Manual Carrier 40RM

This document provides installation, start-up and service instructions for packaged air-handling units. It details safety considerations and pre-installation instructions. It also covers unit installation including positioning, piping, wiring and ductwork connection. Servicing topics include fan maintenance, coil cleaning and filter replacement.

Uploaded by

Ricardo OM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views

Manual Carrier 40RM

This document provides installation, start-up and service instructions for packaged air-handling units. It details safety considerations and pre-installation instructions. It also covers unit installation including positioning, piping, wiring and ductwork connection. Servicing topics include fan maintenance, coil cleaning and filter replacement.

Uploaded by

Ricardo OM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

40RM

40RMQ
40RMS
Packaged Air-Handling Units
50/60 Hz

Installation, Start-Up and


Service Instructions
CONTENTS filters. All other operations should be performed by trained
Page service personnel.
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . 1 When working on the equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
PRE-INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 1 equipment.
Moving and Storage . . . . . . . . . . . . . . . . . . . . . . . . 1 • Follow all safety codes.
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
• Wear safety glasses and work gloves.
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 • Use care in handling, rigging, and setting bulky
Uncrating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 equipment.
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Be sure all power to equipment is shut off before per-
Refrigerant and Chilled Water forming maintenance or service. More than one discon-
Piping Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 nect may be present.
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chilled Water Piping . . . . . . . . . . . . . . . . . . . . . . . 17
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Fan Motors and Drives . . . . . . . . . . . . . . . . . . . . . 18 PRE-INSTALLATION
Power Supply and Wiring . . . . . . . . . . . . . . . . . . . 19
Connecting Ductwork . . . . . . . . . . . . . . . . . . . . . . 22 Moving and Storage — To transfer unit from truck to
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . 22 storage site, use a fork truck. Do not stack units more than
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 2 high during storage. If unit is to be stored for more than
2 weeks before installation, choose a level, dry storage site
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-39 free from vibration. Do not remove plastic wrap or skid from
Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 unit until final installation.
Fan Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . 23
Fan Shaft Bearings . . . . . . . . . . . . . . . . . . . . . . . . . 23 Rigging — All 40RM Series units can be rigged by us-
Centering Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . 24 ing the shipping skid. Units are shipped fully assembled. Do
Fan Shaft Position Adjustment . . . . . . . . . . . . . . 24 not remove shipping skids or protective covering until unit
Individual Fan Wheel Adjustment . . . . . . . . . . . 24 is ready for final placement; damage to bottom panels can
Fan Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 result. Use slings and spreader bars as applicable to lift unit.
Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Pulley Alignment . . . . . . . . . . . . . . . . . . . . . . . 25
Pulley and Drive Adjustment . . . . . . . . . . . . . . . . 25
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . 25 INSTALLATION
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . 25 General — Allow 21⁄2 ft at front and side of unit for
Chilled Water Coil Freeze Protection . . . . . . . . 25 service clearance and airflow. For units equipped with an econo-
Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 mizer, refer to the accessory installation instructions for ad-
Cleaning Cooling Coil . . . . . . . . . . . . . . . . . . . . . . 25 ditional clearance requirements. Be sure floor, wall, or ceil-
Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . . . 25 ing can support unit weight (Tables 1A-1F). See
Replacing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Fig. 1A-1C for dimensions.
START-UP CHECKLIST . . . . . . . . . . . . . . . . CL-1,CL-2
Uncrating — Move unit as near as possible to final lo-
cation before removing shipping skid.
SAFETY CONSIDERATIONS Remove metal banding, top skid, and plastic wrap. Ex-
Installing, starting up, and servicing this equipment can amine unit for shipping damage. If shipping damage is
be hazardous due to system pressures, electrical components evident, file claim with transportation agency. Remove base
and equipment location (elevated structures, etc.). skid just prior to actual installation.
Only trained, qualified installers and service mechanics Check nameplate information against available power
should install, start up, and service this equipment. supply and model number description in Fig. 2.
Untrained personnel can perform basic maintenance func- Accessories — Refer to instructions shipped with each
tions such as cleaning coils, and cleaning and replacing accessory for specific information.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI Pg 1 11-95 Replaces: 40RM-1SI
Tab 3c 2e
More user manuals on ManualsBase.com
Table 1A — 40RM Physical Data, English
UNIT 40RM 007 008 012 014 016 024 028 034
NOMINAL CAPACITY (Tons) 6 71⁄2 10 121⁄2 15 20 25 30
OPERATING WEIGHT (lb)
Base Unit with TXV 381 385 405 670 685 690 1020 1030
Plenum 97 97 97 140 140 140 180 180
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18
Nominal Airflow (cfm) 2400 3000 4000 5000 6000 8,000 10,000 12,000
Airflow Range (cfm) 1800- 2250- 3000- 3750- 4500- 6,000- 7,500- 9,000-
3000 3750 5000 6250 7500 10,000 12,500 15,000
Nominal Motor Hp (Standard Motor)
208/230-1-60 1.3 2.4 — — — — — —
208/230-3-60 and 460-3-60 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0
575-3-60 1.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0
230-3-50, 400-3-50 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Motor Speed (rpm)
208/230-1-60 1725 1725 — — — — — —
208/230-3-60 and 460-3-60 1725 1725 1725 1725 1725 1745 1745 1745
575-3-60 1725 1725 1725 1725 1725 1745 1755 1755
230-3-50, 400-3-50 1425 1425 1425 1425 1425 1425 1425 1425
REFRIGERANT R-22
Operating charge (lb) 3.0 3.0 1.5/1.5 2.0/2.0 2.5/2.5 3.5/3.5 4.5/4.5 5.0/5.0
(approx per circuit)*
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 435
Face Area (sq ft) 6.67 8.33 10.0 13.25 17.67 19.88 24.86 29.83
No. of Splits 1 1 2 2 2 2 2 2
No. of Circuits per Split 12 15 9 9 12 13 15 18
Split Type...Percentage — — Face...50/50
Rows...Fins/in. 3...15 3...15 3...17 3...15 3...15 3...17 3...15 3...15
STEAM COIL
Max Working Pressure (psig at 400 F) 175
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure (psig) 150
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...12.5 2...12.5
Water Volume
(gal) 8.3 13.9 14.3
(ft3) 1.1 1.85 1.90
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...11⁄8 1...11⁄8 2...11⁄8 2...11⁄8 2...11⁄8 2...11⁄8 2...13⁄8 2...13⁄8
DX Coil — Liquid Refrigerant (ODF) 1...5⁄8 2...5⁄8
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 20 x 2 4...20 x 24 x 2
4...16 x 24 x 2 4...20 x 25 x 2
Access Location Either Side
LEGEND
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.

2
More user manuals on ManualsBase.com
Table 1B — 40RMQ Physical Data, English
UNIT 40RMQ 008 012 016
NOMINAL CAPACITY (Tons) 71⁄2 10 15
OPERATING WEIGHT (lb)
Base Unit with TXV 385 427 713
Plenum 97 97 140
FANS
Qty...Diam. (in.) 1...15 1...15 2...15
Nominal Airflow (cfm) 3000 4000 6000
Airflow Range (cfm) 2250-3750 3000-5000 4500-7500
Nominal Motor Hp (Standard Motor)
208/230-1-60 2.4 — —
208/230-3-60 and 460-3-60 2.4 2.4 3.7
575-3-60 2.0 2.0 3.0
230-3-50, 400-3-50 2.4 2.9 2.9
Motor Speed (rpm)
208/230-1-60 1725 — —
208/230-3-60 and 460-3-60 1725 1725 1725
575-3-60 1725 1725 1725
230-3-50, 400-3-50 1425 1425 1425
REFRIGERANT R-22
Operating charge (lb) 3.0 2.0/2.0 3.0/3.0
(approx per circuit)*
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 435
Face Area (sq ft) 8.33 10.0 17.67
No. of Splits 1 2 2
No. of Circuits per Split 15 9 16
Split Type...Percentage — Face...50/50
Rows...Fins/in. 3...15 4...15 4...15
STEAM COIL
Max Working Pressure (psig at 400 F) 175
Total Face Area (sq ft) 6.67 6.67 13.33
Rows...Fins/in. 1...9 1...9 1...10
HOT WATER COIL
Max Working Pressure (psig) 150
Total Face Area (sq ft) 6.67 6.67 13.33
Rows...Fins/in. 2...8.5 2...8.5 2...8.5
Water Volume
(gal) 8.3 13.9
(ft3) 1.1 1.85
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...11⁄8 2...11⁄8 2...11⁄8
DX Coil — Liquid Refrigerant (ODF) 1...5⁄8 2...5⁄8 2...5⁄8
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 20 x 2
4...16 x 24 x 2
Access Location Either Side
LEGEND
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.

3
More user manuals on ManualsBase.com
Table 1C — 40RMS Physical Data, English
UNIT 40RMS 008 010 012 014 016 024 028 034
NOMINAL CAPACITY (Tons) 71⁄2 8 1 ⁄2 10 121⁄2 15 20 25 30
OPERATING WEIGHT (lb)
Base Unit 390 391 391 661 677 683 1035 1042
Plenum 97 97 97 140 140 140 180 180
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18
Nominal Airflow (cfm) 3000 3400 4000 5000 6000 8000 10,000 12,000
Airflow Range (cfm) 2250-3750 2250-4250 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000
Nominal Motor Hp
(Standard Motor)
208/230-1-60 2.4 2.4 — — — — — —
208/230-3-60 and 460-3-60 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0
575-3-60 2.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0
230-3-50 and 400-3-50 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Motor Speed (rpm)
208/230-1-60 1725 1725 — — — — — —
208/230-3-60 and 460-3-60 1725 1725 1725 1725 1725 1745 1745 1745
575-3-60 1725 1725 1725 1725 1725 1745 1755 1755
230-3-50 and 400-3-50 1425 1425 1425 1425 1425 1425 1425 1425
CHILLED WATER COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure 435
(psig)
Face Area (sq ft) — Upper 8.3 9.0 4.9 8.3 8.3 11.0 12.4 15.5
Face Area (sq ft) — Lower — — 4.9 5.5 8.3 8.3 12.4 12.4
Rows...Fins/in. 3...15
STEAM COIL
Max Working Pressure 175
(psig at 400 F)
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure 150
(in. wg)
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...12.5 2...12.5
Water Volume
(gal) 8.3 13.9 14.3
(ft3) 1.1 1.85 1.90
PIPING CONNECTIONS,
Quantity...Size (in.)
Chilled Water — In 1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
Chilled Water — Out 1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 20 x 2 4...20 x 24 x 2
4...16 x 24 x 2 4...20 x 25 x 2
Access Location Either Side

4
More user manuals on ManualsBase.com
Table 1D — 40RM Physical Data, SI
UNIT 40RM 007 008 012 014 016 024 028 034
NOMINAL CAPACITY (kW) 21 26 35 43 52 70 87 105
OPERATING WEIGHT (kg)
Base Unit with TXV 173 175 184 304 311 313 463 467
Plenum 44 44 44 63 63 63 82 82
FANS
Qty...Diam. (mm) 1...381 1...381 1...381 2...381 2...381 2...381 2...457 2...457
Nominal Airflow (L/s) 1133 1604 1888 2360 2831 3775 4719 5663
Airflow Range (L/s) 850-1416 1203-2006 1416-2360 1770-2949 2124-3539 2831-4719 3539-5899 4247-7079
Nominal Motor kW (Standard Motor)
208/230-1-60 0.97 1.79 — — — — — —
208/230-3-60 and 460-3-60 1.79 1.79 1.79 2.16 2.76 3.73 5.60 7.46
575-3-60 0.75 1.49 1.49 2.24 2.24 3.73 5.60 7.46
230-3-50, 400-3-50 1.79 1.79 2.16 2.16 2.16 3.73 5.60 7.46
Motor Speed (r/s)
208/230-1-60 28.8 28.8 — — — — — —
208/230-3-60 and 460-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.1 29.1
575-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.3 29.3
230-3-50, 400-3-50 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8
REFRIGERANT R-22
Operating charge (kg)
(approx per circuit)* 1.36 1.36 0.68/0.68 0.90/0.90 1.13/1.13 1.59/1.59 2.04/2.04 2.27/2.27
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag) 2999
Face Area (sq m) 0.62 0.77 0.93 0.93 1.64 1.85 2.30 2.77
No. of Splits 1 1 2 2 2 2 2 2
No. of Circuits per Split 12 15 9 9 12 13 15 18
Split Type...Percentage — — Face...50/50
Rows...Fins/m 3...591 3...591 3...670 3...591 3...591 3...670 3...591 3...591
STEAM COIL
Max Working Pressure (kPag at 204.4 C) 1207
Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39
Rows...Fins/m 1...355 1...355 1...355 1...394 1...394 1...394 1...394 1...394
HOT WATER COIL
Max Working Pressure (kPag) 1034
Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39
Rows...Fins/m 2...335 2...335 2...335 2...335 2...335 2...335 2...493 2...493
Water Volume
(L) 31.4 52.6 54.1
(m3) 0.031 0.052 0.054
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...11⁄8 1...11⁄8 2...11⁄8 2...11⁄8 2...11⁄8 2...11⁄8 2...13⁄8 2...13⁄8
DX Coil — Liquid Refrigerant (ODF) 1...5⁄8 2...5⁄8
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size 4...406 x 610 x 51 4...406 x 508 x 51 4...508 x 610 x 51
4...406 x 610 x 51 4...508 x 635 x 51
Access Location Either Side
LEGEND
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.

5
More user manuals on ManualsBase.com
Table 1E — 40RMQ Physical Data, SI
UNIT 40RMQ 008 012 016
NOMINAL CAPACITY (kW) 26 35 52
OPERATING WEIGHT (kg)
Base Unit with TXV 175 194 323
Plenum 44 44 63
FANS
Qty...Diam. (mm) 1...381 1...381 2...381
Nominal Airflow (L/s) 1604 1888 2831
Airflow Range (L/s) 1203-2006 1416-2360 2124-3539
Nominal Motor kW (Standard Motor)
208/230-1-60 1.79 — —
208/230-3-60 and 460-3-60 1.79 1.79 2.76
575-3-60 1.49 1.49 2.24
230-3-50, 400-3-50 1.79 2.16 2.16
Motor Speed (r/s)
208/230-1-60 28.8 — —
208/230-3-60 and 460-3-60 28.8 28.8 28.8
575-3-60 28.8 28.8 28.8
230-3-50, 400-3-50 23.8 23.8 23.8
REFRIGERANT R-22
Operating charge (kg)
(approx per circuit)* 1.36 0.91/0.91 1.36/1.36
DIRECT-EXPANSION COIL
Max Working Pressure (kPag) 2999
Face Area (sq m) 0.77 0.93 1.64
No. of Splits 1 2 2
No. of Circuits per Split 15 9 16
Split Type...Percentage — Face...50/50
Rows...Fins/m 3...591 4...591 4...591
STEAM COIL
Max Working Pressure (kPag at 204.4 C) 1207
Total Face Area (sq m) 0.62 0.62 1.24
Rows...Fins/m 1...355 1...355 1...394
HOT WATER COIL
Max Working Pressure (kPag) 1034
Total Face Area (sq m) 0.62 0.62 1.24
Rows...Fins/m 2...335 2...335 2...335
Water Volume
(L) 31.4 52.6
(m3) 0.031 0.052
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...11⁄8 2...11⁄8 2...11⁄8
DX Coil — Liquid Refrigerant (ODF) 1...5⁄8 2...5⁄8 2...5⁄8
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (Male PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size 4...406 x 610 x 51 4...406 x 508 x 51
4...406 x 610 x 51
Access Location Either Side
LEGEND
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.

6
More user manuals on ManualsBase.com
Table 1F — 40RMS Physical Data, SI
UNIT 40RMS 008 010 012 014 016 024 028 034
NOMINAL CAPACITY (kW) 26 29 35 43 52 70 87 105
OPERATING WEIGHT (kg)
Base Unit 177 177 177 300 307 310 469 473
Plenum 44 44 44 63 63 63 82 82
FANS
Qty...Diam. (mm) 1...381 1...381 1...381 2...381 2...381 2...381 2...457 2...457
Nominal Airflow (L/s) 1416 1605 1888 2360 2831 3775 4719 5663
1062- 1204- 1416- 1770- 2124- 2831- 3539- 4247-
Airflow Range (L/s) 1770 2006 2360 2949 3539 4719 5899 7079
Nominal Motor kW
(Standard Motor)
208/230-1-60 1.79 1.79 — — — — — —
208/230-3-60, 460-3-60 1.79 1.79 1.79 1.79 2.76 3.73 5.60 7.46
575-3-60 1.49 1.49 1.49 1.49 2.24 3.73 5.60 7.46
230-3-50, 400-3-50 1.79 1.79 2.16 2.16 2.16 3.73 5.60 7.46
Motor Speed (r/s)
208/230-1-60 28.8 28.8 — — — — — —
208/230-3-60, 460-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.1 29.1
575-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.3 29.3
230-3-50, 400-3-50 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8
CHILLED WATER COIL
Max Working Pressure 2999
(kPag)
Face Area (sq m) — Upper 0.77 0.84 0.91 0.77 0.77 1.02 1.15 1.44
Face Area (sq m) — Lower — — — 0.51 0.77 0.77 1.15 1.15
Rows...Fins/m 3...591 3...591 3...591 3...591 3...591 3...591 3...591 3...591
STEAM COIL
Max Working Pressure 1207
(kPag at 204.4 C)
Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39
Rows...Fins/m 1...355 1...355 1...355 1...355 1...394 1...394 1...394 1...394
HOT WATER COIL
Max Working Pressure 1034
(kPag)
Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39
Rows...Fins/m 2...335 2...335 2...335 2...335 2...335 2...335 2...493 2...493
Water Volume
(L) 31.4 52.6 54.1
(m3) 0.031 0.052 0.054
PIPING CONNECTIONS,
Quantity...Size (in.)
Chilled Water — In 1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
Chilled Water — Out 1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
4...406 x 508 x 51 4...508 x 610 x 51
Quantity...Size (mm) 4...406 x 610 x 51 4...406 x 610 x 51 4...508 x 635 x 51
Access Location Either Side

7
More user manuals on ManualsBase.com
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm )
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RMS units may require alternate or ad-
ditional field-fabricated piping access holes.

UNIT UNIT WEIGHT


lb (kg)
40RM007 381 (173)
40RM008 385 (175)
40RM012 405 (184)
40RMQ008 385 (175)
40RMQ012 427 (194)
40RMS008 390 (177)
40RMS010 391 (177)
40RMS012 391 (177)

Fig. 1A — Dimensions — Sizes 007-012

8
More user manuals on ManualsBase.com
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RMQ016 and 40RMS units may re-
quire alternate or additional field-fabricated
piping access holes.

UNIT UNIT WEIGHT


lb (kg)
40RM014 670 (304)
40RM016 685 (311)
40RM024 690 (313)
40RMQ016 713 (323)
40RMS014 661 (300)
40RMS016 677 (307)
40RMS024 683 (310)

Fig. 1B — Dimensions — Sizes 014-024

9
More user manuals on ManualsBase.com
UNIT UNIT WEIGHT
lb (kg)
40RM028 1020 (463)
40RM034 1030 (467)
40RMS028 1035 (469)
40RMS034 1042 (473)

TXV — Thermostatic Expansion Valve


NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RMS units may require alternate or
additional field-fabricated piping ac-
cess holes.

Fig. 1C — Dimensions — Sizes 028,034

10
More user manuals on ManualsBase.com
*YC and WD option codes for all 034 size units and 008, 010 units with 208/230-1-60
power designate standard motor and high-static drive.
NOTE: See the following table for the sizes available for each unit.

UNIT 007 008 010 012 014 016 024 028 034
40RM X X X X X X X X
40RMQ X X X
40RMS X X X X X X X X

Fig. 2 — Model Number Nomenclature

Unit Positioning — The unit can be mounted on the


floor for vertical application with return air entering the face
of the unit and supply air discharging vertically through the
top of the unit. The unit can also be applied in a horizontal
arrangement with return air entering horizontally and the sup-
ply air discharging horizontally. When applying the unit in
a horizontal arrangement, ensure the condensate drain pan is
located at the bottom center of the unit for adequate con-
densate disposal. See Fig. 3 for condensate connections for LEGEND
each unit position. Accessory Line
Typical positioning and alternate return air locations are
Alternate Air Intake and Discharge
shown in Fig. 3. Alternate return air locations can be used by
moving the unit panel from the alternate return air location Air Intake and Discharge
to the standard return air location.
IMPORTANT: Do NOT attempt to install unit with Fig. 3 — Typical Unit Positioning
return air entering top panel of unit. Condensate will
not drain from unit.

11
More user manuals on ManualsBase.com
Unit Isolation — Where extremely quiet operation is Refrigerant Piping — See Tables 1A, 1B, 1D, 1E for
essential, install isolators between floor and base of unit, or refrigerant pipe connection sizes. For ease in brazing, it is
between ceiling and top section of unit. recommended that all internal solder joints be made before
Be sure that unit is level and adequately supported. Use unit is placed in final position.
channels at front and sides of unit for reference points when The 40RM and 40RMQ direct-expansion units have
leveling. internal factory-installed thermostatic expansion valves (TXVs),
distributors, and nozzles for use with R-22. See Table 2 for
Refrigerant and Chilled Water Piping Access — part numbers. Knockouts are provided in the unit corner posts
The 40RM Series units come with standard knockouts for for 40RM and 40RMQ008 and 012 refrigerant piping. The
refrigerant and chilled water piping. These knockouts are lo- 40RMQ016 unit requires additional field-fabricated piping
cated on both sides of the unit for installation flexibility. The access holes. See Fig. 4, which also lists recommended knock-
standard knockouts provide sufficient access to the unit’s coils outs and access holes to use for each 40RM and 40RMQ
for all 40RM and some 40RMQ units, however, for 40RMQ016 unit size. Recommended fittings are listed in Table 3.
and 40RMS units, additional holes must be field-fabricated The sensor bulb capillary tubes must be routed from the
to accommodate the piping. See Fig. 4 for the positions and TXVs inside the unit through one of the piping access holes.
dimensions of the additional access holes required for these Clamp the TXV sensor bulb on a vertical portion of the suc-
units, including hole diameters and drilling dimensions. Rec- tion line, outside the unit. See Fig. 5.
ommended access hole use is also listed for all units. Note
that Fig. 4 shows the access holes on the control-box side of
the unit; this is the side of the unit with the coil headers, so
it is used most often for piping access.

FIELD-FABRICATED HOLE DIAMETERS, FIELD-FABRICATED HOLE POSITION


UNIT USE HOLE in. (mm) DIMENSIONS, in. (mm)
NUMBERS
No. 5 No. 6 No. 7 No. 8 A B C D
40RM007,008 1, 3 — — — — — — — —
40RMQ008
40RM012-034 1, 2, 3, 4 — — — — — — — —
40RMQ012
40RMS008-012 4, 5 1 ⁄ (44.5)
34 — — — 6.25 (158.8) — — —
40RMS014-024 4, 5, 6, 7 13⁄4 (44.5) 13⁄4 (44.5) 13⁄4 (44.5) — 3.0 (76.2) 6.0 (152.4) 10.5 (266.7) —
40RMQ016 3*, 5, 6, 7 11⁄8 (28.6) 11⁄8 (28.6) 13⁄4 (44.5) — 3.25 (82.6) 6.125 (155.6) 10.38 (263.7) —
40RMS028,034 5, 6, 7, 8 21⁄2 (63.5) 21⁄2 (63.5) 21⁄2 (63.5) 21⁄2 (63.5) 6.0 (152.4) 9.625 (244.5) 13.38 (339.9) 17.0 (431.8)

*Must be enlarged from 11⁄8 in. to 13⁄4 inches.


NOTE: Access hole knockouts 1-4 are factory-supplied.
Fig. 4 — Refrigerant and Chilled Water Piping Access Holes

12
More user manuals on ManualsBase.com
IMPORTANT: Never attach the sensor to the suction
manifold. Do NOT mount the sensor on a trapped por-
tion of the suction line.

40RM Series evaporator coils have a face-split design. En-


sure that lower circuit of coil is first on/last off when con-
nected to the condensing unit and/or system controls. See
Fig. 6.
External TXV equalizer connections are provided and factory-
brazed into the coil suction manifolds.
If suction line must be horizontal, clamp bulb to suction
line at least 45 degrees above bottom, at approximately the
4 o’clock or 8 o’clock position. See Fig. 7.
NOTE: The 40RMQ units are supplied with factory-installed
thermostatic expansion valves and check valve bypasses.
No extra piping connections or kits are required to install the
40RMQ with a 38AQS condensing unit in a heat pump FIRST ON/LAST OFF=B
system, however, some field supplied components may be VERTICAL INSTALLATION
required. See the following two sections.

FIRST ON/LAST OFF=A


HORIZONTAL INSTALLATION
Fig. 6 — Typical Evaporator Coil Connections
(40RM, 40RMQ)

LEGEND
TXV — Thermostatic Expansion Valve
NOTE: Component location arrangement shown for field installation
of sight glasses, solenoid valves, filter driers, and TXV sensing bulbs.
The TXVs and equalizer lines are factory installed.
Fig. 5 — Face-Split Coil Suction and
Liquid Line Piping (Typical)

LEGEND
TXV — Thermostatic Expansion Valve
NOTE: The 8 o’clock position is shown above.
Fig. 7 — TXV Sensing Bulb Location

13
More user manuals on ManualsBase.com
Table 2 — Factory-Installed Nozzle and Distributor Data

TXV DISTRIBUTOR FEEDER TUBES NOZZLE


UNIT Qty...Part No. Qty...Part No. PER DISTRIBUTOR* Qty...Part No.
Qty...Size (in.)
40RM007 1...XVE-5 1...1116 12 1...E5
40RM008 1...SVE-8 1...1126 15 1...C6
40RMQ008 1...SVE-8 1...1657 15 1...C6
40RM012 2...XVE-4 2...1115 9 2...E4
40RMQ012 2...XVE-4 2...1655 9 2...E4
40RM014 2...XVE-5 2...1115 9 2...E5
40RM016 2...XVE-8 2...1116 12 2...E6
40RMQ016 2...SVE-8 2...1126 16 2...C6
40RM024 2...XVE-10 2...1116 13 2...E8
40RM028 2...EBSVE-11 2...1126 15 2...C10
40RM034 2...SVE-15 2...1126 18 2...C12
* Feeder tube size is 1⁄4 in. (6.35 mm).
NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.

38AQS008/40RMQ008 HEAT PUMP SYSTEM PIPING —


Addition of a liquid solenoid valve (LLSV) is recommended
when the piping system length exceeds 75 feet. The LLSV
must be a bi-flow type suited for use in heat pump systems.
The recommended valve is Sporlan model CB14S2 (5/8-in.
ODF, 7/8-in. ODM) available from the Replacement Com-
ponents Division as part number EF23JS-214. This solenoid
valve requires Sporlan part no. MKC-2 coils that must be
purchased locally. Wire the solenoid valve in parallel with
the compressor contactor coil.

The LLSV must be installed at the outdoor unit with the LEGEND
flow arrow pointed toward the outdoor unit (in-flow TXV — Thermostatic Expansion Valve
direction for the heating mode.)
RECOMMENDED FILTER DRIERS*
(38AQS012,016/40RMQ SYSTEMS)
FILTER DRIER REQUIREMENTS FOR 38AQS012/
40RMQ012 AND 38AQS016/40RMQ016 HEAT PUMP LIQUID
SYSTEMS — The 38AQS012 and 016 units do not in- UNIT LINE PART NO. QUANTITY FIGURE
clude filter driers. Filter driers must be field-supplied 38AQS SIZE REQUIRED REFERENCE
(in.)
and installed in 38AQS012/40RMQ012 and 38AQS016/ 1⁄2
40RMQ016 systems. The filter driers used with these sys- P504-8084S 2 A
012 5⁄8
tems must be bi-flow types suited for use in heat pump P504-8165S 1 B
1⁄2 P504-8084S 2 A
applications. The Replacement Component Division part num- 016
bers listed in Fig. 8 are recommended and available for field 5⁄8 P504-8085S 2 A
installation. *Available from Carrier Replacement Components Division.
Fig. 8 — Filter Drier Requirements —
38AQS012/40RMQ012 and 38AQS016/40RMQ016
Heat Pump Systems

14
More user manuals on ManualsBase.com
Table 3 — Fitting Requirements

UNIT ACCESS CONNECTION CIRCUIT FITTINGS REQUIRED†


HOLE NO.* TYPE (in.)
11⁄8 Street Elbow
1 Suction — 11⁄8 Nipple, 105⁄8 L
40RM 11⁄8 Long Radius Elbow
007 5⁄8 Street Elbow

3 Liquid — 5⁄8 Nipple, 85⁄8 L


5⁄8 Long Radius Elbow

11⁄8 Street Elbow


1 Suction — 11⁄8 Nipple, 85⁄8 L
40RM 11⁄8 Long Radius Elbow
40RMQ 5⁄8 Street Elbow
008
3 Liquid — 5⁄8 Nipple, 85⁄8 L
5⁄8 Long Radius Elbow

13⁄8 Nipple, 43⁄8 L


13⁄8 Long Radius Elbow
4 Return — 13⁄8 Nipple, 73⁄8 L
40RMS
008-012 13⁄8 Long Radius Elbow
5 Supply — 13⁄8 Nipple, 65⁄8 L
13⁄8 Long Radius Elbow
1 Suction Lower (2) 11⁄8 Street Elbow
5⁄8 Street Elbow

2 Liquid Lower 5⁄8 Nipple, 81⁄2 L


5⁄8 Long Radius Elbow

5⁄8 Street Elbow


40RM
012 3 Liquid Upper 5⁄8 Nipple, 131⁄2 L
5⁄8 Long Radius Elbow

11⁄8 Nipple, 53⁄4 L


11⁄8 Long Radius Elbow
4 Suction Upper
11⁄8 Nipple, 12 L
11⁄8 Long Radius Elbow
1 Suction Lower (2) 11⁄8 Street Elbow
5⁄8 Street Elbow

2 Liquid Lower 5⁄8 Nipple, 51⁄2 L


5⁄8 Long Radius Elbow

5⁄8 Street Elbow


40RMQ
012 3 Liquid Upper 5⁄8 Nipple, 101⁄2 L
5⁄8 Long Radius Elbow

11⁄8 Nipple, 55⁄8 L


4 Suction Upper 11⁄8 Long Radius Elbow
11⁄8 Nipple, 12 L
11⁄8 Long Radius Elbow
11⁄8 Street Elbow
1 Suction Lower 11⁄8 Nipple, 75⁄8 L
11⁄8 Long Radius Elbow
5⁄8 Street Elbow

2 Liquid Lower 5⁄8 Nipple, 17⁄16 L


5⁄8 Long Radius Elbow
40RM 5⁄8 Street Elbow
014
3 Liquid Upper 5⁄8 Nipple, 111⁄2 L
5⁄8 Long Radius Elbow

11⁄8 Nipple, 55⁄8 L


4 Suction Upper 11⁄8 Long Radius Elbow
11⁄8 Nipple, 13 L
11⁄8 Long Radius Elbow
13⁄8 Long Radius Elbow
4 Supply Lower 13⁄8 Nipple, 33⁄4 L
13⁄8 Long Radius Elbow
13⁄8 Long Radius Elbow
5 Return Lower 13⁄8 Nipple, 33⁄8 L
40RMS 13⁄8 Long Radius Elbow
014-024 13⁄8 Long Radius Elbow
6 Return Upper 13⁄8 Nipple, 7 L
13⁄8 Long Radius Elbow
13⁄8 Long Radius Elbow
7 Supply Upper 13⁄8 Nipple, 113⁄4 L
13⁄8 Long Radius Elbow
*See Fig. 4 for access hole location by number.
†Fittings are listed in order from header or tee stub connection out to access hole in corner support post.

15
More user manuals on ManualsBase.com
Table 3 — Fitting Requirements (cont)

UNIT ACCESS CONNECTION CIRCUIT FITTINGS REQUIRED†


HOLE NO.* TYPE (in.)
11⁄8 Street Elbow
1 Suction Lower 11⁄8 Nipple, 23⁄4 L
11⁄8 Long Radius Elbow
5⁄8 Street Elbow

2 Liquid Lower 5⁄8 Nipple, 13⁄8 L


5⁄8 Long Radius Elbow
40RM 5⁄8 Street Elbow
016
3 Liquid Upper 5⁄8 Nipple, 111⁄2 L
5⁄8 Long Radius Elbow

11⁄8 Nipple, 55⁄8 L


11⁄8 Long Radius Elbow
4 Suction Upper
11⁄8 Nipple, 13 L
11⁄8 Long Radius Elbow
11⁄8 Nipple, 3 L
3 Suction Lower
11⁄8 Long Radius Elbow
5⁄8 Nipple, 27⁄8 L
5⁄8 45° Elbow
5 Liquid Lower 5⁄8 Nipple, 15⁄8 L
5⁄8 Long Radius Elbow

40RMQ 5⁄8 Nipple, 27⁄8 L


016 5⁄8 45° Elbow
6 Liquid Upper 5⁄8 Nipple, 41⁄4 L
5⁄8 Long Radius Elbow

11⁄8 Nipple, 5 L
7 Suction Upper 11⁄8 45° Elbow
11⁄8 Nipple, 83⁄4 L
11⁄8 Long Radius Elbow
11⁄8 Street Elbow
1 Suction Lower 11⁄8 Nipple, 75⁄8 L
11⁄8 Long Radius Elbow
5⁄8 Street Elbow

2 Liquid Lower 5⁄8 Nipple, 61⁄2 L


5⁄8 Long Radius Elbow
40RM 5⁄8 Street Elbow
024
3 Liquid Upper 5⁄8 Nipple, 91⁄2 L
5⁄8 Long Radius Elbow

11⁄8 Nipple, 55⁄8 L


4 Suction Upper 11⁄8 Long Radius Elbow
11⁄8 Nipple, 11 L
11⁄8 Long Radius Elbow
13⁄8 Street Elbow
1 Suction Lower 13⁄8 Nipple, 11 L
13⁄8 Long Radius Elbow
5⁄8 Street Elbow

2 Liquid Lower 5⁄8 Nipple, 11⁄2 L


5⁄8 Long Radius Elbow
40RM 5⁄8 Street Elbow
028
3 Liquid Upper 5⁄8 Nipple, 193⁄4 L
5⁄8 Long Radius Elbow

13⁄8 Nipple, 43⁄16 L


13⁄8 Long Radius Elbow
4 Suction Upper
13⁄8 Nipple, 231⁄4 L
13⁄8 Long Radius Elbow

*See Fig. 4 for access hole location by number.


†Fittings are listed in order from header or tee stub connection out to access hole in corner support post.

16
More user manuals on ManualsBase.com
Table 3 — Fitting Requirements (cont)

UNIT ACCESS CONNECTION CIRCUIT FITTINGS REQUIRED†


HOLE NO.* TYPE (in.)
21⁄8 Long Radius Elbow
5 Supply Lower 21⁄8 Nipple, 31⁄2 L
21⁄8 Long Radius Elbow
21⁄8 Long Radius Elbow
6 Return Lower 21⁄8 Nipple, 3 L
40RMS 21⁄8 Long Radius Elbow
028, 034 21⁄8 Long Radius Elbow
7 Return Upper 21⁄8 Nipple, 67⁄8 L
21⁄8 Long Radius Elbow
21⁄8 Long Radius Elbow
8 Supply Upper 21⁄8 Nipple, 117⁄8 L
21⁄8 Long Radius Elbow
13⁄8 Street Elbow
1 Suction Lower 13⁄8 Nipple, 3 L
13⁄8 Long Radius Elbow
5⁄8 Street Elbow

2 Liquid Lower 5⁄8 Nipple, 73⁄4 L


5⁄8 Long Radius Elbow
40RM 5⁄8 Street Elbow
034
3 Liquid Upper 5⁄8 Nipple, 181⁄2 L
5⁄8 Long Radius Elbow

13⁄8 Nipple, 43⁄16 L


4 Suction Upper 13⁄8 Long Radius Elbow
13⁄8 Nipple, 191⁄4 L
13⁄8 Long Radius Elbow
*See Fig. 4 for access hole location by number.
†Fittings are listed in order from header or tee stub connection out to access hole in corner support post.

Chilled Water Piping — See Tables 1C and 1F for To size, design, and install chilled water piping, consult
chilled water connection sizes. For ease in brazing, it is rec- the Carrier System Design manual. See Fig. 9 for an ex-
ommended that all internal solder joints be made before unit ample of a typical installation. Recommended fittings are listed
is placed in final position. in Table 3.
Knockouts are provided in the unit corner posts for 40RM To access 40RMS coil vents and drains, remove the unit
and 40RMQ refrigerant piping; additional field-fabricated ac- side panel over the coil header. Vent and drain plugs are on
cess holes are required for 40RMS chilled water piping. See the top and bottom of header, respectively. See the Service
Fig. 4, which lists recommended knockouts and access holes section for information on preventing coil freeze-up during
to use for each 40RMS unit size. winter.

Fig. 9 — Typical 40RMS Chilled Water Piping

17
More user manuals on ManualsBase.com
Condensate Drain — Install a trapped condensate drain outlet at both ends of the unit, push drain pan down in
line to unit connection as shown in Fig. 10. The unit drain the slots near the drain connection, and up in the slots
connection is a PVC stub. See Fig. 11. Some areas may re- on the opposite end. Retighten screws. The pan should
quire an adapter to connect to either galvanized steel or have a pitch of at least 1⁄4-in. over its length toward the drain
copper pipe. For these applications, install a field-supplied connection.
threaded PVC adapter.
Fan Motors and Drives — Motor and drive pack-
NOTE: A trap must be installed in the condensate drain line ages are factory installed in all units. The standard motor
to ensure that the static pressure of fans is balanced with the and drive packages consist of the following items:
water column in the drain line and that condensate can drain
completely from pan. Without a trap, air can be drawn up 1 — fan motor
drain line until water level in condensate pan becomes equal 1 — adjustable motor pulley
to static pressure created by fans, preventing complete drain- 1 — fan pulley
age. Conditions will worsen as filters become dirty.
1 —fan belt (40RM007-016, 40RMQ008-016, 40RMS
Install clean-out plugs in trap. Pitch drain line downward 008-016 units)
to an open floor drain or sump. Provide service clearance
around drain line to permit removal of unit panels. Observe 2 —matched fan belts (40RM024-034, 40RMS024-034
all local sanitary codes. units)
As shipped, the unit’s condensate drain pan is NOT sloped For instructions on changing fan rotation, changing drive
towards the drain connection. The pan slope must be changed speeds and adjusting drives, see Pulley and Drive Adjust-
to pitch towards the side of the unit with the drain con- ment in the Service section.
nection. See Fig. 11. Loosen the 2 screws next to the drain

Fig. 11 — Drain Pan Slope Adjustment


NOTE: Dimensions in [ ] are in millimeters.
Fig. 10 — Condensate Drains

18
More user manuals on ManualsBase.com
Power Supply and Wiring — Check the unit data 230-v, 3-ph, 60 Hz operation. Rewire the motor according to
plate to ensure that available power supply matches electri- the diagram plate on the motor. After reconfiguring the mo-
cal characteristics of the unit. Provide a disconnect switch of tor, place the sticker specifying 230-v operation (supplied in
size required to provide adequate fan motor starting current. installation packet) over the 460-v sticker on the units cor-
See Tables 4 - 6 for unit electrical data. ner post.
Install disconnect switch and power wiring in accordance Fan motors are factory installed on all units. Indoor-fan
with all applicable local codes. See Fig. 12-14 and the unit contactors are located in the fan contactor box behind the
label diagram. For units with motor sizes less than 5 Hp side access panel (see Fig. 12 and 13). Wire the thermostat
(3.7 kW), connect power wiring to unit with no. 10 ring ter- to the 24-v control circuit terminal block located in the side
minal. For units with motor sizes of 5 Hp (3.7 kW) or more, of the fan contactor control box, according to Fig. 14 or the
connect power wiring with 1⁄4-in. ring terminal. unit label diagram. If the air handler is part of a split system,
complete the wiring from the condensing unit to the ther-
The 40RM, 40RMQ and 40RMS size 007-016 units (ex-
cept 40RM016 with YC or WD option) that have motors wired mostat shown in Fig. 14.
for 460-v, 3-ph, 60 Hz operation can be field-converted to

FAN SCROLL FAN


CONTACTOR
BOX
MOTOR
AND DRIVE WIRING
ACCESS

CONDENSATE

RJ AW
DRAIN FAN DRIVE

105° C 600V
CONNECTION PULLEY
(HORIZONTAL)

23 22

COIL
21

FILTER TXV BULB


ELEMENTS ACCESS
FAN
CONTACTOR 13 12 11

REFRIGERANT/
CHILLED WATER
FILTER PIPING ACCESS 24V
RETAINER TERMINAL
CLIP BLOCK
CONDENSATE
DRAIN POWER
CONNECTION WIRING
(VERTICAL) KNOCKOUT

TXV — Thermostatic Expansion Valve


Fig. 12 — Wiring and Service Access Fig. 13 — Fan Contactor Box and Terminal Block
(Side Panel Removed) (Cover Removed) (Typical)

19
More user manuals on ManualsBase.com
Table 4 — Electrical Data, Standard Motors
FAN MOTOR POWER SUPPLY
UNIT V*-PH-HZ VOLTAGE
LIMITS Minimum
Hp FLA Circuit Amps MOCP
208/230-1-60 187-253 1.3 7.6 9.5 15
208/230-3-60 187-253 2.4 5.8 7.3 15
40RM 460-3-60 414-528 2.4 2.6 3.3 15
007 575-3-60 518-632 1.0 1.35 1.7 15
230-3-50 207-253 2.4 5.8 7.3 15
400-3-50 360-440 2.4 2.6 3.3 15
208/230-1-60 187-253 2.4 11.0 13.8 20
208/230-3-60 187-253 2.4 5.8 7.3 15
40RM
40RMQ 460-3-60 414-528 2.4 2.6 3.3 15
40RMS 575-3-60 518-632 2.0 2.4 3.0 15
008
230-3-50 207-253 2.4 5.8 7.3 15
400-3-50 360-440 2.4 2.6 3.3 15
208/230-1-60 187-253 2.4 11.0 13.8 20
208/230-3-60 187-253 2.4 5.8 7.3 15
40RMS 460-3-60 414-528 2.4 2.6 3.3 15
010 575-3-60 518-632 2.0 2.4 3.0 15
230-3-50 207-253 2.4 5.8 7.3 15
400-3-50 360-440 2.4 2.6 3.3 15
208/230-3-60 187-253 2.4 5.8 7.3 15
40RM 460-3-60 414-528 2.4 2.6 3.3 15
40RMQ
40RMS 575-3-60 518-632 2.0 2.4 3.0 15
012 230-3-50 207-253 2.9 7.5 9.4 15
400-3-50 360-440 2.9 3.4 4.3 15
208/230-3-60 187-253 2.9 7.5 9.4 15
40RM 460-3-60 414-528 2.9 3.4 4.3 15
40RMS 575-3-60 518-632 3.0 3.8 4.8 15
014 230-3-50 207-253 2.9 7.5 9.4 15
400-3-50 360-440 2.9 3.4 4.3 15
208/230-3-60 187-253 3.7 10.6 13.3 20
40RM 460-3-60 414-528 3.7 4.8 6.0 15
40RMQ 575-3-60 518-632 3.0 3.8 4.8 15
40RMS
016 230-3-50 207-253 2.9 7.5 9.4 15
400-3-50 360-440 2.9 3.4 4.3 15
208/230-3-60 187-253 5.0 15.2/14.4 19.0/18.0 30/30
40RM 460-3-60 414-528 5.0 7.2 9.0 15
40RMS 575-3-60 518-632 5.0 5.6 7.0 15
024 230-3-50 207-253 5.0 14.4 18.0 30
400-3-50 360-440 5.0 7.2 9.0 15
208/230-3-60 187-253 7.5 22.0/21.0 27.5/26.3 45/45
40RM 460-3-60 414-528 7.5 10.5 13.1 20
40RMS 575-3-60 518-632 7.5 7.6 9.5 15
028 230-3-50 207-253 7.5 21.0 26.3 45
400-3-50 360-440 7.5 10.5 13.1 20
208/230-3-60 187-253 10.0 26.4/25.0 33.0/31.3 55/55
40RM 460-3-60 414-528 10.0 12.5 15.6 25
40RMS 575-3-60 518-632 10.0 9.6 12.0 20
034 230-3-50 207-253 10.0 25.0 31.3 55
440-3-50 360-440 10.0 12.5 15.6 25
See Legend and Notes on page 21.

20
More user manuals on ManualsBase.com
Table 5 — Electrical Data, Alternate Motors
FAN MOTOR POWER SUPPLY
UNIT V*-PH-HZ VOLTAGE
LIMITS Minimum
Hp FLA Circuit Amps MOCP
208/230-1-60 187-253 2.4 11.0 13.8 20
40RM 208/230-3-60 187-253 2.9 7.5 9.4 15
007 460-3-60 414-528 2.9 3.4 4.3 15
575-3-60 518-632 2.0 2.4 3.0 15
208/230-3-60 187-253 2.9 7.5 9.4 15
40RM 460-3-60 414-528 2.9 3.4 4.3 15
40RMQ 575-3-60 518-632 3.0 3.8 4.8 15
40RMS
008 230-3-50 207-253 2.9 7.5 9.4 15
400-3-50 360-440 2.9 3.4 4.3 15
208/230-3-60 187-253 2.9 7.5 9.4 15
460-3-60 414-528 2.9 3.4 4.3 15
40RMS 575-3-60 518-632 3.0 3.8 4.8 15
010
230-3-50 207-253 2.9 7.5 9.4 15
400-3-50 360-440 2.9 3.4 4.3 15
208/230-3-60 187-253 3.7 10.6 13.3 20
40RM 460-3-60 414-528 3.7 4.8 6.0 15
40RMQ 575-3-60 518-632 3.0 3.8 4.8 15
40RMS
012 230-3-50 207-253 5.0 14.4 18.0 30
400-3-50 360-440 5.0 7.2 9.0 15
208/230-3-60 187-253 3.7 10.6 13.3 20
40RM 460-3-60 414-528 3.7 4.8 6.0 15
40RMS 575-3-60 518-632 5.0 5.6 7.0 15
014 230-3-50 207-253 5.0 14.4 18.0 30
400-3-50 360-440 5.0 7.2 9.0 15
208/230-3-60 187-253 5.0 15.2/14.4 19.9/18.0 30/30
40RM 460-3-60 414-528 5.0 7.2 9.0 15
40RMQ 575-3-60 518-632 5.0 5.6 7.0 15
40RMS
016 230-3-50 207-253 5.0 14.4 18.0 30
400-3-50 360-440 5.0 7.2 9.0 15
208/230-3-60 187-253 7.5 22.0/21.0 27.5/26.3 45/45
40RM 460-3-60 414-528 7.5 10.5 13.1 20
40RMS 575-3-60 518-632 7.5 7.6 9.5 15
024 230-3-50 207-253 7.5 21.0 26.3 45
400-3-50 360-440 7.5 10.5 13.1 20
208/230-3-60 187-253 10.0 26.4/25.0 33.0/31.3 55/55
40RM 460-3-60 414-528 10.0 12.5 15.6 25
40RMS 575-3-60 518-632 10.0 9.6 12.0 20
028 230-3-50 207-253 10.0 25.0 31.3 55
400-3-50 360-440 10.0 12.5 15.6 25
LEGEND EXAMPLE: Supply voltage is 400-3-50.
FLA — Full Load Amps AB = 393 v
MOCP — Maximum Overcurrent Protection BC = 403 v
*Motors are designed for satisfactory operation within 10% of nomi- AC = 396 v
nal voltages shown. Voltages should not exceed the limits shown in 393 + 403 + 396
Average Voltage =
the Voltage Limits column. 3
NOTES: 1192
=
1. Minimum Circuit Amp and MOCP values are calculated in 3
accordance with NEC (National Electrical Code) (U.S.A. stand- = 397
ard), Article 440. Determine maximum deviation from average voltage.
2. Motor FLA values are established in accordance with UL (Under- (AB) 397 − 393 = 4 v
writers’ Laboratories) Standard 1995 (U.S.A. standard). (BC) 403 − 397 = 6 v
3. Unbalanced 3-Phase Supply Voltage (AC) 397 − 396 = 1 v
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine Maximum deviation is 6 v.
the percentage of voltage imbalance. Determine percent voltage imbalance.
% Voltage Imbalance 6
% Voltage Imbalance = 100 x
397
max voltage deviation from average voltage = 1.5%
= 100 x
average voltage This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than


2%, contact your local electric utility company immediately.

21
More user manuals on ManualsBase.com
LEGEND
CB — Circuit Breaker
HC — Heating Contactor
HTR — Electric Heater
IFC — Indoor-Fan Contactor
IFM — Indoor-Fan Motor
NEC — National Electrical Code
TB — Terminal Block
T’STAT — Thermostat
Factory Wiring
Field Control Wiring
NOTE: Use copper conductors only.

→ Fig. 14 — Unit Wiring

Table 6 — Fan Contactor Coil Data


UNIT VOLTAGE MAXIMUM
40RM, 40RMQ (vac) HOLDING
40RMS VA
007-034 24 10

Connecting Ductwork — Refer to the Carrier Sys-


tem Design Manual for the recommended design and layout
of ductwork. Figure 15 shows recommended duct connec-
tion to units with 2 fans.
DISCHARGE CONNECTIONS — Duct flanges are factory
supplied; they are shipped inside the unit attached to the hair-
pin end of the coil tube sheet for field installation. Using the
existing screws, install the duct flanges on the unit’s fan deck.
Each fan discharge requires 2 flanges; each flange must be
bent in the middle to conform to the discharge opening. See
Fig. 16. After flanges are installed, connect them to the sup-
ply duct using a canvas connection to prevent vibration. It is
important that this connection be properly fabricated to pre-
vent high air friction losses and air noise.
RETURN CONNECTION — When using return-air duct-
work, route return-air duct to the unit’s return air inlet near
the filter rack, using a canvas connection to prevent trans-
mission of unit vibration. If the duct blocks off the unit’s
access panel, provide a slip joint in the ductwork to permit
removal for servicing.
OUTDOOR-AIR INLET CONNECTION — Connect outdoor-
air inlet to field-installed accessory economizer. Refer to econo-
mizer Installation Instructions.
Return-Air Filters — Type and size of filters are Fig. 15 — Typical Fan Discharge Connections
shown in Tables 1A-1F and are factory-supplied and in- for Multiple Fan Units
stalled. In all units with 2 fans, a filter replacement tool (hook)
is shipped inside the unit for field use when replacing filters.
See the Service section for instructions on filter element
replacement.
596 22
More user manuals on ManualsBase.com
Fig. 16 — Duct Flange Installation

START-UP Fan Motor Lubrication — Fan motor supplied with


unit is permanently lubricated and requires no further
Before starting unit, check the following and correct as lubrication.
necessary:
• Is unit solidly supported? Fan Shaft Bearings — Bearings on 007-012 size units
• Is fan adjusted for speed and pulley alignment? are sealed, permanently lubricated bearings that require no
• Are pulleys, motor, and bearings securely mounted? further lubrication. Size 014-034 units have pillow-block bear-
• Are there any loose parts that will rattle or vibrate? ings (Fig. 17) that must be lubricated with suitable bearing
• Is condensate drain pan pitched for correct drainage? grease approximately every 3 months. See Table 7 for suit-
• Are coil baffle plates tight against coil to prevent air able lubricants.
bypass?
• Are all panels securely fastened? Table 7 — Lubricant Data
• Are all electrical connections correct and tight?
MANUFACTURER LUBRICANT
Also refer to condensing unit instructions before starting Sunoco Prestige 42
a split system. A split system start-up checklist is provided Texaco Multifak 2
in the back of these instructions. Texaco Regal AFB-2*
Mobil Mobilplex EP No. 2
*Preferred lubricant because it contains rust and oxidation
SERVICE inhibitors.

Inspection and maintenance should be performed at


regular intervals and should include the following:
• Complete cleaning of cabinet, fan wheel, cooling coil, con-
densate pan and drain, heating coils, and return-air grille
(if present).
• Inspection of panels and sealing of unit against air
leakage.
• Adjustment of fan motor, belt, bearings, and wheels.
• Cleaning or replacement of filters.
• Testing for cooling/heating system leaks.
• Checking of all electrical connections.
Most unit service can be performed by removing one or
both of the unit’s side panels. Coil cleaning or removal or
insulation cleaning may require removal of a rear, top, or
bottom panel, depending on the unit’s orientation. When serv-
ice is completed, replace unit panels.
Panels — Panels are fastened to unit frame with sheet Fig. 17 — Fan Shaft, Bearings, and Fan Wheel
metal screws. Fan and coil compartment must be sealed tightly (Typical)
after service to prevent air from bypassing the cooling coil.

23
More user manuals on ManualsBase.com
Centering Fan Wheel — If fan and fan shaft assem- Individual Fan Wheel Adjustment — Loosen the
bly are not properly centered, blades may scrape against scroll 2 locking bolts holding fan wheel hub to shaft. See Fig. 17.
or may create an objectionable whistling noise. It may be Position fan wheel in center of the fan housing and tighten
necessary to adjust individual fan wheels or move entire fan locking bolts. Clearance between wheel and housing should
shaft. See the following two sections. be the same on both sides.
Fan Shaft Position Adjustment — Loosen set- Fan Belts — Motor mounting plate and motor support
screw or locking collar of each fan shaft bearing. Slide shaft angles are slotted to permit both vertical and horizontal
into correct position and replace locking collar (Fig. 18). To adjustment. Adjust belt(s) for correct deflection by loosen-
replace locking collar, push collar up against inner face of ing motor plate mounting bolts, moving motor/plate assem-
bearing. Turn collar in direction of fan rotation until tight, bly forward or back, and retightening bolts. Press down on
and tighten setscrew. Tightening locking collar in direction belt with one finger midway between fan and motor pulleys
of fan rotation results in further tightening of collar should to check deflection. For units with motor sizes up to and
setscrew work itself loose. including 3.7 Hp (2.76 kW), correct deflection is 3⁄16-in.
(4.8 mm) For larger motor sizes, correct deflection is 1⁄8-in.
(3.2 mm). See Fig. 19.
NOTE: The 028 and 034 size units with 60 Hz motors are
shipped with an extra set of matching belts. Use the pre-
installed belts or extra belts depending on the adjustable
pulley setting.
If complete belt replacement is required during serv-
icing, loosen the motor plate mounting bolts (Fig. 19), move
motor/plate assembly towards fan pulley, and pull belt(s) off
pulleys. Reverse the procedure with new bolts and readjust
deflection.
Fan Rotation — Correct fan rotation with respect to
fan outlet is shown in Fig. 20.
To reverse the direction of rotation of a 3-phase fan mo-
tor, reverse any 2 of the power leads. Refer to the connection
diagram on the inside of motor terminal box cover for proper
reversing procedure of single-phase motor.
Fig. 18 — Fan Shaft Bearing

Fig. 19 — Fan Motor Mounting

24
More user manuals on ManualsBase.com
Fig. 20 — Fan Rotation

Fan Pulley Alignment — Align as follows:


1. Loosen setscrews on pulleys.
2. Align pulleys visually and tighten setscrews on fan pul-
ley to lock it in place.
3. Use the methods shown in Fig. 21 to check proper pulley
alignment. Fig. 21 — Fan Pulley Adjustments
4. If pulleys are not in correct alignment, loosen the motor
holddown bolts and slide the motor axially until the pul-
leys are aligned. Alternative freeze protection methods follow:
5. Tighten motor holddown bolts. • Circulate hot water within the water coil’s supply main or
supplementary space heating.
• Close off supply lines to unit and open a union or field-
Pulley and Drive Adjustment — To obtain desired supplied drain valve in the return line.
fan speed, refer to the fan motor and drive data in
Tables 8A-10D and adjust fan motor pulley as follows: IMPORTANT: Draining from return line will not
completely drain water from coils.
1. Remove belt from fan motor pulley after loosening mo-
tor from motor base.
After draining as much water as possible from coils, add
2. Loosen setscrew in moveable flange of pulley. Screw move- sufficient antifreeze to prevent residual water in the coil
able flange toward fixed flange to increase the fan speed from freezing.
and away from fixed flange to reduce speed. Before tight- • Add a sufficient quantity of non-corrosive antifreeze to the
ening setscrew, make certain that setscrew is over nearest entire system to prevent all water within the system from
flat surface of pulley hub (Fig. 21). freezing.
Coil Removal — Remove unit panels and corner posts
as required. Disconnect coil connections and remove fasten-
Increasing fan speed produces a greater load on mo- ing screws. Remove coil through end or side sections of unit.
tor. Do not exceed rated capacity of motor.
Cleaning Cooling Coil — Remove return-air filters.
Remove any heavy dirt that may have accumulated on un-
Condensate Drains — Keep condensate drains free of derside of coil. Coil can be cleaned more easily with a stiff
dirt and foreign matter. brush, vacuum cleaner, or compressed air when coil is dry.
If coil is wet or if water is to be used for cleaning, guard
Return-Air Filters — Refer to Replacing Filters sec- against splashing water on electrical components or dam-
tion, page 39, for filter accessibility and removal. Replace aging surrounding area. Clean coil baffles as applicable and
with clean filters of the sizes listed in Tables 1A-1F. check for tight fit to be sure air does not bypass coil.
Chilled Water Coil Freeze Protection — Shut off Cleaning Insulation — The insulation contains an
water supply to unit. Remove side panel of unit and remove immobilized antimicrobial agent that helps prevent the
vent and drain plugs in top and bottom of coil header. Drain growth of bacteria and fungi. Clean the inner surface of the
coil and blow out remaining water. Reinstall plugs and side insulation according to the separate maintenance instruc-
panel. tions shipped with the unit.

25
More user manuals on ManualsBase.com
Table 8A — Fan Motor Data, Standard Motor — English
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
208/230-1-60
Speed (rpm) 1725 1725 1725 — — — — — —
Hp 1.3 2.4 2.4 — — — — — —
Frame (NEMA) 56Y 56Y 56Y — — — — — —
Shaft Dia (in.) 5⁄8 5 ⁄8 5⁄8 — — — — — —
208/230-3-60 and 460-3-60
Speed (rpm) 1725 1725 1725 1725 1725 1725 1745 1745 1745
Hp 2.4 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y 56Y S184T S213T S215T
Shaft Dia (in.) 5⁄8 5 ⁄8 5⁄8 5 ⁄8 7 ⁄8 7 ⁄8 1 1 ⁄8 13⁄8 13⁄8
575-3-60
Speed (rpm) 1725 1725 1725 1725 1725 1725 1745 1755 1755
Hp 1.0 2.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0
Frame (NEMA) 56 56HZ 56HZ 56HZ 56HZ 56HZ 184T S213T D215T
Shaft Dia (in.) 5⁄8 7 ⁄8 7⁄8 7 ⁄8 7 ⁄8 7 ⁄8 1 1 ⁄8 13⁄8 13⁄8
230-3-50 and 400-3-50
Speed (rpm) 1425 1425 1425 1425 1425 1425 1425 1425 1425
Hp 2.4 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y 56Y 184T S213T S215T
Shaft Dia (in.) 5⁄8 5 ⁄8 5⁄8 7 ⁄8 7 ⁄8 7 ⁄8 1 1 ⁄8 13⁄8 13⁄8

NEMA — National Electrical Manufacturers Association

Table 8B — Fan Motor Data, Alternate Motor — English


40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS
007 40RMS 010 40RMS 40RMS
008 012 014 016 024 028
208/230-1-60
Speed (rpm) 1725 — — — — — — —
Hp 2.4 — — — — — — —
Frame (NEMA) 56Y — — — — — — —
Shaft Dia (in.) 5⁄8 — — — — — — —
208/230-3-60 and 460-3-60
Speed (rpm) 1725 1725 1725 1725 1725 1725 1745 1745
Hp 2.9 2.9 2.9 3.7 3.7 5.0 7.5 10.0
Frame (NEMA) 56Y 56Y 56Y Y56Y Y56Y S184T S213T S215T
Shaft Dia (in.) 7⁄8 7 ⁄8 7⁄8 7 ⁄8 7⁄8 11⁄8 13⁄8 13⁄8
575-3-60
Speed (rpm) 1725 1725 1725 1725 1745 1745 1755 1750
Hp 2.0 3.0 3.0 3.0 5.0 5.0 7.5 10.0
Frame (NEMA) 56HZ 56HZ 56HZ 56HZ 184T 184T S213T D215T
Shaft Dia (in.) 7⁄8 7 ⁄8 7⁄8 7 ⁄8 1 1 ⁄8 11⁄8 13⁄8 13⁄8
230-3-50 and 400-3-50
Speed (rpm) — 1425 1425 1425 1425 1425 1425 1425
Hp — 2.9 2.9 5.0 5.0 5.0 7.5 10.0
Frame (NEMA) — 56Y 56Y S184T S184T S184T S213T S215T
Shaft Dia (in.) — 7 ⁄8 7⁄8 7 ⁄8 1 1 ⁄8 11⁄8 13⁄8 13⁄8

NEMA — National Electrical Manufacturers Association

26
More user manuals on ManualsBase.com
Table 8C — Fan Motor Data, Standard Motor — SI
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
208/230-1-60
Speed (r/s) 28.75 28.75 28.75 — — — — — —
Shaft kW 0.97 1.79 1.79 — — — — — —
Frame (NEMA) 56Y 56Y 56Y — — — — — —
Shaft Dia (mm) 15.9 15.9 15.9 — — — — — —
208/230-3-60 and 460-3-60
Speed (r/s) 28.75 28.75 28.75 28.75 28.75 28.75 29.08 29.08 29.08
Shaft kW 1.79 1.79 1.79 1.79 2.16 2.76 3.73 5.60 7.46
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y 56Y S184T S213T S215T
Shaft Dia (mm) 15.9 15.9 15.9 15.9 22.2 22.2 28.6 34.9 34.9
575-3-60
Speed (r/s) 28.75 28.75 28.75 28.75 28.75 28.75 29.08 29.25 29.25
Shaft kW 0.746 1.49 1.49 1.49 2.24 2.24 3.73 5.60 7.46
Frame (NEMA) 56 56HZ 56HZ 56HZ 56HZ 56HZ 184T S213T S215T
Shaft Dia (mm) 15.9 22.2 22.2 22.2 22.2 22.2 28.6 34.9 34.9
230-3-50 and 400-3-50
Speed (r/s) 23.75 23.75 23.75 23.75 23.75 23.75 23.75 23.75 23.75
Shaft kW 1.79 1.79 1.79 2.16 2.16 2.16 3.73 5.60 7.46
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y 56Y 184T S213T S215T
Shaft Dia (mm) 15.9 15.9 15.9 22.2 22.2 22.2 28.6 34.9 34.9
NEMA — National Electrical Manufacturers Association

Table 8D — Fan Motor Data, Alternate Motor — SI


40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS
007 40RMS 010 40RMS 40RMS
008 012 014 016 024 028
208/230-1-60
Speed (r/s) 28.75 — — — — — — —
Shaft kW 1.79 — — — — — — —
Frame (NEMA) 56Y — — — — — — —
Shaft Dia (mm) 15.9 — — — — — — —
208/230-3-60 and 460-3-60
Speed (r/s) 28.75 28.75 28.75 28.75 28.75 29.08 29.08 29.17
Shaft kW 2.16 2.16 2.16 2.76 2.76 3.73 5.60 7.46
Frame (NEMA) 56Y 56Y 56Y Y56Y Y56Y S184T S213T S215T
Shaft Dia (mm) 22.2 22.2 22.2 22.2 22.2 28.6 34.9 34.9
575-3-60
Speed (r/s) 28.75 28.75 28.75 28.75 29.08 29.08 29.25 29.17
Shaft kW 1.49 2.24 2.24 2.24 3.73 3.73 5.60 7.46
Frame (NEMA) 56HZ 56HZ 56HZ 56HZ 184T 184T S213T D215T
Shaft Dia (mm) 22.2 22.2 22.2 22.2 28.6 28.6 34.9 34.9
230-3-50 and 400-3-50
Speed (r/s) — 23.75 23.75 23.75 23.75 23.75 23.75 23.75
Shaft kW — 2.16 2.16 3.73 3.73 3.73 5.60 7.46
Frame (NEMA) — 56Y 56Y S184T S184T S184T S213T S215T
Shaft Dia (mm) — 22.2 22.2 22.2 28.6 28.6 34.9 34.9

NEMA — National Electrical Manufacturers Association

27
More user manuals on ManualsBase.com
Table 9A — Standard Drive Data, 60 Hz — English
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 2.4-3.4 2.8-3.8 2.8-3.8 3.4-4.4 2.8-3.8 2.8-3.8 3.7-4.7 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting 2.5 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.) 8.8 8.8 8.8 8.8 9.0 9.0 9.4 11.0 11.0
Pulley Bore (in.) 1 1 1 1 17⁄16 17⁄16 17⁄16 115⁄16 115⁄16
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—A 2—B 2—B* 2—B*
Belt Pitch (in.) 40.3 41.3 41.3 42.3 42.3 42.3 41.8 (2) 42.8 (2) 42.8
(2) 43.8 (2) 43.8
FAN SPEEDS (rpm)
Factory Setting 568 647 647 764 632 632 771 752 752
Range 470-666 549-745 549-745 666-863 537-728 537-728 679-863 682-841 674-831
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1200 1100 1100
Change per 1⁄2 Turn of
Moveable Motor Pulley 19.6 19.6 19.6 19.7 19.1 19.1 15.3 13.1 13.1
Flange
MAX FULL TURNS FROM 5 5 5 5 5 5 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 10.44- 10.44- 9.12- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 12.32 12.32 10.99 9.43 9.43
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

Table 9B — Medium-Static Drive Data, 60 Hz — English


40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 40RMS
008 012 014 016 024 028 034
MOTOR DRIVE
Motor Pulley Pitch Diameter 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.3-5.3 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting
Full Turns Open 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 8.8 8.0 8.0 8.0 8.2 8.6 9.4 9.4 9.4
Pulley Bore (in.) 1 1 1 1 17⁄16 17⁄16 17⁄16 115⁄16 115⁄16
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—B 2—B 2—B* 2—B*
Belt Pitch (in.) 42.3 40.3 40.3 40.3 41.3 41.8 41.8 (2) 38.8 (2) 38.8
(2) 39.8 (2) 39.8
FAN SPEEDS (rpm)
Factory Setting 764 841 841 841 820 842 881 881 881
Range 666-863 733-949 733-949 733-949 715-926 742-943 798-984 798-984 798-984
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1200 1100 1100
Change per 1⁄2 Turn of
Moveable Motor Pulley 19.7 21.6 21.6 21.6 21.1 16.7 15.3 15.3 15.3
Flange
MAX FULL TURNS FROM
CLOSED POSITION 5 5 5 5 5 6 6 6 6
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 10.44- 10.44- 9.16- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 12.32 12.32 10.99 9.43 9.43
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

28
More user manuals on ManualsBase.com
Table 9C — High-Static Drive Data, 60 Hz — English
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.3-5.3 4.3-5.3 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.) 7.0 6.0* 6.0 6.0 7.4 7.9 7.4 8.6 8.6
Pulley Bore (in.) 1 1 1 1 17⁄16 17⁄16 17⁄16 115⁄16 115⁄16
Belt No. — Section 1—A 1—A 1—A 1—A 1—B 1—B 2—B 2—B 2—B
Belt Pitch (in.) 41.3 37.3 37.3 37.3 39.8 39.8 36.8 37.8 37.8
FAN SPEEDS (rpm)
Factory Setting 961 1121 1121 1121 979 1060 1118 1024 1024
838- 978- 978- 978- 873- 950- 1014- 873- 873-
Range 1084 1200*† 1200† 1200† 1096 1171 1200† 1075 1075
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1200 — —
Change per 1⁄2 Turn of
Moveable Motor Pulley 24.6 28.7 28.7 28.7 19.4 18.4 19.4 16.7 16.7
Flange
MAX FULL TURNS FROM 5 5 5 5 6 6 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 10.44- 9.16- 8.16- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 12.32** 10.99 10.02 9.43 9.43
*Valves for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in.
and resulting fan speed is 837-1096 rpm.
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.
**575-v unit has a center distance of 9.16-10.99.

Table 9D — Standard Drive Data, 50 Hz — English


40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 40RMS
008 012 014 016 024 028 034
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.) 2.4-3.4 2.8-3.8 2.8-3.8 3.4-4.4 3.4-4.4 3.4-4.4 4.3-5.3 4.3-5.3 4.3-5.3
Pulley Factory Setting
Full Turns Open 2.5 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 8.0 8.0 8.0 8.0 9.0 9.0 8.6 11.0 11.0
Pulley Bore (in.) 1 1 1 1 17⁄16 17⁄16 17⁄16 115⁄16 115⁄16
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—A 1—B 2—B 2—B
Belt Pitch (in.) 39.3 39.3 39.3 40.3 42.3 42.3 41.8 43.8 43.8
FAN SPEEDS (rpm)
Factory Setting 517 588 588 695 618 618 795 622 622
Range 428-606 499-677 449-677 606-784 538-697 538-697 713-878 557-687 557-687
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1200 1100 1100
Change per 1⁄2 Turn of
Moveable Motor Pulley 17.8 17.8 17.8 17.8 15.9 15.9 13.8 10.8 10.8
Flange
MAX FULL TURNS FROM
CLOSED POSITION 5 5 5 5 5 5 6 6 6
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 10.44- 10.44- 9.12- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 12.32 12.32 10.99 9.43 9.43

29
More user manuals on ManualsBase.com
Table 9E — Medium-Static Drive Data, 50 Hz — English
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.0-5.0 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting 2.5 2.5 2.5 2.5 2.5 3.0 2.5 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.) 8.0 7.0 7.0 6.0 7.5 7.9 7.0 9.4 9.4
Pulley Bore (in.) 1 1 1 1 17⁄16 17⁄16 17⁄16 115⁄16 115⁄16
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—B 2—A 2—B 2—B
Belt Pitch (in.) 40.3 41.3 41.3 37.3 39.3 39.8 36.8 39.8 39.8
FAN SPEEDS (rpm)
Factory Setting 695 794 794 926 741 756 916 728 728
Range 606-784 692-896 692-896 808-1045 646-836 667-848 814-1018 652-803 652-803
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1200 1100 1100
Change per 1⁄2 Turn of
Moveable Motor Pulley 17.8 20.4 20.4 23.7 19.0 15.1 20.4 12.6 12.6
Flange
MAX FULL TURNS FROM 5 5 5 5 5 6 5 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 10.44- 9.16- 9.16- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 12.32 10.99 10.99 9.43 9.43

Table 9F — High-Static Drive Data, 50 Hz — English


40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 40RMS
008 012 014 016 024 028 034
MOTOR DRIVE
Motor Pulley Pitch Diameter 3.4-4.4 3.4-4.4 3.4-4.4 4.0-5.0 3.4-4.4 4.0-5.0 4.0-5.0 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting
Full Turns Open 2.5 2.5 2.5 3.0 2.5 3.0 3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 6.0 5.5 5.5 5.5 6.0 7.0 6.4 8.0 8.6
Pulley Bore (in.) 1 1 1 1 17⁄16 17⁄16 17⁄16 115⁄16 115⁄16
Belt No. — Section 1—A 1—A 1—A 1—A 2—A 2—A 2—A 2—B 2—B
Belt Pitch (in.) 37.3 37.3 37.3 36.3 36.3 39.3 34.3 36.8 37.8
FAN SPEEDS (rpm)
Factory Setting 926 1010 1010 1166 926 916 1002 855 795
Range 808- 881- 881- 1036- 808- 814- 891- 766- 713-
1045 1140 1140 1200* 1045 1018 1113 944 878
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1200 1100 1100
Change per 1⁄2 Turn of
Moveable Motor Pulley 23.7 25.9 25.9 21.6 23.7 17.0 18.5 14.8 13.8
Flange
MAX FULL TURNS FROM
CLOSED POSITION 5 5 5 6 5 6 6 6 6
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 916- 9.16- 9.16- 8.16- 6.67- 6.67-
(in.) 12.32 12.32 12.32 10.99 10.99 10.99 10.02 9.43 9.43
*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.

30
More user manuals on ManualsBase.com
Table 9G — Standard Drive Data, 60 Hz — SI
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 61.0- 71.1- 71.1- 86.4- 71.1- 71.1- 94.0- 109.2- 109.2-
(mm) 86.4 96.5 96.5 111.8 96.5 96.5 119.4 134.6 134.6
Pulley Factory Setting 2.5 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm) 224 224 224 224 229 229 239 279 279
Pulley Bore (mm) 25.4 25.4 25.4 25.4 36.5 36.5 36.5 49.2 49.2
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—A 2—B 2—B* 2—B*
Belt Pitch (mm) 1024 1049 1049 1074 1074 1074 1062 (2) 1087 (2) 1087
(2) 1113 (2) 1113
FAN SPEEDS (r/s)
Factory Setting 9.5 10.8 10.8 12.7 10.5 10.5 12.9 12.5 12.5
Range 7.8-11.1 9.2-12.4 9.2-12.4 11.1-14.4 9.0-12.1 9.0-12.1 11.3-14.4 11.4-14.0 11.2-13.9
Max Allowable Speed (r/s) 20.0 20.0 20.0 20.0 20.0 20.0 20.0 18.3 18.3
Change per 1⁄2 Turn of
Moveable Motor Pulley 0.327 0.327 0.327 0.328 0.318 0.318 0.255 0.218 0.218
Flange
MAX FULL TURNS FROM 5 5 5 5 5 5 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 265-313 265-313 265-313 265-313 265-313 265-313 232-279 169-240 169-240
(mm)
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

Table 9H — Medium-Static Drive Data, 60 Hz — SI


40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 40RMS
008 012 014 016 024 028 034
MOTOR DRIVE
Motor Pulley Pitch Diameter 86.4- 86.4- 86.4- 86.4- 86.4- 94.0- 109.2- 109.2- 109.2-
(mm) 111.8 111.8 111.8 111.8 111.8 119.4 134.6 134.6 134.6
Pulley Factory Setting
Full Turns Open 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (mm) 224 203 203 203 208 218 239 239 239
Pulley Bore (mm) 25.4 25.4 25.4 25.4 36.5 36.5 36.5 49.2 49.2
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—B 2—B 2—B* 2—B*
Belt Pitch (mm) 1074 1024 1024 1024 1049 1062 1062 (2) 986 (2) 986
(2) 1011 (2) 1011
FAN SPEEDS (r/s)
Factory Setting 12.7 14.0 14.0 14.0 13.7 14.0 14.7 14.7 14.7
Range 11.1- 12.2- 12.2- 12.2- 11.9- 12.4- 13.3- 13.3- 13.3-
14.4 15.8 15.8 15.8 15.4 15.7 16.4 16.4 16.4
Max Allowable Speed (r/s) 20.0 20.0 20.0 20.0 20.0 20.0 20.0 18.3 18.3
Change per 1⁄2 Turn of
Moveable Motor Pulley 0.328 0.360 0.360 0.360 0.352 0.278 0.255 0.255 0.255
Flange
MAX FULL TURNS FROM 5 5 5 5 5 6 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 265-313 265-313 265-313 265-313 265-313 265-313 232-279 169-240 169-240
(mm)
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

31
More user manuals on ManualsBase.com
Table 9I — High-Static Drive Data, 60 Hz — SI
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 86.4- 86.4- 86.4- 86.4- 94.0- 109.2 109.2- 109.2- 109.2-
(mm) 111.8 111.8 111.8 111.8 119.4 134.6 134.6 134.6 134.6
Pulley Factory Setting 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm) 178 152* 152 152 188 201 188 203 203
Pulley Bore (mm) 25.4 25.4 25.4 25.4 36.5 36.5 36.5 49.2 49.2
Belt No. — Section 1—A 1—A 1—A 1—A 1—B 1—B 2—B 2—B 2—B
Belt Pitch (mm) 1049 947 947 947 1011 1011 935 935 960
FAN SPEEDS (r/s)
Factory Setting 16.0 18.7 18.7 18.7 16.3 17.7 18.6 17.1 17.1
Range 14.0- 16.3- 16.3- 16.3- 14.4- 15.8- 16.9- 14.6- 14.6-
18.1 20.0*† 20.0† 20.0† 18.3 19.5 20.0† 17.9 17.9
Max Allowable Speed (r/s) 20.0 20.0 20.0 20.0 20.0 20.0 20.0 18.3 18.3
Change per 1⁄2 Turn of
Moveable Motor Pulley 0.410 0.478 0.478 0.478 0.323 0.307 0.323 0.278 0.278
Flange
MAX FULL TURNS FROM 5 5 5 5 6 6 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 265-313 265-313 265-313 265-313 265-313** 232-279 207-255 169-240 169-240
(mm)
*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 178 mm and
resulting fan speed is 14.0-18.3 r/s.
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed
20 r/s.
**575-v unit has a center distance of 233-279.

Table 9J — Standard Drive Data, 50 Hz — SI


40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 40RMS
008 012 014 016 024 028 034
MOTOR DRIVE
Motor Pulley Pitch Diameter 61.0- 71.1- 71.1- 86.4- 86.4- 86.4- 109.2- 109.2- 109.2-
(mm) 86.4 96.5 96.5 111.8 111.8 111.8 134.6 134.6 134.6
Pulley Factory Setting
Full Turns Open 2.5 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (mm) 203 203 203 203 229 229 218 279 279
Pulley Bore (mm) 25.4 25.4 25.4 25.4 36.5 36.5 36.5 49.2 49.2
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—A 1—B 2—B 2—B
Belt Pitch (mm) 998 998 998 1024 1074 1074 1062 1113 1113
FAN SPEEDS (r/s)
Factory Setting 8.6 9.8 9.8 11.6 10.3 10.3 13.3 10.4 10.4
7.1- 8.3- 8.3- 10.1- 9.0- 9.0- 11.9- 9.3- 9.3-
Range 10.1 11.3 11.3 13.1 11.6 11.6 14.6 11.5 11.5
Max Allowable Speed (r/s) 20.0 20.0 20.0 20.0 20.0 20.0 20.0 18.3 18.3
Change per 1⁄2 Turn of
Moveable Motor Pulley 0.297 0.297 0.297 0.297 0.265 0.265 0.230 0.180 0.180
Flange
MAX FULL TURNS FROM 5 5 5 5 5 5 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 265-313 265-313 265-313 265-313 265-313 265-313 232-279 169-240 169-240
(mm)

32
More user manuals on ManualsBase.com
Table 9K — Medium-Static Drive Data, 50 Hz — SI
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 86.4- 86.4- 86.4- 86.4- 86.4- 94.0- 101.6- 109.2- 109.2-
(mm) 111.8 111.8 111.8 111.8 111.8 119.4 127.0 134.6 134.6
Pulley Factory Setting 2.5 2.5 2.5 2.5 2.5 3.0 2.5 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm) 203 178 178 152 191 201 178 239 239
Pulley Bore (mm) 25.4 25.4 25.4 25.4 36.5 36.5 36.5 49.2 49.2
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—B 2—A 2—B 2—B
Belt Pitch (mm) 1024 1049 1049 947 998 1011 922 1011 1011
FAN SPEEDS (r/s)
Factory Setting 11.6 13.2 13.2 15.4 12.4 12.6 15.3 12.1 12.1
Range 10.1- 11.5- 11.5- 13.5- 10.8- 11.1- 13.6- 10.9- 10.9-
13.1 14.9 14.9 17.4 13.9 14.1 17.0 13.4 13.4
Max Allowable Speed (r/s) 20.0 20.0 20.0 20.0 20.0 20.0 20.0 18.3 18.3
Change per 1⁄2 Turn of
Moveable Motor Pulley 0.297 0.340 0.340 0.395 0.317 0.252 0.340 0.210 0.210
Flange
MAX FULL TURNS FROM 5 5 5 5 5 6 5 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 265-313 265-313 265-313 265-313 265-313 232-279 232-279 169-240 169-240
(mm)

Table 9L — High-Static Drive Data, 50 Hz — SI


40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 40RMS
008 012 014 016 024 028 034
MOTOR DRIVE
Motor Pulley Pitch Diameter 86.4- 86.4- 86.4- 101.6- 86.4- 101.6- 101.6- 109.2- 109.2-
(mm) 111.8 111.8 111.8 127.0 111.8 127.0 127.0 134.6 134.6
Pulley Factory Setting
Full Turns Open 2.5 2.5 2.5 3.0 2.5 3.0 3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (mm) 152 140 140 140 152 178 163 203 218
Pulley Bore (mm) 25.4 25.4 25.4 25.4 36.5 36.5 36.5 49.2 49.2
Belt No. — Section 1—A 1—A 1—A 1—A 2—A 2—A 2—A 2—B 2—B
Belt Pitch (mm) 947 947 947 922 922 998 871 935 960
FAN SPEEDS (r/s)
Factory Setting 15.4 16.8 16.8 19.4 15.4 15.3 16.7 14.3 13.3
Range 13.5- 14.7- 14.7- 17.3- 13.5- 13.6- 14.9- 12.8- 11.9-
17.4 19.0 19.0 20.0* 17.4 17.0 18.6 15.7 14.6
Max Allowable Speed (r/s) 20.0 20.0 20.0 20.0 20.0 20.0 20.0 18.3 18.3
Change per 1⁄2 Turn of
Moveable Motor Pulley 0.395 0.432 0.432 0.360 0.395 0.283 0.308 0.247 0.230
Flange
MAX FULL TURNS FROM 5 5 5 6 5 6 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 265-313 265-313 265-313 234-279 232-279 232-279 207-255 169-240 169-240
(mm)
*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 20 r/s.

33
More user manuals on ManualsBase.com
Table 10A — Fan Performance Data — 0.0-1.2 in. wg ESP — English
EXTERNAL STATIC PRESSURE (in. wg)
UNIT AIRFLOW 0.0 0.2 0.4 0.6 0.8 1.0 1.2
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1,800 320 0.22 442 0.32 534 0.42 611 0.52 678 0.61 739 0.70 795 0.80
2,100 373 0.31 483 0.42 569 0.53 642 0.63 708 0.73 767 0.82 821 0.92
40RM 2,400 427 0.42 526 0.53 606 0.64 676 0.75 739 0.86 796 0.96 849 1.06
007
2,700 480 0.54 570 0.67 646 0.78 712 0.89 773 1.00 828 1.11 880 1.21
3,000 533 0.69 616 0.82 687 0.94 750 1.05 808 1.16 862 1.28 912 1.39
2,250 359 0.32 472 0.44 560 0.55 634 0.65 700 0.75 759 0.86 814 0.96
40RM 2,600 415 0.45 516 0.57 599 0.68 669 0.79 732 0.90 790 1.01 843 1.11
40RMQ 3,000 478 0.62 569 0.75 645 0.86 712 0.98 773 1.09 828 1.20 879 1.32
40RMS
008 3,400 542 0.82 624 0.95 695 1.08 758 1.20 815 1.31 869 1.43 918 1.55
3,750 598 1.03 673 1.17 740 1.29 800 1.42 855 1.60 906 1.66 954 1.78
2,550 396 0.42 502 0.54 586 0.65 658 0.76 722 0.87 780 0.97 833 1.08
2,975 462 0.60 556 0.72 634 0.84 701 0.95 762 1.06 818 1.18 870 1.29
40RMS 3,400 527 0.80 612 0.93 684 1.06 748 1.18 806 1.30 860 1.41 910 1.53
010
3,825 593 1.05 670 1.18 737 1.31 797 1.44 852 1.56 904 1.68 952 1.80
4,250 659 1.33 729 1.47 791 1.60 848 1.73 901 1.86 950 1.98 997 2.11
3,000 444 0.58 541 0.71 621 0.83 691 0.94 753 1.05 809 1.17 862 1.28
40RM 3,500 518 0.82 604 0.95 677 1.08 742 1.20 801 1.32 855 1.44 906 1.56
40RMS 4,000 592 1.11 669 1.25 736 1.38 797 1.51 853 1.63 904 1.75 953 1.88
012 4,500 666 1.44 735 1.59 797 1.72 854 1.86 907 1.99 956 2.12 1003 2.24
5,000 740 1.83 803 1.98 861 2.12 914 2.26 964 2.39 1010 2.53 1055 2.66
3,000 471 0.61 564 0.74 642 0.86 710 0.97 771 1.09 827 1.20 878 1.31
3,500 550 0.87 632 1.00 703 1.13 766 1.25 824 1.37 877 1.49 926 1.60
40RMQ 4,000 628 1.17 701 1.31 766 1.44 825 1.57 879 1.69 930 1.82 978 1.94
012
4,500 706 1.53 772 1.67 832 1.81 887 1.94 938 2.07 987 2.20 1032 2.33
5,000 785 1.93 845 2.08 900 2.22 952 2.36 1000 2.50 1045 2.63 1089 2.76
3,750 363 0.37 475 0.58 566 0.80 645 1.02 715 1.24 779 1.47 839 1.69
40RM 4,300 416 0.53 517 0.78 601 1.02 676 1.26 743 1.50 805 1.74 862 1.99
40RMS 5,000 484 0.81 573 1.08 650 1.35 719 1.62 782 1.89 841 2.16 896 2.44
014 5,700 552 1.17 631 1.47 702 1.76 766 2.06 826 2.36 881 2.66 934 2.96
6,250 605 1.51 678 1.83 744 2.15 805 2.47 862 2.79 915 3.11 966 3.43
4,500 391 0.51 495 0.75 581 1.00 657 1.25 725 1.50 787 1.76 845 2.02
40RM 5,300 460 0.80 551 1.08 629 1.35 700 1.63 764 1.91 823 2.20 878 2.48
40RMS 6,000 521 1.13 602 1.43 675 1.73 741 2.04 801 2.34 858 2.65 911 2.96
016 6,800 590 1.60 663 1.93 730 2.26 791 2.59 847 2.92 901 3.26 951 3.60
7,500 651 2.10 718 2.45 779 2.81 837 3.16 890 3.52 941 3.88 990 4.24
4,500 405 0.54 507 0.79 592 1.03 667 1.28 735 1.54 797 1.80 854 2.06
5,300 476 0.85 566 1.13 643 1.40 713 1.68 776 1.97 835 2.26 890 2.55
40RMQ
016 6,000 539 1.20 620 1.50 691 1.81 756 2.11 816 2.42 872 2.73 924 3.05
6,800 611 1.69 683 2.03 748 2.36 809 2.69 865 3.03 918 3.37 968 3.71
7,500 674 2.22 740 2.58 800 2.93 857 3.29 910 3.65 960 4.02 1008 4.38
6,000 503 1.07 587 1.37 661 1.67 727 1.97 789 2.28 846 2.59 900 2.90
40RM 7,000 586 1.64 660 1.98 726 2.31 787 2.65 844 2.99 898 3.33 948 3.67
40RMS 8,000 670 2.37 735 2.74 795 3.12 851 3.49 904 3.86 954 4.23 1001 4.61
024 9,000 754 3.28 812 3.69 867 4.09 918 4.50 967 4.90 1014 5.31 1059 5.72
10,000 838 4.39 891 4.83 941 5.27 988 5.70 1034 6.14 1077 6.85 1120 7.02
7,500 412 1.15 492 1.53 568 2.00 640 2.56 710 3.22 776 3.98 840 4.83
40RM 8,750 481 1.76 550 2.17 616 2.66 680 3.22 742 3.86 802 4.58 860 5.38
40RMS 10,000 549 2.55 610 2.99 669 3.50 726 4.07 782 4.70 836 5.40 889 6.17
028 11,250 618 3.52 672 4.00 725 4.53 777 5.12 827 5.76 876 6.45 925 7.21
12,500 687 4.71 735 5.22 783 5.78 830 6.38 876 7.04 922 7.74 966 8.49
9,000 471 1.78 539 2.17 604 2.63 667 3.17 728 3.78 788 4.46 845 5.22
40RM 10,500 550 2.72 608 3.15 665 3.64 720 4.18 774 4.79 827 5.45 878 6.18
40RMS 12,000 628 3.93 679 4.40 730 4.92 779 5.48 827 6.09 874 6.76 921 7.47
034 13,500 707 5.44 752 5.94 797 6.49 841 7.08 885 7.71 928 8.38 970 9.10
15,000 785 7.27 826 7.81 867 8.39 907 9.01 947 9.66 986 10.35 1024 11.07
See Legend and Notes on page 36.

34
More user manuals on ManualsBase.com
Table 10B — Fan Performance Data — 1.4-2.4 in. wg ESP — English
EXTERNAL STATIC PRESSURE (in. wg)
UNIT AIRFLOW 1.4 1.6 1.8 2.0 2.2 2.4
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1,800 847 0.89 896 0.98 942 1.07 986 1.16 1027 1.25 — —
2,100 872 1.02 920 1.11 965 1.21 1008 1.30 1050 1.40 — —
40RM 2,400 899 1.16 946 1.26 990 1.36 1033 1.46 1073 1.55 — —
007
2,700 928 1.32 974 1.42 1018 1.52 1059 1.63 1099 1.73 — —
3,000 959 1.49 1004 1.60 1046 1.71 1087 1.81 1126 1.92 — —
2,250 865 1.06 913 1.16 958 1.27 1001 1.37 1042 1.47 — —
40RM 2,600 893 1.22 940 1.33 984 1.43 1027 1.54 1067 1.65 — —
40RMQ 3,000 928 1.43 973 1.54 1017 1.65 1058 1.76 1098 1.87 — —
40RMS
008 3,400 965 1.66 1010 1.78 1052 1.89 1092 2.00 1131 2.12 — —
3,750 1000 1.90 1043 2.02 1084 2.13 1124 2.25 1162 2.37 — —
2,550 884 1.18 931 1.29 975 1.40 1018 1.50 1059 1.61 — —
2,975 919 1.40 965 1.51 1009 1.62 1050 1.73 1090 1.84 — —
40RMS 3,400 957 1.64 1002 1.76 1044 1.87 1085 1.98 1124 2.10 — —
010
3,825 998 1.92 1041 2.04 1082 2.16 1122 2.27 1160 2.39 — —
4,250 1041 2.23 1083 2.35 1123 2.48 1161 2.60 1199 2.72 — —
3,000 911 1.39 958 1.50 1002 1.61 1044 1.72 1084 1.83 1123 1.94
40RM 3,500 953 1.67 998 1.79 1041 1.90 1082 2.02 1122 2.13 1159 2.25
40RMS 4,000 999 2.00 1042 2.12 1084 2.24 1124 2.36 1162 2.48 1199 2.60
012 4,500 1047 2.37 1089 2.50 1129 2.62 1168 2.74 — — — —
5,000 1097 2.79 1138 2.92 1177 3.05 — — — — — —
3,000 927 1.43 973 1.54 1017 1.65 1058 1.76 1098 1.87 1137 1.98
3,500 973 1.72 1018 1.84 1060 1.95 1101 2.07 1139 2.18 1177 2.30
40RMQ 4,000 1023 2.06 1066 2.19 1107 2.31 1146 2.43 1184 2.55 — —
012
4,500 1075 2.45 1116 2.58 1156 2.71 1194 2.83 — — — —
5,000 1130 2.90 1170 3.03 — — — — — — — —
3,750 894 1.91 947 2.14 996 2.37 1044 2.60 1089 2.83 — —
40RM 4,300 916 2.23 967 2.48 1016 2.73 1062 2.98 1107 3.24 — —
40RMS 5,000 948 2.71 997 2.98 1044 3.26 1089 3.53 1133 3.81 — —
014 5,700 984 3.25 1031 3.55 1076 3.86 1120 4.16 1162 4.46 — —
6,250 1014 3.75 1060 4.07 1104 4.39 1147 4.71 1188 5.03 — —
4,500 899 2.29 951 2.56 999 2.84 1046 3.12 1091 3.41 1133 3.70
40RM 5,300 930 2.78 980 3.08 1027 3.38 1072 3.68 1116 3.99 1157 4.30
40RMS 6,000 961 3.28 1009 3.60 1055 3.92 1098 4.24 1141 4.57 1181 4.91
016 6,800 999 3.94 1045 4.28 1089 4.63 1132 4.98 1173 5.33 — —
7,500 1036 4.60 1080 4.97 1123 5.34 1164 5.71 — — — —
4,500 908 2.33 959 2.61 1008 2.89 1054 3.17 1098 3.46 1141 3.75
5,300 941 2.84 991 3.14 1038 3.45 1082 3.75 1126 4.06 1167 4.38
40RMQ
016 6,000 974 3.36 1022 3.69 1067 4.01 1111 4.34 1153 4.67 1193 5.00
6,800 1015 4.05 1061 4.40 1104 4.75 1146 5.10 1187 5.46 — —
7,500 1054 4.75 1098 5.12 1140 5.49 1181 5.86 — — — —
6,000 950 3.21 999 3.53 1045 3.85 1089 4.17 1131 4.50 1172 4.83
40RM 7,000 996 4.02 1042 4.37 1086 4.72 1129 5.07 1169 5.43 — —
40RMS 8,000 1047 4.99 1091 5.37 1133 5.75 1173 6.13 — — — —
024 9,000 1102 6.13 1143 6.54 1183 6.96 — — — — — —
10,000 1160 7.46 1200 7.91 — — — — — — — —
7,500 903 5.79 963 6.83 1021 7.98 1078 9.21 — — — —
40RM 8,750 917 6.26 972 7.22 1025 8.26 1078 9.38 — — — —
40RMS 10,000 941 7.01 991 7.91 1040 8.89 1089 9.93 — — — —
028 11,250 972 8.02 1019 8.89 1064 9.83 — — — — — —
12,500 1010 9.29 1053 10.15 1095 11.05 — — — — — —
9,000 901 6.07 955 6.98 1008 7.98 1060 9.05 — — — —
40RM 10,500 928 6.98 978 7.84 1026 8.76 1073 9.74 — — — —
40RMS 12,000 966 8.24 1011 9.07 1055 9.95 1098 10.88 — — — —
034 13,500 1011 9.86 1052 10.67 1092 11.52 — — — — — —
15,000 1062 11.84 — — — — — — — — — —
See Legend and Notes on page 36.

35
More user manuals on ManualsBase.com
Legend and Notes for Table 10A and 10B
LEGEND Factory-Supplied Filter Pressure Drop — English
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure UNIT AIRFLOW PRESSURE DROP
(Cfm) (in. wg)
NOTES: 1,800 0.05
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and 40RM 2,400 0.08
034; 1200 rpm for all other sizes. 007 3,000 0.11
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See right for factory-supplied filter pres- 40RM
40RMQ 2,250 0.07
sure drop. 3,000 0.11
3. Refer to fan motor and drive tables for additional data. 40RMS 3,750 0.15
008
2,550 0.09
40RMS 3,400 0.13
010 4,250 0.18
40RM
40RMQ 3,000 0.11
40RMS 4,000 0.17
012 5,000 0.23
40RM 3,750 0.06
40RMS 5,000 0.10
014 6,250 0.13
40RM
40RMQ 4,500 0.08
40RMS 6,000 0.12
016 7,500 0.17
40RM 6,000 0.12
40RMS 8,000 0.19
024 10,000 0.26
40RM 7,500 0.15
40RMS 10,000 0.22
028 12,500 0.30
40RM 9,000 0.19
40RMS 12,000 0.29
034 15,000 0.40

36
More user manuals on ManualsBase.com
Table 10C — Fan Performance Data — 0-300 Pa ESP — SI
EXTERNAL STATIC PRESSURE (Pa)
UNIT AIRFLOW 0 50 100 150 200 250 300
(L/s)
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
850 5.34 0.17 7.38 0.25 8.91 0.32 10.20 0.39 11.30 0.46 12.30 0.53 13.30 0.60
1000 6.28 0.24 8.10 0.32 9.53 0.40 10.80 0.48 11.80 0.55 12.80 0.63 13.70 0.70
40RM 1150 7.22 0.33 8.86 0.41 10.20 0.50 11.40 0.58 12.40 0.66 13.40 0.73 14.20 0.81
007
1300 8.17 0.43 9.64 0.52 10.90 0.61 12.00 0.69 13.00 0.77 13.90 0.85 14.80 0.93
1450 9.11 0.55 10.50 0.64 11.60 0.73 12.70 0.82 13.60 0.91 14.50 0.99 15.40 1.07
1000 5.63 0.22 7.61 0.30 9.11 0.38 10.40 0.45 11.50 0.53 12.50 0.61 13.40 0.68
40RM 1200 6.76 0.32 8.49 0.41 9.88 0.50 11.10 0.57 12.10 0.66 13.10 0.74 14.00 0.82
40RMQ 1400 7.89 0.46 9.42 0.55 10.70 0.64 11.80 0.72 12.80 0.81 13.80 0.89 14.60 0.97
40RMS
008 1600 9.01 0.62 10.40 0.71 11.60 0.80 12.60 0.89 13.60 0.98 14.50 1.07 15.30 1.16
1800 10.10 0.80 11.40 0.90 12.50 0.10 13.50 1.09 14.40 1.18 15.20 1.27 16.00 1.36
1200 6.58 0.31 8.35 0.40 9.76 0.49 11.00 0.57 12.00 0.65 13.00 0.73 13.90 0.81
1400 7.67 0.44 9.25 0.54 10.60 0.63 11.70 0.71 12.70 0.80 13.60 0.88 14.50 0.96
40RMS 1600 8.77 0.60 10.20 0.70 11.40 0.79 12.50 0.88 13.40 0.97 14.30 1.05 15.20 1.14
010
1800 9.86 0.78 11.10 0.88 12.30 0.98 13.30 1.07 14.20 1.16 15.10 1.25 15.90 1.34
2000 11.0 0.99 12.10 1.09 13.20 1.19 14.10 1.29 15.00 3.38 15.80 1.48 16.60 1.57
1450 7.58 0.46 9.18 0.56 10.50 0.65 11.60 0.73 12.70 0.82 13.60 0.90 14.50 0.99
40RM 1670 8.73 0.63 10.20 0.73 11.40 0.83 12.50 0.92 13.40 1.01 14.30 1.10 15.20 1.18
40RMS 1900 9.93 0.84 11.20 0.95 12.30 1.05 13.30 1.14 14.30 1.24 15.10 1.33 15.90 1.42
012 2120 11.10 1.08 12.20 1.18 13.30 1.29 14.20 1.39 15.10 1.48 15.90 1.58 16.70 1.68
2350 12.30 1.36 13.30 1.17 14.30 1.57 15.20 1.68 16.00 1.78 16.80 1.88 17.60 1.98
1450 8.04 0.49 9.57 0.58 10.90 0.67 12.00 0.76 13.00 0.85 13.90 0.93 14.80 1.02
1670 9.26 0.67 10.60 0.77 11.80 0.86 12.90 0.95 13.80 1.04 14.70 1.13 15.50 1.22
40RMQ 1900 10.50 0.89 11.80 0.99 12.80 1.09 13.80 1.19 14.70 1.28 15.60 1.38 16.40 1.47
012
2120 11.80 1.14 12.90 1.24 13.90 1.35 14.80 1.45 15.60 1.55 16.40 1.64 17.20 1.74
2350 13.00 1.43 14.00 1.54 15.00 1.65 15.80 1.75 16.60 1.85 17.40 1.95 18.10 2.05
1750 5.99 0.27 7.88 0.43 9.41 0.59 10.70 0.75 11.90 0.92 13.00 1.08 14.00 1.25
40RM 2050 7.01 0.41 8.68 0.60 10.10 0.78 11.30 0.96 12.40 1.14 13.50 1.33 14.40 1.51
40RMS 2350 8.04 0.60 9.53 0.81 10.80 1.01 12.00 1.21 13.00 1.41 14.00 1.61 14.90 1.82
014 2650 9.07 0.84 10.40 1.06 11.60 1.28 12.70 1.50 13.70 1.72 14.60 1.94 15.50 2.16
2950 10.10 1.13 11.30 1.37 12.40 1.61 13.40 1.85 14.40 2.08 15.30 2.32 16.10 2.56
2100 6.43 0.37 8.19 0.55 9.65 0.73 10.90 0.92 12.10 1.11 13.10 1.30 14.10 1.50
40RM 2450 7.51 0.57 9.06 0.77 10.40 0.97 11.60 1.18 12.70 1.39 13.70 1.60 14.60 1.81
40RMS 2800 8.58 0.82 9.96 1.05 11.20 1.27 12.30 1.49 13.30 1.72 14.30 1.95 15.10 2.18
016 3150 9.65 1.14 10.90 1.38 12.00 1.63 13.10 1.87 14.00 2.12 14.90 2.36 15.80 2.61
3500 10.70 1.52 11.90 1.78 12.90 2.05 13.90 2.31 14.80 2.58 15.60 2.84 16.40 3.11
2100 6.65 0.39 8.39 0.58 9.83 0.76 11.10 0.95 12.20 1.13 13.30 1.31 14.20 1.50
2450 7.76 0.60 9.30 0.81 10.60 1.01 11.80 1.22 12.90 1.43 13.80 1.63 14.80 1.84
40RMQ
016 2800 8.87 0.86 10.20 1.09 11.50 1.32 12.50 1.55 13.60 1.78 14.50 2.01 15.40 2.24
3150 9.98 1.19 11.20 1.44 12.30 1.70 13.40 1.95 14.30 2.20 15.20 2.45 16.00 2.70
3500 11.10 1.59 12.20 1.86 13.20 2.14 14.20 2.41 15.10 2.68 15.90 2.95 16.70 3.22
2900 8.58 0.86 9.96 1.09 11.20 1.32 12.30 1.55 13.30 1.78 14.20 2.01 15.10 2.25
40RM 3350 9.91 1.28 11.10 1.53 12.20 1.79 13.20 2.04 14.20 2.30 15.10 2.55 15.90 2.81
40RMS 3800 11.30 1.81 12.30 2.09 13.30 2.37 14.30 2.64 15.10 2.93 16.00 3.21 16.80 3.49
024 4250 12.60 2.46 13.60 2.76 14.50 3.07 15.30 3.37 16.10 3.67 16.90 3.98 17.70 4.28
4700 13.90 3.24 14.80 3.57 15.60 3.90 16.40 4.22 17.20 4.55 17.90 4.88 18.60 5.21
3500 6.79 0.84 8.14 1.12 9.42 1.47 10.70 1.89 11.80 2.39 12.90 2.96 14.00 3.61
40RM 4100 7.95 1.29 9.12 1.60 10.20 1.96 11.30 2.38 12.40 2.86 13.40 3.40 14.30 4.00
40RMS 4700 9.12 1.88 10.10 2.21 11.10 2.59 12.10 3.02 13.00 3.49 13.90 4.02 14.80 4.60
028 5300 10.30 2.62 11.20 3.00 12.10 3.37 12.90 3.81 13.80 4.29 14.60 4.82 15.40 5.38
5900 11.40 3.52 12.30 3.90 13.10 4.32 13.90 4.77 14.60 5.26 15.40 5.79 16.10 6.35
4250 7.86 1.33 8.99 1.63 10.10 1.97 11.10 2.37 12.20 2.83 13.20 3.34 14.10 3.92
40RM 4950 9.15 2.03 10.10 2.35 11.10 2.72 12.00 3.12 12.90 3.58 13.80 4.08 14.70 4.62
40RMS 5650 10.40 2.92 11.30 3.27 12.20 3.66 13.00 4.08 13.80 4.54 14.60 5.04 15.40 5.57
034 6350 11.70 4.02 12.50 4.40 13.30 4.81 14.00 5.25 14.70 5.72 15.50 6.23 16.20 6.77
7050 13.00 5.37 13.70 5.77 14.40 6.21 15.10 6.66 15.70 7.15 16.40 7.67 17.10 8.21
See Legend and Notes on page 39.

37
More user manuals on ManualsBase.com
Table 10D — Fan Performance Data — 350-600 Pa ESP — SI
EXTERNAL STATIC PRESSURE (Pa)
UNIT AIRFLOW 350 400 450 500 550 600
(L/s)
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
850 14.10 0.67 15.00 0.74 15.70 0.81 16.50 0.87 17.20 0.94 — —
1000 14.60 0.77 15.40 0.84 16.10 0.91 16.90 0.98 17.60 1.06 — —
40RM 1150 15.10 0.88 15.90 0.96 16.60 1.03 17.30 1.11 18.00 1.18 — —
007
1300 15.60 1.01 16.40 1.09 17.10 1.17 17.80 1.25 18.40 1.32 — —
1450 16.10 1.15 16.90 1.24 17.60 1.32 18.30 1.40 18.90 1.48 — —
1000 14.30 0.76 15.10 0.83 15.80 0.91 16.60 0.99 17.30 1.06 — —
40RM 1200 14.80 0.90 15.60 0.98 16.40 1.05 17.10 1.13 17.80 1.21 — —
40RMQ 1400 15.40 1.06 16.20 1.14 16.90 1.22 17.60 1.30 18.30 1.39 — —
40RMS
008 1600 16.10 1.24 16.80 1.33 17.50 1.41 18.20 1.50 18.90 1.58 — —
1800 16.80 1.45 17.50 1.54 18.20 1.63 18.90 1.72 19.50 1.80 — —
1200 14.70 0.89 15.50 0.97 16.30 1.05 17.00 1.12 17.70 1.20 — —
1400 15.30 1.05 16.10 1.13 16.80 1.21 17.50 1.29 18.20 1.37 — —
40RMS 1600 16.00 1.23 16.70 1.31 17.40 1.40 18.10 1.48 18.80 1.57 — —
010
1800 16.60 1.43 17.40 1.52 18.10 1.61 18.70 1.70 19.40 1.79 — —
2000 17.30 1.66 18.00 1.76 18.70 1.85 19.40 1.94 — — — —
1450 15.30 1.07 16.10 1.15 16.80 1.24 17.50 1.32 18.20 1.40 18.80 1.48
40RM 1670 16.00 1.27 16.70 1.36 17.40 1.44 18.10 1.53 18.80 1.62 19.40 1.70
40RMS 1900 16.70 1.51 17.40 1.60 18.10 1.69 18.80 1.78 19.40 1.87 — —
012 2120 17.50 1.77 18.20 1.86 18.80 1.96 19.50 2.05 — — — —
2350 18.30 2.07 19.00 2.17 19.60 2.27 — — — — — —
1450 15.60 1.10 16.30 1.18 17.10 1.27 17.80 1.35 18.40 1.43 19.10 1.52
1670 16.30 1.31 17.00 1.40 17.80 1.48 18.40 1.57 19.10 1.66 19.70 1.74
40RMQ 1900 17.10 1.56 17.80 1.65 18.50 1.74 19.20 1.83 19.80 1.92 — —
012
2120 17.90 1.83 18.60 1.93 19.30 2.02 19.90 2.11 — — — —
2350 18.80 2.15 19.50 2.25 — — — — — — — —
1750 14.90 1.42 15.80 1.58 16.60 1.75 17.40 1.93 18.20 2.10 — —
40RM 2050 15.30 1.70 16.20 1.88 17.00 2.07 17.80 2.26 18.50 2.45 — —
40RMS 2350 15.80 2.02 16.60 2.22 17.40 2.43 18.20 2.64 18.90 2.84 — —
014 2650 16.30 2.39 17.10 2.61 17.90 2.83 18.60 3.06 19.30 3.28 — —
2950 16.90 2.80 17.70 3.04 18.40 3.28 19.10 3.53 19.80 3.77 — —
2100 15.00 1.70 15.80 1.90 16.70 2.11 17.40 2.32 18.20 2.53 18.90 2.74
40RM 2450 15.50 2.03 16.30 2.25 17.10 2.47 17.80 2.70 18.60 2.93 19.30 3.16
40RMS 2800 16.00 2.42 16.80 2.66 17.60 2.90 18.30 3.14 19.00 3.38 19.70 3.63
016 3150 16.60 2.87 17.40 3.12 18.10 3.38 18.80 3.64 19.50 3.90 — —
3500 17.20 3.38 18.00 3.65 18.70 3.93 19.40 4.20 — — — —
2100 15.10 1.68 16.00 1.87 16.80 2.06 17.50 2.24 18.30 2.43 19.00 2.62
2450 15.60 2.05 16.40 2.25 17.20 2.46 18.00 2.67 18.70 2.88 19.40 3.09
40RMQ
016 2800 16.20 2.47 17.00 2.69 17.80 2.92 18.50 3.15 19.20 3.38 19.80 3.61
3150 16.80 2.95 17.60 3.19 18.30 3.44 19.00 3.69 19.70 3.94 — —
3500 17.50 3.49 18.20 3.76 19.00 4.03 19.60 4.30 — — — —
2900 16.00 2.49 16.80 2.73 17.50 2.97 18.30 3.22 19.00 3.47 19.70 3.72
40RM 3350 16.70 3.08 17.50 3.34 18.20 3.61 18.90 3.87 19.60 4.14 — —
40RMS 3800 17.50 3.77 18.20 4.06 18.90 4.35 19.60 4.64 — — — —
024 4250 18.40 4.59 19.10 4.90 19.80 5.21 — — — — — —
4700 19.30 5.54 20.00 5.87 — — — — — — — —
3500 15.10 4.33 16.10 5.12 17.10 5.98 18.00 6.92 — — — —
40RM 4100 15.30 4.67 16.20 5.39 17.10 6.18 18.00 7.02 — — — —
40RMS 4700 15.70 5.23 16.50 5.91 17.40 6.64 18.20 7.43 — — — —
028 5300 16.20 5.99 17.00 6.65 17.80 7.35 — — — — — —
5900 16.90 6.95 17.60 7.59 18.30 8.27 — — — — — —
4250 15.00 4.55 16.00 5.24 16.80 5.99 17.70 6.79 — — — —
40RM 4950 15.50 5.22 16.30 5.86 17.10 6.56 17.90 7.30 — — — —
40RMS 5650 16.10 6.16 16.90 6.77 17.60 7.43 18.30 8.13 — — — —
034 6350 16.90 7.34 17.50 7.94 18.20 8.58 — — — — — —
7050 17.70 8.79 18.30 9.39 — — — — — — — —
See Legend and Notes on page 39.

38
More user manuals on ManualsBase.com
Legend and Notes for Tables 10C and 10D Replacing Filters — Filters can be removed and in-
stalled from either side of the unit. Install new filters in units
LEGEND that have one fan as follows:
ESP — External Static Pressure
1. Remove the side access panel (retain screws).
NOTES:
1. Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and 2. Remove the filter retainer clip.
034; 20 r/s for all other sizes. 3. Remove old filters by tilting them and lifting them out of
2. Fan performance is based on deductions for wet coil, clean 51-mm the filter track. See Fig. 12 and 22.
filters, and unit casing. See right for factory-supplied filter pres-
sure drop. 4. Reverse the procedure to install new filters.
3. Refer to fan motor and drive tables for additional data.
To install new filters in larger units that have 2 fans, fol-
Factory-Supplied Filter Pressure Drop — SI low the preceding steps, but use the factory-supplied
filter hook to slide filters within reach for removal. The
UNIT AIRFLOW PRESSURE DROP filter hook is shipped inside the unit in the baserail.
(L/s) (Pa)
850 13
40RM 1150 20
007 1450 28 Do not operate unit without air filters.
40RM
40RMQ 1000 17
40RMS 1400 27
008 1800 38
1200 21
40RMS 1600 32
010 2000 45
40RM
40RMQ 1450 28
40RMS 1900 42
012 2350 56
40RM 1750 15
40RMS 2350 24
014 2950 33
40RM
40RMQ 2100 20
40RMS 2800 30
016 3500 42
40RM 2900 32
40RMS 3800 47
024 4700 64
40RM 3500 36
40RMS 4700 55
028 5900 76
40RM 4250 47
40RMS 5650 71
034 7050 98

Fig. 22 — Filter Removal/Replacement

39
More user manuals on ManualsBase.com
More user manuals on ManualsBase.com
More user manuals on ManualsBase.com
Copyright 1995 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI Pg 42 596 11-95 Replaces: 40RM-1SI
Tab 3c 2e
More user manuals on ManualsBase.com
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
START-UP CHECKLIST
(SPLIT SYSTEMS WITH 40RM/RMQ/RMS UNITS)

A. Preliminary Information
OUTDOOR: MODEL NO. SERIAL NO.

INDOOR: MODEL NO. SERIAL NO.

ADDITIONAL ACCESSORIES

B. Pre-Start-Up
CUT ALONG DOTTED LINE

OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? (Y/N)
IF SO, WHERE:

WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N)


CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N)
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N)
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N)
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? (Y/N)

CONTROLS
ARE THERMOSTAT(S) AND INDOOR FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED? (Y/N)
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)
HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N)

INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N)
ARE PROPER AIR FILTERS IN PLACE? (Y/N)
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)
DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)
CUT ALONG DOTTED LINE

PIPING
40RM,RMQ
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT COILS AS REQUIRED? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,
TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS.
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N)
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS? (Y/N)

40RMS
HAS AIR BEEN BLED FROM SYSTEM? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CHILLERS, VALVES, AND INDOOR COILS? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI CL-1 11-95 Replaces: 40RM-1SI
Tab 3c 2e
More user manuals on ManualsBase.com
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB V AC V BC V
(AB + AC + BC)/3 = AVERAGE VOLTAGE = V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = %
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.

C. Start-Up
CHECK EVAPORATOR FAN SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

COMP A1 COMP B1
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING OUTDOOR UNIT AIR TEMP
LEAVING OUTDOOR UNIT AIR TEMP
INDOOR UNIT ENTERING AIR DB TEMP
INDOOR UNIT ENTERING AIR WB TEMP
INDOOR UNIT LEAVING AIR DB TEMP
INDOOR UNIT LEAVING AIR WB TEMP
OUTDOOR UNIT ENTERING WATER TEMP
(40RMS ONLY)
OUTDOOR UNIT LEAVING WATER TEMP
(40RMS ONLY)
INDOOR UNIT ENTERING WATER TEMP
(40RMS ONLY)
INDOOR UNIT LEAVING WATER TEMP
(40RMS ONLY)

COMPRESSOR AMPS (L1/L2/L3) / / / /

CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING
OIL LEVEL AT 1⁄8 TO 1⁄3 FULL? (Y/N)

NOTES:

Copyright 1995 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI CL-2 596 11-95 Replaces: 40RM-1SI
Tab 3c 2e