Paper 1
Paper 1
Abstract—According to the low voltage ride through (LVRT) the accuracy of network division is hard to be guaranteed.
requirement stipulated by the distribution grid standards, an
LVRT strategy based on reactive power support of the inverter The fault current expression of IIDGs is obtained in [7],
interfaced distribution generation (IIDG) was first presented. taking IIDGs as constant power sources. The error may be
The maximum energy output, which achieves the optimal great since the fault current also depends on the control
efficiency of distributed power supply, was also taken into strategies. A fault current calculation model was deduced in [8],
account. Then the fault characteristics of IIDG with LVRT considering the relation between DG and sequence voltages of
strategy were analyzed. Considering the impact of LVRT PCC.
controlled IIDG on power distribution, the short circuit current
analysis is discussed and a short circuit calculation model of In this paper, firstly, an LVRT strategy aiming at supplying
distribution networks with IIDG was established. Case study in the reactive power support is proposed through reactive current
Digsilent shows the effectiveness of the LVRT strategy and the control. Secondly, considering the LVRT strategies, the current
fault calculation method. output of IIDG under system fault is analyzed to obtain the
equivalent fault model. Thereafter, fault calculation of
Keywords—inverter interfaced distributed generation, low distribution networks with IIDG is given. Case study based on
voltage ride through, fault analysis, short circuit model DigSILENT verifies the effectiveness of the proposed models.
(4) Z15 ZT
Zload2 Zload3
Zload1
pu
-0.2
U fb U fc 0 0.1 0.2 0.3 0.4 t/s 0.5 0.6
(11)
I fb I fc
Fig. 5. reference and actual value of d and q-axis fault currents
0.8
(12)
pu
0.6
Equation (9) could be solved by iteration method by 0.4 Positive sequence voltage
0.2
integrating the voltage-controlled current source of IIDG in 0 0.1 0.2 0.3 0.4 t/s 0.5
0.6
, I n Gnm I DGi Yi1 Yii Yin U i
T 1000
I1 , I 2 , (13)
Udc
kV
800
Y Y Y
DGm n1
I ni nn U n 600
System System
Branch impedance / Transformer / Load /
capacity /MVA impecance /
500 j0.27
0.233+j 1.683+j 0.267+j 0.642+j 0.928+j 0.894+j 0.949+j
5+j5
0.187 1.068 0.377 0.283 0.371 0.446 0.316
TABLE.2 COMPARISON OF THEORETICAL AND SIMULATION VALUE WHEN INTERPHASE FAULT OCCURS AT DOWNSTREAM BUS OF SINGLE IIDG
Current of main grid /kA IIDG current /kA Fault current /kA IIDG voltage /p.u.
Positive Negative Positive Negative Positive Negative Positive Negative
sequence sequence sequence sequence sequence sequence sequence sequence
Simulation 0.402∠
1.392 -45.52 0.786 159.65 1.085 -129.5 0 1.016 -16.91 0.856 160.46 0.542 15.784
value 5.45
Calculation
1.390 -45.63 0.755 160.02 1.065 -130 0 1.012 -16.93 0.866 160.40 0.553 15.523 0.4∠5.50
value
TABLE.3 COMPARISON OF THEORETICAL AND SIMULATION VALUE WHEN THREE-PHASE FAULT OCCURS AT DOWNSTREAM BUS OF SINGLE IIDG
Current of IIDG current Fault current Voltage of IIDG voltage Voltage of Voltage of
main grid /kA /kA /kA main grid /kV /kV Node 2 /kV Node 3 /kV
Simulation
2.225 -35.862 0.606 -87.62 1.511 -21.62 0.985 -1.161 0.152 2.101 0.329 8.177 0.184 2.152
value
Calculatio
2.21 -35.78 0.612 -87.55 1.50 -21.73 0.991 -1.08 0.16 2.35 0.344 8.15 0.186 2.18
n value