 /S-O-NL/S=he :A\ddng jo adh, r
OT WT” seourpediu! doo}
sjuewunySU]
eae
sommzap
fpumo;y"*30\9e y,
UOD
S11Nsja¥ 1S31 40 JINGAHIS
ON WHOA p WOT
v/9ZE
Appx 7
148
NOTES ON SCHEDULE OF TEST RESULTS
* Short-circuit capacity of the device is noted, see Table 7.2A of the On-Site Guide or 2.7.15 of GN3
* Prospective fault current (PFC). The value recorded is the greater of either the short-circuit current or the earth fault current.
Preferably determined by enquiry of the distributor.
The following tests, where relevant, shall be carried out in the following sequence:
*6 Continuity
Where Test Method 1 is used, enter the measured resistance of the phase conductor plus the circuit protective conductor (R1+ R2).
See 10.3.1 of the On-Site Guide or 2.7.5 of GN3.
During the continuity testing (Test Method 1) the following polarity checks are to be carried out:
(a) every fuse and single-pole control and protective device is connected in the phase conductor only
(b) centre-contact bayonet and Edison screw lampholders have outer contact connected to the neutral conductor
(¢) wiring is correctly connected to socket-outlets and similar accessories.
Compliance is to be indicated by a tick in polarity column 11.
*7 Where Test Method 2is used, the maximum value of R2 is recorded in column 7.
Where the alternative method of Regulation 413-02-12 is used for shock protection, the resistance of the circuit
protective conductor R2 is measured and recorded in column 7.
See 10.3.1 of the On-Site Guide or 2.7.5 of GN3.
All the preceding tests should be carried out before the installation is energised.
*11 Polarity
A satisfactory polarity test may be indicated by a tick in column 11.
Only in a Schedule of Test Results associated with a Periodic Inspection Report is it acceptable to record incorrect polarity.
*12 Earth fault loop impedance Zs
This may be determined either by direct measurement at the furthest point of a live circuit or by adding (Ry + R2) of column 6 to
Ze. Ze is determined by measurement at the origin of the installation or preferably the value declared by the distributor used.
Z; = Ze + (R1 + Ra). Zs should be less than the values given in Appendix 2 of the On-Site Guide or App 2 of GN3.
*13 Functional testing
The operation of RCDs (including RCBOs) shall be tested by simulating a fault condition, independent of any test facility in the device.
Record operating time in column 13. Effectiveness of the test button must be confirmed.
See Section 11 of the On-Site Guide or 2.7.16 of GN3.
they are properly
*14 All switchgear and controlgear assemblies, drives, control and interlocks, etc must be operated to ensure that
mounted, adjusted, and installed.
Satisfactory operation is indicated by a tick in column 14.
149
Appx 7
APPENDIX 8
Introduction
150
Appx 8
Final circuits using socket-outlets complying with BS 1363-2
and fused connection units complying with BS 1363-4
General
TABLE 8A
Final circuits using BS 1363 socket-outlets and connection units
Minimum conductor
cross-sectional area*
Copper Copper
Overcurrent conductor conductor Maximum
Type of circuit protective | thermoplastic or mineral floor area
device thermosetting |insulated cables served
insulated cables
Rating A
3 4 5
A2
*The tabulated values of conductor size may be reduced for fused spurs
151
Appx
Where two.or more ring final circuits are installed the socket-
outlets and permanently connected equipment to be served
are to be reasonably distributed among the circuits.
Circuit protection
Conductor size
The conductor size for a fused spur is determined from the total
current demand served by that spur, which is limited to a
maximum of 13 A.
152
Appx 8
Spurs
General
Circuit protection
153
Appx 8
Conductor size
Types of socket-outlets
154
Appx 8
Heights of switches and sockets
Sockets
entry phon TV sockets
switches
doorbells a telephone jack points
1200 mm maximum
Number of socket-outlets
155
Appx 8
TABLE 8B
Recommended provision of socket-outlets
(All socket-outlets are twin)
(3) Larger dwellings will require proportionally more socket-outlets than smaller
dwellings.
(4) Kitchens should be fitted with socket-outlets above work surfaces as well as
specific socket-outlets for built in appliances.
(6) Bedrooms intended for younger persons should have adequate provision of
socket-outlets for computer and electronic equipment.
(7) One twin socket-outlet should be installed near any telephone outlet to supply
mains powered telecommunication equipment.
(8) The provisions for an office at home may require more consideration with the
user to identify and locate all necessary equipment than is the case with an
ordinary domestic installation.
(9) The use of IT and other electrical equipment with high earth protective 607-02
conductor currents may require the application of Regulation 607 to
accommodate cumulative leakage currents.
156
Appx 8
APPENDIX 9
where
Z; = Ze + R1 + R2
where
157
Appx 9
TABLE 9A
Value of resistance/metre for copper and aluminium conductors and
of R1 + R2 per metre at 20 °C in milliohms/metre
Phase Protective
conductor conductor Aluminium
ree
aera
aE mau
4
4
4 Ul
ul
4
6
6 ul
6
6 a
Pn
158
Appx 9
TABLE 9B
Ambient temperature multipliers to Table 9A
Note:
The correction factor is given by:
{1 + 0.004 (ambient temp - 20 °C}
where 0.004 is the simplified resistance coefficient per °C at 20 °C given by BS 6360
for copper and aluminium conductors.
(a) earth fault loop impedance of Table 41B1, Table 41B2 — Table 4181
or Table 41D of BS 7671 Table 41B2
Table 41D
(b) earth fault loop impedance and resistance of protective
conductor of Table 41C of BS 7671. Table 41C
159
Appx 9
current-carrying capacity) the multipliers given in Table 9C may
be reduced accordingly.
Conductor sone
Installation thermoplastic |thermosetting | thermosetting
(rubber)
Table 54B
Not incorporated
in a cable and
not bunched -
note 1
Table 54C
Incorporated ina
cable or bunched
- note 2
Note 1 See Table 54B of BS 7671: applies where the protective conductor is Table 54B
not incorporated or bunched with cables, or for bare protective
conductors in contact with cable covering.
Note 2 See Table 54C of BS 7671: applies where the protective conductor is a Table 54C
core in a cable or is bunched with cables.
160
Appx 9
APPENDIX 10
TABLE 10A
Main earthing and main equipotential bonding conductor sizes
(copper equivalent) for TN-S and TN-C-S supplies
Phase conductor or
neutral conductor of
PME supplies
Main equipotential
bonding conductor Go Ge peor 1013 10s IOS Om e?> ato
see notes
Main equipotential
bonding conductor 1 Wo GT 1 WW Ws 2s Mls
for PME supplies
(TN-C-S)
161
Appx 10
‘py JO € SUWUNJOD - Sed-aAIIDNPUOI-pasodxa UBAaMIaq sPpUOg 10} pasinbad }eUy
eu} Ja||eWS OU aq JsNnW PUOG au} ‘Wed-anly2NnpUOd-pasodxe Ue O} Pa}2BULOD SI! SLed-BAIJDNPUOI-SNOSUeIIX9 BUY} JO BUO }] 1 940N
zuwiw zuiw 7 WU
papeajoid pape}o01d papeajoid , papeaj}oid papeajoid papejoid JoyNpuo?
Ajjed1ueudaW JOU Ajjed1ueydaui | Ajjediueydaw YOU Ajjed1ueyraw | Ajje.!ueydaWwW JOU Ajjyed1ueydoW aAipejoid
}INDIID $O 9ZIS
(L) Wed-anljInpuod-snosuel}X9 yed-anijpnpuod-pasodxa yed-anipnpuod-snosuesxa}
0} ed-aAlyNpUOd-sNoOsuUeIIXA 01 Yed-aAlpNpuod-pasodxy 0} Wed-anl~npuod-pasodxy
Bulpuog Aueyuawajddns jo ease jeUuO!DAaS-ssO1D WUINWIUII
$10}2npuo> Hulpuog Aie}uawiajddns
€0-LvS d0l F1aVL
Appx 10
162
Appx 10
163
WW 9 UeY} ssa] JOU pu JOP NPUOD Huiyyea
au} 10} pasinbay yey} Jey UY} ssa] JOU JO ease [eUOIIDAS-ssoJD eB BAY ||EYsS JOP NPUOD Hulpuog jeljua}odinba ujew sy
~
‘Z0-L0-€7S UONe|nBay Jad se aulwuajap WYO | Ue} Ssa| SeQUepad! 104
“yjyeaus e Aq uolsoijo2 ysulebe pa}a}014
‘SOON
jediueydow
jediueyudowW
oabewep
abewep
7Uu
UOo!lsolo>
UO1SO1109
Z
pue
IDENTIFICATION OF CONDUCTORS
1. Introduction
164
Appx 11
Table 51
TABLE 11A 514-03-01
Identification of conductors (harmonized)
165
Appx 11
2. Alteration or addition to an existing installation
2.1. Single-phase
166
Appx 11
4. Intermediate and two-way switch wires in a new
installation or an alteration or addition to an
existing installation
Table 7C
TABLE 11D
Standard 600/1000V armoured cable BS 6346, BS 5467 or BS 6724
167
Appx 11
TABLE ALE Table 7D
Flexible cable to BS 6500
Cable type Old core colours New core colours
Two-core Brown, Blue No change
Three-core Brown, Blue, No change
Green-and-Yellow
Four-core Black, Blue, Brown, Brown, Black, Grey,
Green-and-Yellow Green-and-Yellow
Five-core Black, Blue, Brown, Black Brown, Black, Grey, Blue,
Green-and-Yellow Green-and-Yellow
168
Appx 11
PICTORIAL INDEX
To use the index, turn to the relevant index, and find paragraph
references against the appropriate schematic drawing.
169
Shere
sejqeo
J
VIVO
sebe}on
~~
JUSIOSJI
JEUILUOU
aouesaid
Bumjeqey
a
Lg jo
(1)
BHuipeseoxe
peyoedxeun
(I!) abeljon
AOE
Lg Slemous
)
pue swoouyeq
pue
()b9
Bujeqel _
=
801Aep
LQ (WA)
e10W ue} auo Aq
Huryjaqeeiostpuliede|
uolejos! w oy
\ BAI}0E}01dSEDIABP
8o10yo
JO
Be
YOUMS
y'S
Aouebiewe
(1!) °G UOIFeIOS|
zg Bulyowms =~
jeuoljoun}
g 98S BulyouMs
pue uoyejos! |
\ SUO!}IPUCD
Hulpuog A €8 peuinsse
Buu ie <Y tae peuinbes s! LZ eqe
aunjonuys yg ums —_UB|s UoSU (Ales ‘epod d| = (XI)7'7SyNDID = UOMUEHE =—syinouio yeu
UOIPeUOJUI See ea juawidinbe jeuia}xe |pueq seinoed = peuonuanuood
Z| UONeWOJU! dISeq
NOILVTIVLSNI 3H (!) xepul
170
JUawdinbse
171
()L'9°E
solsuajoeseuo
BdIMas
InoKe|
614
‘e}
pure (A)z’z GO 40
Jo az
SJaWUNSUOD
UleW
YOUMS
JOyeM
seb
A\ddnsbh
L°€
BOIASp
(\)Z'g yno-yno
eee
adh}
@Aoe}0Jd
Jo
(ve $J0}NqUySIP
S9DINIOS
}OB]UOD
JOAIIP jeluesse (uo?
fan ew
ysurebe
uoloe}01d 40}OWW
s]le}
(x1) 1-9 Buysse} (Al)e'%
==7)[ea2
pue
Bunoedsul YOUMS SJaijddns
S$Jaijddns
oipoued
BHuyjaqe|
(Woe
49}8W
801lAep
(pe ea10yo
Go
2g
Buiyoyms
40 L
__—
yeuonouny
(1x) L°g pure (x!) ,°9
‘(A) Lg Buyjeqe| JOB}UOD JOSJIPU!
puewep
uoloe}0
sureBe
Ajissaaip
¢Ge soul}
(Sswa\shs
UO!}JOSUUODSIP
S-9-NL
ddyf
uoWNqUsIp
Buidnosb
lb
bod
sajqeo
UOHe/OS!
S-NL
pueog
pue
‘LL
uoi08}01d
JOJ)
|°G
o9€
GOU
Aq
GOUY k'9°€
(WD L'9°E GO"
Burjjeqe|
uol0a}01d
Aq
Aq
uonoejo
syoddns
(1x)
€'€
uooejoid
LQ
uold98}01d
uonoejes
ajqeo
peo|iaAo
juewno-1jne4
ddy
ajqeo
Ge
¢ tp
iddy{
wy,
main ventilation *
ducting
exposed metallic *
structural parts oil
4.1(v) accessible *
structural
steelwork ese
lightning
conductor
exclusion of copper
covered aluminium
conductors 4.2(i)
.
labelling 6.1 (iv) |
Px
; earthing
lightning Ny conductor 4.2
conductor ‘ NI
test point /\ main bonding comductors|4.2
Se
earth electrode 4.8 earth fault loop impedance
— maximum value 1.1 (iv),
4.8
* metal parts only require main bonding when they
are extraneous-conductive-parts, see Section 4
172
Index (ii) BONDING AND EARTHING
See also Fig 4a, Fig 4b and Fig 4c
information
structure
wiring
bonding
gas installation
pipes 4.1(ii)
cooker
fal fre sl
a
Sas)
PSs
ia a Ba S46 e7en®
earthing
conductor circuit protective conductors
4.2
Exposed-conductive-parts
(cooker, switch plates, metal)
173
|g pauinbeu sI z' 1g Buneey
uonueye sejnored Joo|epun
wodluyeq
woojpeq
1g ajqe) seuoz
ul juawidinbe jeoujo8|98 8 a|qe] SOUOZ JO}
gjqeyins yuewdinbe
e
Z'8 BjOIGno 4amoys Z'g wooipeq
a ec
UYIM WOO! Ul ey90S —U!_ 8J91GNd JaMoYs
Lg aiqel yyeq au}
Bulpuoq uIUIM JUsUdINbe
Bui jeoujo9a
eunjoniys
Oe SGDYU GNV SNOILVDO7 1VID3dS (1!) xepul
174
€°g pauinbei S| cr
175
JejNoIed uolueye 9€ eel
on dou
abeiebh/peys
L'L'8(Al)
dou Gol
sedlAep 8Al}0e}01d
WH (LDLITI
pueog uoWNqUIs!p
LOE cS
sJoopj}no yuewdinbe Buryy6i
ajqeuod A\jddns Loe af ah
0} pe}0edx9 JayD0S sJoopyno juewdinbe
cGe ajqeuod A\ddns a
SyINoJIO 0} payoedxe ja490
jeloeds
4J8MOUS JOBACYS uel
J@Moys
Le6
1SI}4OOUO 1S9}
2 ddy
gouepedtul doo} € Ol
sainpeooid se}
€'€'0} Bursa}
eoue\sised
uolye|nsul
veo
Bunse} Ayejod
ZO} pue
Leo} Bunse} 7 Ol S}S9}
Aynuyuod
jo eouanbes
LO} Busey
Huunp Ajeyes
Ol 99S
saj}ou eouepin6
Hulse} elul
Hulpuog
Bum
eunjoniys
UOIEUWOJU! DNILSAL GNV NOILD4 dSNI (A!) Xepul
176
177
ddy
‘16
LZ
uolye}USLUNDOP UO!}e|dWo0d
syne}
€'6
JO UO!}08109 9 OL
Hulse} eouepedui!
jeul9a}xe pue
€6
seposjoeja
yS!p4OeYO UOHOedsul
Buse}Ge
or
yee
L'Z'6 uoNoedsul
esodind
jo
jo
L6 }S9}
pure joedsul
0} JueWAaIINbe1
Buse}
08g
"SGOU
LL
40
Index (v) ALPHABETICAL
179
Electric shock 3.4 7
58
Emergency lighting 74.2 Bi,
Emergency switching 5.4 35
Equipotential bonding 24
F
Fault current
measurement 10.3.7 80
protection 33 li?
72.5 (1) 49
Table 7.2A 50
Final circuits 7 40
Fire alarms VAA 56
Fireman’s switch 5.4 35
Fixed wiring Table 3A 94
Flexible cords Table 3B oT,
Floors el 52
Functional
extra-low voltage 10.3.3(vi) 75
switching a2 35
testing 10.3.8 80
Fuses Te2eD 49
distributor’s 1.1(ili) 11
272\\) 14
G
Garages 8.3 60
Garden buildings 8.3 60
Gas pipes 4.1 24
Gas service 4.2 24
Grouping e2s|
Table 6C 118
H
Hand-held equipment 3.5.2(ii)
Hearing aid loop 7.3.4
Height of overhead wiring Table 4B
Height of switches, sockets Fig 8A
I
Immersion heaters Appx 8
Indirect contact 3.A(ii)
Information fez
Inspection and Testing 9
Inspection certificate Appx 7
Inspection schedule SU
Appx 7
180
Insulation resistance a5
IOs
Isolation Dal
J
Joists i341
L
Labelling 6
Lighting demand Table 1A
diversity Table 1B
Lightning protection
Live part
Load characteristics
Load estimation
Loop impedance
testing
M
Main earthing
bar Figs 4a, 4b, 4c
bonding Figs 4a, 4b, 4c
terminal Figs 4a, 4b, 4c
Maximum demand Appx 1
Mechanical maintenance oye)
Metal pipework
Metal structures
Meter
Meter tails 2.2(iii)
Figs 4a, 4b, 4c
Mineral cable Table 3A
Minor works certificate Appx 7
Motors diversity Table 1B
N
Notices 6
Number of socket-outlets Table 8B
O
Oil service pipe 4.2
Overhead wiring Appx 4
Overload protection ane
P
Partition walls Pl Pe
PELV 3.A(iii)
Ddait
Table 10.1
10.3.3(v)
Periodic reports Appx 7
181
Plastic pipes
Polarity testing
Portable equipment
Protection
Protective conductors
Protective conductor current
Protective device
Proximity
R
Radial circuits
testing
RCBO
RCD
RCD testing
Reference method
Reports
Resistance of conductors
Ring circuits
testing
S
Schedules
Scope
SELV
Table 10.1
10.3.3(v)
Sequence of tests 10.2
Service position 2
Short-circuit protection 33
Table 7.2A
Showers 8
Skilled persons 121
Smoke alarms Ae
Socket-outlets 3.6.1
Appx 8
Special locations 8
Spurs Appx 8
Standard circuits Appx 8
Supplementary bonding 4.5
4.6
4.7
Table 10B
182
Supplier's cut-out see distributor’s cut-out
Supplier’s switch oe
Supply 4
Supply tails Figs 4a, 4b, 4c
Switching 5
Switches, height of Fig 8A
T
Telecommunication circuits ase
Temporary buildings 3
Test equipment 10.1
Test results schedule onl
Appx 7
Testing a
10
Thermal insulation Appx 6
Thermoplastic (pvc) cable 7.1
Table 6D1
Table 6E1
Table 6F
Thermosetting cable 7.2.2
Table 6D1
Table 6E1
TN-C-S system Fig 4b
TN-S system Fig 4a
Trunking
capacities Appx 5
supports Table 4D
TT system Fig 4c
7.2.4
Two-way circuits Fig 7.3.4
10.3.3(ii)
U
Underfloor heating Saez 58
V
Voltage bands 9.2.2 62
Voltage drop Appx 6 115
Table 6D2 122
Table 6E2 126
Table 6F 126
Ww
Walls Das 53
Warning notices 6
Water heaters Appx 8 150
Water pipes 4.1 24
183
eeceemmenpenee® —_—
GUIDANCE NOTES
The IEE’s series of Guidance Notes offers extensive, industry-endorsed guidance to
designers and installers in the effective use of BS 7671.
Seven IEE Guidance Notes are currently available:
1. Selection and Erection of Equipment 5. Protection against Electric Shock
2. Isolation and Switching 6. Protection against Overcurrent
3. Inspection and Testing 7. Special Locations
4. Protection against Fire
CODES OF PRACTICE
The IEE Code of Practice for In-Service Inspection and Testing of Electrical
Equipment offers guidance for the inspection, testing and maintenance of electrical
appliances, plus advice on compliance with health and safety legislation.
The IEE Electrical Maintenance - Code of Practice offers guidance on electrical aspects of
building maintenance, including electrical installation, fire alarms, emergency lighting and
more, plus detailed guidance on legal responsibilities.
Please send me further information on the following IEE products and/or courses:
; Name
:Company
7Address
Dates and venues for these and other courses can be found from the IEE:
e by telephone: 01438 767288 e by fax: 01438 767291
e by email: [email protected] e via the web: www.iee.org/courses
A Three-phase
winding - delta
YW Buzzer Three-phase
winding - Star
[kK Horn Changer,
Converter,
@ Telephone
handset
oC) Microphone
@ Machine 4H Battery
* Function
M = Motor -~QD- Transformer -
G = Generator general symbol
Generator 10° giga G
10° mega M
@® Indicating 103 kilo k
instrument
* function
102 milli m
V = Voltmeter 10° micro p
A= Ammeter 10° nano n
em
The IEE
MichaekFarada
SIPaLCM MEN
Stevenage Herts
SGI 2AY.
United Kangdo
ISBN 0 86341