0% found this document useful (0 votes)
38 views40 pages

APC MGE Galaxy 3500 Quick - Reference (EN)

Uploaded by

Neto Santos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views40 pages

APC MGE Galaxy 3500 Quick - Reference (EN)

Uploaded by

Neto Santos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

Quick Reference

MGE™ Galaxy™
3500 Series
10-40 kVA 380/400/415 V 3:3
15-40 kVA 380/400/415 V 3:1
Contents

Product Overview............................................................ 1
UPS for up to 2 battery modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UPS for up to 4 battery modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Availability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Serviceability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Manageability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Total Cost of Ownership . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Default Settings............................................................... 3

AC Input ........................................................................... 4
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
380 V, 400 V, and 415 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
380 V, 400 V, and 415 V 3:1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Input Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

AC Output ........................................................................ 6
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
380 V, 400 V, and 415 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
380 V, 400 V, and 415 V 3:1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Efficiency ......................................................................... 7
Efficiency Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Derating due to Load Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Environmental ............................................................... 10
Heat Dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
380 V, 400 V, and 415 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
380 V, 400 V, and 415 V 3:1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference i


Batteries ......................................................................... 11
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Efficiency DC to AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
380 V, 400 V, and 415 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
380 V, 400 V, and 415 V 3:1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Battery Run-Times (Minutes) - APC Battery Solution . . . . . . . . . . . 12


10 kVA 400 V typical performances . . . . . . . . . . . . . . . . . . . . . . . . . 12
15 kVA 400 V typical performances . . . . . . . . . . . . . . . . . . . . . . . . . 13
20 kVA 400 V typical performances . . . . . . . . . . . . . . . . . . . . . . . . . 14
30 kVA 400 V typical performances . . . . . . . . . . . . . . . . . . . . . . . . . 15
40 kVA 400 V typical performances . . . . . . . . . . . . . . . . . . . . . . . . . 16

Battery Run-Times - Non-Modular Batteries . . . . . . . . . . . . . . . . . . 17


10 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
15 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
20 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
30 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
40 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Battery Discharge Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19


380 V, 400 V, and 415 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

End of Discharge Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

AC Bypass...................................................................... 20
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
380 V, 400 V, and 415 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
380 V, 400 V, and 415 V 3:1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Physical .......................................................................... 21
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
380 V, 400 V, and 415 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
380 V, 400 V, and 415 V 3:1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
XR battery enclosure weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

ii MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Cables .............................................................................22
Recommended Cable Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
380 V, 400 V, and 415 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
380 V, 400 V, and 415 V 3:1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

Fuses and Breakers.......................................................23


Single utility/mains system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

Dual utility/mains system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

Parallel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

Fuse and Breaker Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24


380 V, 400 V, and 415 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
380 V, 400 V, and 415 V 3:1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
380 V, 400 V, and 415 V Parallel system with up to three
UPS units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Minimum Breaker Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26


380 V, 400 V, and 415 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
380 V, 400 V, and 415 V 3:1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Communication and Management ............................... 27


Network Management Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

Input and Output Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28


Pin connections J106 (UPS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

EPO ................................................................................. 29
Pin connections J108 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29

Compliance .................................................................... 30

Options ........................................................................... 31
Parallel MBP - wall-mount. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31

Empty Cabinet for batteries - floor-mount . . . . . . . . . . . . . . . . . . . .31

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference iii


Empty Cabinet for Transformer - floor-mount . . . . . . . . . . . . . . . . . 31

Parallel Capabilities....................................................... 32
Communication cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Schematic of the PBus cables layout . . . . . . . . . . . . . . . . . . . . . . . 32
System arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Overview of Power Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

iv MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Product Overview
The MGE Galaxy 3500 UPS is available in the following models:

UPS for up to 2 battery modules

• MGE Galaxy 3500 10 kVA 400 V


• MGE Galaxy 3500 15 kVA 400 V
• MGE Galaxy 3500 15 kVA 400 V 3:1
• MGE Galaxy 3500 20 kVA 400 V
• MGE Galaxy 3500 20 kVA 400 V 3:1

UPS for up to 4 battery modules

• MGE Galaxy 3500 10 kVA 400 V


• MGE Galaxy 3500 15 kVA 400 V
• MGE Galaxy 3500 15 kVA 400 V 3:1
• MGE Galaxy 3500 20 kVA 400 V
• MGE Galaxy 3500 20 kVA 400 V 3:1
• MGE Galaxy 3500 30 kVA 400 V
• MGE Galaxy 3500 30 kVA 400 V 3:1
• MGE Galaxy 3500 40 kVA 400 V
• MGE Galaxy 3500 40 kVA 400 V 3:1

Features
Availability

• Dual mains input: Increases availability by allowing the UPS to be connected to two separate
power sources
• Scalable runtime: Allows additional runtime to be quickly added as needed
• Hot-swappable batteries: Ensure clean, uninterrupted power to protected equipment while
batteries are being replaced
• Generator compatible: Ensure clean, uninterrupted power to protected equipment when generator
power is used
• Automatic internal static bypass: Supplies utility power to the connected loads in the event of a
UPS overload condition or fault
• Battery modules connected in parallel: Delivers higher availability through redundant batteries

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 1


Serviceability

• Batteries that can be replaced by qualified personnel: Increases availability by allowing qualified
personnel to perform upgrades and replacement of the batteries reducing the Mean Time To
Repair (MTTR)
• Automatic self-test: Periodic battery self-test ensures early detection of a battery that needs to be
replaced
• Shippable with modules installed: Enables pre-installation UPS staging and testing and faster
installation
• Modular design: Provides fast serviceability and reduced maintenance requirements via self-
diagnosing, field-replaceable modules

Manageability

• Network manageable: Provides remote management of the UPS over the network
• InfraStruXure Central Compatible: Enables centralized management via InfraStruXure Central
• LCD: Alphanumeric display which displays system parameters and alarms
• Audible alarms: Provides notification of changing utility power and UPS conditions
• Programmable frequency: Ensures compatibility with different input frequencies
• LED status indicators: Quickly understand unit and power status with visual indicators
• SmartSlot: Customize UPS capabilities with managements cards

Total Cost of Ownership

• Input power factor correction: Minimizes installation costs by enabling the use of smaller
generators and cabling
• Temperature-compensated battery charging: Prolongs battery life by regulating the charge voltage
according to battery temperature
• Manual maintenance bypass: Reduces installation costs by eliminating the need for an external
mechanical bypass
• Intelligent battery management: Maximizes battery performance, life, and reliability through
intelligent, precision charging

Protection

• Frequency and voltage regulation: Gives higher application availability by correcting poor
frequency and voltage conditions without using the battery
• Safety-agency approved: Ensures the product has been tested and approved to work safely with
the connected service provider equipment and within the specified environment. UL, FCC, CE,
C-Tick approvals
• Cold-start capable: Provides temporary battery power when the utility power is out

2 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Default Settings
System settings (only updated when in load disconnect) Default setting
Nominal output voltage (ph-ph) 380/400/415 V
Frequency 50 Hz
Frequency self-detect mode Auto
Frequency range ±10 Hz
Frequency slew rate 1 Hz/s
Generator charge percentage 100%
Cyclic charge mode enabled Off
Auto start On
Parallel UPS number 1
No. of parallel UPSs 1
MBP present No
Shutdown mode (can only be set from service port) Never
Shutdown setting
Low battery duration 2 minutes
Shutdown delay 20 seconds
Turn on delay 0 seconds
Return of battery capacity 0%
Alarm settings
Load alarm threshold System power rating
Runtime alarm threshold 0 (disabled)
Parallel redundancy alarm threshold n+0 (disabled)
Other settings
Battery self test Off
External battery capacity 0 Ah
Display settings
Display language English
Display contrast 0
Display beeper state PwerFail+30
Display beeper volume Low
Display key click Off

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 3


AC Input
Specifications
380 V, 400 V, and 415 V

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
Connection type 5-wire (3PH + N + PE)
Input frequency (Hz) 40-70
I thd < 5% at full load
Nom input current (A) 13.0 12.3 11.9 19.4 18.5 17.8 26.0 24.7 23.8 38.6 36.7 35.3 51.7 49.1 47.3
Max input current (A) 14.3 13.5 13.1 21.4 20.3 19.6 28.6 27.2 26.2 42.5 40.3 38.9 56.8 54.0 52.1
Input current limitation (A) 16.8 16.8 16.8 25.2 25.2 25.2 33.8 33.8 33.8 50.1 50.1 50.1 66.9 66.9 66.9
Input power factor correction > 0.98 at load > 50%

380 V, 400 V, and 415 V 3:1

15 kVA 20 kVA 30 kVA 40 kVA


380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
Connection type 5-wire (3PH + N + PE)
Input frequency (Hz) 40-70
I thd < 5% at full load
Nom input current (A) 19.4 18.5 17.8 26.0 24.7 23.8 38.6 36.7 35.3 51.7 49.1 47.3
Max input current (A) 21.4 20.3 19.6 28.6 27.2 26.2 42.5 40.3 38.9 56.8 54.0 52.1
Input current limitation (A) 25.2 25.2 25.2 33.8 33.8 33.8 50.1 50.1 50.1 66.9 66.9 66.9
Input power factor correction > 0.98 at load > 50%

Input Power Factor


Input Pow er Factor

1,00

0,98

0,96

0,94

0,92
Input PF

Input PF @ resistive load


0,90
Input PF @ non-linear load

0,88

0,86

0,84

0,82

0,80
0 10 20 30 40 50 60 70 80 90 100
Load %

4 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


AC Output
Specifications
380 V, 400 V, and 415 V

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
Connection type 5-wire (3PH + N + PE)
150% for 1 minute (normal operation)
125% for 10 minutes (normal operation)
150% for 1 minute (battery operation)
Output capacity
125% for 10 minutes (battery operation)
110% continuous (bypass operation)
800% for 500 ms (bypass operation)
Voltage tolerance +/- 20% (304-477 V) at full load
Nom output current (A) 15.2 14.4 13.9 22.8 21.7 20.9 30.4 28.9 27.8 45.6 43.3 41.7 60.8 57.7 55.6
Output frequency (sync to mains) 47-53 Hz for 50 Hz nominal
Slew rate (Hz/Sec) 0.25-1

Total Harmonic Distortion (THD) < 1.5% linear


< 3.5% non-linear
Output power factor 0.8
Dynamic load response +/- 5%
Output voltage regulation +/- 1%

380 V, 400 V, and 415 V 3:1

15 kVA 20 kVA 30 kVA 40 kVA


220 V 230 V 240 V 220 V 230 V 240 V 220 V 230 V 240 V 220 V 230 V 240 V
Connection type 3-wire (1PH + N + G)
150% for 1 minute (normal operation)
125% for 10 minutes (normal operation)
Output capacity 150% for 1 minute (battery operation)
125% for 10 minutes (battery operation)
110% continuous (bypass operation)
800% for 500 ms (bypass operation)
Voltage tolerance +/- 20% (304-477 V) at full load
Nom output current (A) 68.4 65.0 62.6 91.2 86.6 83.5 136.7 129.9 125.2 182.3 173.2 166.9
Output frequency (sync to mains) 47-53 Hz for 50 Hz nominal
Slew rate (Hz/Sec) 0.25-1
Total Harmonic Distortion < 1.5% linear
(THD) < 3.5% non-linear
Output power factor 0.8
Dynamic load response +/- 5%
Output voltage regulation +/- 1%

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 5


Efficiency
Note: The below figures are for the 3:3 version only.

System 25% load 50% load 75% load 100% load


10 kVA 400 V 91.9 94.4 94.7 94.5
15 kVA 400 V 93.2 95.4 95.7 95.7
20 kVA 400 V 94.4 95.7 95.7 95.6
30 kVA 400 V 94 95.6 95.8 95.8
40 kVA 400 V 94.9 95.8 95.8 95.6

Note: Low line is 348 V and high line is 452 V (+/- 13%).

Efficiency Curves
10 kVA 400 V
98,0

96,0

94,0

92,0
Efficiency [%]

Low line voltage


90,0
Nominal line voltage
High line voltage
88,0
Battery operation
86,0

84,0

82,0

80,0
0 20 40 60 80 100
Load [%]

15 kVA 400 V
98,0

96,0

94,0

92,0
Efficiency [%]

Low line voltage


90,0
Nominal line voltage
High line voltage
88,0
Battery operation
86,0

84,0

82,0

80,0
0 20 40 60 80 100
Load [%]

6 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


20 kVA 400 V 98,0

96,0

94,0

92,0

Efficiency [%]
Low line voltage
90,0
Nominal line voltage
High line voltage
88,0
Battery operation
86,0

84,0

82,0

80,0
0 20 40 60 80 100
Load [%]

30 kVA 400 V
98,0

96,0

94,0

92,0
Efficiency [%]

Low line voltage


90,0
Nominal line voltage
High line voltage
88,0
Battery operation
86,0

84,0

82,0

80,0
0 20 40 60 80 100
Load [%]

40 kVA 400 V
98,0

96,0

94,0

92,0
Efficiency [%]

Low line voltage


90,0
Nominal line voltage
High line voltage
88,0
Battery operation
86,0

84,0

82,0

80,0
0 20 40 60 80 100
Load [%]

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 7


Derating due to Load Power Factor
kW
LEADING 1.00 LAGGING

Co f =

=0 8
0.
0.75

sf

Co osf =
Co

.7
Co

=0 . 7
6
s
Co sf = = 0.

.8

sf
C
sf =0.5
0
s f 0. 0.50 o
=0 6 C o sf
.5 C
0.25

kVAr kVAr

-1.0 -0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8 1.0

8 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Environmental
General
Temperature
• Operating 0-40º C
• Storage with batteries -15-45º C
• Storage without batteries -30-70º C
Humidity
• Operating 0-95%, non-condensing
• Storage 0-95%, non-condensing
Elevation
• Operating 0-1000 m: 100% load
1000-1500 m: 95% load
1500-2000 m: 91% load
2000-2500 m: 86% load
2500-3000 m: 82% load
• Storage 0-15000 m
Audible noise
• At 70% load
10-15 kVA 208/220 V 42.3 dBA
20-30 kVA 208/220 V 46.2 dBA
10-20 kVA 380/400/415 V 42.3 dBA
30-40 kVA 380/400/415 V 46.2 dBA
• At 100% load
10-15 kVA 208/220 V 51.3 dBA
20-30 kVA 208/220 V 55.0 dBA
10-20 kVA 380/400/415 V 51.3 dBA
30-40 kVA 380/400/415 V 55.0 dBA
Protection class Up to IP51

Colour Dark grey

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 9


Heat Dissipation
380 V, 400 V, and 415 V

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


Batteries Batteries Batteries Batteries Batteries Batteries Batteries Batteries Batteries Batteries
fully charged charging fully charged charging fully charged charging fully charged charging fully charged charging
Heat dissipation 0.46 (1583) 0.54 0.54 (1842) 0.66 0.77 (2620) 0.93 1.08 (3685) 1.32 1.82
kw (BTU/hr) (1856) (2252) (3166) (4504) 1.50 (5132) (6223)

380 V, 400 V, and 415 V 3:1

15 kVA 20 kVA 30 kVA 40 kVA


Batteries Batteries Batteries Batteries Batteries Batteries Batteries Batteries
fully charged charging fully charged charging fully charged charging fully charged charging
Heat dissipation 0.58 (1965) 0.70 0.80 (2730) 0.96 1.15 (3931) 1.39 1.57 (5350) 1.89
kw (BTU/hr) (2375) (3276) (4750) (6442)

10 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Batteries
Specifications
10-40 kVA 380/400/415 V
Type VRLA
Nominal voltage (VDC) +/- 192
Float voltage (VDC) +/- 219
End of discharge voltage (VDC) +/- 154
Battery current (at full load) 87.9 A at + 192 V
Max. current (at end of discharge) 110.1 A at + 154 V
10 kVA: 800
15 kVA: 1200
Max. charging power 20 kVA: 1600
30 kVA: 2400
40 kVA: 3200
5 hours
Typical re-charge time

End voltage 1.6-1.75 V/cell (automatic, depending on load)

Efficiency DC to AC
380 V, 400 V, and 415 V

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
Efficiency at nominal
94.0 94.1 94.2 95.0 95.1 95.2 94.7 94.9 95.1 95.1 95.2 95.3 94.9 95.0 95.1
batt. voltage (%)

380 V, 400 V, and 415 V 3:1

15 kVA 20 kVA 30 kVA 40 kVA


220 V 230 V 240 V 220 V 230 V 240 V 220 V 230 V 240 V 220 V 230 V 240 V
Efficiency at nominal 94.9 95.0 95.1 94.7 94.8 94.9 94.9 95.0 95.1 94.8 94.9 95.0
batt. voltage (%)

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 11


Battery Run-Times (Minutes) - APC Battery
Solution
Note: “# of battery shelves” indicates the total number of populated battery shelves in the UPS
and Battery Enclosure.

10 kVA 400 V typical performances

Load kVA
600
# of 570
1
battery 1 2 4 6 8 10 540
510 2
shelves
480 3
1 118 56 24 14 9 6 450 4
420 5
2 276 133 60 36 25 18 390

Runtime [Minutes]
6
360
3 452 219 99 61 43 32 330 7
300 8
4 639 311 142 88 62 47 270 10
240
5 837 407 187 116 82 62 12
210
180 14
6 1043 508 233 145 103 78 16
150
120 18
7 1255 611 281 175 124 95
90 20
8 1474 718 331 206 147 112 60
22
30
0 24
9 1698 828 382 238 170 130
0 2 4 6 8 10 26
10 1928 940 433 271 193 148 Load [kVA], PF 0.8

11 2162 1054 486 304 217 166


12 2400 1171 540 338 241 185
13 2642 1289 595 372 266 204
14 2888 1409 651 407 291 223
15 3138 1531 707 443 316 243
16 3391 1655 765 479 342 262
17 3647 1780 823 515 368 282
18 3906 1907 881 552 394 303
19 4168 2035 941 589 421 323
20 4433 2164 1001 627 448 344
21 4701 2295 1061 665 475 365
22 4971 2427 1122 704 503 386
23 5243 2560 1184 742 530 408
24 5518 2694 1246 781 558 429
25 5795 2830 1309 821 586 451
26 6075 2966 1372 861 615 473

12 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


15 kVA 400 V typical performances

Load kVA
600
570 2
# of
battery 1 3 6 9 12 15 540 3
shelves 510 4
480
5
1 n.a. n.a. n.a. n.a. n.a. n.a. 450
420 6
2 260 82 36 21 14 10 390 7

Runtime [Minutes]
360 8
3 425 136 60 36 25 18 330
10
300
4 602 193 87 53 37 27 270 12
240 14
5 788 253 114 70 49 37 210 16
180 18
6 982 316 143 88 62 47 150
20
120
7 1182 381 173 107 75 57 22
90
8 1388 448 204 126 89 68 60 24
30 26
9 1600 517 235 146 103 79 0
0 2 4 6 8 10 12 14 16
10 1816 587 268 166 118 90 Load [kVA], PF 0.8

11 2036 659 300 187 132 101


12 2261 731 334 208 147 113
13 2489 806 368 229 163 124
14 2721 881 403 251 178 136
15 2956 957 438 273 194 148
16 3194 1035 473 295 210 161
17 3435 1113 509 317 226 173
18 3680 1192 546 340 242 185
19 3926 1272 582 363 259 198
20 4176 1353 620 387 275 211
21 4428 1435 657 410 292 224
22 4682 1518 695 434 309 237
23 4939 1601 733 458 326 250
24 5198 1685 772 482 343 263
25 5459 1770 811 506 361 277
26 5723 1856 850 531 378 290

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 13


20 kVA 400 V typical performances

Load kVA
600
570 2
# of
battery 2 4 8 12 16 20 540 3
shelves 510 4
480
5
1 n.a. n.a. n.a. n.a. n.a. n.a. 450
420 6
2 129 59 25 14 9 6 390 7

Runtime [Minutes]
360 8
3 212 98 42 25 17 12 330
10
300
4 300 139 61 37 25 18 270 12
240 14
5 394 183 81 49 34 25 210 16
180 18
6 491 229 102 62 43 32 150
20
120
7 591 276 123 75 53 40 22
90
8 695 325 145 89 63 47 60 24
30 26
9 801 375 168 103 73 55 0
0 4 8 12 16 20
10 909 426 191 118 83 63 Load [kVA], PF 0.8
11 1020 478 215 132 93 71
12 1132 531 239 147 104 79
13 1247 585 263 163 115 87
14 1363 639 288 178 126 96
15 1481 695 313 194 137 105
16 1601 751 339 210 149 113
17 1722 808 364 226 160 122
18 1844 866 391 242 172 131
19 1968 924 417 259 183 140
20 2093 983 444 275 195 149
21 2220 1043 471 292 207 158
22 2347 1103 498 309 219 168
23 2476 1163 525 326 232 177
24 2606 1224 553 343 244 187
25 2737 1286 581 361 256 196
26 2869 1348 609 378 269 206

14 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


30 kVA 400 V typical performances

Load kVA
600
570 3
# of
battery 2 6 12 18 24 30 540 4
shelves 510 5
480
6
1 n.a. n.a. n.a. n.a. n.a. n.a. 450
420 7
2 n.a. n.a. n.a. n.a. n.a. n.a. 390 8

Runtime [Minutes]
360 10
3 195 58 25 14 9 6 330
12
300
4 276 84 36 21 14 10 270
14
240 16
5 362 111 48 29 19 14 210 18
180 20
6 452 139 61 37 25 18
150
22
7 544 168 74 45 31 23 120
90 24
8 639 198 88 53 37 28 60 26
30 28
9 737 228 102 62 43 32 0
0 5 10 15 20 25 30
10 837 259 116 71 50 37
Load [kVA], PF 0.8
11 939 291 130 80 56 42
12 1043 324 145 89 63 47
13 1148 357 160 98 69 52
14 1255 390 175 108 76 58
15 1364 424 191 118 83 63
16 1474 459 206 127 90 68
17 1585 494 222 137 97 74
18 1698 529 238 147 104 79
19 1812 565 255 157 111 85
20 1928 601 271 168 118 90
21 2044 637 287 178 126 96
22 2162 674 304 188 133 102
23 2280 711 321 199 141 107
24 2400 749 338 209 148 113
25 2521 786 355 220 156 119
26 2642 824 372 231 164 125
27 2765 863 390 242 171 131
28 2888 901 407 253 179 137

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 15


40 kVA 400 V typical performances

Load kVA
600
# of 570
4
battery 4 8 16 24 32 40 540
510 5
shelves
480 6
1 n.a. n.a. n.a. n.a. n.a. n.a. 450 7
420 8
2 n.a. n.a. n.a. n.a. n.a. n.a. 390

Runtime [Minutes]
10
360
3 n.a. n.a. n.a. n.a. n.a. n.a. 330 12
300 14
4 133 60 25 14 9 6 270 16
240
5 175 79 34 19 13 9 18
210
180 20
6 219 99 43 25 17 12 150 22
120 24
7 264 120 52 31 21 15
90 26
8 311 142 62 37 25 19 60
28
30
9 358 164 72 43 30 22 0
0 8 16 24 32 40
10 407 187 82 50 34 25 Load [kVA], PF 0.8
11 457 210 92 56 39 29
12 508 233 103 63 43 33
13 559 257 114 69 48 36
14 611 281 124 76 53 40
15 664 306 135 83 58 44
16 718 331 147 90 63 47
17 773 356 158 97 68 51
18 828 382 170 104 73 55
19 884 407 181 111 78 59
20 940 433 193 118 83 63
21 997 460 205 126 89 67
22 1054 486 217 133 94 71
23 1112 513 229 141 99 75
24 1171 540 241 148 105 79
25 1230 568 253 156 110 84
26 1289 595 266 164 115 88
27 1349 623 278 171 121 92
28 1409 651 291 179 127 96

16 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Battery Run-Times - Non-Modular Batteries
• The below battery run-times are based on high quality batteries from approved manufacturers
• The run-times are based on high rate batteries designed for UPS systems
• The run-times are intended as a guide only, and APC disclaim the responsibility for these run-
times

10 kVA

Battery Ah Load %
120
Approx. 110
20 hr rate equivalent
40 50 60 70 80 90 100 100
Ah 10 hr rate
Ah 90
7.2 6.7 24 18 14 11 9 7 6 80 2x16x12V/7.2(6.7)Ah

Runtime [Minutes]
2x16x12V/11(10)Ah
11 10 42 32 25 20 17 14 12 70
2x16x12V/15(14)Ah
60 2x16x12V/20(19)Ah
15 14 63 48 38 31 26 22 19
50 2x16x12V/24(22)Ah
20 19 90 69 55 46 39 33 29 2x16x12V/30(28)Ah
40 2x16x12V/38(35)Ah
24 22 113 87 70 58 49 42 37
30
30 28 149 115 92 77 65 56 49 20

38 35 199 154 124 103 88 76 67 10

0
40 60 80 100
Load %

15 kVA

Battery Ah Load % 120

Approx. 110
20 hr rate equivalent 40 50 60 70 80 90 100
Ah 10 hr rate 100
Ah 90

11 10 25 19 14 11 9 7 6 80 2x16x12V/11(10)Ah
Runtime [Minutes]

2x16x12V/15(14)Ah
15 14 38 29 22 18 15 13 11 70
2x16x12V/20(19)Ah
60 2x16x12V/24(22)Ah
20 19 55 42 33 27 23 19 17
2x16x12V/30(28)Ah
50
24 22 70 53 42 35 29 25 21 2x16x12V/38(35)Ah
40 2x16x12V/50(47)Ah
30 28 92 70 56 46 39 34 29 30

38 35 124 95 76 63 53 46 40 20

50 47 174 133 107 89 75 65 57 10

0
40 60 80 100
Load %

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 17


20 kVA

Battery Ah Load % 120


Approx. 110
20 hr rate equivalent 40 50 60 70 80 90 100
Ah 10 hr rate 100
Ah 90

15 14 26 19 15 12 10 8 7 80 2x16x12V/15(14)Ah

Runtime [Minutes]
2x16x12V/20(19)Ah
20 19 39 29 23 18 15 13 11 70
2x16x12V/24(22)Ah
60 2x16x12V/30(28)Ah
24 22 49 37 29 24 20 17 14
2x16x12V/38(35)Ah
50
30 28 65 49 39 32 27 23 20 2x16x12V/50(47)Ah
40 2x16x12V/65(60)Ah
38 35 88 67 53 44 37 31 27 30

50 47 123 94 75 62 52 45 39 20

65 60 170 130 104 86 73 63 55 10

0
40 60 80 100
Load %

30 kVA

Battery Ah Load % 120

Approx. 110
20 hr rate equivalent 40 50 60 70 80 90 100
Ah 10 hr rate 100
Ah 90

24 22 29 21 17 13 11 9 7 80 2x16x12V/24(22)Ah
Runtime [Minutes]

2x16x12V/30(28)Ah
70
30 28 39 29 23 18 15 13 11 2x16x12V/38(35)Ah
60 2x16x12V/50(47)Ah
38 35 53 40 31 26 21 18 15 2x16x12V/65(60)Ah
50
2x16x12V/80(74)Ah
50 47 75 57 45 37 31 27 23 40 2x16x12V/100(93)Ah
65 60 104 79 63 52 44 38 33 30

20
80 74 135 103 82 68 57 49 43
10
100 93 178 136 109 90 76 66 57
0
40 60 80 100
Load %

40 kVA

Battery Ah Load % 120

Approx. 110
20 hr rate equivalent
40 50 60 70 80 90 100 100
Ah 10 hr rate
Ah 90

30 28 27 20 15 12 10 8 7 80 2x16x12V/30(28)Ah
Runtime [Minutes]

2x16x12V/38(35)Ah
70
38 35 37 27 21 17 14 12 10 2x16x12V/50(47)Ah
60 2x16x12V/65(60)Ah
50 47 52 39 31 25 21 18 15 2x16x12V/80(74)Ah
50
2x16x12V/100(93)Ah
65 60 73 55 44 36 30 26 22 40 2x16x12V/120(112)Ah
80 74 95 72 57 47 40 34 30 30

20
100 93 125 95 76 63 53 46 40
10
120 112 157 120 96 79 67 58 50
0
40 60 80 100
Load %

18 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Battery Discharge Current
380 V, 400 V, and 415 V

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


I bat @ Vbat nominal, 100% load 22 33 44 66 88
I bat @ Vbat min, 100% load 28 41 55 83 110
I bat @ Vbat min, 150% load 40 62 83 125 166

End of Discharge Voltage


Volts per Cell

1.75 End-of-Discharge Voltage

1.70

1.65

1.60
Discharge CA-rate

0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 19


AC Bypass
Specifications
380 V, 400 V, and 415 V

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
Connection type 5-wire (3PH + N + PE)
Input frequency (Hz) 40-70
Nom input current (A) 15.2 14.4 13.9 22.8 21.7 20.9 30.4 28.9 27.8 45.6 43.3 41.7 60.8 57.7 55.6

380 V, 400 V, and 415 V 3:1

15 kVA 20 kVA 30 kVA 40 kVA


220 V 230 V 240 V 220 V 230 V 240 V 220 V 230 V 240 V 220 V 230 V 240 V
Connection type 3-wire (1PH + N + PE)
Input frequency (Hz) 40-70
Nom input current (A) 68.4 65.0 62.6 91.2 86.6 83.5 136.7 129.9 125.2 182.3 173.2 166.9

20 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Physical
Dimensions
Enclosure net dimensions mm (in)
Height 1499 (59)
Depth
- exclusive of the conduit box 838 (33)
- inclusive of the conduit box 925 (36)
Width
- narrow 356 (14)
- wide 523 (21)

Weights
380 V, 400 V, and 415 V

380/400/415 V kg 380/400/415 V kg
G35T10KH1B2S 245 G35T10KH2B2S 336
G35T10KH1B4S 382 G35T10KH2B4S 474
G35T10KH3B4S 566 G35T10KH4B4S 657
G35T15KH2B2S 433 G35T15KH2B4S 474
G35T15KH3B4S 566 G35T15KH4B4S 657
G35T20KH2B2S 433 G35T20KH2B4S 474
G35T20KH3B4S 566 G35T20KH4B4S 657
G35T30KH3B4S 601 G35T30KH4B4S 692
G35T40KH4B4S 692

380 V, 400 V, and 415 V 3:1

220/230/240 V kg lbs 220/230/240 V kg lbs


G35T15K3I2B2S 428 944 G35T15K3I2B4S 505 1113
G35T15K3I3B4S 566 1248 G35T15K3I4B4S 686 1512
G35T20K3I2B2S 428 944 G35T20K3I2B4S 505 1113
G35T20K3I3B4S 566 1248 G35T20K3I4B4S 686 1512
G35T30K3I3B4S 566 1248 G35T30K3I4B4S 686 1512
G35T40K3I4B4S 686 1512

XR battery enclosure weights

Part Nos. kg lbs Part Nos. kg lbs


G35TXR2B6 418 922 G35TXR6B6* 807 1779
G35TBXR2B6 418 922 G35TBXR6B6* 807 1779

* The total weight of the XR battery enclosure including the separate battery package.

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 21


Cables
Recommended Cable Sizes
Note: Refer to IEC 60364-5-52 for installation methods. The recommended cable sizes are for
installation method B2 and based on an environment with an ambient temperature of 30° C.

Note: Temperature ratings of conductors: 70°C. Use only copper conductors and PVC isolated
cables.

380 V, 400 V, and 415 V

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


Utility/mains input 2.5 mm2 6 mm2 10 mm2 16 mm2 25 mm2
Static bypass input 2.5 mm2 6 mm2 10 mm2 16 mm2 25 mm2
DC input 50 mm2 50 mm2 50 mm2 50 mm2 50 mm2
Output 2.5 mm2 6 mm2 10 mm2 16 mm2 25 mm2

380 V, 400 V, and 415 V 3:1

15 kVA 20 kVA 30 kVA 40 kVA


2 2 2
Utility/mains input 6 mm 10 mm 16 mm 25 mm2
Static bypass input 25 mm2 35 mm2 70 mm2 95 mm2
DC input 50 mm2 50 mm2 50 mm2 50 mm2
2 2 2
Output 25 mm 35 mm 70 mm 95 mm2

Torque Specifications
The power wiring should be torqued to 7 Nm.

22 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Fuses and Breakers
Single utility/mains system

Q1: Utility input Q3: Manual Bypass


Q2: UPS output MBS: Mechanical bypass switch

Dual utility/mains system

Q1: UPS input Q5: Static bypass input


Q2: UPS output
Q3: Manual bypass MBS: Mechanical bypass switch

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 23


Parallel System
Q3

Q5B Q4

Q1B Q2B
UPS B

XR Battery
Enclosure
(optional)

Q5A

Q1A Q2A
UPS A

XR Battery
Enclosure
(optional)

Q1: Utility input Q4: System output


Q2: UPS output Q5: Static bypass input
Q3: Manual bypass

Fuse and Breaker Sizes


380 V, 400 V, and 415 V

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


Mains input Q1 (A)1 16 25 35 50 63
Bypass input Q5 (A) 16 25 35 50 63
Output Q2 (A) 16 25 35 50 63
1 Required upstream current protection: gL type fuse.

380 V, 400 V, and 415 V 3:1

15 kVA 20 kVA 30 kVA 40 kVA


1
Mains input Q1 (A) 25 35 50 63
1
Bypass input Q5 (A) 75 100 150 200
Output Q2 (A) 75 100 150 200
1 Required upstream current protection: gL type fuse

24 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


380 V, 400 V, and 415 V Parallel system with up to three UPS units

Note: It is not possible to run the 3:1 version in parallel.

Q3 and Q4 in capacity systems.

Units in parallel 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


2 35 A 50 A 63 A 100 A 125 A
3 50 A 80 A 100 A 160 A 200 A
4 63 A 100 A 200 A 200 A 250 A

Q3 and Q4 in redundant systems (n+1).

Units in parallel 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


2 16 A 25 A 35 A 50 A 63 A
3 35 A 50 A 63 A 100 A 125 A
4 50 A 80 A 100 A 160 A 200 A

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 25


Minimum Breaker Settings
380 V, 400 V, and 415 V

150% overload 125% overload


800% overload
normal/battery normal/battery Continuously
bypass operation
operation operation

Duration 500 ms 60 s 10 min. ∞

Mains input -1 - - 16.4 A


10 kVA Bypass input 121.5 A - - 16.7 A
Output 121.5 A 22.8 A 19 A 16.7 A
Mains input -1 - - 24.6 A
15 kVA Bypass input 182 A - - 25.1 A
Output 182 A 34.2 A 25.4 A 25.1 A
Mains input -1 - - 32.5 A
20 kVA Bypass input 244 A - - 33.4 A
Output 244 A 45.6 A 38 A 33.4 A
Mains input -1 - - 49.1 A
30 kVA Bypass input 364 A - - 50.1 A
Output 364 A 68.4 A 57 A 50.1 A
Mains input -1 - - 65.6 A
40 kVA Bypass input 487 A - - 66.9 A
Output 487 A 91.2 A 76 A 66.9 A

Note:1 For single mains systems, use the higher value of mains and bypass.

380 V, 400 V, and 415 V 3:1

150% overload 125% overload


800% overload
normal/battery normal/battery Continuously
bypass operation
operation operation

Duration 500 ms 60 s 10 min. ∞

Mains input - - - 24.6 A


15 kVA Bypass input 547 A - - 75 A
Output 547 A 103 A 86 A 75 A
Mains input - - - 32.5 A
20 kVA Bypass input 730 A - - 100 A
Output 730 A 137 A 114 A 100 A
Mains input - - - 49.1 A
30 kVA Bypass input 1094 A - - 150 A
Output 1094 A 205 A 171 A 150 A
Mains input - - - 65.6 A
40 kVA Bypass input 1459 A - - 200 A
Output 1459 A 274 A 228 A 200 A

26 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Communication and Management
Network Management Card
The system is equipped with one network management card for remote monitoring and control of an
individual UPS by connecting it directly to the network.

Network Management Card

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 27


Input and Output Contacts
Pin connections J106 (UPS)
Pins 7 and 8 are for external charge control. When 7 and 8 are
closed, the UPS charges batteries with a pre-defined
J106
Charging control percentage (0-25-50-75-100%) of the maximum charging
switch power. To be used in generator applications, or if special
codes require control of charging.
When Q3 is closed, signals are fed back to the UPS
Q3 switch controller.

Pins 5 and 6 are for external maintenance bypass Q3


J200 (XR (auxiliary switch N/C type).
Batteries) When Q3 is closed, signals are fed back to the UPS controller
(see Q3 drawing).

Pins 1 to 4 are for battery measurement (only applicable to


MGE Galaxy 3500 XR Battery Enclosures - see J200 drawing).

Pin connections J106 (UPS)


8) Exernal charging control return
7) External control of charging
6) Q3 active return
5) Q3 active
4) Battery measurement supply*
3) Battery unit quantity*
2) Max. battery temperature*
1) Battery measurement return*
* Should be used with MGE Galaxy 3500 XR Enclosures

28 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


EPO
Pin connections J108
J108 1: Dry Contacts Normally Open
EPO is activated when pin 1 is connected
to pins 3 and 5.
EPO circuit Connections: 2-4-6,
3-5 and 1 ( )

J108 2: +24 V Normally Open


+24 V
EPO is activated when an isolated SELV 24
EPO circuit VDC voltage is supplied on pin 1 with
0V reference to pin 2.
Connections: 3-5 and 4-6.

J108 3: Dry Contacts Normally Closed


EPO is activated when a connection from
pin 3 to pin 5 is opened.
Connections: 4-6.

EPO circuit

J108 4: +24 V Normally Closed


EPO is activated when a SELV 24 VDC
+24 V voltage is removed from pin 3 with
reference to pin 4.
EPO circuit
0V

Pin connections J108


1) Normally open EPO
2) Normally open EPO return
3) Normally closed EPO
4) Normally closed EPO return
5) +24 V SELV supply
6) SELV ground

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 29


Compliance
Regulatory Approvals
89/336/EDC
Directives for CE marking
73/237/EEC
EN/IEC62040-1-1
Safety
UL1778
EN50091-2/IEC62040-2
EMC
FCC15A
Performance EN/IEC62040-3
EN/IEC 61000-4-2 level 3, performance criteria A
Electromagnetic compatibility (EMC) EN/IEC 61000-4-3 level 2, performance criteria A
EN/IEC 61000-4-4 level 2, performance criteria A
EN/IEC 61000-4-5 level 3, performance criteria A

30 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Options
Parallel MBP - wall-mount
• For a line-up-and-match solution with up to three UPS units in parallel
• Two versions for 10-20 kVA and 30-40 kVA UPS units
• Two ratings: 60 kVA and 120 kVA
• Top or bottom cable entry
• Including three communication boards
• With lamps for status indication

Empty Cabinet for batteries - floor-mount


• For a line-up-and-match solution for 3rd party batteries
• Up to eight trays for 32 customer-supplied batteries (16 on + bus and 16 and - bus). Maximum
size of battery 197 x 165 x 175 mm.
• Including battery breaker
• Top or bottom cable entry

Empty Cabinet for Transformer - floor-mount


• For a line-up-and-match solution for 3rd party transformers
• Including mounting rails for transformer
• Top or bottom cable entry

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 31


Parallel Capabilities
Up to four UPS units can be connected in parallel via the Parallel Communication Kit.

Parallel Communication Box

Communication cables
Schematic of the PBus cables layout
UPS 1
TERMINATORS UPS 2 UPS 3 UPS 4
PBus1 PBus2 PBus1 PBus2 PBus1 PBus2
1A 2A 1A 2A 1A 2A 1A 2A

1B 2B 1B 2B 1B 2B 1B 2B

PBus1 PBus2 TERMINATORS

Note: If the configuration consists of only two UPSs, the terminators must be installed in
UPS 2. With three UPSs the terminators must be installed in UPS 3.

System arrangements

Examples with two parallel systems using interconnection plates/baying kits

UPS XR XR XR XR UPS XR XR XR XR UPS XR XR XR XR UPS XR XR XR XR

XR XR XR XR UPS UPS XR XR XR XR UPS UPS UPS UPS

Note: UPS units and their respective XR Battery Enclosure can be bayed together. XR
Battery Enclosures must never be shared in a parallel UPS system.

32 MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference


Overview of Power Connections
The below diagrams shows a parallel system with three UPS units and XR Battery Enclosures.

MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference 33


APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer
support requests.
– www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer support
information.
– www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
• Contact the APC Customer Support Center by telephone or e-mail.
– Local, country-specific centers: go to www.apc.com/support/contact for contact information.

For information on how to obtain local customer support, contact the APC representative or other distributors
from whom you purchased your APC product.

Entire contents copyright 2009 American Power Conversion Corporation. All rights reserved. Reproduction
in whole or in part without permission is prohibited. APC and the APC logo are trademarks of American
Power Conversion Corporation. All other trademarks, product names, and corporate names are the property
of their respective owners and are used for informational purposes only.

990-3661-001 10/2009
*990-3661-001*

You might also like