Telegrams Manual Draft3 Sharp
Telegrams Manual Draft3 Sharp
Table of contents
1 Overview ............................................................................................................. 6
1.1 Scope ................................................................................................... 6
1.2 What is a Telegram? ............................................................................ 6
1.3 How to Interpret This Document .......................................................... 7
2 Application Class and Telegram Support ....................................................... 8
2.1 Telegram Application Class.................................................................. 8
2.1.1 Siemens Supported Application Classes ............................................. 8
2.1.2 Telegram Supported Application Classes ............................................ 9
2.2 Drive supported telegrams ................................................................. 10
3 Telegram Contents .......................................................................................... 11
3.1 Telegram 1 for Basic Speed Setpoint (16-bit) .................................... 11
3.1.1 Description ......................................................................................... 11
3.1.2 Telegram 1 Structure .......................................................................... 11
3.1.3 Telegram 1 Input Words ..................................................................... 12
3.1.4 Telegram 1 Output Words .................................................................. 13
3.1.5 Telegram 1 Associated Parameters ................................................... 14
3.2 Telegram 2 for Basic Speed Setpoint (32-bit) .................................... 21
© Siemens AG copyright year All rights reserved
3.19 Telegram 393 for Control Unit, Digital I/O 24/9, 8 Measuring Probes,
and Analog Input .............................................................................. 296
3.19.1 Description ....................................................................................... 296
3.19.2 Telegram 393 Structure .................................................................... 296
3.19.3 Telegram 393 Input Words ............................................................... 297
3.19.4 Telegram 393 Output Words ............................................................ 301
3.19.5 Telegram 393 Associated Parameters ............................................. 308
3.20 Telegram 394 for Control Unit and Digital I/O 24/9 .......................... 319
3.20.1 Description ....................................................................................... 319
3.20.2 Telegram 394 Structure .................................................................... 319
3.20.3 Telegram 394 Input Words ............................................................... 320
3.20.4 Telegram 394 Output Words ............................................................ 323
3.20.5 Telegram 394 Associated Parameters ............................................. 326
3.21 Telegram 395 for Control Unit, Digital I/O 24/9, and 16 Measuring
Probes .............................................................................................. 333
3.21.1 Description ....................................................................................... 333
3.21.2 Telegram 395 Structure .................................................................... 333
3.21.3 Telegram 395 Input Words ............................................................... 335
3.21.4 Telegram 395 Output Words ............................................................ 339
3.21.5 Telegram 395 Associated Parameters ............................................. 345
3.22 Supplementary Telegram 700 for Safety Info Channel .................... 354
3.22.1 Description ....................................................................................... 354
3.22.2 Telegram 700 Structure .................................................................... 354
3.22.3 Telegram 700 Output Words ............................................................ 355
3.22.4 Telegram 700 Associated Parameters ............................................. 356
3.23 Telegram 999 for Free Interconnection ............................................ 360
3.23.1 Description ....................................................................................... 360
3.23.2 Telegram 999 Structure .................................................................... 360
3.23.3 Extending an Existing Telegram using Telegram 999 ..................... 361
3.23.4 Telegram 999 Associated Parameters ............................................. 362
4 Additional Resources .................................................................................... 367
1 Overview
1.1 Scope
This document contains telegram compatibility information, individual telegram
structure, and process word structure for a series of drives and telegrams. Each
telegram section contains a short description, tables for the process word structure
and content of each process word, and an information list for parameters
associated with the contents of each process word.
This document does not contain telegram information about telegrams that are not
easily accessible for standard applications, such as Telegram 166 for hydraulic
drives. A guide for the electronic data sheet (EDS) files used within some supplier’s
programming platforms to configure telegrams is not within the scope of this
manual.
As of the listed date and firmware revisions listed below, the information in this
document is accurate.
Telegrams are universal blocks of data that organize parameters and functions into
a uniform consistent format that all Siemens drives can use to pass data to the
PLC. They are organized into 16-bit process words (abbreviated as PZD) that
contain relevant information such as control words, status words, and setpoints.
Most telegrams have a control word, status word, speed setpoint, and speed
feedback word in common.
The content of a process word may have subtle differences depending on what
telegram is used. For example, several bits of Control Word 1 have different
functions between telegrams 1 and 110. Therefore, it is best practice to learn the
content of a desired process word in the context of a specific telegram to be used.
© Siemens AG copyright year All rights reserved
The PROFIdrive profile supports six different applications classes; Siemens uses
the first four classes. The purpose of these four classes are briefly discussed in the
following diagram.
© Siemens AG copyright year All rights reserved
The telegrams discussed in this document may support one or more of the
Siemens-supported applications classes as discussed in the following table. Note
that Application Class 2 is omitted because no telegram in this document supports
it. No telegram in this document supports the Dynamic Servo Control (DSC)
capability as part of Application Class 4.
Notes:
Telegrams 370-395 are specific to Control Unit drive objects and are not applicable to
classes 1 through 4.
Supported Telegrams
Drive Model FRN1 1 2 3 4 7 9 20 110 111 350 352 353
G110M 4.7 X X X X X
G120C 4.7 X X X X X
G120X 1.0 X X X X X
DCM DO: DC_CTRL 1.4 X X X X X
DCM DO: CU_DC 1.4
G120 CU240E-2 4.7 X X X X X
G120 CU240E-2 PN 4.7 X X X X X
G120 CU240E-2 PN-F 4.7 X X X X X
G120 CU250S-2 4.7 X X X X X X X X X X X X
G120D CU240D-2 4.7 X X X X X
G120D CU250D-2 PN 4.7 X X X X
G120D CU250D-2 PN-F 4.7 X X X X
G130 2.6 X X X X X X
G150 2.6 X X X X X X
S120 CU310 PN 2.6 X X X X X X X X X X
© Siemens AG copyright year All rights reserved
Supported Telegrams
Drive Model FRN 354 370 371 390 391 392 393 394 395 396 700 999
G110M 4.7 X X
G120C 4.7 X X
G120X 1.0 X X
DCM DO: DC_CTRL 1.4 X
DCM DO: CU_DC 1.4 X X
G120 CU240E-2 4.7 X X
G120 CU240E-2 PN 4.7 X X
G120 CU240E-2 PN-F 4.7 X X X
G120 CU250S-2 4.7 X X X
G120D CU240D-2 4.7 X X
G120D CU250D-2 PN 4.7 X
G120D CU250D-2 PN-F 4.7 X X
G130 2.6 X X X X X X X
G150 2.6 X X X X X X X
S120 CU310 PN 2.6 X X X X X X X X X X
S120 CU310-2 PN 5.2 X X X X X X X X X X
S120 CU320-2 PN 5.2 X X X X X X X X X X
S150 CU320-2 PN 5.2 X X X X X X X X X X
3 Telegram Contents
3.1 Telegram 1 for Basic Speed Setpoint (16-bit)
3.1.1 Description
4 Enable Ramp Function Generator (RFG) 1 = RFG output enabled; 0 = RFG output set to 0 p1140[0]
5 Continue Ramp Function Generator 1 = RFG follows setpoint input; 0 = RFG freezes at current value p1141[0]
6 Setpoint Enable 1 = RFG setpoint input enabled; 0 = RFG input set to 0 p1142[0]
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
10 Master Control by PLC 1 = Control is by PLC; 0 = No control by PLC p0854[0]
11 Setpoint Inversion 1 = Invert setpoint; 0 = Do not invert setpoint p1113[0]
12 Reserved
13 Motorized Potentiometer (MOP) Raise 1 = Raise MOP setpoint; 0 = No action p1035[0]
14 Motorized Potentiometer Lower 1 = Lower MOP setpoint; 0 = No action p1036[0]
15 Reserved
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed values.
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Motor at Acceptable Speed 1 = Speed deviation within tolerance; 0 = Speed deviation outside tolerance r2197.7
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Speed Above Max Speed 1 = Speed greater than or equal to max speed; 0 = Speed less than max speed r2199.1
11 Torque Limit Reached 1 = Torque limit reached; 0 = Torque limit not reached r0052.11
12 Holding Brake Open 1 = Holding brake open; 0 = Holding brake closed r0899.12
13 No Motor Overtemperature Alarm 1 = No overtemperature alarm; 0 = Overtemperature alarm present r2135.14
14 Motor Rotation Direction 1 = Motor rotates clockwise; 0 = Motor rotates counterclockwise r2197.3
15 No Converter Thermal Overload 1 = No converter thermal overload alarm; 0 = Thermal overload alarm present r2135.15
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its factory
r2004
[FloatingPoint32] default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
This telegram is a standard Siemens telegram of four words in length. It will control
the state of the drive by selecting the appropriate bits in the control word and set
the running speed in the speed setpoint word (32-bit). Additionally, this telegram
contains a second control and status word.
5 Continue Ramp Function Generator 1 = RFG follows setpoint input; 0 = RFG freezes at current value p1141[0]
6 Setpoint Enable 1 = RFG setpoint input enabled; 0 = RFG input set to 0 p1142[0]
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
10 Master Control by PLC 1 = Control is by PLC; 0 = No control by PLC p0854[0]
11 Setpoint Inversion 1 = Invert setpoint; 0 = Do not invert setpoint p1113[0]
12 Reserved
13 Motorized Potentiometer (MOP) Raise 1 = Raise MOP setpoint; 0 = No action p1035[0]
14 Motorized Potentiometer Lower 1 = Lower MOP setpoint; 0 = No action p1036[0]
15 Reserved
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed values.
8 Traverse to Fixed Endstop 1 = Activate travel to fixed endstop function; 0 = Travel to fixed endstop inactive p1545[0]
9 Reserved
10 Reserved
11 Motor Changeover Feedback Signal When p0833.04 = 1, this bit must be set after motor changeover to enable pulse generation. p0828[0]
12 Master sign-of-life Bit 0 p2045 = r2050[3]
13 Master sign-of-life Bit 1 p2045 = r2050[3]
14 Master sign-of-life Bit 2 p2045 = r2050[3]
15 Master sign-of-life Bit 3 p2045 = r2050[3]
4 p0833.0 sets the configuration for the motor and encoder changeover. 1 = Changeover from the application; 0 = Changeover from the drive.
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Motor at Acceptable Speed 1 = Speed deviation within tolerance; 0 = Speed deviation outside tolerance r2197.7
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Speed Above Max Speed 1 = Speed greater than or equal to max speed; 0 = Speed less than max speed r2199.1
11 Torque Limit Reached 1 = Torque limit reached; 0 = Torque limit not reached r0052.11
12 Holding Brake Open 1 = Holding brake open; 0 = Holding brake closed r0899.12
13 No Motor Overtemperature Alarm 1 = No overtemperature alarm; 0 = Overtemperature alarm present r2135.14
14 Motor Rotation Direction 1 = Motor rotates clockwise; 0 = Motor rotates counterclockwise r2197.3
15 No Converter Thermal Overload 1 = No converter thermal overload alarm; 0 = Thermal overload alarm present r2135.15
8 Travel to Fixed Stop Status1 1 = Travel to fixed endstop function active; 0 = Travel to fixed endstop inactive r1406.8
9 Reserved
10 Pulse Status 1 = Pulses enabled; 0 = Pulses inhibited r0899.11
11 Motor Data Set Changeover Status 1 = Motor data set changeover active; 0 = Motor data set changeover inactive r0835.0
12 Slave sign-of-life Bit 0 implicit
13 Slave sign-of-life Bit 1 implicit
14 Slave sign-of-life Bit 2 implicit
15 Slave sign-of-life Bit 3 implicit
1 This bit is only available for the S120 and is not available for vector U/f control.
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
© Siemens AG copyright year All rights reserved
Parameters p0821[0], p0822[0], p0823[0], and p0824[0] function exactly as p0820[0] for their
respective Drive Data Set bits.
r0835.0...12 CO/BO: Data set changeover status word / Data set sw ZSW
© Siemens AG copyright year All rights reserved
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or
p2003
[FloatingPoint32] torque. Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its
r2004
[FloatingPoint32] factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
This telegram is a Siemens telegram of 9 words in length. It will control the state of
the drive by selecting the appropriate bits in the two control words and set the
running speed in the speed setpoint word. The control word, status word, and
position feedback of the encoder is also included.
7 Empty (G1_XIST1)
Notes:
5 Continue Ramp Function Generator 1 = RFG follows setpoint input; 0 = RFG freezes at current value p1141[0]
6 Setpoint Enable 1 = RFG setpoint input enabled; 0 = RFG input set to 0 p1142[0]
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
10 Master Control by PLC 1 = Control is by PLC; 0 = No control by PLC p0854[0]
11 Setpoint Inversion 1 = Invert setpoint; 0 = Do not invert setpoint p1113[0]
12 Reserved
13 Motorized Potentiometer (MOP) Raise 1 = Raise MOP setpoint; 0 = No action p1035[0]
14 Motorized Potentiometer Lower 1 = Lower MOP setpoint; 0 = No action p1036[0]
15 Reserved
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed values.
8 Traverse to Fixed Endstop 1 = Activate travel to fixed endstop function; 0 = Travel to fixed endstop inactive p1545[0]
9 Reserved
10 Reserved
11 Motor Changeover Feedback Signal When p0833.01 = 1, this bit must be set after motor changeover to enable pulse generation. p0828[0]
12 Master sign-of-life Bit 0 p2045 = r2050[3]
13 Master sign-of-life Bit 1 p2045 = r2050[3]
14 Master sign-of-life Bit 2 p2045 = r2050[3]
15 Master sign-of-life Bit 3 p2045 = r2050[3]
1 p0833.0 sets the configuration for the motor and encoder changeover. 1 = Changeover from the application; 0 = Changeover from the drive.
3 Request Function 4 negative start direction falling edge of reference cam 2 r2050[4]
4 Request Command Bit 0 1 = Activate the function requested using bits 0…3 r2050[4]
5 Request Command Bit 1 1 = Read the value requested using bits 0…3 r2050[4]
6 Request Command Bit 2 Reserved r2050[4]
7 Function Mode Selection 1 = Flying measurement function set; 0 = Reference cam search function set r2050[4]
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Request Absolute Value Cyclic 1 = Request for cyclic transfer of actual position value of encoder 1 r2050[4]
14 Request Parking Encoder 1 = Request to park the encoder r2050[4]
15 Request Acknowledge Encoder Fault 1 = Acknowledge encoder fault (on rising edge) r2050[4]
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Motor at Acceptable Speed 1 = Speed deviation within tolerance; 0 = Speed deviation outside tolerance r2197.7
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Speed Above Max Speed 1 = Speed greater than or equal to max speed; 0 = Speed less than max speed r2199.1
11 Torque Limit Reached 1 = Torque limit reached; 0 = Torque limit not reached r0052.11
12 Holding Brake Open 1 = Holding brake open; 0 = Holding brake closed r0899.12
13 No Motor Overtemperature Alarm 1 = No overtemperature alarm; 0 = Overtemperature alarm present r2135.14
14 Motor Rotation Direction 1 = Motor rotates clockwise; 0 = Motor rotates counterclockwise r2197.3
15 No Converter Thermal Overload 1 = No converter thermal overload alarm; 0 = Thermal overload alarm present r2135.15
8 Travel to Fixed Stop Status1 1 = Travel to fixed endstop function active; 0 = Travel to fixed endstop inactive r1406.8
9 Reserved
10 Pulse Status 1 = Pulses enabled; 0 = Pulses inhibited r0899.11
11 Motor Data Set Changeover Status 1 = Motor data set changeover active; 0 = Motor data set changeover inactive r0835.0
12 Slave sign-of-life Bit 0 implicit
13 Slave sign-of-life Bit 1 implicit
14 Slave sign-of-life Bit 2 implicit
15 Slave sign-of-life Bit 3 implicit
1 This bit is only available for the S120 and is not available for vector U/f control.
6 Status Value 3 1 = Actual position at ref. cam 2 1 = Flying referencing to rising edge of ref. cam 2 complete r2051[4]
7 Status Value 4 1 = Actual position at ref. cam 2 1 = Flying referencing to falling edge of ref. cam 2 complete r2051[4]
8 Measuring Probe 1 Deflection Status 1 = Measuring probe 1 deflected; 0 = Measuring probe 1 not deflected r2051[4]
9 Measuring Probe 2 Deflection Status 1 = Measuring probe 2 deflected; 0 = Measuring probe 2 not deflected r2051[4]
10 Encoder 1 Status 1 = Encoder 1 on; 0 = Encoder 1 off r2051[4]
11 Acknowledge 1 = Acknowledge encoder fault is active r2051[4]
12 Encoder 1 Status 1 = Encoder 1 on; 0 = Encoder 1 off r2051[4]
13 Cyclic Absolute Value Status 1 = Actual position displayed in r04831; 0 = No value displayed r2051[4]
14 Parking Status 1 = Encoder is parked; 0 = Encoder is not parked r2051[4]
15 Fault Status 1 = Encoder indicates its fault type in r0483; 0 = No fault r2051[4]
1 r0483[0] displays the encoder position value; r0483[1] displays the encoder fault number if a fault is present.
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
© Siemens AG copyright year All rights reserved
Parameters p0821[0], p0822[0], p0823[0], and p0824[0] function exactly as p0820[0] for their
respective Drive Data Set bits.
p0480[0...2] CI: Encoder control word Gn_STW signal source / Enc Gn_STW S_src
© Siemens AG copyright year All rights reserved
r0835.0...12 CO/BO: Data set changeover status word / Data set sw ZSW
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its factory
r2004
[FloatingPoint32] default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
Notes:
5 Continue Ramp Function Generator 1 = RFG follows setpoint input; 0 = RFG freezes at current value p1141[0]
6 Setpoint Enable 1 = RFG setpoint input enabled; 0 = RFG input set to 0 p1142[0]
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
10 Master Control by PLC 1 = Control is by PLC; 0 = No control by PLC p0854[0]
11 Setpoint Inversion 1 = Invert setpoint; 0 = Do not invert setpoint p1113[0]
12 Reserved
13 Motorized Potentiometer (MOP) Raise 1 = Raise MOP setpoint; 0 = No action p1035[0]
14 Motorized Potentiometer Lower 1 = Lower MOP setpoint; 0 = No action p1036[0]
15 Reserved
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed values.
8 Traverse to Fixed Endstop 1 = Activate travel to fixed endstop function; 0 = Travel to fixed endstop inactive p1545[0]
9 Reserved
10 Reserved
11 Motor Changeover Feedback Signal When p0833.01 = 1, this bit must be set after motor changeover to enable pulse generation. p0828[0]
12 Master sign-of-life Bit 0 p2045 = r2050[3]
13 Master sign-of-life Bit 1 p2045 = r2050[3]
14 Master sign-of-life Bit 2 p2045 = r2050[3]
15 Master sign-of-life Bit 3 p2045 = r2050[3]
1 p0833.0 sets the configuration for the motor and encoder changeover. 1 = Changeover from the application; 0 = Changeover from the drive.
3 Request Function 4 negative start direction falling edge of reference cam 2 r2050[4]
4 Request Command Bit 0 1 = Activate the function requested using bits 0…3 r2050[4]
5 Request Command Bit 1 1 = Read the value requested using bits 0…3 r2050[4]
6 Request Command Bit 2 Reserved r2050[4]
7 Function Mode Selection 1 = Flying measurement function set; 0 = Reference cam search function set r2050[4]
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Request Absolute Value Cyclic 1 = Request for cyclic transfer of actual position value of encoder 1 r2050[4]
14 Request Parking Encoder 1 = Request to park the encoder r2050[4]
15 Request Acknowledge Encoder Fault 1 = Acknowledge encoder fault (on rising edge) r2050[4]
3 Request Function 4 with negative start direction falling edge of reference cam 2 p2050[9]
4 Request Command Bit 0 1 = Activate the function requested using bits 0…3 p2050[9]
5 Request Command Bit 1 1 = Read the value requested using bits 0…3 p2050[9]
6 Request Command Bit 2 Reserved p2050[9]
1 = Flying measurement function set; 0 = Reference cam search function
7 Function Mode Selection set p2050[9]
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Request Absolute Value Cyclic 1 = Request for cyclic transfer of actual position value of encoder 1 p2050[9]
14 Request Parking Encoder 1 = Request to park the encoder p2050[9]
15 Request Acknowledge Encoder Fault 1 = Acknowledge encoder fault (on rising edge) p2050[9]
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Motor at Acceptable Speed 1 = Speed deviation within tolerance; 0 = Speed deviation outside tolerance r2197.7
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Speed Above Max Speed 1 = Speed greater than or equal to max speed; 0 = Speed less than max speed r2199.1
11 Torque Limit Reached 1 = Torque limit reached; 0 = Torque limit not reached r0052.11
12 Holding Brake Open 1 = Holding brake open; 0 = Holding brake closed r0899.12
13 No Motor Overtemperature Alarm 1 = No overtemperature alarm; 0 = Overtemperature alarm present r2135.14
14 Motor Rotation Direction 1 = Motor rotates clockwise; 0 = Motor rotates counterclockwise r2197.3
15 No Converter Thermal Overload 1 = No converter thermal overload alarm; 0 = Thermal overload alarm present r2135.15
8 Travel to Fixed Stop Status1 1 = Travel to fixed endstop function active; 0 = Travel to fixed endstop inactive r1406.8
9 Reserved
10 Pulse Status 1 = Pulses enabled; 0 = Pulses inhibited r0899.11
11 Motor Data Set Changeover Status 1 = Motor data set changeover active; 0 = Motor data set changeover inactive r0835.0
12 Slave sign-of-life Bit 0 implicit
13 Slave sign-of-life Bit 1 implicit
14 Slave sign-of-life Bit 2 implicit
15 Slave sign-of-life Bit 3 implicit
1 This bit is only available for the S120 and is not available for vector U/f control.
6 Status Value 3 1 = Actual position at ref. cam 2 1 = Flying referencing to rising edge of ref. cam 2 complete r2051[4]
7 Status Value 4 1 = Actual position at ref. cam 2 1 = Flying referencing to falling edge of ref. cam 2 complete r2051[4]
8 Measuring Probe 1 Deflection Status 1 = Measuring probe 1 deflected; 0 = Measuring probe 1 not deflected r2051[4]
9 Measuring Probe 2 Deflection Status 1 = Measuring probe 2 deflected; 0 = Measuring probe 2 not deflected r2051[4]
10 Encoder 1 Status 1 = Encoder 1 on; 0 = Encoder 1 off r2051[4]
11 Acknowledge 1 = Acknowledge encoder fault is active r2051[4]
12 Encoder 1 Status 1 = Encoder 1 on; 0 = Encoder 1 off r2051[4]
13 Cyclic Absolute Value Status 1 = Actual position displayed in r04831; 0 = No value displayed r2051[4]
14 Parking Status 1 = Encoder is parked; 0 = Encoder is not parked r2051[4]
15 Fault Status 1 = Encoder indicates its fault type in r0483; 0 = No fault r2051[4]
1 r0483[0] displays the encoder position value; r0483[1] displays the encoder fault number if a fault is present.
6 Status Value 3 1 = Actual position at ref. cam 2 1 = Flying referencing to rising edge of ref. cam 2 complete p2051[9]
7 Status Value 4 1 = Actual position at ref. cam 2 1 = Flying referencing to falling edge of ref. cam 2 complete p2051[9]
8 Measuring Probe 1 Deflection Status 1 = Measuring probe 1 deflected; 0 = Measuring probe 1 not deflected p2051[9]
9 Measuring Probe 2 Deflection Status 1 = Measuring probe 2 deflected; 0 = Measuring probe 2 not deflected p2051[9]
10 Encoder 1 Status 1 = Encoder 1 on; 0 = Encoder 1 off p2051[9]
11 Acknowledge 1 = Acknowledge encoder fault is active p2051[9]
12 Encoder 1 Status 1 = Encoder 1 on; 0 = Encoder 1 off p2051[9]
13 Cyclic Absolute Value Status 1 = Actual position displayed in r0483; 0 = No value displayed p2051[9]
14 Parking Status 1 = Encoder is parked; 0 = Encoder is not parked p2051[9]
15 Fault Status 1 = Encoder indicates its fault in r0483; 0 = No fault p2051[9]
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
© Siemens AG copyright year All rights reserved
Parameters p0821[0], p0822[0], p0823[0], and p0824[0] function exactly as p0820[0] for their
respective Drive Data Set bits.
p0480[0...2] CI: Encoder control word Gn_STW signal source / Enc Gn_STW S_src
© Siemens AG copyright year All rights reserved
r0835.0...12 CO/BO: Data set changeover status word / Data set sw ZSW
© Siemens AG copyright year All rights reserved
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its
r2004
[FloatingPoint32] factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
Notes:
To access this telegram, the “basic positioner” capability must be configured.
© Siemens AG copyright year All rights reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 EPOS Manual Data Input (MDI) Activation For direct setpoint entry. 1 = Activate MDI; 0 = Deactivate MDI p2647
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Following Error in Tolerance 1 = Following error within tolerance; 0 = Following error outside of tolerance r2684.8
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Target Position Reached 1 = Target position reached; 0 = Target position not reached r2684.10
11 Reference Point Set 1 = Reference point set; 0 = Reference point not set r2684.11
12 Acknowledgement Trav. Block Active 1 = On; 0 = Off r2684.12
1 = Absolute actual speed below threshold value 3 (p2161[0]); 0 = Speed above or greater
13 Speed Below Threshold 3 than threshold value 3 r2199.0
14 Reserved
15 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 EPOS Manual Data Input (MDI) Status 1 = MDI Active; 0 = MDI Inactive r2670.15
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
p2633 BI: EPOS external block change (0 -> 1) / Ext BlckChg (0->1)
p2625 BI: EPOS traversing block selection bit 0 / Trav_blk sel bit 0
Parameters p2626, p2627, p2628, p2629, p2630 function exactly as p2625 for their respective
© Siemens AG copyright year All rights reserved
r2670.0...15 CO/BO: EPOS status word active traversing block / ZSW act trav_block
© Siemens AG copyright year All rights reserved
8
MDI Acceleration Override (MDI_ACC)
9
10 MDI Mode (MDI_MOD)
Notes:
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 EPOS Manual Data Input (MDI) Activation For direct setpoint entry. 1 = Activate MDI; 0 = Deactivate MDI p2647
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
1 Positioning Method Selection Bit 0 00 or 11 = Absolute positioning through the shortest distance. p2651
10 = Absolute positioning in the positive direction.
2 Positioning Method Selection Bit 1 01 = Absolute positioning in the negative direction. p2652
3 Reserved
4 Reserved
5 Reserved
6 Reserved
© Siemens AG copyright year All rights reserved
7 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
3 Fault Active 1 = Converter fault. Acknowledge with Control Word 1, bit 7; 0 = No fault active r2139.3
4 Coast to Stop Off 1 = Coast down (OFF2) inactive; 0 = Coast down active r0899.4
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Following Error in Tolerance 1 = Following error within tolerance; 0 = Following error outside of tolerance r2684.8
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Target Position Reached 1 = Target position reached; 0 = Target position not reached r2684.10
11 Reference Point Set 1 = Reference point set; 0 = Reference point not set r2684.11
12 Acknowledgement Trav. Block Active 1 = On; 0 = Off r2684.12
1 = Absolute actual speed below threshold value 3 (p2161[0]); 0 = Speed above or greater
13 Speed Below Threshold 3 than threshold value 3 r2199.0
14 Reserved
15 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 EPOS Manual Data Input (MDI) Status 1 = MDI Active; 0 = MDI Inactive r2670.15
8 Travel to Fixed Stop Status 1 = Travel to fixed endstop function active; 0 = Travel to fixed endstop inactive r1406.8
9 Reserved
10 Pulse Status 1 = Pulses enabled; 0 = Pulses inhibited r0899.11
11 Motor Data Set Changeover Status 1 = Motor data set changeover active; 0 = Motor data set changeover inactive r0835.0
12 Slave sign-of-life Bit 0 implicit
13 Slave sign-of-life Bit 1 implicit
14 Slave sign-of-life Bit 2 implicit
15 Slave sign-of-life Bit 3 implicit
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
p2633 BI: EPOS external block change (0 -> 1) / Ext BlckChg (0->1)
p2625 BI: EPOS traversing block selection bit 0 / Trav_blk sel bit 0
Parameters p2626, p2627, p2628, p2629, p2630 function exactly as p2625 for their respective
© Siemens AG copyright year All rights reserved
p2642 CI: EPOS direct setpoint input/MDI position setpoint / MDI s_set
p2643 CI: EPOS direct setpoint input/MDI velocity setpoint / MDI v_set
p2644 CI: EPOS direct setpoint input/MDI acceleration override / MDI a_over
© Siemens AG copyright year All rights reserved
p2645 CI: EPOS direct setpoint input/MDI deceleration override / MDI -a_over
p2648 BI: EPOS direct setpoint input/MDI positioning type / MDI pos_type
p2651 BI: EPOS direct setpoint input/MDI direction selection, positive / MDI dir_sel pos
© Siemens AG copyright year All rights reserved
p2652 BI: EPOS direct setpoint input/MDI direction selection negative / MDI dir_sel neg
Note: p2652 has the same dependencies and note information as p2651.
r2670.0...15 CO/BO: EPOS status word active traversing block / ZSW act trav_block
© Siemens AG copyright year All rights reserved
r0835.0...12 CO/BO: Data set changeover status word / Data set sw ZSW
1 The default setting for this process word is MELD_NAMUR, a message word for the VIK-NAMUR
interface mode (a chemical industry specific application).
6 Setpoint Enable 1 = RFG setpoint input enabled; 0 = RFG input set to 0 p1142[0]
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
10 Master Control by PLC 1 = Control is by PLC; 0 = No control by PLC p0854[0]
11 Setpoint Inversion 1 = Invert setpoint; 0 = Do not invert setpoint p1113[0]
12 Reserved
13 Motorized Potentiometer (MOP) Raise 1 = Raise MOP setpoint; 0 = No action p1035[0]
14 Motorized Potentiometer Lower 1 = Lower MOP setpoint; 0 = No action p1036[0]
15 Reserved
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed, current, torque, and power values.
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Motor at Acceptable Speed 1 = Speed deviation within tolerance; 0 = Speed deviation outside tolerance r2197.7
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Speed Above Max Speed 1 = Speed greater than or equal to max speed; 0 = Speed less than max speed r2199.1
11 Torque Limit Reached 1 = Torque limit reached; 0 = Torque limit not reached r0052.11
12 Holding Brake Open 1 = Holding brake open; 0 = Holding brake closed r0899.12
13 No Motor Overtemperature Alarm 1 = No overtemperature alarm; 0 = Overtemperature alarm present r2135.14
14 Motor Rotation Direction 1 = Motor rotates clockwise; 0 = Motor rotates counterclockwise r2197.3
15 No Converter Thermal Overload 1 = No converter thermal overload alarm; 0 = Thermal overload alarm present r2135.15
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its
r2004
[FloatingPoint32] factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 EPOS Manual Data Input (MDI) Activation For direct setpoint entry. 1 = Activate MDI; 0 = Deactivate MDI p2647
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Master sign-of-life Bit 0
13 Master sign-of-life Bit 1
14 Master sign-of-life Bit 2
15 Master sign-of-life Bit 3
1 Positioning Method Selection Bit 0 00 or 11 = Absolute positioning through the shortest distance. p2651
10 = Absolute positioning in the positive direction.
2 Positioning Method Selection Bit 1 01 = Absolute positioning in the negative direction. p2652
3 Reserved
4 Reserved
5 Reserved
6 Reserved
© Siemens AG copyright year All rights reserved
7 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Following Error on Tolerance 1 = Following error within tolerance; 0 = Following error outside of tolerance r2684.8
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Target Position Reached 1 = Target position reached; 0 = Target position not reached r2684.10
11 Reference Point Set 1 = Reference point set; 0 = Reference point not set r2684.11
12 Acknowledgement Trav. Block Active 1 = On; 0 = Off r2684.12
Speed Below Threshold 3 1 = Absolute actual speed below threshold value 3 (p2161[0])
13 0 = Speed above or greater than threshold value 3 r2199.0
14 Reserved
15 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 EPOS Manual Data Input (MDI) Status 1 = MDI Active; 0 = MDI Inactive r2670.15
8 Cam Switching Position 1 Status 1 = Position less than or equal to cam switching position 1 r2683.8
9 Cam Switching Position 2 Status 1 = Position less than or equal to cam switching position 2 r2683.9
10 Direct Output 1 Via Traversing Block 1 = Yes; 0 = No r2683.10
11 Direct Output 2 Via Traversing Block 1 = Yes; 0 = No r2683.11
12 Fixed Stop Status 1 = Fixed stop reached; 0 = Fixed stop not reached r2683.12
13 Fixed Stop Clamping Torque Status 1 = Fixed stop clamping torque reached; 0 = Clamping torque not reached r2683.13
14 Travel to Fixed Stop Status 1 = Traveling to fixed stop active; 0 = Traveling to fixed stop inactive r2683.14
15 EPOS Status Word 1 Status 1 = On; 0 = Off r2683
8 Travel to Fixed Stop Status 1 = Travel to fixed endstop function active; 0 = Travel to fixed endstop inactive r1406.8
9 Reserved
10 Pulse Status 1 = Pulses enabled; 0 = Pulses inhibited r0899.11
11 Motor Data Set Changeover Status 1 = Motor data set changeover active; 0 = Motor data set changeover inactive r0835.0
12 Slave sign-of-life Bit 0 implicit
13 Slave sign-of-life Bit 1 implicit
14 Slave sign-of-life Bit 2 implicit
15 Slave sign-of-life Bit 3 implicit
8 Speed Within Setpoint Tolerance 1 = Speed within setpoint tolerance; 0 = Speed outside of setpoint tolerance r2199.4
9 Reserved
10 Reserved
11 Controller Enabled 1 = Controller enabled; 0 = Controller disabled r0899.8
12 Drive Ready Status 1 = Yes; 0 = No r0899.7
13 Pulses Enabled Status 1 = Yes; 0 = No r0899.11
14 2nd Variable Signaling Function Status 1 = On; 0 = Off r3294.1
15 3rd Variable Signaling Function Status 1 = On; 0 = Off r3294.2
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
p2633 BI: EPOS external block change (0 -> 1) / Ext BlckChg (0->1)
p2625 BI: EPOS traversing block selection bit 0 / Trav_blk sel bit 0
Parameters p2626, p2627, p2628, p2629, p2630 function exactly as p2625 for their respective
© Siemens AG copyright year All rights reserved
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
Parameter p0821[0] functions exactly as p0820[0] for its respective Drive Data Set bit.
p2642 CI: EPOS direct setpoint input/MDI position setpoint / MDI s_set
p2643 CI: EPOS direct setpoint input/MDI velocity setpoint / MDI v_set
p2644 CI: EPOS direct setpoint input/MDI acceleration override / MDI a_over
© Siemens AG copyright year All rights reserved
p2645 CI: EPOS direct setpoint input/MDI deceleration override / MDI -a_over
p2648 BI: EPOS direct setpoint input/MDI positioning type / MDI pos_type
p2651 BI: EPOS direct setpoint input/MDI direction selection, positive / MDI dir_sel pos
© Siemens AG copyright year All rights reserved
p2652 BI: EPOS direct setpoint input/MDI direction selection negative / MDI dir_sel neg
See above p2651 for the functionality of binary inputs p2651 and p2652.
r2670.0...15 CO/BO: EPOS status word active traversing block / ZSW act trav_block
r0835.0...12 CO/BO: Data set changeover status word / Data set sw ZSW
r3294.0...2 BO: Variable signaling function output signal / Var sig outp_sig
© Siemens AG copyright year All rights reserved
6
MDI Position (MDI_TARPOS) Actual Position Value A (XIST_A)
7
8
MDI Velocity (MDI_VELOCITY) Actual Speed (NIST_B)
9
10 MDI Acceleration Override (MDI_ACC) Fault Code Word (FAULT_CODE)
11 MDI Deceleration Override (MDI_DEC) Alarm Code Word (ALARM_CODE)
12 Freely Assignable Freely Assignable
8 Positioning Type Selection 1 = Absolute positioning is selected; 0 = Relative positioning is selected p2648
9 Absolute Positioning Method Bit 0 p2651
Absolute positioning method by: 0 = shortest distance; 1 = Positive direction;
10 Absolute Positioning Method Bit 1 2 = Negative direction; 3 = Shortest distance p2652
11 Reserved
12 Value Transfer Method 1 = Continuous Transfer; 0 = Transfer on rising edge of p2650 1 p2649
13 Reserved
14 Setting-up Selection 1 = Drive in setting-up mode selected; 0 = Drive in positioning mode selected p2653
15 EPOS Manual Data Input (MDI) Activation For direct setpoint entry. 1 = Activate MDI; 0 = Deactivate MDI p2647
1 p2650 sets the signal source to accept the values for edge-triggered selection in the operating mode „direct setpoint input/MDI“
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Master sign-of-life Bit 0
13 Master sign-of-life Bit 1
14 Master sign-of-life Bit 2
15 Master sign-of-life Bit 3
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Following Error on Tolerance 1 = Following error within tolerance; 0 = Following error outside of tolerance r2684.8
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Target Position Reached 1 = Target position reached; 0 = Target position not reached r2684.10
11 Reference Point Set 1 = Reference point set; 0 = Reference point not set r2684.11
12 Acknowledgement Trav. Block Active 1 = On; 0 = Off r2684.12
Speed Below Threshold 3 1 = Absolute actual speed below threshold value 3 (p2161[0])
13 0 = Speed above or greater than threshold value 3 r2199.0
14 Axis Accelerating 1 = Yes; 0 = No r2684.4
15 Axis Decelerating 1 = Yes; 0 = No r2684.5
8 STOP Cam Minus 1 = STOP cam minus active; 0 = STOP cam minus inactive r2684[13]
9 STOP Cam Plus 1 = STOP cam plus active; 0 = STOP cam plus inactive r2684[14]
10 Jogging Status 1 = Jogging active; 0 = Jogging inactive r2094[0]
11 Reference Point Approach 1 = Reference point approach active; 0 = Reference point approach inactive r2094[1]
12 Flying Referencing Status 1 = Flying referencing active; 0 = Flying referencing inactive r2684[1]
13 Traversing Block Status 1 = Traversing block active; 0 = Traversing block inactive r2094[2]
14 Setting-up Status 1 = Drive setting-up active; 0 = Drive setting-up inactive r2094[4]
15 EPOS Manual Data Input (MDI) Status 1 = MDI Active; 0 = MDI Inactive r2670[15]
8 Cam Switching Position 1 Status 1 = Position less than or equal to cam switching position 1 r2683.8
9 Cam Switching Position 2 Status 1 = Position less than or equal to cam switching position 2 r2683.9
10 Direct Output 1 Via Traversing Block 1 = Yes; 0 = No r2683.10
11 Direct Output 2 Via Traversing Block 1 = Yes; 0 = No r2683.11
12 Fixed Stop Status 1 = Fixed stop reached; 0 = Fixed stop not reached r2683.12
13 Fixed Stop Clamping Torque Status 1 = Fixed stop clamping torque reached; 0 = Clamping torque not reached r2683.13
14 Travel to Fixed Stop Status 1 = Traveling to fixed stop active; 0 = Traveling to fixed stop inactive r2683.14
15 Traversing Command Status 1 = Traversing command active; 0 = Traversing command inactive r2683.15
8 Travel to Fixed Stop Status 1 = Travel to fixed endstop function active; 0 = Travel to fixed endstop inactive r1406.8
9 Reserved
10 Pulse Status 1 = Pulses enabled; 0 = Pulses inhibited r0899.11
11 Motor Data Set Changeover Status 1 = Motor data set changeover active; 0 = Motor data set changeover inactive r0835.0
12 Slave sign-of-life Bit 0 implicit
13 Slave sign-of-life Bit 1 implicit
14 Slave sign-of-life Bit 2 implicit
15 Slave sign-of-life Bit 3 implicit
8 Speed Within Setpoint Tolerance 1 = Speed within setpoint tolerance; 0 = Speed outside of setpoint tolerance r2199.4
9 Reserved
10 Reserved
11 Controller Enabled 1 = Controller enabled; 0 = Controller disabled r0899.8
12 Drive Ready Status 1 = Yes; 0 = No r0899.7
13 Pulses Enabled Status 1 = Yes; 0 = No r0899.11
14 2nd Variable Signaling Function Status 1 = On; 0 = Off r3294.1
15 3rd Variable Signaling Function Status 1 = On; 0 = Off r3294.2
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed values.
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
p2633 BI: EPOS external block change (0 -> 1) / Ext BlckChg (0->1)
© Siemens AG copyright year All rights reserved
p2625 BI: EPOS traversing block selection bit 0 / Trav_blk sel bit 0
Note: parameters p2626, p2627, and p2628 function exactly as p2625 for their respective bits in
the selection of the traversing block.
p2648 BI: EPOS direct setpoint input/MDI positioning type / MDI pos_type
© Siemens AG copyright year All rights reserved
p2651 BI: EPOS direct setpoint input/MDI direction selection, positive / MDI dir_sel pos
p2652 BI: EPOS direct setpoint input/MDI direction selection negative / MDI dir_sel neg
Note: p2652 has the same dependencies and note information as p2651.
p2649 BI: EPOS direct setpoint input/MDI transfer type selection / MDI trans_type sel
© Siemens AG copyright year All rights reserved
p2653 BI: EPOS direct setpoint input/MDI setting-up selection / MDI setting-up sel
p2604 BI: EPOS search for reference start direction / Srch for ref dir
© Siemens AG copyright year All rights reserved
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
Parameter p0821[0] functions exactly as p0820[0] for its respective Drive Data Set bit.
p2642 CI: EPOS direct setpoint input/MDI position setpoint / MDI s_set
p2643 CI: EPOS direct setpoint input/MDI velocity setpoint / MDI v_set
p2644 CI: EPOS direct setpoint input/MDI acceleration override / MDI a_over
© Siemens AG copyright year All rights reserved
p2645 CI: EPOS direct setpoint input/MDI deceleration override / MDI -a_over
r2670.0...15 CO/BO: EPOS status word active traversing block / ZSW act trav_block
r0835.0...12 CO/BO: Data set changeover status word / Data set sw ZSW
r3294.0...2 BO: Variable signaling function output signal / Var sig outp_sig
© Siemens AG copyright year All rights reserved
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its
r2004
[FloatingPoint32] factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
5 Continue Ramp Function Generator 1 = RFG follows setpoint input; 0 = RFG freezes at current value p1141[0]
6 Setpoint Enable 1 = RFG setpoint input enabled; 0 = RFG input set to 0 p1142[0]
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
10 Master Control by PLC 1 = Control is by PLC; 0 = No control by PLC p0854[0]
11 Setpoint Inversion 1 = Invert setpoint; 0 = Do not invert setpoint p1113[0]
12 Reserved
13 Motorized Potentiometer (MOP) Raise 1 = Raise MOP setpoint; 0 = No action p1035[0]
14 Motorized Potentiometer Lower 1 = Lower MOP setpoint; 0 = No action p1036[0]
15 Reserved
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed values.
4 Drive data set selection (DDS) Bit 0 Bits 4-5 are used to select a drive data set. p0820
5 Drive data set selection (DDS) Bit 1 p0821
6 Reserved
7 Reserved
8 Technology Controller Enable 1 = Technology Controller Enabled; 0 = Technology Controller Disable p2200[0]
9 DC Braking Enable 1 = Enable DC braking; 0 = DC braking disabled p1230[0]
10 Reserved
11 Droop Feedback Enable 1 = Speed controller droop enable; 0 = Speed controller droop disable p1492[0]
12 Vector Control Mode 1 = Torque control active; 0 = Speed control active p1501[0]
13 External Fault Status 1 = No external fault; 0 = External fault present p2106[0]
14 Reserved
15 Command Data Set Selection Bit 0 Bit 15 is used to select a command data set (CDS). p0811[0]
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Motor at Acceptable Speed 1 = Speed deviation within tolerance; 0 = Speed deviation outside tolerance r2197.7
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Speed Above Max Speed 1 = Speed greater than or equal to max speed; 0 = Speed less than max speed r2199.1
11 Torque Limit Reached 1 = Torque limit reached; 0 = Torque limit not reached r0052.11
12 Holding Brake Open 1 = Holding brake open; 0 = Holding brake closed r0899.12
13 No Motor Overtemperature Alarm 1 = No overtemperature alarm; 0 = Overtemperature alarm present r2135.14
14 Motor Rotation Direction 1 = Motor rotates clockwise; 0 = Motor rotates counterclockwise r2197.3
15 No Converter Thermal Overload 1 = No converter thermal overload alarm; 0 = Thermal overload alarm present r2135.15
8 DC Link Voltage Above Threshold 1 = DC link voltage above threshold value; 0 = DC link voltage below threshold value r0053.8
9 Ramp Function Generator Status 1 = Ramp up or ramp down completed (RFG inactive); 0 = Ramp up or ramp down incomplete r0053.9
10 Technology Controller Lower Limit 1 = Tech controller output at or below lower limit (p2292); 0 = Output above lower limit r0053.10
11 Technology Controller Upper Limit 1 = Tech controller output above upper limit (p2291); 0 = Output below or at upper limit r0053.11
12 Reserved
13 Reserved
14 Reserved
15 Reserved
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
p1552[0...n] CI: Torque limit upper scaling without offset / M_max up w/o offs
© Siemens AG copyright year All rights reserved
Note: p1021[0], p1022[0], and p1023[0] function exactly as p1020[0] for their respective speed
setpoint selection bits.
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
© Siemens AG copyright year All rights reserved
Note: Parameter p0821[0] functions exactly as p0820[0] for its respective Drive Data Set bit.
p0811 BI: Command data set selection CDS bit 1 / CDS select., bit 1
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its
r2004
[FloatingPoint32] factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
5 Continue Ramp Function Generator 1 = RFG follows setpoint input; 0 = RFG freezes at current value p1141[0]
6 Setpoint Enable 1 = RFG setpoint input enabled; 0 = RFG input set to 0 p1142[0]
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
10 Master Control by PLC 1 = Control is by PLC; 0 = No control by PLC p0854[0]
11 Setpoint Inversion 1 = Invert setpoint; 0 = Do not invert setpoint p1113[0]
12 Reserved
13 Motorized Potentiometer (MOP) Raise 1 = Raise MOP setpoint; 0 = No action p1035[0]
14 Motorized Potentiometer Lower 1 = Lower MOP setpoint; 0 = No action p1036[0]
15 Reserved
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed values.
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Motor at Acceptable Speed 1 = Speed deviation within tolerance; 0 = Speed deviation outside tolerance r2197.7
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Speed Above Max Speed 1 = Speed greater than or equal to max speed; 0 = Speed less than max speed r2199.1
11 Torque Limit Reached 1 = Torque limit reached; 0 = Torque limit not reached r0052.11
12 Holding Brake Open 1 = Holding brake open; 0 = Holding brake closed r0899.12
13 No Motor Overtemperature Alarm 1 = No overtemperature alarm; 0 = Overtemperature alarm present r2135.14
14 Motor Rotation Direction 1 = Motor rotates clockwise; 0 = Motor rotates counterclockwise r2197.3
15 No Converter Thermal Overload 1 = No converter thermal overload alarm; 0 = Thermal overload alarm present r2135.15
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its
r2004
[FloatingPoint32] factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
This telegram is a Siemens telegram of 2 words in length. It will control the state of
the drive by selecting the appropriate bits in the control word and set the running
speed in the speed setpoint word. It is identical to Telegram 1, with the exception
that the speed feedback value is smoothed.
5 Continue Ramp Function Generator 1 = RFG follows setpoint input; 0 = RFG freezes at current value p1141[0]
6 Setpoint Enable 1 = RFG setpoint input enabled; 0 = RFG input set to 0 p1142[0]
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
10 Master Control by PLC 1 = Control is by PLC; 0 = No control by PLC p0854[0]
11 Setpoint Inversion 1 = Invert setpoint; 0 = Do not invert setpoint p1113[0]
12 Reserved
13 Motorized Potentiometer (MOP) Raise 1 = Raise MOP setpoint; 0 = No action p1035[0]
14 Motorized Potentiometer Lower 1 = Lower MOP setpoint; 0 = No action p1036[0]
15 Reserved
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed values.
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Motor at Acceptable Speed 1 = Speed deviation within tolerance; 0 = Speed deviation outside tolerance r2197.7
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Speed Above Max Speed 1 = Speed greater than or equal to max speed; 0 = Speed less than max speed r2199.1
11 Torque Limit Reached 1 = Torque limit reached; 0 = Torque limit not reached r0052.11
12 Holding Brake Open 1 = Holding brake open; 0 = Holding brake closed r0899.12
13 No Motor Overtemperature Alarm 1 = No overtemperature alarm; 0 = Overtemperature alarm present r2135.14
14 Motor Rotation Direction 1 = Motor rotates clockwise; 0 = Motor rotates counterclockwise r2197.3
15 No Converter Thermal Overload 1 = No converter thermal overload alarm; 0 = Thermal overload alarm present r2135.15
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its
r2004
[FloatingPoint32] factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
Telegram 354 is a Siemens telegram of 6 words in length for speed control with
VECTOR Drive Objects. This telegram cannot be used with SERVO Drive Objects.
This telegram offers four optional User Defined Control Setpoints, and four added
status words returning to the PLC for Current, Torque, Alarm Word, and Fault
Word.
5 Continue Ramp Function Generator 1 = RFG follows setpoint input; 0 = RFG freezes at current value p1141[0]
6 Setpoint Enable 1 = RFG setpoint input enabled; 0 = RFG input set to 0 p1142[0]
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
10 Master Control by PLC 1 = Control is by PLC; 0 = No control by PLC p0854[0]
11 Setpoint Inversion 1 = Invert setpoint; 0 = Do not invert setpoint p1113[0]
12 Reserved
13 Motorized Potentiometer (MOP) Raise 1 = Raise MOP setpoint; 0 = No action p1035[0]
14 Motorized Potentiometer Lower 1 = Lower MOP setpoint; 0 = No action p1036[0]
15 Reserved
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed values.
5 Quick Stop Off 1 = Quick stop (OFF3) inactive; 0 = Quick stop active r0899.5
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Motor at Acceptable Speed 1 = Speed deviation within tolerance; 0 = Speed deviation outside tolerance r2197.7
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Speed Above Max Speed 1 = Speed greater than or equal to max speed; 0 = Speed less than max speed r2199.1
11 Torque Limit Reached 1 = Torque limit reached; 0 = Torque limit not reached r0052.11
12 Holding Brake Open 1 = Holding brake open; 0 = Holding brake closed r0899.12
13 No Motor Overtemperature Alarm 1 = No overtemperature alarm; 0 = Overtemperature alarm present r2135.14
14 Motor Rotation Direction 1 = Motor rotates clockwise; 0 = Motor rotates counterclockwise r2197.3
15 No Converter Thermal Overload 1 = No converter thermal overload alarm; 0 = Thermal overload alarm present r2135.15
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its
r2004
[FloatingPoint32] factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
Notes:
This telegram cannot be configured for any drive object that is not a line module. To select this
telegram, parameter p0922 of the supply module must be set to 370. Any other drive objects
connected to the supply will support their own independent telegrams.
© Siemens AG copyright year All rights reserved
Status Word 1 for Active Infeed for Metals Industry (E_ZSW1_BM) p2080[0…15]
Bit Name Functionality Interconnection
0 Ready to Power On 1 = Drive ready; 0 = Drive not ready r0899.0
1 Ready to Run 1 = Ready to run (motor is on); 0 = Not ready to run (motor is off or fault active) r0899.1
2 Operation Enabled 1 = Motor enabled (see Control Word 1 STW1, bit 3); 0 = Motor not enabled r0899.2
3 Fault Active 1 = Converter fault. Acknowledge with Control Word 1, bit 7; 0 = No fault active r2139.3
4 Coast to Stop Off 1 = Coast down (OFF2) inactive; 0 = Coast down active r0899.4
5 Reserved
© Siemens AG copyright year All rights reserved
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Reserved
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Reserved
11 Precharging Status 1 = Precharging completed; 0 = Precharging incomplete r0899.11
12 Line Contactor Status 1 = Line contactor closed; 0 = Line contactor open r0899.12
13 Reserved
14 Reserved
15 Controller sign-of-life toggle bit 1 = On; 0 = Off r2090.15
p3533 BI: Infeed inhibit generator mode / INF gen mode inhib
© Siemens AG copyright year All rights reserved
r0899.0...12 CO/BO: Status word sequence control infeed / ZSW seq_ctrl INF
1 Control Word 1 for Active Infeed Status Word 1 for Active Infeed
for Metals Industry (E_STW1_BM) for Metals Industry (E_ZSW1_BM)
2 Freely Assignable Actual Current (IAIST)
3 Freely Assignable Alarm Code (WARN_CODE)
4 Freely Assignable Fault Code (FAULT_CODE)
5 Freely Assignable Freely Assignable
6 Freely Assignable
7 Freely Assignable
© Siemens AG copyright year All rights reserved
8 Freely Assignable
Notes:
This telegram cannot be configured for any drive object that is not a line module. To select this
telegram, parameter p0922 of the supply module must be set to 371. Any other drive objects
connected to the supply will support their own independent telegrams.
Control Word 1 for Active Infeed for Metals Industry (E_STW1_BM) r2090.0…15
Bit Name Functionality Interconnection
0 Drive Enable (ON/OFF1) 1 = Enable drive; 0 = Ramp down and disable drive p0840[0]
1 Coast Stop Command (OFF2) 1 = No stop command issued; 0 = Immediate disable and coast to stop p0844[0]
2 Reserved
3 Enable Operation1 1 = Enable drive (pulses enabled); 0 = Inverter prohibited from generating pulses p0852[0]
4 Reserved
5 Inhibit Motoring Operation2 1 = Infeed inhibit motoring operation; 0 = No action p3532
© Siemens AG copyright year All rights reserved
Status Word 1 for Active Infeed for Metals Industry (E_ZSW1_BM) p2080[0…15]
Bit Name Functionality Interconnection
0 Ready to Power On 1 = Drive ready; 0 = Drive not ready r0899.0
1 Ready to Run 1 = Ready to run (motor is on); 0 = Not ready to run (motor is off or fault active) r0899.1
2 Operation Enabled 1 = Motor enabled (see Control Word 1 STW1, bit 3); 0 = Motor not enabled r0899.2
3 Fault Active 1 = Converter fault. Acknowledge with Control Word 1, bit 7; 0 = No fault active r2139.3
4 Coast to Stop Off 1 = Coast down (OFF2) inactive; 0 = Coast down active r0899.4
5 Reserved
© Siemens AG copyright year All rights reserved
6 Switch-On Inhibited 1 = Motor inhibited from switching on; 0 = Motor can be switched on r0899.6
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 Reserved
9 Master Control Request 1 = Master control requested; 0 = No action r0899.9
10 Reserved
11 Precharging Status 1 = Precharging completed; 0 = Precharging incomplete r0899.11
12 Line Contactor Status 1 = Line contactor closed; 0 = Line contactor open r0899.12
13 Reserved
14 Reserved
15 Controller sign-of-life toggle bit 1 = On; 0 = Off r2090.15
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed values.
p3533 BI: Infeed inhibit generator mode / INF gen mode inhib
© Siemens AG copyright year All rights reserved
r0899.0...12 CO/BO: Status word sequence control infeed / ZSW seq_ctrl INF
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its
r2004
[FloatingPoint32] factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
3.16 Telegram 390 for Control Unit and Digital I/O 16/8
3.16.1 Description
Notes:
This telegram can only be configured for a Control Unit drive object. Any drive object of a
different type will support its own independent telegram.
© Siemens AG copyright year All rights reserved
6 Reserved
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
1 This bit is only available when the “extended setpoint channel” function module is active by setting r0108.9 = 1.
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
6 Reserved
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 System Time Sync 1 = System time synchronized; 0 = System time not synchronized r0899.8
9 Group Alarm Status 1 = No alarm present; 0 = Alarm present r3114.9
10 Group Fault Status 1 = No fault present; 0 = Fault present r3114.10
11 Safety Group Message Status 1 = No safety message present; 0 = Safety message present r3114.11
12 Slave sign-of-life Bit 0 1 = On, 0 = Off
13 Slave sign-of-life Bit 1 1 = On, 0 = Off
14 Slave sign-of-life Bit 2 1 = On, 0 = Off
15 Slave sign-of-life Bit 3 1 = On, 0 = Off
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
2 Digital inputs 4 to 7 (bits 12 to 15) are only available for the CU320-2.
3.17 Telegram 391 for Control Unit and Digital I/O 16/8 with
2 Measuring Probes
3.17.1 Description
4 Measuring Probe 1
Measuring Time Falling Edge (MT1_ZS_F)
5 Measuring Probe 1
Measuring Time Rising Edge (MT1_ZS_S)
© Siemens AG copyright year All rights reserved
6 Measuring Probe 2
Measuring Time Falling Edge (MT2_ZS_F)
7 Measuring Probe 2
Measuring Time Rising Edge (MT2_ZS_S)
Notes:
This telegram can only be configured for a Control Unit drive object. Any drive object of a
different type will support its own independent telegram.
6 Reserved
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
6 Reserved
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 System Time Sync 1 = System time synchronized; 0 = System time not synchronized r0899.8
9 Group Alarm Status 1 = No alarm present; 0 = Alarm present r3114.9
10 Group Fault Status 1 = No fault present; 0 = Fault present r3114.10
11 Safety Group Message Status 1 = No safety message present; 0 = Safety message present r3114.11
12 Slave sign-of-life Bit 0 1 = On, 0 = Off
13 Slave sign-of-life Bit 1 1 = On, 0 = Off
14 Slave sign-of-life Bit 2 1 = On, 0 = Off
15 Slave sign-of-life Bit 3 1 = On, 0 = Off
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
2 Digital inputs 4 to 7 (bits 12 to 15) are only available for the CU320-2.
p0681 BI: Central measuring probe synchronizing signal signal source / Cen meas
sync_sig
p0682 CI: Central measuring probe control word signal source / Cen meas STW S_src
© Siemens AG copyright year All rights reserved
r0688 CO: Central measuring probe status word display / Cen meas ZSW disp
© Siemens AG copyright year All rights reserved
r0686[0...7] CO: Central measuring probe measuring time rising edge / CenMeas t_meas
0/1
© Siemens AG copyright year All rights reserved
r0687[0...7] CO: Central measuring probe measuring time falling edge / CenMeas t_meas
1/0
3.18 Telegram 392 for Control Unit, Digital I/O 16/8, and 6
Measuring Probes
3.18.1 Description
4 Measuring Probe 1
Measuring Time Falling Edge (MT1_ZS_F)
5 Measuring Probe 1
Measuring Time Rising Edge (MT1_ZS_S)
© Siemens AG copyright year All rights reserved
6 Measuring Probe 2
Measuring Time Falling Edge (MT2_ZS_F)
7 Measuring Probe 2
Measuring Time Rising Edge (MT2_ZS_S)
8 Measuring Probe 3
Measuring Time Falling Edge (MT3_ZS_F)
9 Measuring Probe 3
Measuring Time Rising Edge (MT3_ZS_S)
10 Measuring Probe 4
Measuring Time Falling Edge (MT4_ZS_F)
11 Measuring Probe 4
Measuring Time Rising Edge (MT4_ZS_S)
12 Measuring Probe 5
Measuring Time Falling Edge (MT5_ZS_F)
13 Measuring Probe 5
Measuring Time Rising Edge (MT5_ZS_S)
14 Measuring Probe 6
Measuring Time Falling Edge (MT6_ZS_F)
15 Measuring Probe 6
Measuring Time Rising Edge (MT6_ZS_S)
Notes:
This telegram can only be configured for a Control Unit drive object. Any drive object of a
different type will support its own independent telegram.
6 Reserved
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
6 Reserved
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 System Time Sync 1 = System time synchronized; 0 = System time not synchronized r0899.8
9 Group Alarm Status 1 = No alarm present; 0 = Alarm present r3114.9
10 Group Fault Status 1 = No fault present; 0 = Fault present r3114.10
11 Safety Group Message Status 1 = No safety message present; 0 = Safety message present r3114.11
12 Slave sign-of-life Bit 0 1 = On, 0 = Off
13 Slave sign-of-life Bit 1 1 = On, 0 = Off
14 Slave sign-of-life Bit 2 1 = On, 0 = Off
15 Slave sign-of-life Bit 3 1 = On, 0 = Off
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
2 Digital inputs 4 to 7 (bits 12 to 15) are only available for the CU320-2.
p0681 BI: Central measuring probe synchronizing signal signal source / Cen meas
sync_sig
p0682 CI: Central measuring probe control word signal source / Cen meas STW S_src
© Siemens AG copyright year All rights reserved
r0688 CO: Central measuring probe status word display / Cen meas ZSW disp
© Siemens AG copyright year All rights reserved
r0686[0...7] CO: Central measuring probe measuring time rising edge / CenMeas t_meas
0/1
© Siemens AG copyright year All rights reserved
r0687[0...7] CO: Central measuring probe measuring time falling edge / CenMeas t_meas
1/0
Notes:
This telegram can only be configured for a Control Unit drive object. Any drive object of a
different type will support its own independent telegram.
Digital Output A_DIGITAL_1 and Analog Input E_ANALOG are only available for drive objects
CU_S_AC and CU_I_D410.
6 Reserved
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
1 This bit is only available when the “extended setpoint channel” function module is active by setting r0108.9 = 1.
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
8 Digital Output 16 (DI/DO 16)1 Signal source for terminal DI/DO 16 p0746
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
1 This bit is not reserved only for drive objects CU_S_AC and CU_I_D410.
6 Reserved
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 System Time Sync 1 = System time synchronized; 0 = System time not synchronized r0899.8
9 Group Alarm Status 1 = No alarm present; 0 = Alarm present r3114.9
10 Group Fault Status 1 = No fault present; 0 = Fault present r3114.10
11 Safety Group Message Status 1 = No safety message present; 0 = Safety message present r3114.11
12 Slave sign-of-life Bit 0 1 = On, 0 = Off
13 Slave sign-of-life Bit 1 1 = On, 0 = Off
14 Slave sign-of-life Bit 2 1 = On, 0 = Off
15 Slave sign-of-life Bit 3 1 = On, 0 = Off
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
2 Digital inputs 4 to 7 (bits 12 to 15) are only available for the CU320-2.
Connector output for measuring time of measuring probe 3 rising edge. It has a resolution of 0.25 µs. r0686[2]
Connector output for measuring time of measuring probe 7 rising edge. It has a resolution of 0.25 µs. r0686[6]
Notes:
This word is only available for drive objects CU_S_AC and CU_I_D410.
p0756[0] is used to determine the scaling parameter that is applied to E_ANALOG according to the following:
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect analog input values.
p0681 BI: Central measuring probe synchronizing signal signal source / Cen meas
sync_sig
p0682 CI: Central measuring probe control word signal source / Cen meas STW S_src
© Siemens AG copyright year All rights reserved
r0688 CO: Central measuring probe status word display / Cen meas ZSW disp
© Siemens AG copyright year All rights reserved
r0686[0...7] CO: Central measuring probe measuring time rising edge / CenMeas t_meas
0/1
© Siemens AG copyright year All rights reserved
r0687[0...7] CO: Central measuring probe measuring time falling edge / CenMeas t_meas
1/0
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its
r2004
[FloatingPoint32] factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
3.20 Telegram 394 for Control Unit and Digital I/O 24/9
3.20.1 Description
Notes:
© Siemens AG copyright year All rights reserved
This telegram can only be configured for a Control Unit drive object. Any other type of drive
object will support its own independent telegram.
The process data Digital Output (A_DIGITAL_1) is only available for drive objects CU_S_AC
and CU_I_D410.
6 Reserved
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
1 This bit is only available when the “extended setpoint channel” function module is active by setting r0108.9 = 1.
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
8 Digital Output 16 (DI/DO 16)1 Signal source for terminal DI/DO 16 p0746
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
1 This bit is not reserved only for drive objects CU_S_AC and CU_I_D410.
6 Reserved
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 System Time Sync 1 = System time synchronized; 0 = System time not synchronized r0899.8
9 Group Alarm Status 1 = No alarm present; 0 = Alarm present r3114.9
10 Group Fault Status 1 = No fault present; 0 = Fault present r3114.10
11 Safety Group Message Status 1 = No safety message present; 0 = Safety message present r3114.11
12 Slave sign-of-life Bit 0 1 = On, 0 = Off
13 Slave sign-of-life Bit 1 1 = On, 0 = Off
14 Slave sign-of-life Bit 2 1 = On, 0 = Off
15 Slave sign-of-life Bit 3 1 = On, 0 = Off
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
2 Digital inputs 4 to 7 (bits 12 to 15) are only available for the CU320-2.
p0681 BI: Central measuring probe synchronizing signal signal source / Cen meas
sync_sig
3.21 Telegram 395 for Control Unit, Digital I/O 24/9, and 16
Measuring Probes
3.21.1 Description
(continued)
Notes:
This telegram can only be configured for a Control Unit drive object. A drive object of any other
type will support its own independent telegram.
The process data Digital Output (A_DIGITAL_1) is only available for drive objects CU_S_AC
and CU_I_D410.
6 Reserved
7 First Fault Acknowledge 1 = Acknowledge faults (on rising edge) p2103[0]
8 Reserved
9 Reserved
1 This bit is only available when the “extended setpoint channel” function module is active by setting r0108.9 = 1.
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
8 Digital Output 16 (DI/DO 16)1 Signal source for terminal DI/DO 16 p0746
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
1 This bit is not reserved only for drive objects CU_S_AC and CU_I_D410.
6 Reserved
7 Active Alarm 1 = Alarm active; 0 = No alarm active r2139.7
8 System Time Sync 1 = System time synchronized; 0 = System time not synchronized r0899.8
9 Group Alarm Status 1 = No alarm present; 0 = Alarm present r3114.9
10 Group Fault Status 1 = No fault present; 0 = Fault present r3114.10
11 Safety Group Message Status 1 = No safety message present; 0 = Safety message present r3114.11
12 Slave sign-of-life Bit 0 1 = On, 0 = Off
13 Slave sign-of-life Bit 1 1 = On, 0 = Off
14 Slave sign-of-life Bit 2 1 = On, 0 = Off
15 Slave sign-of-life Bit 3 1 = On, 0 = Off
1 Digital outputs can be configured as digital inputs using bits 8 to 15 of p0728: 1 = Configured as output; 0 = Configured as input.
2 Digital inputs 4 to 7 (bits 12 to 15) are only available for the CU320-2.
Interconnection
Connector output for the time stamp MT_ZS_6. It is a 16-bit value with 0.25 µs resolution. r0565[5]
Interconnection
Connector output for the time stamp MT_ZS_14. It is a 16-bit value with 0.25 µs resolution. r0565[13]
p0681 BI: Central measuring probe synchronizing signal signal source / Cen meas
sync_sig
p0682 CI: Central measuring probe control word signal source / Cen meas STW S_src
© Siemens AG copyright year All rights reserved
r0688 CO: Central measuring probe status word display / Cen meas ZSW disp
© Siemens AG copyright year All rights reserved
Notes
The arrangement of process data (PZD) for telegram 700 depends on the telegram selection
(p0922, p2079) and the receive and send words reserved (p2070, p2071). To select this
© Siemens AG copyright year All rights reserved
The telegram 700 is appended to the telegram selected with respect to the words reserved.
5 Reserved
6 Safety Limited Sped (SLS) Selected 1 = Yes; 0 = No
7 Internal Event Status 1 = One of STOP A…F is active; 0 = None of STOP A…F active r9734.7
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Safe Direction (SDI) Positive Selected 1 = Yes; 0 = No r9734.12
13 Safe Direction (SDI) Negative Selected 1 = Yes; 0 = No r9734.13
14 Extended Stop and Retract (ESR) Requested 1 = Yes; 0 = No r9734.14
15 Reserved
1 See Reference Scaling Parameters in the Associated Parameters section for a description of how the scaling parameters affect speed values.
r9734.0...14 CO/BO: SI Safety Info Channel status word S_ZSW1B / SIC S_ZSW1B
© Siemens AG copyright year All rights reserved
Reference Force or Torque The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque.
p2003
[FloatingPoint32] Factory default values: 100.00 N (force), 1.00 Nm (torque)
Reference Power The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its
r2004
[FloatingPoint32] factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).
Reference Angle The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle.
p2005
[FloatingPoint32] Factory default values: 90.00 degrees
Reference Temperature The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature.
p2006
[FloatingPoint32] Factory default values: 100.00 degrees C
Reference Acceleration The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational
p2007
[FloatingPoint32] acceleration. Factory default values: 0.01 revolutions/sec^2
p2070 IF1 PROFIdrive supplementary telegram receive beginning / Suppl_tele rec beg
© Siemens AG copyright year All rights reserved
p2070 IF1 PROFIdrive supplementary telegram receive beginning / Suppl_tele rec beg
p2071 IF1 PROFIdrive supplementary telegram send beginning / Suppl_tel send beg
p2071 IF1 PROFIdrive supplementary telegram send beginning / Suppl_tel send beg
© Siemens AG copyright year All rights reserved
This telegram is a standard PROFIdrive telegram of variable word length. The first
word of Telegram 999 consists of a control and status word, and the rest of the
telegram is freely configurable.
Notes:
To select this telegram, p0922 must be set to 999. When switching from a different telegram to
telegram 999, the interconnections of the previous telegram will be inherited by default at the
beginning of telegram 999. Inherited interconnections can be changed once p0922 = 999.
© Siemens AG copyright year All rights reserved
The maximum number of available process words is determined by the drive object type.
1 The first control and status word of Telegram 999 may not be STW1 or ZSW1 depending on the inherited
telegram; the above are used as an example.
The following table details the maximum number of available process words for
each drive object:
© Siemens AG copyright year All rights reserved
For more information, see 3.2.1 “Telegrams and Process Data” in the S120
Communications Function Manual linked in the Additional Resources section of this
document.
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
4 Additional Resources
4.1 List Manuals
The following documents contain telegram charts, parameter information, function
diagrams, and fault and alarm information.