The document provides information about a MxNet module used for fire detection and suppression control panels. The module allows devices to be connected in a line-redundant loop network and communicate via a serial RS-232 interface. It can network up to 32 devices in a ring and is powered by the networked devices.

Uploaded by

long yu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
61 views

112 MINIMAX Data Sheet of MxNet Module

The document provides information about a MxNet module used for fire detection and suppression control panels. The module allows devices to be connected in a line-redundant loop network and communicate via a serial RS-232 interface. It can network up to 32 devices in a ring and is powered by the networked devices.

Uploaded by

long yu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Product Sheet I Detection

Fire detection and suppression control panels


Modules/cards

MxNet module Part no.: 904877


Functional module for use in all design variants of the
fire detection series FMZ 5000, as well as mimic panels and
operating panels.
Allows devices to be connected in a line-redundant loop
network. Communication with the connected devices takes
place via a serial interface in RS-232 standard.
All data lines are continuously monitored. In the event of
line faults in the network, line redundancy means that the
functions of the devices are not affected.
The module is supplied with power by the networked device.

Product features Application


• Communication to the networked devices uses The module enables a device to communicate with other
the MX2 protocol in all versions devices in a loop network. The signals from the devices
can be displayed at several central control points. Likewise,
• Up to 32 devices can be networked in a ring
commands to the devices are possible from different points in
• No adjustment work is required the network and from outside the network (control stations).
For each network participant a module required.

Technical specifications Included in delivery


Operating voltage 19 V - 29 V DC Module completely assembled and ready for installation in
the fire alarm panel
Quiescent current 58 mA DC
COM1 RS-232 SUB-D socket
Outputs Path 1 RS-485 modular terminal Note
Path 2 RS-485 modular terminal All parameters can be set using jumpers.
Max. terminal cross-section 2.5 mm2 (AWG 13) Module is preconfigured by jumpers.
Alternatively the module and the network can be configured
-5 °C to +40 °C
Ambient temperature centrally using the configuration program “MxNet.exe”.
(+23 °F to +104 °F)
Use of the module in a FMZ 5000 fired detection control
Relative humidity max. 95 % panel requires additionally a
(IEC 721-3-3) no condensation
module SIO1 903466
IP rating (EN 60529) IP 20
or
Enclosure Polyamide PA6.6, green
module SIO3 903467
Installation position vertical
The module must be placed directly to the right of the SIO
Mounting rail 35 mm DIN 46277, module. Activation is done via the R-232 interface by means
Mounting
top hat profile
of a ribbon cable.
The contents of this publication are subject to modifications without notice. All rights reserved.

Weight 200 g (0.4 lbs)


The network can be executed in fiber optics, for this the
35 x 99 x 114.5 mm (WxHxD) module FO-RS485 converters MxNet, part no. 922034, is
Dimensions
1.4 x 3.9 x 4.5 inch (WxHxD)
required.

Approvals / marking
See panels