a) PV display window:
1. set status: parameter code display settings
2. measuring status: display real-time pressure
value
b) SV display window:
1. set status: display setting values
2. measuring status: display controller pressure
value
c) MPa: pressure unit
d) 0-100% : output power display bar
e) AL-1: first alarm indicator
f) AL-2 : second alarm indicator
g) CAE: calibration indicator
h) MAN: manual operation indicator
i) MODE: mode key (empty) , Complete
withdrawal from the main Menu
j) A/M: Auto/Manual switch operation key
k) AC: reset key
l) CAE: calibration key
m) SET: Function key : the pressure value would be zero clearing , if you press thefunction key and AC reset
key at the same time .
n) < : Shift key : if you mistake the zero clearing operation , now you need to press function key and the shift
key for 5 seconds to restore the calibration value .
o) ∨: Moving down key
p) ∧: moving up key
a) The first alarm indicator light AL-1, when it alarms , the indicator light is ok , when it doesn’t , the indicator
light is off .
b) The second alarm indicator light AL-2, when it alarms , the indicator light is ok , when it doesn’t , the
indicator light is off .
c) The calibration indicator light CAE , when the instrument do the automatic calibration operation , the
indicator light starts flickering , otherwise it will off .
d) The manual status indicator light MAN ,when the manual status selected , the light is on , when the
automatic state selected , it will be off .
4.5) CAE calibration (only applicable to pressure sensor with a calibration line)
Sure has been properly connected pressure sensor, and the current no pressure status;
In working state, instrument according to the instructions by 4.1 first, adjust to manual control status ;
Press "CAE", CAE lights;
The functional role : if "PV" shows deviation is too much , the instrument need to calibration;
If “PV” no change, can be initially determined sensor is faulty.
4.6) Using CAE calibration the instrument zero / span (only applicable to pressure
sensor with a calibration line)
Sure has been properly connected pressure sensor, and the current no pressure status;
In working state, instrument according to the instructions by 4.1 first, adjust to manual control status ;
press the "MODE" and "CAE" button at the same time, until the "SV" shows "0028", then loosen the button;
"SV" shows a digital countdown, timing to zero, zero span end of calibration.
Notice : in order to protect the parameters of the instrument user privacy, the meter no backdoor
password. So once the user changed the initial password, please your new password . If lost the new
password and cause parameters can be setting problem, the user need to ship back the instrument to the
manufacturer to unlock. All fees by the user.
For example : if the controller output is 0-10v , Output amplitude high limited value setting “ 80.0” ; then
the controller output maximum value will be 8V , no matter manual or automatic adjust , the controller
output value is not more than 8V .
The functional role: to prevent poor feeding, collection the coasters phenomenon caused by pressure
drop.The exact value setting , need users according to the actual usage Settings.
For example : if the controller output is 0-10v , Output amplitude high limited value setting “ 10.0” ; then
the controller output maximum value will be 1V , no matter manual or automatic adjust , the controller
output value is not less than 1V .
In the manual control , is not subject to this value, the lowest drops to zero.
The functional role: to prevent discharging stuck, instantaneous pressure caused by the phenomenon of
downtime. The exact value setting , need users according to the actual usage Settings.
For example : if the controller current range is “ 10.00 “ , and transducer pressure range is 15MPa ,
according to the above steps, and setting the controller range to "15.00".
For example : according to the 3 settings different value , The first pressure alarm (AL-1) value, the first
pressure alarm function (SEL1 ) and the first pressure alarm hysteresis zone ( HC-1)
Example 1 :
if setting the AL-1 as “5.00 “ , setting the SEL-1 as “HJ” , setting the HC-1 as “ 0.20 “ .
In working state, AL-1 relay working status as following :
Example 2 :
if setting the AL-1 as “5.00 “ , setting the SEL1 as “LJ” , setting the HC-1 as “ 0.20 “ .
In working state, AL-1 relay working status as following :
The functional role: the AL-2 is similar as AL-1 , but AL-2 no NC terminal , we just supply the NO terminal .
The functional role: type 0 adjustment range is big, is suitable for the plate making industry .
type 1 adjustment range is small, be applicable to the silk industry .
The functional role: if lock parameters setting 1 , next time the user enter menu setting need to input
the password .
5. Safety warning
5.1 ) the controller terminal for the bare installation, when the controller connected with the power , the
body any parts contact the terminal is not allowed
5.2 ) the controller is an open device, please avoid dust, corrosive liquid, high humidity too much or strong
vibration environment use.
5.3 ) when the instrument malfunction, please do not open the instrument without authorization.
Range
Model Input Output Power Supply Alarm Other requirement
(bar)
PD9001 * * * * * ---
Example: PD9001-350BAR-4-20mA-0-10V-220V-2