Packaged Air-Handling Units
50/60 Hz
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI Pg 1 11-95 Replaces: 40RM-1SI
Tab 3c 2e
More user manuals on ManualsBase.com
Table 1A — 40RM Physical Data, English
UNIT 40RM 007 008 012 014 016 024 028 034
NOMINAL CAPACITY (Tons) 6 71⁄2 10 121⁄2 15 20 25 30
OPERATING WEIGHT (lb)
Base Unit with TXV 381 385 405 670 685 690 1020 1030
Plenum 97 97 97 140 140 140 180 180
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18
Nominal Airflow (cfm) 2400 3000 4000 5000 6000 8,000 10,000 12,000
Airflow Range (cfm) 1800- 2250- 3000- 3750- 4500- 6,000- 7,500- 9,000-
3000 3750 5000 6250 7500 10,000 12,500 15,000
Nominal Motor Hp (Standard Motor)
208/230-1-60 1.3 2.4 — — — — — —
208/230-3-60 and 460-3-60 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0
575-3-60 1.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0
230-3-50, 400-3-50 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Motor Speed (rpm)
208/230-1-60 1725 1725 — — — — — —
208/230-3-60 and 460-3-60 1725 1725 1725 1725 1725 1745 1745 1745
575-3-60 1725 1725 1725 1725 1725 1745 1755 1755
230-3-50, 400-3-50 1425 1425 1425 1425 1425 1425 1425 1425
REFRIGERANT R-22
Operating charge (lb) 3.0 3.0 1.5/1.5 2.0/2.0 2.5/2.5 3.5/3.5 4.5/4.5 5.0/5.0
(approx per circuit)*
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 435
Face Area (sq ft) 6.67 8.33 10.0 13.25 17.67 19.88 24.86 29.83
No. of Splits 1 1 2 2 2 2 2 2
No. of Circuits per Split 12 15 9 9 12 13 15 18
Split Type...Percentage — — Face...50/50
Rows...Fins/in. 3...15 3...15 3...17 3...15 3...15 3...17 3...15 3...15
STEAM COIL
Max Working Pressure (psig at 400 F) 175
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure (psig) 150
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...12.5 2...12.5
Water Volume
(gal) 8.3 13.9 14.3
(ft3) 1.1 1.85 1.90
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...11⁄8 1...11⁄8 2...11⁄8 2...11⁄8 2...11⁄8 2...11⁄8 2...13⁄8 2...13⁄8
DX Coil — Liquid Refrigerant (ODF) 1...5⁄8 2...5⁄8
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 20 x 2 4...20 x 24 x 2
4...16 x 24 x 2 4...20 x 25 x 2
Access Location Either Side
LEGEND
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
2
More user manuals on ManualsBase.com
Table 1B — 40RMQ Physical Data, English
UNIT 40RMQ 008 012 016
NOMINAL CAPACITY (Tons) 71⁄2 10 15
OPERATING WEIGHT (lb)
Base Unit with TXV 385 427 713
Plenum 97 97 140
FANS
Qty...Diam. (in.) 1...15 1...15 2...15
Nominal Airflow (cfm) 3000 4000 6000
Airflow Range (cfm) 2250-3750 3000-5000 4500-7500
Nominal Motor Hp (Standard Motor)
208/230-1-60 2.4 — —
208/230-3-60 and 460-3-60 2.4 2.4 3.7
575-3-60 2.0 2.0 3.0
230-3-50, 400-3-50 2.4 2.9 2.9
Motor Speed (rpm)
208/230-1-60 1725 — —
208/230-3-60 and 460-3-60 1725 1725 1725
575-3-60 1725 1725 1725
230-3-50, 400-3-50 1425 1425 1425
REFRIGERANT R-22
Operating charge (lb) 3.0 2.0/2.0 3.0/3.0
(approx per circuit)*
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 435
Face Area (sq ft) 8.33 10.0 17.67
No. of Splits 1 2 2
No. of Circuits per Split 15 9 16
Split Type...Percentage — Face...50/50
Rows...Fins/in. 3...15 4...15 4...15
STEAM COIL
Max Working Pressure (psig at 400 F) 175
Total Face Area (sq ft) 6.67 6.67 13.33
Rows...Fins/in. 1...9 1...9 1...10
HOT WATER COIL
Max Working Pressure (psig) 150
Total Face Area (sq ft) 6.67 6.67 13.33
Rows...Fins/in. 2...8.5 2...8.5 2...8.5
Water Volume
(gal) 8.3 13.9
(ft3) 1.1 1.85
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...11⁄8 2...11⁄8 2...11⁄8
DX Coil — Liquid Refrigerant (ODF) 1...5⁄8 2...5⁄8 2...5⁄8
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 20 x 2
4...16 x 24 x 2
Access Location Either Side
LEGEND
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
3
More user manuals on ManualsBase.com
Table 1C — 40RMS Physical Data, English
UNIT 40RMS 008 010 012 014 016 024 028 034
NOMINAL CAPACITY (Tons) 71⁄2 8 1 ⁄2 10 121⁄2 15 20 25 30
OPERATING WEIGHT (lb)
Base Unit 390 391 391 661 677 683 1035 1042
Plenum 97 97 97 140 140 140 180 180
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18
Nominal Airflow (cfm) 3000 3400 4000 5000 6000 8000 10,000 12,000
Airflow Range (cfm) 2250-3750 2250-4250 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000
Nominal Motor Hp
(Standard Motor)
208/230-1-60 2.4 2.4 — — — — — —
208/230-3-60 and 460-3-60 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0
575-3-60 2.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0
230-3-50 and 400-3-50 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Motor Speed (rpm)
208/230-1-60 1725 1725 — — — — — —
208/230-3-60 and 460-3-60 1725 1725 1725 1725 1725 1745 1745 1745
575-3-60 1725 1725 1725 1725 1725 1745 1755 1755
230-3-50 and 400-3-50 1425 1425 1425 1425 1425 1425 1425 1425
CHILLED WATER COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure 435
(psig)
Face Area (sq ft) — Upper 8.3 9.0 4.9 8.3 8.3 11.0 12.4 15.5
Face Area (sq ft) — Lower — — 4.9 5.5 8.3 8.3 12.4 12.4
Rows...Fins/in. 3...15
STEAM COIL
Max Working Pressure 175
(psig at 400 F)
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure 150
(in. wg)
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...12.5 2...12.5
Water Volume
(gal) 8.3 13.9 14.3
(ft3) 1.1 1.85 1.90
PIPING CONNECTIONS,
Quantity...Size (in.)
Chilled Water — In 1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
Chilled Water — Out 1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 20 x 2 4...20 x 24 x 2
4...16 x 24 x 2 4...20 x 25 x 2
Access Location Either Side
4
More user manuals on ManualsBase.com
Table 1D — 40RM Physical Data, SI
UNIT 40RM 007 008 012 014 016 024 028 034
NOMINAL CAPACITY (kW) 21 26 35 43 52 70 87 105
OPERATING WEIGHT (kg)
Base Unit with TXV 173 175 184 304 311 313 463 467
Plenum 44 44 44 63 63 63 82 82
FANS
Qty...Diam. (mm) 1...381 1...381 1...381 2...381 2...381 2...381 2...457 2...457
Nominal Airflow (L/s) 1133 1604 1888 2360 2831 3775 4719 5663
Airflow Range (L/s) 850-1416 1203-2006 1416-2360 1770-2949 2124-3539 2831-4719 3539-5899 4247-7079
Nominal Motor kW (Standard Motor)
208/230-1-60 0.97 1.79 — — — — — —
208/230-3-60 and 460-3-60 1.79 1.79 1.79 2.16 2.76 3.73 5.60 7.46
575-3-60 0.75 1.49 1.49 2.24 2.24 3.73 5.60 7.46
230-3-50, 400-3-50 1.79 1.79 2.16 2.16 2.16 3.73 5.60 7.46
Motor Speed (r/s)
208/230-1-60 28.8 28.8 — — — — — —
208/230-3-60 and 460-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.1 29.1
575-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.3 29.3
230-3-50, 400-3-50 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8
REFRIGERANT R-22
Operating charge (kg)
(approx per circuit)* 1.36 1.36 0.68/0.68 0.90/0.90 1.13/1.13 1.59/1.59 2.04/2.04 2.27/2.27
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag) 2999
Face Area (sq m) 0.62 0.77 0.93 0.93 1.64 1.85 2.30 2.77
No. of Splits 1 1 2 2 2 2 2 2
No. of Circuits per Split 12 15 9 9 12 13 15 18
Split Type...Percentage — — Face...50/50
Rows...Fins/m 3...591 3...591 3...670 3...591 3...591 3...670 3...591 3...591
STEAM COIL
Max Working Pressure (kPag at 204.4 C) 1207
Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39
Rows...Fins/m 1...355 1...355 1...355 1...394 1...394 1...394 1...394 1...394
HOT WATER COIL
Max Working Pressure (kPag) 1034
Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39
Rows...Fins/m 2...335 2...335 2...335 2...335 2...335 2...335 2...493 2...493
Water Volume
(L) 31.4 52.6 54.1
(m3) 0.031 0.052 0.054
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...11⁄8 1...11⁄8 2...11⁄8 2...11⁄8 2...11⁄8 2...11⁄8 2...13⁄8 2...13⁄8
DX Coil — Liquid Refrigerant (ODF) 1...5⁄8 2...5⁄8
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size 4...406 x 610 x 51 4...406 x 508 x 51 4...508 x 610 x 51
4...406 x 610 x 51 4...508 x 635 x 51
Access Location Either Side
LEGEND
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
5
More user manuals on ManualsBase.com
Table 1E — 40RMQ Physical Data, SI
UNIT 40RMQ 008 012 016
NOMINAL CAPACITY (kW) 26 35 52
OPERATING WEIGHT (kg)
Base Unit with TXV 175 194 323
Plenum 44 44 63
FANS
Qty...Diam. (mm) 1...381 1...381 2...381
Nominal Airflow (L/s) 1604 1888 2831
Airflow Range (L/s) 1203-2006 1416-2360 2124-3539
Nominal Motor kW (Standard Motor)
208/230-1-60 1.79 — —
208/230-3-60 and 460-3-60 1.79 1.79 2.76
575-3-60 1.49 1.49 2.24
230-3-50, 400-3-50 1.79 2.16 2.16
Motor Speed (r/s)
208/230-1-60 28.8 — —
208/230-3-60 and 460-3-60 28.8 28.8 28.8
575-3-60 28.8 28.8 28.8
230-3-50, 400-3-50 23.8 23.8 23.8
REFRIGERANT R-22
Operating charge (kg)
(approx per circuit)* 1.36 0.91/0.91 1.36/1.36
DIRECT-EXPANSION COIL
Max Working Pressure (kPag) 2999
Face Area (sq m) 0.77 0.93 1.64
No. of Splits 1 2 2
No. of Circuits per Split 15 9 16
Split Type...Percentage — Face...50/50
Rows...Fins/m 3...591 4...591 4...591
STEAM COIL
Max Working Pressure (kPag at 204.4 C) 1207
Total Face Area (sq m) 0.62 0.62 1.24
Rows...Fins/m 1...355 1...355 1...394
HOT WATER COIL
Max Working Pressure (kPag) 1034
Total Face Area (sq m) 0.62 0.62 1.24
Rows...Fins/m 2...335 2...335 2...335
Water Volume
(L) 31.4 52.6
(m3) 0.031 0.052
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...11⁄8 2...11⁄8 2...11⁄8
DX Coil — Liquid Refrigerant (ODF) 1...5⁄8 2...5⁄8 2...5⁄8
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (Male PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size 4...406 x 610 x 51 4...406 x 508 x 51
4...406 x 610 x 51
Access Location Either Side
LEGEND
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
6
More user manuals on ManualsBase.com
Table 1F — 40RMS Physical Data, SI
UNIT 40RMS 008 010 012 014 016 024 028 034
NOMINAL CAPACITY (kW) 26 29 35 43 52 70 87 105
OPERATING WEIGHT (kg)
Base Unit 177 177 177 300 307 310 469 473
Plenum 44 44 44 63 63 63 82 82
FANS
Qty...Diam. (mm) 1...381 1...381 1...381 2...381 2...381 2...381 2...457 2...457
Nominal Airflow (L/s) 1416 1605 1888 2360 2831 3775 4719 5663
1062- 1204- 1416- 1770- 2124- 2831- 3539- 4247-
Airflow Range (L/s) 1770 2006 2360 2949 3539 4719 5899 7079
Nominal Motor kW
(Standard Motor)
208/230-1-60 1.79 1.79 — — — — — —
208/230-3-60, 460-3-60 1.79 1.79 1.79 1.79 2.76 3.73 5.60 7.46
575-3-60 1.49 1.49 1.49 1.49 2.24 3.73 5.60 7.46
230-3-50, 400-3-50 1.79 1.79 2.16 2.16 2.16 3.73 5.60 7.46
Motor Speed (r/s)
208/230-1-60 28.8 28.8 — — — — — —
208/230-3-60, 460-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.1 29.1
575-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.3 29.3
230-3-50, 400-3-50 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8
CHILLED WATER COIL
Max Working Pressure 2999
(kPag)
Face Area (sq m) — Upper 0.77 0.84 0.91 0.77 0.77 1.02 1.15 1.44
Face Area (sq m) — Lower — — — 0.51 0.77 0.77 1.15 1.15
Rows...Fins/m 3...591 3...591 3...591 3...591 3...591 3...591 3...591 3...591
STEAM COIL
Max Working Pressure 1207
(kPag at 204.4 C)
Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39
Rows...Fins/m 1...355 1...355 1...355 1...355 1...394 1...394 1...394 1...394
HOT WATER COIL
Max Working Pressure 1034
(kPag)
Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39
Rows...Fins/m 2...335 2...335 2...335 2...335 2...335 2...335 2...493 2...493
Water Volume
(L) 31.4 52.6 54.1
(m3) 0.031 0.052 0.054
PIPING CONNECTIONS,
Quantity...Size (in.)
Chilled Water — In 1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
Chilled Water — Out 1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
Steam Coil, In (MPT) 1...21⁄2 1...21⁄2
Steam Coil, Out (MPT) 1...11⁄2 1...11⁄2
Hot Water Coil, In (MPT) 1...11⁄2 1...11⁄2 1...2
Hot Water Coil, Out (MPT) 1...11⁄2 1...11⁄2 1...2
Condensate (PVC) 1...11⁄4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
4...406 x 508 x 51 4...508 x 610 x 51
Quantity...Size (mm) 4...406 x 610 x 51 4...406 x 610 x 51 4...508 x 635 x 51
Access Location Either Side
7
More user manuals on ManualsBase.com
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm )
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RMS units may require alternate or ad-
ditional field-fabricated piping access holes.
8
More user manuals on ManualsBase.com
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RMQ016 and 40RMS units may re-
quire alternate or additional field-fabricated
piping access holes.
9
More user manuals on ManualsBase.com
UNIT UNIT WEIGHT
lb (kg)
40RM028 1020 (463)
40RM034 1030 (467)
40RMS028 1035 (469)
40RMS034 1042 (473)
10
More user manuals on ManualsBase.com
*YC and WD option codes for all 034 size units and 008, 010 units with 208/230-1-60
power designate standard motor and high-static drive.
NOTE: See the following table for the sizes available for each unit.
UNIT 007 008 010 012 014 016 024 028 034
40RM X X X X X X X X
40RMQ X X X
40RMS X X X X X X X X
11
More user manuals on ManualsBase.com
Unit Isolation — Where extremely quiet operation is Refrigerant Piping — See Tables 1A, 1B, 1D, 1E for
essential, install isolators between floor and base of unit, or refrigerant pipe connection sizes. For ease in brazing, it is
between ceiling and top section of unit. recommended that all internal solder joints be made before
Be sure that unit is level and adequately supported. Use unit is placed in final position.
channels at front and sides of unit for reference points when The 40RM and 40RMQ direct-expansion units have
leveling. internal factory-installed thermostatic expansion valves (TXVs),
distributors, and nozzles for use with R-22. See Table 2 for
Refrigerant and Chilled Water Piping Access — part numbers. Knockouts are provided in the unit corner posts
The 40RM Series units come with standard knockouts for for 40RM and 40RMQ008 and 012 refrigerant piping. The
refrigerant and chilled water piping. These knockouts are lo- 40RMQ016 unit requires additional field-fabricated piping
cated on both sides of the unit for installation flexibility. The access holes. See Fig. 4, which also lists recommended knock-
standard knockouts provide sufficient access to the unit’s coils outs and access holes to use for each 40RM and 40RMQ
for all 40RM and some 40RMQ units, however, for 40RMQ016 unit size. Recommended fittings are listed in Table 3.
and 40RMS units, additional holes must be field-fabricated The sensor bulb capillary tubes must be routed from the
to accommodate the piping. See Fig. 4 for the positions and TXVs inside the unit through one of the piping access holes.
dimensions of the additional access holes required for these Clamp the TXV sensor bulb on a vertical portion of the suc-
units, including hole diameters and drilling dimensions. Rec- tion line, outside the unit. See Fig. 5.
ommended access hole use is also listed for all units. Note
that Fig. 4 shows the access holes on the control-box side of
the unit; this is the side of the unit with the coil headers, so
it is used most often for piping access.
12
More user manuals on ManualsBase.com
IMPORTANT: Never attach the sensor to the suction
manifold. Do NOT mount the sensor on a trapped por-
tion of the suction line.
LEGEND
TXV — Thermostatic Expansion Valve
NOTE: Component location arrangement shown for field installation
of sight glasses, solenoid valves, filter driers, and TXV sensing bulbs.
The TXVs and equalizer lines are factory installed.
Fig. 5 — Face-Split Coil Suction and
Liquid Line Piping (Typical)
LEGEND
TXV — Thermostatic Expansion Valve
NOTE: The 8 o’clock position is shown above.
Fig. 7 — TXV Sensing Bulb Location
13
More user manuals on ManualsBase.com
Table 2 — Factory-Installed Nozzle and Distributor Data
The LLSV must be installed at the outdoor unit with the LEGEND
flow arrow pointed toward the outdoor unit (in-flow TXV — Thermostatic Expansion Valve
direction for the heating mode.)
RECOMMENDED FILTER DRIERS*
(38AQS012,016/40RMQ SYSTEMS)
FILTER DRIER REQUIREMENTS FOR 38AQS012/
40RMQ012 AND 38AQS016/40RMQ016 HEAT PUMP LIQUID
SYSTEMS — The 38AQS012 and 016 units do not in- UNIT LINE PART NO. QUANTITY FIGURE
clude filter driers. Filter driers must be field-supplied 38AQS SIZE REQUIRED REFERENCE
(in.)
and installed in 38AQS012/40RMQ012 and 38AQS016/ 1⁄2
40RMQ016 systems. The filter driers used with these sys- P504-8084S 2 A
012 5⁄8
tems must be bi-flow types suited for use in heat pump P504-8165S 1 B
1⁄2 P504-8084S 2 A
applications. The Replacement Component Division part num- 016
bers listed in Fig. 8 are recommended and available for field 5⁄8 P504-8085S 2 A
installation. *Available from Carrier Replacement Components Division.
Fig. 8 — Filter Drier Requirements —
38AQS012/40RMQ012 and 38AQS016/40RMQ016
Heat Pump Systems
14
More user manuals on ManualsBase.com
Table 3 — Fitting Requirements
15
More user manuals on ManualsBase.com
Table 3 — Fitting Requirements (cont)
11⁄8 Nipple, 5 L
7 Suction Upper 11⁄8 45° Elbow
11⁄8 Nipple, 83⁄4 L
11⁄8 Long Radius Elbow
11⁄8 Street Elbow
1 Suction Lower 11⁄8 Nipple, 75⁄8 L
11⁄8 Long Radius Elbow
5⁄8 Street Elbow
16
More user manuals on ManualsBase.com
Table 3 — Fitting Requirements (cont)
Chilled Water Piping — See Tables 1C and 1F for To size, design, and install chilled water piping, consult
chilled water connection sizes. For ease in brazing, it is rec- the Carrier System Design manual. See Fig. 9 for an ex-
ommended that all internal solder joints be made before unit ample of a typical installation. Recommended fittings are listed
is placed in final position. in Table 3.
Knockouts are provided in the unit corner posts for 40RM To access 40RMS coil vents and drains, remove the unit
and 40RMQ refrigerant piping; additional field-fabricated ac- side panel over the coil header. Vent and drain plugs are on
cess holes are required for 40RMS chilled water piping. See the top and bottom of header, respectively. See the Service
Fig. 4, which lists recommended knockouts and access holes section for information on preventing coil freeze-up during
to use for each 40RMS unit size. winter.
17
More user manuals on ManualsBase.com
Condensate Drain — Install a trapped condensate drain outlet at both ends of the unit, push drain pan down in
line to unit connection as shown in Fig. 10. The unit drain the slots near the drain connection, and up in the slots
connection is a PVC stub. See Fig. 11. Some areas may re- on the opposite end. Retighten screws. The pan should
quire an adapter to connect to either galvanized steel or have a pitch of at least 1⁄4-in. over its length toward the drain
copper pipe. For these applications, install a field-supplied connection.
threaded PVC adapter.
Fan Motors and Drives — Motor and drive pack-
NOTE: A trap must be installed in the condensate drain line ages are factory installed in all units. The standard motor
to ensure that the static pressure of fans is balanced with the and drive packages consist of the following items:
water column in the drain line and that condensate can drain
completely from pan. Without a trap, air can be drawn up 1 — fan motor
drain line until water level in condensate pan becomes equal 1 — adjustable motor pulley
to static pressure created by fans, preventing complete drain- 1 — fan pulley
age. Conditions will worsen as filters become dirty.
1 —fan belt (40RM007-016, 40RMQ008-016, 40RMS
Install clean-out plugs in trap. Pitch drain line downward 008-016 units)
to an open floor drain or sump. Provide service clearance
around drain line to permit removal of unit panels. Observe 2 —matched fan belts (40RM024-034, 40RMS024-034
all local sanitary codes. units)
As shipped, the unit’s condensate drain pan is NOT sloped For instructions on changing fan rotation, changing drive
towards the drain connection. The pan slope must be changed speeds and adjusting drives, see Pulley and Drive Adjust-
to pitch towards the side of the unit with the drain con- ment in the Service section.
nection. See Fig. 11. Loosen the 2 screws next to the drain
18
More user manuals on ManualsBase.com
Power Supply and Wiring — Check the unit data 230-v, 3-ph, 60 Hz operation. Rewire the motor according to
plate to ensure that available power supply matches electri- the diagram plate on the motor. After reconfiguring the mo-
cal characteristics of the unit. Provide a disconnect switch of tor, place the sticker specifying 230-v operation (supplied in
size required to provide adequate fan motor starting current. installation packet) over the 460-v sticker on the units cor-
See Tables 4 - 6 for unit electrical data. ner post.
Install disconnect switch and power wiring in accordance Fan motors are factory installed on all units. Indoor-fan
with all applicable local codes. See Fig. 12-14 and the unit contactors are located in the fan contactor box behind the
label diagram. For units with motor sizes less than 5 Hp side access panel (see Fig. 12 and 13). Wire the thermostat
(3.7 kW), connect power wiring to unit with no. 10 ring ter- to the 24-v control circuit terminal block located in the side
minal. For units with motor sizes of 5 Hp (3.7 kW) or more, of the fan contactor control box, according to Fig. 14 or the
connect power wiring with 1⁄4-in. ring terminal. unit label diagram. If the air handler is part of a split system,
complete the wiring from the condensing unit to the ther-
The 40RM, 40RMQ and 40RMS size 007-016 units (ex-
cept 40RM016 with YC or WD option) that have motors wired mostat shown in Fig. 14.
for 460-v, 3-ph, 60 Hz operation can be field-converted to
CONDENSATE
RJ AW
DRAIN FAN DRIVE
105° C 600V
CONNECTION PULLEY
(HORIZONTAL)
23 22
COIL
21
REFRIGERANT/
CHILLED WATER
FILTER PIPING ACCESS 24V
RETAINER TERMINAL
CLIP BLOCK
CONDENSATE
DRAIN POWER
CONNECTION WIRING
(VERTICAL) KNOCKOUT
19
More user manuals on ManualsBase.com
Table 4 — Electrical Data, Standard Motors
FAN MOTOR POWER SUPPLY
UNIT V*-PH-HZ VOLTAGE
LIMITS Minimum
Hp FLA Circuit Amps MOCP
208/230-1-60 187-253 1.3 7.6 9.5 15
208/230-3-60 187-253 2.4 5.8 7.3 15
40RM 460-3-60 414-528 2.4 2.6 3.3 15
007 575-3-60 518-632 1.0 1.35 1.7 15
230-3-50 207-253 2.4 5.8 7.3 15
400-3-50 360-440 2.4 2.6 3.3 15
208/230-1-60 187-253 2.4 11.0 13.8 20
208/230-3-60 187-253 2.4 5.8 7.3 15
40RM
40RMQ 460-3-60 414-528 2.4 2.6 3.3 15
40RMS 575-3-60 518-632 2.0 2.4 3.0 15
008
230-3-50 207-253 2.4 5.8 7.3 15
400-3-50 360-440 2.4 2.6 3.3 15
208/230-1-60 187-253 2.4 11.0 13.8 20
208/230-3-60 187-253 2.4 5.8 7.3 15
40RMS 460-3-60 414-528 2.4 2.6 3.3 15
010 575-3-60 518-632 2.0 2.4 3.0 15
230-3-50 207-253 2.4 5.8 7.3 15
400-3-50 360-440 2.4 2.6 3.3 15
208/230-3-60 187-253 2.4 5.8 7.3 15
40RM 460-3-60 414-528 2.4 2.6 3.3 15
40RMQ
40RMS 575-3-60 518-632 2.0 2.4 3.0 15
012 230-3-50 207-253 2.9 7.5 9.4 15
400-3-50 360-440 2.9 3.4 4.3 15
208/230-3-60 187-253 2.9 7.5 9.4 15
40RM 460-3-60 414-528 2.9 3.4 4.3 15
40RMS 575-3-60 518-632 3.0 3.8 4.8 15
014 230-3-50 207-253 2.9 7.5 9.4 15
400-3-50 360-440 2.9 3.4 4.3 15
208/230-3-60 187-253 3.7 10.6 13.3 20
40RM 460-3-60 414-528 3.7 4.8 6.0 15
40RMQ 575-3-60 518-632 3.0 3.8 4.8 15
40RMS
016 230-3-50 207-253 2.9 7.5 9.4 15
400-3-50 360-440 2.9 3.4 4.3 15
208/230-3-60 187-253 5.0 15.2/14.4 19.0/18.0 30/30
40RM 460-3-60 414-528 5.0 7.2 9.0 15
40RMS 575-3-60 518-632 5.0 5.6 7.0 15
024 230-3-50 207-253 5.0 14.4 18.0 30
400-3-50 360-440 5.0 7.2 9.0 15
208/230-3-60 187-253 7.5 22.0/21.0 27.5/26.3 45/45
40RM 460-3-60 414-528 7.5 10.5 13.1 20
40RMS 575-3-60 518-632 7.5 7.6 9.5 15
028 230-3-50 207-253 7.5 21.0 26.3 45
400-3-50 360-440 7.5 10.5 13.1 20
208/230-3-60 187-253 10.0 26.4/25.0 33.0/31.3 55/55
40RM 460-3-60 414-528 10.0 12.5 15.6 25
40RMS 575-3-60 518-632 10.0 9.6 12.0 20
034 230-3-50 207-253 10.0 25.0 31.3 55
440-3-50 360-440 10.0 12.5 15.6 25
See Legend and Notes on page 21.
20
More user manuals on ManualsBase.com
Table 5 — Electrical Data, Alternate Motors
FAN MOTOR POWER SUPPLY
UNIT V*-PH-HZ VOLTAGE
LIMITS Minimum
Hp FLA Circuit Amps MOCP
208/230-1-60 187-253 2.4 11.0 13.8 20
40RM 208/230-3-60 187-253 2.9 7.5 9.4 15
007 460-3-60 414-528 2.9 3.4 4.3 15
575-3-60 518-632 2.0 2.4 3.0 15
208/230-3-60 187-253 2.9 7.5 9.4 15
40RM 460-3-60 414-528 2.9 3.4 4.3 15
40RMQ 575-3-60 518-632 3.0 3.8 4.8 15
40RMS
008 230-3-50 207-253 2.9 7.5 9.4 15
400-3-50 360-440 2.9 3.4 4.3 15
208/230-3-60 187-253 2.9 7.5 9.4 15
460-3-60 414-528 2.9 3.4 4.3 15
40RMS 575-3-60 518-632 3.0 3.8 4.8 15
010
230-3-50 207-253 2.9 7.5 9.4 15
400-3-50 360-440 2.9 3.4 4.3 15
208/230-3-60 187-253 3.7 10.6 13.3 20
40RM 460-3-60 414-528 3.7 4.8 6.0 15
40RMQ 575-3-60 518-632 3.0 3.8 4.8 15
40RMS
012 230-3-50 207-253 5.0 14.4 18.0 30
400-3-50 360-440 5.0 7.2 9.0 15
208/230-3-60 187-253 3.7 10.6 13.3 20
40RM 460-3-60 414-528 3.7 4.8 6.0 15
40RMS 575-3-60 518-632 5.0 5.6 7.0 15
014 230-3-50 207-253 5.0 14.4 18.0 30
400-3-50 360-440 5.0 7.2 9.0 15
208/230-3-60 187-253 5.0 15.2/14.4 19.9/18.0 30/30
40RM 460-3-60 414-528 5.0 7.2 9.0 15
40RMQ 575-3-60 518-632 5.0 5.6 7.0 15
40RMS
016 230-3-50 207-253 5.0 14.4 18.0 30
400-3-50 360-440 5.0 7.2 9.0 15
208/230-3-60 187-253 7.5 22.0/21.0 27.5/26.3 45/45
40RM 460-3-60 414-528 7.5 10.5 13.1 20
40RMS 575-3-60 518-632 7.5 7.6 9.5 15
024 230-3-50 207-253 7.5 21.0 26.3 45
400-3-50 360-440 7.5 10.5 13.1 20
208/230-3-60 187-253 10.0 26.4/25.0 33.0/31.3 55/55
40RM 460-3-60 414-528 10.0 12.5 15.6 25
40RMS 575-3-60 518-632 10.0 9.6 12.0 20
028 230-3-50 207-253 10.0 25.0 31.3 55
400-3-50 360-440 10.0 12.5 15.6 25
LEGEND EXAMPLE: Supply voltage is 400-3-50.
FLA — Full Load Amps AB = 393 v
MOCP — Maximum Overcurrent Protection BC = 403 v
*Motors are designed for satisfactory operation within 10% of nomi- AC = 396 v
nal voltages shown. Voltages should not exceed the limits shown in 393 + 403 + 396
Average Voltage =
the Voltage Limits column. 3
NOTES: 1192
=
1. Minimum Circuit Amp and MOCP values are calculated in 3
accordance with NEC (National Electrical Code) (U.S.A. stand- = 397
ard), Article 440. Determine maximum deviation from average voltage.
2. Motor FLA values are established in accordance with UL (Under- (AB) 397 − 393 = 4 v
writers’ Laboratories) Standard 1995 (U.S.A. standard). (BC) 403 − 397 = 6 v
3. Unbalanced 3-Phase Supply Voltage (AC) 397 − 396 = 1 v
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine Maximum deviation is 6 v.
the percentage of voltage imbalance. Determine percent voltage imbalance.
% Voltage Imbalance 6
% Voltage Imbalance = 100 x
397
max voltage deviation from average voltage = 1.5%
= 100 x
average voltage This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
21
More user manuals on ManualsBase.com
LEGEND
CB — Circuit Breaker
HC — Heating Contactor
HTR — Electric Heater
IFC — Indoor-Fan Contactor
IFM — Indoor-Fan Motor
NEC — National Electrical Code
TB — Terminal Block
T’STAT — Thermostat
Factory Wiring
Field Control Wiring
NOTE: Use copper conductors only.
23
More user manuals on ManualsBase.com
Centering Fan Wheel — If fan and fan shaft assem- Individual Fan Wheel Adjustment — Loosen the
bly are not properly centered, blades may scrape against scroll 2 locking bolts holding fan wheel hub to shaft. See Fig. 17.
or may create an objectionable whistling noise. It may be Position fan wheel in center of the fan housing and tighten
necessary to adjust individual fan wheels or move entire fan locking bolts. Clearance between wheel and housing should
shaft. See the following two sections. be the same on both sides.
Fan Shaft Position Adjustment — Loosen set- Fan Belts — Motor mounting plate and motor support
screw or locking collar of each fan shaft bearing. Slide shaft angles are slotted to permit both vertical and horizontal
into correct position and replace locking collar (Fig. 18). To adjustment. Adjust belt(s) for correct deflection by loosen-
replace locking collar, push collar up against inner face of ing motor plate mounting bolts, moving motor/plate assem-
bearing. Turn collar in direction of fan rotation until tight, bly forward or back, and retightening bolts. Press down on
and tighten setscrew. Tightening locking collar in direction belt with one finger midway between fan and motor pulleys
of fan rotation results in further tightening of collar should to check deflection. For units with motor sizes up to and
setscrew work itself loose. including 3.7 Hp (2.76 kW), correct deflection is 3⁄16-in.
(4.8 mm) For larger motor sizes, correct deflection is 1⁄8-in.
(3.2 mm). See Fig. 19.
NOTE: The 028 and 034 size units with 60 Hz motors are
shipped with an extra set of matching belts. Use the pre-
installed belts or extra belts depending on the adjustable
pulley setting.
If complete belt replacement is required during serv-
icing, loosen the motor plate mounting bolts (Fig. 19), move
motor/plate assembly towards fan pulley, and pull belt(s) off
pulleys. Reverse the procedure with new bolts and readjust
deflection.
Fan Rotation — Correct fan rotation with respect to
fan outlet is shown in Fig. 20.
To reverse the direction of rotation of a 3-phase fan mo-
tor, reverse any 2 of the power leads. Refer to the connection
diagram on the inside of motor terminal box cover for proper
reversing procedure of single-phase motor.
Fig. 18 — Fan Shaft Bearing
24
More user manuals on ManualsBase.com
Fig. 20 — Fan Rotation
25
More user manuals on ManualsBase.com
Table 8A — Fan Motor Data, Standard Motor — English
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
208/230-1-60
Speed (rpm) 1725 1725 1725 — — — — — —
Hp 1.3 2.4 2.4 — — — — — —
Frame (NEMA) 56Y 56Y 56Y — — — — — —
Shaft Dia (in.) 5⁄8 5 ⁄8 5⁄8 — — — — — —
208/230-3-60 and 460-3-60
Speed (rpm) 1725 1725 1725 1725 1725 1725 1745 1745 1745
Hp 2.4 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y 56Y S184T S213T S215T
Shaft Dia (in.) 5⁄8 5 ⁄8 5⁄8 5 ⁄8 7 ⁄8 7 ⁄8 1 1 ⁄8 13⁄8 13⁄8
575-3-60
Speed (rpm) 1725 1725 1725 1725 1725 1725 1745 1755 1755
Hp 1.0 2.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0
Frame (NEMA) 56 56HZ 56HZ 56HZ 56HZ 56HZ 184T S213T D215T
Shaft Dia (in.) 5⁄8 7 ⁄8 7⁄8 7 ⁄8 7 ⁄8 7 ⁄8 1 1 ⁄8 13⁄8 13⁄8
230-3-50 and 400-3-50
Speed (rpm) 1425 1425 1425 1425 1425 1425 1425 1425 1425
Hp 2.4 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y 56Y 184T S213T S215T
Shaft Dia (in.) 5⁄8 5 ⁄8 5⁄8 7 ⁄8 7 ⁄8 7 ⁄8 1 1 ⁄8 13⁄8 13⁄8
26
More user manuals on ManualsBase.com
Table 8C — Fan Motor Data, Standard Motor — SI
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
208/230-1-60
Speed (r/s) 28.75 28.75 28.75 — — — — — —
Shaft kW 0.97 1.79 1.79 — — — — — —
Frame (NEMA) 56Y 56Y 56Y — — — — — —
Shaft Dia (mm) 15.9 15.9 15.9 — — — — — —
208/230-3-60 and 460-3-60
Speed (r/s) 28.75 28.75 28.75 28.75 28.75 28.75 29.08 29.08 29.08
Shaft kW 1.79 1.79 1.79 1.79 2.16 2.76 3.73 5.60 7.46
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y 56Y S184T S213T S215T
Shaft Dia (mm) 15.9 15.9 15.9 15.9 22.2 22.2 28.6 34.9 34.9
575-3-60
Speed (r/s) 28.75 28.75 28.75 28.75 28.75 28.75 29.08 29.25 29.25
Shaft kW 0.746 1.49 1.49 1.49 2.24 2.24 3.73 5.60 7.46
Frame (NEMA) 56 56HZ 56HZ 56HZ 56HZ 56HZ 184T S213T S215T
Shaft Dia (mm) 15.9 22.2 22.2 22.2 22.2 22.2 28.6 34.9 34.9
230-3-50 and 400-3-50
Speed (r/s) 23.75 23.75 23.75 23.75 23.75 23.75 23.75 23.75 23.75
Shaft kW 1.79 1.79 1.79 2.16 2.16 2.16 3.73 5.60 7.46
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y 56Y 184T S213T S215T
Shaft Dia (mm) 15.9 15.9 15.9 22.2 22.2 22.2 28.6 34.9 34.9
NEMA — National Electrical Manufacturers Association
27
More user manuals on ManualsBase.com
Table 9A — Standard Drive Data, 60 Hz — English
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 2.4-3.4 2.8-3.8 2.8-3.8 3.4-4.4 2.8-3.8 2.8-3.8 3.7-4.7 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting 2.5 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.) 8.8 8.8 8.8 8.8 9.0 9.0 9.4 11.0 11.0
Pulley Bore (in.) 1 1 1 1 17⁄16 17⁄16 17⁄16 115⁄16 115⁄16
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—A 2—B 2—B* 2—B*
Belt Pitch (in.) 40.3 41.3 41.3 42.3 42.3 42.3 41.8 (2) 42.8 (2) 42.8
(2) 43.8 (2) 43.8
FAN SPEEDS (rpm)
Factory Setting 568 647 647 764 632 632 771 752 752
Range 470-666 549-745 549-745 666-863 537-728 537-728 679-863 682-841 674-831
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1200 1100 1100
Change per 1⁄2 Turn of
Moveable Motor Pulley 19.6 19.6 19.6 19.7 19.1 19.1 15.3 13.1 13.1
Flange
MAX FULL TURNS FROM 5 5 5 5 5 5 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 10.44- 10.44- 9.12- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 12.32 12.32 10.99 9.43 9.43
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
28
More user manuals on ManualsBase.com
Table 9C — High-Static Drive Data, 60 Hz — English
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.3-5.3 4.3-5.3 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.) 7.0 6.0* 6.0 6.0 7.4 7.9 7.4 8.6 8.6
Pulley Bore (in.) 1 1 1 1 17⁄16 17⁄16 17⁄16 115⁄16 115⁄16
Belt No. — Section 1—A 1—A 1—A 1—A 1—B 1—B 2—B 2—B 2—B
Belt Pitch (in.) 41.3 37.3 37.3 37.3 39.8 39.8 36.8 37.8 37.8
FAN SPEEDS (rpm)
Factory Setting 961 1121 1121 1121 979 1060 1118 1024 1024
838- 978- 978- 978- 873- 950- 1014- 873- 873-
Range 1084 1200*† 1200† 1200† 1096 1171 1200† 1075 1075
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1200 — —
Change per 1⁄2 Turn of
Moveable Motor Pulley 24.6 28.7 28.7 28.7 19.4 18.4 19.4 16.7 16.7
Flange
MAX FULL TURNS FROM 5 5 5 5 6 6 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 10.44- 9.16- 8.16- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 12.32** 10.99 10.02 9.43 9.43
*Valves for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in.
and resulting fan speed is 837-1096 rpm.
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.
**575-v unit has a center distance of 9.16-10.99.
29
More user manuals on ManualsBase.com
Table 9E — Medium-Static Drive Data, 50 Hz — English
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.0-5.0 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting 2.5 2.5 2.5 2.5 2.5 3.0 2.5 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.) 8.0 7.0 7.0 6.0 7.5 7.9 7.0 9.4 9.4
Pulley Bore (in.) 1 1 1 1 17⁄16 17⁄16 17⁄16 115⁄16 115⁄16
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—B 2—A 2—B 2—B
Belt Pitch (in.) 40.3 41.3 41.3 37.3 39.3 39.8 36.8 39.8 39.8
FAN SPEEDS (rpm)
Factory Setting 695 794 794 926 741 756 916 728 728
Range 606-784 692-896 692-896 808-1045 646-836 667-848 814-1018 652-803 652-803
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1200 1100 1100
Change per 1⁄2 Turn of
Moveable Motor Pulley 17.8 20.4 20.4 23.7 19.0 15.1 20.4 12.6 12.6
Flange
MAX FULL TURNS FROM 5 5 5 5 5 6 5 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 10.44- 9.16- 9.16- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 12.32 10.99 10.99 9.43 9.43
30
More user manuals on ManualsBase.com
Table 9G — Standard Drive Data, 60 Hz — SI
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 61.0- 71.1- 71.1- 86.4- 71.1- 71.1- 94.0- 109.2- 109.2-
(mm) 86.4 96.5 96.5 111.8 96.5 96.5 119.4 134.6 134.6
Pulley Factory Setting 2.5 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm) 224 224 224 224 229 229 239 279 279
Pulley Bore (mm) 25.4 25.4 25.4 25.4 36.5 36.5 36.5 49.2 49.2
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—A 2—B 2—B* 2—B*
Belt Pitch (mm) 1024 1049 1049 1074 1074 1074 1062 (2) 1087 (2) 1087
(2) 1113 (2) 1113
FAN SPEEDS (r/s)
Factory Setting 9.5 10.8 10.8 12.7 10.5 10.5 12.9 12.5 12.5
Range 7.8-11.1 9.2-12.4 9.2-12.4 11.1-14.4 9.0-12.1 9.0-12.1 11.3-14.4 11.4-14.0 11.2-13.9
Max Allowable Speed (r/s) 20.0 20.0 20.0 20.0 20.0 20.0 20.0 18.3 18.3
Change per 1⁄2 Turn of
Moveable Motor Pulley 0.327 0.327 0.327 0.328 0.318 0.318 0.255 0.218 0.218
Flange
MAX FULL TURNS FROM 5 5 5 5 5 5 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 265-313 265-313 265-313 265-313 265-313 265-313 232-279 169-240 169-240
(mm)
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
31
More user manuals on ManualsBase.com
Table 9I — High-Static Drive Data, 60 Hz — SI
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 86.4- 86.4- 86.4- 86.4- 94.0- 109.2 109.2- 109.2- 109.2-
(mm) 111.8 111.8 111.8 111.8 119.4 134.6 134.6 134.6 134.6
Pulley Factory Setting 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm) 178 152* 152 152 188 201 188 203 203
Pulley Bore (mm) 25.4 25.4 25.4 25.4 36.5 36.5 36.5 49.2 49.2
Belt No. — Section 1—A 1—A 1—A 1—A 1—B 1—B 2—B 2—B 2—B
Belt Pitch (mm) 1049 947 947 947 1011 1011 935 935 960
FAN SPEEDS (r/s)
Factory Setting 16.0 18.7 18.7 18.7 16.3 17.7 18.6 17.1 17.1
Range 14.0- 16.3- 16.3- 16.3- 14.4- 15.8- 16.9- 14.6- 14.6-
18.1 20.0*† 20.0† 20.0† 18.3 19.5 20.0† 17.9 17.9
Max Allowable Speed (r/s) 20.0 20.0 20.0 20.0 20.0 20.0 20.0 18.3 18.3
Change per 1⁄2 Turn of
Moveable Motor Pulley 0.410 0.478 0.478 0.478 0.323 0.307 0.323 0.278 0.278
Flange
MAX FULL TURNS FROM 5 5 5 5 6 6 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 265-313 265-313 265-313 265-313 265-313** 232-279 207-255 169-240 169-240
(mm)
*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 178 mm and
resulting fan speed is 14.0-18.3 r/s.
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed
20 r/s.
**575-v unit has a center distance of 233-279.
32
More user manuals on ManualsBase.com
Table 9K — Medium-Static Drive Data, 50 Hz — SI
40RM 40RM 40RM 40RM 40RM 40RM 40RM
UNIT 40RM 40RMQ 40RMS 40RMQ 40RMS 40RMQ 40RMS 40RMS 40RMS
007 40RMS 010 40RMS 014 40RMS 024 028 034
008 012 016
MOTOR DRIVE
Motor Pulley Pitch Diameter 86.4- 86.4- 86.4- 86.4- 86.4- 94.0- 101.6- 109.2- 109.2-
(mm) 111.8 111.8 111.8 111.8 111.8 119.4 127.0 134.6 134.6
Pulley Factory Setting 2.5 2.5 2.5 2.5 2.5 3.0 2.5 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm) 203 178 178 152 191 201 178 239 239
Pulley Bore (mm) 25.4 25.4 25.4 25.4 36.5 36.5 36.5 49.2 49.2
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—B 2—A 2—B 2—B
Belt Pitch (mm) 1024 1049 1049 947 998 1011 922 1011 1011
FAN SPEEDS (r/s)
Factory Setting 11.6 13.2 13.2 15.4 12.4 12.6 15.3 12.1 12.1
Range 10.1- 11.5- 11.5- 13.5- 10.8- 11.1- 13.6- 10.9- 10.9-
13.1 14.9 14.9 17.4 13.9 14.1 17.0 13.4 13.4
Max Allowable Speed (r/s) 20.0 20.0 20.0 20.0 20.0 20.0 20.0 18.3 18.3
Change per 1⁄2 Turn of
Moveable Motor Pulley 0.297 0.340 0.340 0.395 0.317 0.252 0.340 0.210 0.210
Flange
MAX FULL TURNS FROM 5 5 5 5 5 6 5 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 265-313 265-313 265-313 265-313 265-313 232-279 232-279 169-240 169-240
(mm)
33
More user manuals on ManualsBase.com
Table 10A — Fan Performance Data — 0.0-1.2 in. wg ESP — English
EXTERNAL STATIC PRESSURE (in. wg)
UNIT AIRFLOW 0.0 0.2 0.4 0.6 0.8 1.0 1.2
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1,800 320 0.22 442 0.32 534 0.42 611 0.52 678 0.61 739 0.70 795 0.80
2,100 373 0.31 483 0.42 569 0.53 642 0.63 708 0.73 767 0.82 821 0.92
40RM 2,400 427 0.42 526 0.53 606 0.64 676 0.75 739 0.86 796 0.96 849 1.06
007
2,700 480 0.54 570 0.67 646 0.78 712 0.89 773 1.00 828 1.11 880 1.21
3,000 533 0.69 616 0.82 687 0.94 750 1.05 808 1.16 862 1.28 912 1.39
2,250 359 0.32 472 0.44 560 0.55 634 0.65 700 0.75 759 0.86 814 0.96
40RM 2,600 415 0.45 516 0.57 599 0.68 669 0.79 732 0.90 790 1.01 843 1.11
40RMQ 3,000 478 0.62 569 0.75 645 0.86 712 0.98 773 1.09 828 1.20 879 1.32
40RMS
008 3,400 542 0.82 624 0.95 695 1.08 758 1.20 815 1.31 869 1.43 918 1.55
3,750 598 1.03 673 1.17 740 1.29 800 1.42 855 1.60 906 1.66 954 1.78
2,550 396 0.42 502 0.54 586 0.65 658 0.76 722 0.87 780 0.97 833 1.08
2,975 462 0.60 556 0.72 634 0.84 701 0.95 762 1.06 818 1.18 870 1.29
40RMS 3,400 527 0.80 612 0.93 684 1.06 748 1.18 806 1.30 860 1.41 910 1.53
010
3,825 593 1.05 670 1.18 737 1.31 797 1.44 852 1.56 904 1.68 952 1.80
4,250 659 1.33 729 1.47 791 1.60 848 1.73 901 1.86 950 1.98 997 2.11
3,000 444 0.58 541 0.71 621 0.83 691 0.94 753 1.05 809 1.17 862 1.28
40RM 3,500 518 0.82 604 0.95 677 1.08 742 1.20 801 1.32 855 1.44 906 1.56
40RMS 4,000 592 1.11 669 1.25 736 1.38 797 1.51 853 1.63 904 1.75 953 1.88
012 4,500 666 1.44 735 1.59 797 1.72 854 1.86 907 1.99 956 2.12 1003 2.24
5,000 740 1.83 803 1.98 861 2.12 914 2.26 964 2.39 1010 2.53 1055 2.66
3,000 471 0.61 564 0.74 642 0.86 710 0.97 771 1.09 827 1.20 878 1.31
3,500 550 0.87 632 1.00 703 1.13 766 1.25 824 1.37 877 1.49 926 1.60
40RMQ 4,000 628 1.17 701 1.31 766 1.44 825 1.57 879 1.69 930 1.82 978 1.94
012
4,500 706 1.53 772 1.67 832 1.81 887 1.94 938 2.07 987 2.20 1032 2.33
5,000 785 1.93 845 2.08 900 2.22 952 2.36 1000 2.50 1045 2.63 1089 2.76
3,750 363 0.37 475 0.58 566 0.80 645 1.02 715 1.24 779 1.47 839 1.69
40RM 4,300 416 0.53 517 0.78 601 1.02 676 1.26 743 1.50 805 1.74 862 1.99
40RMS 5,000 484 0.81 573 1.08 650 1.35 719 1.62 782 1.89 841 2.16 896 2.44
014 5,700 552 1.17 631 1.47 702 1.76 766 2.06 826 2.36 881 2.66 934 2.96
6,250 605 1.51 678 1.83 744 2.15 805 2.47 862 2.79 915 3.11 966 3.43
4,500 391 0.51 495 0.75 581 1.00 657 1.25 725 1.50 787 1.76 845 2.02
40RM 5,300 460 0.80 551 1.08 629 1.35 700 1.63 764 1.91 823 2.20 878 2.48
40RMS 6,000 521 1.13 602 1.43 675 1.73 741 2.04 801 2.34 858 2.65 911 2.96
016 6,800 590 1.60 663 1.93 730 2.26 791 2.59 847 2.92 901 3.26 951 3.60
7,500 651 2.10 718 2.45 779 2.81 837 3.16 890 3.52 941 3.88 990 4.24
4,500 405 0.54 507 0.79 592 1.03 667 1.28 735 1.54 797 1.80 854 2.06
5,300 476 0.85 566 1.13 643 1.40 713 1.68 776 1.97 835 2.26 890 2.55
40RMQ
016 6,000 539 1.20 620 1.50 691 1.81 756 2.11 816 2.42 872 2.73 924 3.05
6,800 611 1.69 683 2.03 748 2.36 809 2.69 865 3.03 918 3.37 968 3.71
7,500 674 2.22 740 2.58 800 2.93 857 3.29 910 3.65 960 4.02 1008 4.38
6,000 503 1.07 587 1.37 661 1.67 727 1.97 789 2.28 846 2.59 900 2.90
40RM 7,000 586 1.64 660 1.98 726 2.31 787 2.65 844 2.99 898 3.33 948 3.67
40RMS 8,000 670 2.37 735 2.74 795 3.12 851 3.49 904 3.86 954 4.23 1001 4.61
024 9,000 754 3.28 812 3.69 867 4.09 918 4.50 967 4.90 1014 5.31 1059 5.72
10,000 838 4.39 891 4.83 941 5.27 988 5.70 1034 6.14 1077 6.85 1120 7.02
7,500 412 1.15 492 1.53 568 2.00 640 2.56 710 3.22 776 3.98 840 4.83
40RM 8,750 481 1.76 550 2.17 616 2.66 680 3.22 742 3.86 802 4.58 860 5.38
40RMS 10,000 549 2.55 610 2.99 669 3.50 726 4.07 782 4.70 836 5.40 889 6.17
028 11,250 618 3.52 672 4.00 725 4.53 777 5.12 827 5.76 876 6.45 925 7.21
12,500 687 4.71 735 5.22 783 5.78 830 6.38 876 7.04 922 7.74 966 8.49
9,000 471 1.78 539 2.17 604 2.63 667 3.17 728 3.78 788 4.46 845 5.22
40RM 10,500 550 2.72 608 3.15 665 3.64 720 4.18 774 4.79 827 5.45 878 6.18
40RMS 12,000 628 3.93 679 4.40 730 4.92 779 5.48 827 6.09 874 6.76 921 7.47
034 13,500 707 5.44 752 5.94 797 6.49 841 7.08 885 7.71 928 8.38 970 9.10
15,000 785 7.27 826 7.81 867 8.39 907 9.01 947 9.66 986 10.35 1024 11.07
See Legend and Notes on page 36.
34
More user manuals on ManualsBase.com
Table 10B — Fan Performance Data — 1.4-2.4 in. wg ESP — English
EXTERNAL STATIC PRESSURE (in. wg)
UNIT AIRFLOW 1.4 1.6 1.8 2.0 2.2 2.4
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1,800 847 0.89 896 0.98 942 1.07 986 1.16 1027 1.25 — —
2,100 872 1.02 920 1.11 965 1.21 1008 1.30 1050 1.40 — —
40RM 2,400 899 1.16 946 1.26 990 1.36 1033 1.46 1073 1.55 — —
007
2,700 928 1.32 974 1.42 1018 1.52 1059 1.63 1099 1.73 — —
3,000 959 1.49 1004 1.60 1046 1.71 1087 1.81 1126 1.92 — —
2,250 865 1.06 913 1.16 958 1.27 1001 1.37 1042 1.47 — —
40RM 2,600 893 1.22 940 1.33 984 1.43 1027 1.54 1067 1.65 — —
40RMQ 3,000 928 1.43 973 1.54 1017 1.65 1058 1.76 1098 1.87 — —
40RMS
008 3,400 965 1.66 1010 1.78 1052 1.89 1092 2.00 1131 2.12 — —
3,750 1000 1.90 1043 2.02 1084 2.13 1124 2.25 1162 2.37 — —
2,550 884 1.18 931 1.29 975 1.40 1018 1.50 1059 1.61 — —
2,975 919 1.40 965 1.51 1009 1.62 1050 1.73 1090 1.84 — —
40RMS 3,400 957 1.64 1002 1.76 1044 1.87 1085 1.98 1124 2.10 — —
010
3,825 998 1.92 1041 2.04 1082 2.16 1122 2.27 1160 2.39 — —
4,250 1041 2.23 1083 2.35 1123 2.48 1161 2.60 1199 2.72 — —
3,000 911 1.39 958 1.50 1002 1.61 1044 1.72 1084 1.83 1123 1.94
40RM 3,500 953 1.67 998 1.79 1041 1.90 1082 2.02 1122 2.13 1159 2.25
40RMS 4,000 999 2.00 1042 2.12 1084 2.24 1124 2.36 1162 2.48 1199 2.60
012 4,500 1047 2.37 1089 2.50 1129 2.62 1168 2.74 — — — —
5,000 1097 2.79 1138 2.92 1177 3.05 — — — — — —
3,000 927 1.43 973 1.54 1017 1.65 1058 1.76 1098 1.87 1137 1.98
3,500 973 1.72 1018 1.84 1060 1.95 1101 2.07 1139 2.18 1177 2.30
40RMQ 4,000 1023 2.06 1066 2.19 1107 2.31 1146 2.43 1184 2.55 — —
012
4,500 1075 2.45 1116 2.58 1156 2.71 1194 2.83 — — — —
5,000 1130 2.90 1170 3.03 — — — — — — — —
3,750 894 1.91 947 2.14 996 2.37 1044 2.60 1089 2.83 — —
40RM 4,300 916 2.23 967 2.48 1016 2.73 1062 2.98 1107 3.24 — —
40RMS 5,000 948 2.71 997 2.98 1044 3.26 1089 3.53 1133 3.81 — —
014 5,700 984 3.25 1031 3.55 1076 3.86 1120 4.16 1162 4.46 — —
6,250 1014 3.75 1060 4.07 1104 4.39 1147 4.71 1188 5.03 — —
4,500 899 2.29 951 2.56 999 2.84 1046 3.12 1091 3.41 1133 3.70
40RM 5,300 930 2.78 980 3.08 1027 3.38 1072 3.68 1116 3.99 1157 4.30
40RMS 6,000 961 3.28 1009 3.60 1055 3.92 1098 4.24 1141 4.57 1181 4.91
016 6,800 999 3.94 1045 4.28 1089 4.63 1132 4.98 1173 5.33 — —
7,500 1036 4.60 1080 4.97 1123 5.34 1164 5.71 — — — —
4,500 908 2.33 959 2.61 1008 2.89 1054 3.17 1098 3.46 1141 3.75
5,300 941 2.84 991 3.14 1038 3.45 1082 3.75 1126 4.06 1167 4.38
40RMQ
016 6,000 974 3.36 1022 3.69 1067 4.01 1111 4.34 1153 4.67 1193 5.00
6,800 1015 4.05 1061 4.40 1104 4.75 1146 5.10 1187 5.46 — —
7,500 1054 4.75 1098 5.12 1140 5.49 1181 5.86 — — — —
6,000 950 3.21 999 3.53 1045 3.85 1089 4.17 1131 4.50 1172 4.83
40RM 7,000 996 4.02 1042 4.37 1086 4.72 1129 5.07 1169 5.43 — —
40RMS 8,000 1047 4.99 1091 5.37 1133 5.75 1173 6.13 — — — —
024 9,000 1102 6.13 1143 6.54 1183 6.96 — — — — — —
10,000 1160 7.46 1200 7.91 — — — — — — — —
7,500 903 5.79 963 6.83 1021 7.98 1078 9.21 — — — —
40RM 8,750 917 6.26 972 7.22 1025 8.26 1078 9.38 — — — —
40RMS 10,000 941 7.01 991 7.91 1040 8.89 1089 9.93 — — — —
028 11,250 972 8.02 1019 8.89 1064 9.83 — — — — — —
12,500 1010 9.29 1053 10.15 1095 11.05 — — — — — —
9,000 901 6.07 955 6.98 1008 7.98 1060 9.05 — — — —
40RM 10,500 928 6.98 978 7.84 1026 8.76 1073 9.74 — — — —
40RMS 12,000 966 8.24 1011 9.07 1055 9.95 1098 10.88 — — — —
034 13,500 1011 9.86 1052 10.67 1092 11.52 — — — — — —
15,000 1062 11.84 — — — — — — — — — —
See Legend and Notes on page 36.
35
More user manuals on ManualsBase.com
Legend and Notes for Table 10A and 10B
LEGEND Factory-Supplied Filter Pressure Drop — English
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure UNIT AIRFLOW PRESSURE DROP
(Cfm) (in. wg)
NOTES: 1,800 0.05
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and 40RM 2,400 0.08
034; 1200 rpm for all other sizes. 007 3,000 0.11
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See right for factory-supplied filter pres- 40RM
40RMQ 2,250 0.07
sure drop. 3,000 0.11
3. Refer to fan motor and drive tables for additional data. 40RMS 3,750 0.15
008
2,550 0.09
40RMS 3,400 0.13
010 4,250 0.18
40RM
40RMQ 3,000 0.11
40RMS 4,000 0.17
012 5,000 0.23
40RM 3,750 0.06
40RMS 5,000 0.10
014 6,250 0.13
40RM
40RMQ 4,500 0.08
40RMS 6,000 0.12
016 7,500 0.17
40RM 6,000 0.12
40RMS 8,000 0.19
024 10,000 0.26
40RM 7,500 0.15
40RMS 10,000 0.22
028 12,500 0.30
40RM 9,000 0.19
40RMS 12,000 0.29
034 15,000 0.40
36
More user manuals on ManualsBase.com
Table 10C — Fan Performance Data — 0-300 Pa ESP — SI
EXTERNAL STATIC PRESSURE (Pa)
UNIT AIRFLOW 0 50 100 150 200 250 300
(L/s)
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
850 5.34 0.17 7.38 0.25 8.91 0.32 10.20 0.39 11.30 0.46 12.30 0.53 13.30 0.60
1000 6.28 0.24 8.10 0.32 9.53 0.40 10.80 0.48 11.80 0.55 12.80 0.63 13.70 0.70
40RM 1150 7.22 0.33 8.86 0.41 10.20 0.50 11.40 0.58 12.40 0.66 13.40 0.73 14.20 0.81
007
1300 8.17 0.43 9.64 0.52 10.90 0.61 12.00 0.69 13.00 0.77 13.90 0.85 14.80 0.93
1450 9.11 0.55 10.50 0.64 11.60 0.73 12.70 0.82 13.60 0.91 14.50 0.99 15.40 1.07
1000 5.63 0.22 7.61 0.30 9.11 0.38 10.40 0.45 11.50 0.53 12.50 0.61 13.40 0.68
40RM 1200 6.76 0.32 8.49 0.41 9.88 0.50 11.10 0.57 12.10 0.66 13.10 0.74 14.00 0.82
40RMQ 1400 7.89 0.46 9.42 0.55 10.70 0.64 11.80 0.72 12.80 0.81 13.80 0.89 14.60 0.97
40RMS
008 1600 9.01 0.62 10.40 0.71 11.60 0.80 12.60 0.89 13.60 0.98 14.50 1.07 15.30 1.16
1800 10.10 0.80 11.40 0.90 12.50 0.10 13.50 1.09 14.40 1.18 15.20 1.27 16.00 1.36
1200 6.58 0.31 8.35 0.40 9.76 0.49 11.00 0.57 12.00 0.65 13.00 0.73 13.90 0.81
1400 7.67 0.44 9.25 0.54 10.60 0.63 11.70 0.71 12.70 0.80 13.60 0.88 14.50 0.96
40RMS 1600 8.77 0.60 10.20 0.70 11.40 0.79 12.50 0.88 13.40 0.97 14.30 1.05 15.20 1.14
010
1800 9.86 0.78 11.10 0.88 12.30 0.98 13.30 1.07 14.20 1.16 15.10 1.25 15.90 1.34
2000 11.0 0.99 12.10 1.09 13.20 1.19 14.10 1.29 15.00 3.38 15.80 1.48 16.60 1.57
1450 7.58 0.46 9.18 0.56 10.50 0.65 11.60 0.73 12.70 0.82 13.60 0.90 14.50 0.99
40RM 1670 8.73 0.63 10.20 0.73 11.40 0.83 12.50 0.92 13.40 1.01 14.30 1.10 15.20 1.18
40RMS 1900 9.93 0.84 11.20 0.95 12.30 1.05 13.30 1.14 14.30 1.24 15.10 1.33 15.90 1.42
012 2120 11.10 1.08 12.20 1.18 13.30 1.29 14.20 1.39 15.10 1.48 15.90 1.58 16.70 1.68
2350 12.30 1.36 13.30 1.17 14.30 1.57 15.20 1.68 16.00 1.78 16.80 1.88 17.60 1.98
1450 8.04 0.49 9.57 0.58 10.90 0.67 12.00 0.76 13.00 0.85 13.90 0.93 14.80 1.02
1670 9.26 0.67 10.60 0.77 11.80 0.86 12.90 0.95 13.80 1.04 14.70 1.13 15.50 1.22
40RMQ 1900 10.50 0.89 11.80 0.99 12.80 1.09 13.80 1.19 14.70 1.28 15.60 1.38 16.40 1.47
012
2120 11.80 1.14 12.90 1.24 13.90 1.35 14.80 1.45 15.60 1.55 16.40 1.64 17.20 1.74
2350 13.00 1.43 14.00 1.54 15.00 1.65 15.80 1.75 16.60 1.85 17.40 1.95 18.10 2.05
1750 5.99 0.27 7.88 0.43 9.41 0.59 10.70 0.75 11.90 0.92 13.00 1.08 14.00 1.25
40RM 2050 7.01 0.41 8.68 0.60 10.10 0.78 11.30 0.96 12.40 1.14 13.50 1.33 14.40 1.51
40RMS 2350 8.04 0.60 9.53 0.81 10.80 1.01 12.00 1.21 13.00 1.41 14.00 1.61 14.90 1.82
014 2650 9.07 0.84 10.40 1.06 11.60 1.28 12.70 1.50 13.70 1.72 14.60 1.94 15.50 2.16
2950 10.10 1.13 11.30 1.37 12.40 1.61 13.40 1.85 14.40 2.08 15.30 2.32 16.10 2.56
2100 6.43 0.37 8.19 0.55 9.65 0.73 10.90 0.92 12.10 1.11 13.10 1.30 14.10 1.50
40RM 2450 7.51 0.57 9.06 0.77 10.40 0.97 11.60 1.18 12.70 1.39 13.70 1.60 14.60 1.81
40RMS 2800 8.58 0.82 9.96 1.05 11.20 1.27 12.30 1.49 13.30 1.72 14.30 1.95 15.10 2.18
016 3150 9.65 1.14 10.90 1.38 12.00 1.63 13.10 1.87 14.00 2.12 14.90 2.36 15.80 2.61
3500 10.70 1.52 11.90 1.78 12.90 2.05 13.90 2.31 14.80 2.58 15.60 2.84 16.40 3.11
2100 6.65 0.39 8.39 0.58 9.83 0.76 11.10 0.95 12.20 1.13 13.30 1.31 14.20 1.50
2450 7.76 0.60 9.30 0.81 10.60 1.01 11.80 1.22 12.90 1.43 13.80 1.63 14.80 1.84
40RMQ
016 2800 8.87 0.86 10.20 1.09 11.50 1.32 12.50 1.55 13.60 1.78 14.50 2.01 15.40 2.24
3150 9.98 1.19 11.20 1.44 12.30 1.70 13.40 1.95 14.30 2.20 15.20 2.45 16.00 2.70
3500 11.10 1.59 12.20 1.86 13.20 2.14 14.20 2.41 15.10 2.68 15.90 2.95 16.70 3.22
2900 8.58 0.86 9.96 1.09 11.20 1.32 12.30 1.55 13.30 1.78 14.20 2.01 15.10 2.25
40RM 3350 9.91 1.28 11.10 1.53 12.20 1.79 13.20 2.04 14.20 2.30 15.10 2.55 15.90 2.81
40RMS 3800 11.30 1.81 12.30 2.09 13.30 2.37 14.30 2.64 15.10 2.93 16.00 3.21 16.80 3.49
024 4250 12.60 2.46 13.60 2.76 14.50 3.07 15.30 3.37 16.10 3.67 16.90 3.98 17.70 4.28
4700 13.90 3.24 14.80 3.57 15.60 3.90 16.40 4.22 17.20 4.55 17.90 4.88 18.60 5.21
3500 6.79 0.84 8.14 1.12 9.42 1.47 10.70 1.89 11.80 2.39 12.90 2.96 14.00 3.61
40RM 4100 7.95 1.29 9.12 1.60 10.20 1.96 11.30 2.38 12.40 2.86 13.40 3.40 14.30 4.00
40RMS 4700 9.12 1.88 10.10 2.21 11.10 2.59 12.10 3.02 13.00 3.49 13.90 4.02 14.80 4.60
028 5300 10.30 2.62 11.20 3.00 12.10 3.37 12.90 3.81 13.80 4.29 14.60 4.82 15.40 5.38
5900 11.40 3.52 12.30 3.90 13.10 4.32 13.90 4.77 14.60 5.26 15.40 5.79 16.10 6.35
4250 7.86 1.33 8.99 1.63 10.10 1.97 11.10 2.37 12.20 2.83 13.20 3.34 14.10 3.92
40RM 4950 9.15 2.03 10.10 2.35 11.10 2.72 12.00 3.12 12.90 3.58 13.80 4.08 14.70 4.62
40RMS 5650 10.40 2.92 11.30 3.27 12.20 3.66 13.00 4.08 13.80 4.54 14.60 5.04 15.40 5.57
034 6350 11.70 4.02 12.50 4.40 13.30 4.81 14.00 5.25 14.70 5.72 15.50 6.23 16.20 6.77
7050 13.00 5.37 13.70 5.77 14.40 6.21 15.10 6.66 15.70 7.15 16.40 7.67 17.10 8.21
See Legend and Notes on page 39.
37
More user manuals on ManualsBase.com
Table 10D — Fan Performance Data — 350-600 Pa ESP — SI
EXTERNAL STATIC PRESSURE (Pa)
UNIT AIRFLOW 350 400 450 500 550 600
(L/s)
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
850 14.10 0.67 15.00 0.74 15.70 0.81 16.50 0.87 17.20 0.94 — —
1000 14.60 0.77 15.40 0.84 16.10 0.91 16.90 0.98 17.60 1.06 — —
40RM 1150 15.10 0.88 15.90 0.96 16.60 1.03 17.30 1.11 18.00 1.18 — —
007
1300 15.60 1.01 16.40 1.09 17.10 1.17 17.80 1.25 18.40 1.32 — —
1450 16.10 1.15 16.90 1.24 17.60 1.32 18.30 1.40 18.90 1.48 — —
1000 14.30 0.76 15.10 0.83 15.80 0.91 16.60 0.99 17.30 1.06 — —
40RM 1200 14.80 0.90 15.60 0.98 16.40 1.05 17.10 1.13 17.80 1.21 — —
40RMQ 1400 15.40 1.06 16.20 1.14 16.90 1.22 17.60 1.30 18.30 1.39 — —
40RMS
008 1600 16.10 1.24 16.80 1.33 17.50 1.41 18.20 1.50 18.90 1.58 — —
1800 16.80 1.45 17.50 1.54 18.20 1.63 18.90 1.72 19.50 1.80 — —
1200 14.70 0.89 15.50 0.97 16.30 1.05 17.00 1.12 17.70 1.20 — —
1400 15.30 1.05 16.10 1.13 16.80 1.21 17.50 1.29 18.20 1.37 — —
40RMS 1600 16.00 1.23 16.70 1.31 17.40 1.40 18.10 1.48 18.80 1.57 — —
010
1800 16.60 1.43 17.40 1.52 18.10 1.61 18.70 1.70 19.40 1.79 — —
2000 17.30 1.66 18.00 1.76 18.70 1.85 19.40 1.94 — — — —
1450 15.30 1.07 16.10 1.15 16.80 1.24 17.50 1.32 18.20 1.40 18.80 1.48
40RM 1670 16.00 1.27 16.70 1.36 17.40 1.44 18.10 1.53 18.80 1.62 19.40 1.70
40RMS 1900 16.70 1.51 17.40 1.60 18.10 1.69 18.80 1.78 19.40 1.87 — —
012 2120 17.50 1.77 18.20 1.86 18.80 1.96 19.50 2.05 — — — —
2350 18.30 2.07 19.00 2.17 19.60 2.27 — — — — — —
1450 15.60 1.10 16.30 1.18 17.10 1.27 17.80 1.35 18.40 1.43 19.10 1.52
1670 16.30 1.31 17.00 1.40 17.80 1.48 18.40 1.57 19.10 1.66 19.70 1.74
40RMQ 1900 17.10 1.56 17.80 1.65 18.50 1.74 19.20 1.83 19.80 1.92 — —
012
2120 17.90 1.83 18.60 1.93 19.30 2.02 19.90 2.11 — — — —
2350 18.80 2.15 19.50 2.25 — — — — — — — —
1750 14.90 1.42 15.80 1.58 16.60 1.75 17.40 1.93 18.20 2.10 — —
40RM 2050 15.30 1.70 16.20 1.88 17.00 2.07 17.80 2.26 18.50 2.45 — —
40RMS 2350 15.80 2.02 16.60 2.22 17.40 2.43 18.20 2.64 18.90 2.84 — —
014 2650 16.30 2.39 17.10 2.61 17.90 2.83 18.60 3.06 19.30 3.28 — —
2950 16.90 2.80 17.70 3.04 18.40 3.28 19.10 3.53 19.80 3.77 — —
2100 15.00 1.70 15.80 1.90 16.70 2.11 17.40 2.32 18.20 2.53 18.90 2.74
40RM 2450 15.50 2.03 16.30 2.25 17.10 2.47 17.80 2.70 18.60 2.93 19.30 3.16
40RMS 2800 16.00 2.42 16.80 2.66 17.60 2.90 18.30 3.14 19.00 3.38 19.70 3.63
016 3150 16.60 2.87 17.40 3.12 18.10 3.38 18.80 3.64 19.50 3.90 — —
3500 17.20 3.38 18.00 3.65 18.70 3.93 19.40 4.20 — — — —
2100 15.10 1.68 16.00 1.87 16.80 2.06 17.50 2.24 18.30 2.43 19.00 2.62
2450 15.60 2.05 16.40 2.25 17.20 2.46 18.00 2.67 18.70 2.88 19.40 3.09
40RMQ
016 2800 16.20 2.47 17.00 2.69 17.80 2.92 18.50 3.15 19.20 3.38 19.80 3.61
3150 16.80 2.95 17.60 3.19 18.30 3.44 19.00 3.69 19.70 3.94 — —
3500 17.50 3.49 18.20 3.76 19.00 4.03 19.60 4.30 — — — —
2900 16.00 2.49 16.80 2.73 17.50 2.97 18.30 3.22 19.00 3.47 19.70 3.72
40RM 3350 16.70 3.08 17.50 3.34 18.20 3.61 18.90 3.87 19.60 4.14 — —
40RMS 3800 17.50 3.77 18.20 4.06 18.90 4.35 19.60 4.64 — — — —
024 4250 18.40 4.59 19.10 4.90 19.80 5.21 — — — — — —
4700 19.30 5.54 20.00 5.87 — — — — — — — —
3500 15.10 4.33 16.10 5.12 17.10 5.98 18.00 6.92 — — — —
40RM 4100 15.30 4.67 16.20 5.39 17.10 6.18 18.00 7.02 — — — —
40RMS 4700 15.70 5.23 16.50 5.91 17.40 6.64 18.20 7.43 — — — —
028 5300 16.20 5.99 17.00 6.65 17.80 7.35 — — — — — —
5900 16.90 6.95 17.60 7.59 18.30 8.27 — — — — — —
4250 15.00 4.55 16.00 5.24 16.80 5.99 17.70 6.79 — — — —
40RM 4950 15.50 5.22 16.30 5.86 17.10 6.56 17.90 7.30 — — — —
40RMS 5650 16.10 6.16 16.90 6.77 17.60 7.43 18.30 8.13 — — — —
034 6350 16.90 7.34 17.50 7.94 18.20 8.58 — — — — — —
7050 17.70 8.79 18.30 9.39 — — — — — — — —
See Legend and Notes on page 39.
38
More user manuals on ManualsBase.com
Legend and Notes for Tables 10C and 10D Replacing Filters — Filters can be removed and in-
stalled from either side of the unit. Install new filters in units
LEGEND that have one fan as follows:
ESP — External Static Pressure
1. Remove the side access panel (retain screws).
NOTES:
1. Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and 2. Remove the filter retainer clip.
034; 20 r/s for all other sizes. 3. Remove old filters by tilting them and lifting them out of
2. Fan performance is based on deductions for wet coil, clean 51-mm the filter track. See Fig. 12 and 22.
filters, and unit casing. See right for factory-supplied filter pres-
sure drop. 4. Reverse the procedure to install new filters.
3. Refer to fan motor and drive tables for additional data.
To install new filters in larger units that have 2 fans, fol-
Factory-Supplied Filter Pressure Drop — SI low the preceding steps, but use the factory-supplied
filter hook to slide filters within reach for removal. The
UNIT AIRFLOW PRESSURE DROP filter hook is shipped inside the unit in the baserail.
(L/s) (Pa)
850 13
40RM 1150 20
007 1450 28 Do not operate unit without air filters.
40RM
40RMQ 1000 17
40RMS 1400 27
008 1800 38
1200 21
40RMS 1600 32
010 2000 45
40RM
40RMQ 1450 28
40RMS 1900 42
012 2350 56
40RM 1750 15
40RMS 2350 24
014 2950 33
40RM
40RMQ 2100 20
40RMS 2800 30
016 3500 42
40RM 2900 32
40RMS 3800 47
024 4700 64
40RM 3500 36
40RMS 4700 55
028 5900 76
40RM 4250 47
40RMS 5650 71
034 7050 98
39
More user manuals on ManualsBase.com
More user manuals on ManualsBase.com
More user manuals on ManualsBase.com
Copyright 1995 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI Pg 42 596 11-95 Replaces: 40RM-1SI
Tab 3c 2e
More user manuals on ManualsBase.com
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
START-UP CHECKLIST
(SPLIT SYSTEMS WITH 40RM/RMQ/RMS UNITS)
A. Preliminary Information
OUTDOOR: MODEL NO. SERIAL NO.
ADDITIONAL ACCESSORIES
B. Pre-Start-Up
CUT ALONG DOTTED LINE
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? (Y/N)
IF SO, WHERE:
CONTROLS
ARE THERMOSTAT(S) AND INDOOR FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED? (Y/N)
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)
HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N)
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N)
ARE PROPER AIR FILTERS IN PLACE? (Y/N)
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)
DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)
CUT ALONG DOTTED LINE
PIPING
40RM,RMQ
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT COILS AS REQUIRED? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,
TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS.
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N)
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS? (Y/N)
40RMS
HAS AIR BEEN BLED FROM SYSTEM? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CHILLERS, VALVES, AND INDOOR COILS? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI CL-1 11-95 Replaces: 40RM-1SI
Tab 3c 2e
More user manuals on ManualsBase.com
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB V AC V BC V
(AB + AC + BC)/3 = AVERAGE VOLTAGE = V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = %
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
C. Start-Up
CHECK EVAPORATOR FAN SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
COMP A1 COMP B1
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING OUTDOOR UNIT AIR TEMP
LEAVING OUTDOOR UNIT AIR TEMP
INDOOR UNIT ENTERING AIR DB TEMP
INDOOR UNIT ENTERING AIR WB TEMP
INDOOR UNIT LEAVING AIR DB TEMP
INDOOR UNIT LEAVING AIR WB TEMP
OUTDOOR UNIT ENTERING WATER TEMP
(40RMS ONLY)
OUTDOOR UNIT LEAVING WATER TEMP
(40RMS ONLY)
INDOOR UNIT ENTERING WATER TEMP
(40RMS ONLY)
INDOOR UNIT LEAVING WATER TEMP
(40RMS ONLY)
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING
OIL LEVEL AT 1⁄8 TO 1⁄3 FULL? (Y/N)
NOTES:
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI CL-2 596 11-95 Replaces: 40RM-1SI
Tab 3c 2e