EF ZT Distance protection

Distance protection
INGEPAC™ EF ZT is a distance protection relay with 5 independent zones of operation on which MHO or quadrilateral
characteristic can be set independently, suitable for transmission lines, or multibreaker configurations such us, breaker and
a half or ring. It determines the type of fault, differentiating among three-phase, two-phase and earth faults.
INGEPAC™ EF ZT includes backup units for one or two breakers, synchronism checking functions or automatic reclose with
different timings for single-pole or three-pole trips. It also provides teleprotection schemes or fault locator function that
provides distance to the fault.

Applications
∙ Primary or secondary protection for cables, overhead or mixed lines in transmission and under-transmission grids
(INGEPAC™ EF ZT0 model)
∙ Primary or secondary protection for breaker-and-a-half schemes (INGEPAC™ EF ZT1 model)

Functions Minimum voltage


T9
21 Quadrilateral and MHO 81M/m, 81 ROCOF
21 High speed zone 37 Undercurrent
Zone 1 extension 49 Thermal image
T1, T2, T3 52-1 ∑ I1+I2 Double line adaptation, 32 Power
79 25
52-1 Serial compensation Stub bus
21 67 68OP 68FF 68ZC
50BF line adaptation, Lines 85 Teleprotection (21,
with CVT 67/67Q)
T10, T11, T12 49 SOTF
50
85
3x50/51 (67), 50N/51N 68ZC, 68FF
STUB
(67N) 78 Power swing
50BF 50G/51G 25 Synchronism
52-2
79 25 27 59 81 32
46TOC (67Q), 46IOC 79 One/three poles
T4, T5, T6 52-2 (67Q) 50 BF Breaker Failure
46BC Broken Conductor with monopolar/tripolar
50 CSC Second harmonic trip
restraint Fault Locator
52-3 T8 SOTF Switch onto fault Breaker monitoring
27, 59, 59N, 47,

Logics based on IEC 61131-3 Local HMI xFE


sutats
status

0
EFx

4,9” display
8F 1F 9 8 7

OR
6 5 4
9F 2F F1

3 2 1

Graphical displays
01F 3F F2
R 0

$.PROT.PTRC1.Op51.ST.stVal IN1 OUT $.GEN.pGGIO1.Ind1.ST.stVal 1


11F 4F F3

CSE UNEM

I/O/L/R pushbuttons
21F 5F F4

31F 6F F5

41F 7F MENU ESC

$.PROT.PTRC1.Op50.ST.stVal IN2 VAR1 2 19 LEDs 7

1
8

2
9

Keyboard
0 R

Data acquisition Synchronization Communications


SOE (1000), faults (20) IEEE 1588 v2 Protocols: IEC 61850, IEC 60870-5-103/104, DNP3, Modbus, PROCOME
Oscillography (12 analog and 100 digital channels) IRIG-B Redundancy: PRP, HSR, D-link failure, switch mode
Measurements: I, V, P, U, Q, f, T, etc. SNTP Web services: HTTP/HTTPs, FTP/sFTP, SSH
Quality: sags and swells, THD, harmonics (15)
EF ZT Distance protection

INSULATION AND
ELECTROMAGNETIC TESTS MAIN FEATURES
Electromagnetic 5 zones on which MHO or quadrilateral characteristic can be applied independently; each
compatibility IEC 60255-26 zone can be set as forward, reverse or non-directional
requirements Independent analysis per each phase combination (AN, BN, CN, AB, BC, CA), characteristic
Dielectric withstand IEC 60255-27 (quadrilateral and MHO) and zone
Insulation resistance Single-phase or three-phase trip; applicable with or without teleprotection schemes
IEC 60255-27
measurement Wide range current inputs allowing the same device to be connected to 1 A and 5 A CT
Voltage impulse IEC 60255-27 secondary
Electrostatic discharge Through the front USB you can access the equipment to retrieve reports and equipment
IEC 61000-4-2
immunity CID, load an external CID, load the firewall configuration or update the equipment firmware

Los datos técnicos de esta ficha están sujetos a cambios sin previo aviso. TF13IPT_PGA01_C/112023
Radiated radiofrequency Synchronization from communications protocols, SNTP, IEEE 1588 v2 (PTP), demodulated
electromagnetic field IEC 61000-4-3 IRIG-B input or PPS input, pacFactory or display
immunity
Web server for monitoring and setting without needing additional software
Electrical fast transient /
IEC 61000-4-4 Cybersecurity features: sFTP, HTTPs, firewall, audit log, password accessing, RBAC, LDAP,
burst immunity
session management, etc.
Surge immunity IEC 61000-4-5
Acquisition of sampled values as per IEC 61869-9 (NCIT) and IEC 61850-9-2LE (SAMU)
Immunity to conducted standards (optional)
disturbances, induced IEC 61000-4-6
by radiofrequency fields
HARDWARE OPTIONS
Power frequency
IEC 61000-4-8
magnetic field immunity
Mounting options Boards options
Impulse magnetic field
IEC 61000-4-9 ∙ 19” 4U rack (up to 6 I/O slots) ∙ CPU: 6 DI + 4 DO
immunity
∙ 11 DI + 9 DO
Damped oscillatory ∙ 32 DI
IEC 61000-4-10
magnetic field immunity ∙ 16 DI + 8 DO
Immunity to conducted, ∙ 16 DI + 16 DO
common mode IEC 61000-4-16 ∙ 16 DI + 8 AI (mA)
disturbances ∙ 8 DI + 8 DO
Ripple on DC input ∙ 11 RTD + 4 AO
IEC 61000-4-17
power port ∙ ½ x 19” 5U rack (up to 2 I/O slots) 100 Ω platinum, 100 Ω nickel, 120
Ω nickel, 10 Ω copper
Damped oscillatory
IEC 61000-4-18
wave immunity
Voltage dips, short Communication ports
interruptions and voltage IEC 61000-4-29 Front:
variations immunity ∙ RJ45
Withstand to radiated ∙ USB
electromagnetic Rear:
IEEE 37.90.2
interference from ∙ Up to 2 Ethernet (FO or RJ45)
transceivers ∙ Up to 6 serial (FO, RS232, RS485)
Optional
CLIMATIC TESTS ∙ High break contact outputs
∙ High speed outputs Power supply
Cold IEC 60068-2-1 ∙ 24, 48, 125 and 220 Vdc
Dry heat IEC 60068-2-2 ∙ Power: 40 W
Optional IP54 front protection ∙ Optionally redundant power supply
Change of temperature IEC 60068-2-14
Damp heat cyclic IEC 60068-2-30
Damp heat steady IEC 60068-2-78
SOFTWARE
External protection level IEC 60529
All the devices in the INGEPAC™ product range can be accessed using powerful software
tools developed by Ingeteam which run on Windows®
MECHANICAL TESTS
Application specifically designed for simple and user-friendly access to the equipment
Vibrations IEC 60255-21-1
Shock and bump IEC 60255-21-2 eFS

Seismic IEC 60255-21-3

Ingeteam Power Technology, S. A.


Parque Tecnológico de Bizkaia, Ed. 110
Zamudio (Bizkaia) - Spain
(+34) 94 403 97 10