CF805T Series User's Manual
CF805T Series User's Manual
1 Installation dimensions
CF805T Series User’s All following annotation dimensions’ units are millimeter (mm).
Manual
609AH
Safety Precautions
For your safe use of this instrument be sure to comply with the
following safety precautions. If the instrument is used in a manner
not specified in this manual, the protection provided by the
instrument may be impaired. We assume no responsibility for the
customer‘s failure to comply with these requirements.
critical applications that directly affect or threaten human lives. Connecting the input wires in parallel with other devices can
Such applications include nuclear power equipment, devices using cause signal degradation, affecting all connected devices.
1. Installation
Warning
2.3 Intelligent sensor
Be sure to turn off the power supply to prevent electric shock or instrument
failure
2.4 Output ENTER Press key to setting or the next layer menu
4. Parameter Tables
3. Operations
lower limit ABH:Absolute biased
upper limit ABL: Absolute biased H:Upper
Alarm mode 02H
lower limit PH:Standby upper limit limit
PL: Standby lower limit PBH:
■ Descriptions on Faceplate & Keys Standby biased upper limit PBL:
Standby biased lower limit
-999999~0.00000
Alarm Set Value 10000 03H
0.00000~999999
Alarm Hysterisis 0.00000~999999 0 04H
Alarm-
Alarm Delay 0~60 0 05H
1
-999999~0.00000
Alarm Bias 0 06H
Alarm 0.00000~999999
GROSS、NET、PEAK、VALLEY、
PEAK-VALLEY、PEAK-PATH、
VALLEY-PATH、Averaged GROSS、
Averaged NET、Captured Max、
Averaged
Alarm Source Captured Min、Captured Inflection-1、 07H
GROSS
Captured Inflection-2、Captured
Inflection-3、Captured Inflection-4、
Captured Inflection-5、Captured
Inflection-6
H:Upper limit L:Lower limit
Name Remarks Alarm- BH:Biased upper limit BL:Biased H:Upper
Alarm mode 08H
1 Input port 4-wires load cell 2 lower limit ABH:Absolute biased limit
upper limit ABL: Absolute biased
Area Under Stress 1.00~9999.99 1.00 92H Pre Interval A 0~9999 100 226H
Gravitation Constant 9.7000~9.9000 9.8012 93H Post Interval B 0~9999 100 227H
-999999~0.00000 Value
Start Threshold 10000 94H 0.00000~999999 1000 228H
0.00000~999999 Difference C
(6) Show the current state of power supply, battery and power supply state
Graph Display
■ Functional specifications
Bar Digital
Graph Display Capture
Display Display
2 capture data:
Title
No. Function
(1) the weighing value is in motion/variation: Blink between “BAR” and (4) Measured value
Capture list
No. Function
Setting parameters
No. Function
(2) channel
(5) Capture unit 2. Modify the value to 1111 by pressing UP, DOWN, LEFT, RIGHT keys
3. Press the ENTER key to save the Security Code,then Instrument display Setting
(6) Capture rate
picture
(7) Capture state
Setting parameters
1. Instrument display Setting picture
Function
2. Modify the cursor position by pressing UP、DOWN keys.
Capture state is divided into four display status, wait trigger, capturing, waveform
3. Short press the ENTER key to enter the parameter list or child parameters
preview, history waveform
GROUP
View Duration must be set to 0 when you want to see history waveform
4. In parameters goup,Short press UP、DOWN keys to modify the cursor position.
Function key
5. Short press ENTER key to enter parameter value mode.
Display“capturing ”or “waveform preview”,press UP key to restart wait trigger. 6. Modify the parameter value by pressing UP, DOWN, LEFT, RIGHT keys.
Display “waveform preview”,press DOWN key to save capture data 7. Short press 2 times to save the change value.
Display “ capturing ” or “ waveform preview ”, waveform can be adjusted 8. Press EXIT key to exit out of change when you don’t want to modify the
Calibration should be performed at first use or after any change made to measurement
7.2 Peak value and Valley value detection
apparatus, especially after replacing load cell .
Press the ENTER key to“Zero Calibration”,,input signal value is displayed (in millivolts) and
★ Peak value and Valley value will be automatically refreshed at every
refresh constantly
threshold crossing
Clear out weighing platform,Press the ENTER key to confirm zero signal when the display is
stable ★ In peak detection status, the Peak process value is always updated
★ In measurement mode,hold DOWN key for more than 2 seconds to reset the
5. Gain Calibration:
peak value and valley value to current gross value
Press the ENTER key to“Gain Calibration”,input signal value is displayed (in millivolts) and
refresh constantly
7.3 Digital input
Press the ENTER key to“Weight for Gain Cali”, ,modify the value to weights A by pressing Nulling,peak value、valley value、peak process value and
1 NULL
UP, DOWN, LEFT, RIGHT keys Valley process value also be reset to zero.
2 TARE Taring
Press the ENTER key to save weight。
Alarm output function is valid when the digital input is active.
No- weight,by load cell specifications Alarm
3 Otherwise, alarm output status is locked and unit indication LED
Permission
4. Sensitivity Calibration: blinks as a hint.
when the digital input is active, display is locked to current state.
Press the ENTER key to“Load Cell SENS”, ,modify the value to 2.0001 by pressing UP, 4 Display Lock
GROSS and NET indicator LED blink as a hint
DOWN, LEFT, RIGHT keys Reset Peak value 、valley value、peak process value and valley process
5
5. Weight Calibration: PEAK,VALLEY value be reset to current gross value when digital input is active
Press the ENTER key to“Weight for Gain Cali”, ,modify the value to weights A by pressing 6 Capture VaitTrig Enter and start capture
Each alarm output has 6 parameters in 1st parameter group. These parameters can be changed
7.1 Measurement
■ 7.1.1 Zero tracking , Nulling and Motion/Variation Detection
Zero Tracking:Zero tracking range, in the unit of scale interval. If the measurement
weight is within the zero tracking range for more than or equal to zero
ARMA Filter: Response time is better than inertial filtering but filtering effect is not so
strong. Value of 1 means moving averaging function is turned off
57600bps 1 1 1 1 2 4 View Duration Value should be greater than the PC read capture data
Save Mode Volatile single buffer or Volatile dual buffers
115200bps 1 1 1 1 1 2
4) Short interval process record and result judgment
128000bps 1 1 1 1 1 2
Work process: wait trigger - > meeting Start Judgement - > start capture- > meeting End
230400bps 1 1 1 1 1 1 Judgement - > end capture - > display waveform preview - > PC read capture data - > end
waveform preview - > wait trigger
This function can be used to tackle the non-linearity of measurement apparatus, for Measure
Sample Rate 1920SPS
ment
example, the non-linearity of load cell.
Capture Duration
Start Threshold
Start Judgement
According to the actual application Settings
End Threshold
Capture
End Judgement
Breakdown Alarm
View Duration 0 or -1
Save Mode Volatile dual buffers
8. Specifications
For measured value less than Corrected Value-1, Linearization is performed according to the ■ General Specifications
slope rate between Corrected Value-1~ Corrected Value-2. Items Specifications
Input:AC 90~260V,50Hz or 60Hz
For measured value greater than Corrected Value-10, Linearization is performed according to Power adapter
Output:DC 12V/2A,the outside interface is negative
the slope rate between Corrected Value-9~ Corrected Value-10 Continuous use time about 18 to 36 hours, related to the
Built-in battery
use
■ Input specifications
Items Specifications
Input signal 4-wires load cell
Load Cell sensitivity 0.1uV / d
Zero Adjustment -10~10 mV
Gain Adjustment 1 ~12 mV
Sample rate 15、120、240、480、960、1920SPS
Accuracy ±0.05%F•S(sample rate:15SPS)
Span Drift < 10 ppm/℃
Resolution 1/100000
Digital input 1 channel
■ Output specifications
Items Specifications
Load cell excitation power DC 5V±2%,100mA(MAX)
supply
Alarm Output Two output channel of Open Collector, ≤35mA
■ Specifications on Optional Accessories Parts
Items Specifications