EDAUMA310018 Servicing and Maintenance
15. Servicing and Maintenance
AY Warring Disconnect om ne main power supply bao serving the a contioner unt.
1 00 NOT pul authe power cod when be power is ON, Ths may cause serious elctca shocks.
Service of the Fitter
= Remove any dust adhering to the fiter by using a vacuum cleaner or wash in lukewarm water (below
40°C) with neural cleaning detergent.
= Rinse the iter well and dry before placing it back onto the unit
= Do not use gascline,volatle substances or chemicals to clean the fer
= Clean the iter at least once every 2 weeks. Or more frequently It necessary
Fitter position
‘Tho flrs are mounted in front ofthe indoor heat exchanger
Unit shown inthe aiagram is UAY90, Other models shal flow the same method.
Remove fer cover or ter serve. ‘Mtomalvaly, remove service panel fo fiter sevice.
Vacuuming and Charging
ne rooftop package units are factory pe-charged with sufficient retigerant, However, there may be a
need for charge recovery during service and maintenance wotks, Thereloe, some precautions must be
taken to ensure optimum and trouble-tee system operation:
(@ The system should be thoroughly vaciumed to ensure no incompressible gas and moisture inthe
system
(i) Use a vacuum pump for R-410A exclusively. Using the same vacuum pump for ciferent retigerants
may damage the vacuum pump ofthe unit
ui) The retrigorant should never be released directly into the envionment
(is}when charging R-#10A, ensure that only quid is being withdrawn trom the cylinder or can,
Inver eyinder
thou pipe
guia
‘thea
—>
Normally the R-410A cylinder or can is being equipped with a cip-pipe for liquid withdrawal. However, the
clip-ipe isnot available, invert the cylinder or ean so as to withdraw liqus rom the valve a the bottom.
‘CAUTION:
+ Ref 10A must be charged as liquid. Usually e104 cylinder is equipped with a dippipe for lauid
withdrawal. If there is no ip-ppe, the cylinder shouldbe inverted so as to withdraw liquid R-410A trom
the vave
= Do not top-up when servicing leak, as this will reduce the unit performance, Vacuum the unt thoroughly
‘and then charge the uit wih fresh R-A10A according to the amount recommended inthe specification
53‘Troubleshooting EDAUMA31001B
16. Troubleshooting
Botore caling Daikn Service Division, check the following points
For any enguities on spare par pleage contact Daikin Service Divsion, I ay malfunction ofthe air