The document contains calculations for pressurizing three staircases (Staircase 01, 02, 03) located in Blocks A and B. It calculates the fan capacity required to maintain a pressure differential of 10Pa with 1m/s air velocity through two open doors on each staircase landing.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
50 views3 pages
Staircase Pressurization Calculation Meppers
The document contains calculations for pressurizing three staircases (Staircase 01, 02, 03) located in Blocks A and B. It calculates the fan capacity required to maintain a pressure differential of 10Pa with 1m/s air velocity through two open doors on each staircase landing.
Project No.: Calculation Sheet No.: Rev. 1 Calculated By: Date: Check By: Date: Pressure Difference 17/12/2020 10 Pa STAIRCASE PRESSURIZATION Velocity through an open door Staircase Reference Staircase 01 1 m/s Pressurization Fan Reference SPF-01 Number of open doors Location Block A 2 1. Pressurization as per NFPA Relief Pressure Number of Landings 2. No pressurised lobbies associated with staircase landings 7 3. Fan closed by motorized smoke damper. 4. (1m/s) through open doors at one successive floor and the discharge floor. The stair pressure differential maintained at 10Pa. Type of Stair Shaft Floors served Number of Landing 7 Pressurization Air Volume Air Leakage Through Landing Doors Landing Door width (m) 1.00 Landing Door height (m) 2.10 Open door area (m2) 2.10 Crack Length (m) 8.90 Quantity of Landing Doors (Nos.) 7 Leakage area(m2) per single leaf door 0.02 Total Leakage Area (m2) Total Leakage Area (m2) 0.14 Calculated supply air volume to achieve pressurization to 10 Pa Formula QE=0.827XAExPE1/2 Leakage Rate (m3/s) 0.37 10 Pa min pressure ventilation rate at 2 open door (m3/s) 10.98 (1m/s) air velocity through the opened door (2 doors open) 4.20 Total airflow for staircase pressurization (m3/s) 11.35 Area of Pressure Relief (m²) 13.23
Calculated Fan Capacity = 40860 m3/h
Selected Fan Capacity = 41000 m3/h Project: HIEX AVLABARI Calculation Title: Staircase Pressurization Reference Project No.: Calculation Sheet No.: Rev. 1 Calculated By: Date: Check By: Date: Pressure Difference 17/12/2020 10 Pa STAIRCASE PRESSURIZATION Velocity through an open door Staircase Reference Staircase 02 1 m/s Pressurization Fan Reference SPF-02 Number of open doors Location Block B 2 1. Pressurization as per NFPA Relief Pressure Number of Landings 2. No pressurised lobbies associated with staircase landings 6 3. Fan closed by motorized smoke damper. 4. (1m/s) through open doors at one successive floor and the discharge floor. The stair pressure differential maintained at 10Pa. Type of Stair Shaft Floors served Number of Landing 6 Pressurization Air Volume Air Leakage Through Landing Doors Landing Door width (m) 1.00 Landing Door height (m) 2.10 Open door area (m2) 2.10 Crack Length (m) 6.60 Quantity of Landing Doors (Nos.) 6 Leakage area(m2) per single leaf door 0.02 Total Leakage Area (m2) Total Leakage Area (m2) 0.12 Calculated supply air volume to achieve pressurization to 10 Pa Formula QE=0.827XAExPE1/2 Leakage Rate (m3/s) 0.31 10 Pa min pressure ventilation rate at 2 open door (m3/s) 10.98 (1m/s) air velocity through the opened door (2 doors open) 4.20 Total airflow for staircase pressurization (m3/s) 11.30 Area of Pressure Relief (m²) 13.23
Calculated Fan Capacity = 40672 m3/h
Selected Fan Capacity = 41000 m3/h Project: HIEX AVLABARI Calculation Title: Staircase Pressurization Reference Project No.: Calculation Sheet No.: Rev. 1 Calculated By: Date: Check By: Date: Pressure Difference 17/12/2020 10 Pa STAIRCASE PRESSURIZATION Velocity through an open door Staircase Reference Staircase 03 1 m/s Pressurization Fan Reference SPF-03 Number of open doors Location Block B 2 1. Pressurization as per NFPA Relief Pressure Number of Landings 2. No pressurised lobbies associated with staircase landings 7 3. Fan closed by motorized smoke damper. 4. (1m/s) through open doors at one successive floor and the discharge floor. The stair pressure differential maintained at 10Pa. Type of Stair Shaft Floors served Number of Landing 7 Pressurization Air Volume Air Leakage Through Landing Doors Landing Door width (m) 1.00 Landing Door height (m) 2.10 Open door area (m2) 2.10 Crack Length (m) 7.40 Quantity of Landing Doors (Nos.) 7 Leakage area(m2) per double leaf door 0.02 Total Leakage Area (m2) Total Leakage Area (m2) 0.14 Calculated supply air volume to achieve pressurization to 10 Pa Formula QE=0.827XAExPE1/2 Leakage Rate (m3/s) 0.37 10 Pa min pressure ventilation rate at 2 open door (m3/s) 10.98 (1m/s) air velocity through the opened door (2 doors open) 4.20 Total airflow for staircase pressurization (m3/s) 11.35 Area of Pressure Relief (m²) 13.23