DL8A Voltage/Ampere Meter User Manual

The document provides details about a DL8A series voltage/ampere meter, including its features, safety instructions, technical specifications, panel illustrations, and connection drawings. It has multiple input channels, measurement ranges, alarm and communication functions.

Uploaded by

vtor.str
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

DL8ASeries

DL8A Voltage/Ampere Meter User Manual

Features:
⊙Accuracy: 0.5%F.S.
⊙AC/DC universal (for AC signal it measures true value).
⊙Different input channel has different range, wide measuring range.
⊙Two Hi/Lo setting alarm output.
⊙With analog output 4-20mA.
⊙RS485 communication interface, Modbus RTU protocol.

For your safe, please read the below content carefully before you use the meter!
Safe Caution
Please read the manual carefully before you use the meter.
※ Please comply with the below important points.
Warning An accident may happen if the operation does not comply with the instruction.
Notice An operation that does not comply with the instruction may lead to product damage.
The instruction of the symbol in the manual is as below.
An accident danger may happen in a special condition.
Warning
1. safty protection equipment must be installed or please contact with us for the relative information if the product is used under the
1.A
circumstance such as nuclear control, medical treatment equipment, automobile, train, airplane, aviation and equipment etc.. Otherwise,
it may cause serious loss, fire or person injury.
2.
2.A panel must be installed, otherwise it may cause creepage (leakage).
3.Do not touch wire connectors when the power is on, otherwise you may get an electric shock.
3.
4.Do not dismantle or modify the product. If you have to do so, please contact with us first. Otherwise it may cause electric shock and fire.
4.
5.Please
5. check the connection number while you connect the power supply wire or input signal, otherwise it may cause fire.
Caution
1.This product cannot be used outdoors. Otherwise the working life of the product will become shorter, or an electric shock accident may happen.
2.When you connect wire to the power input connectors or signal input connectors, the moment of the No.20 AWG (0.50 mm) screw
2.
tweaked to the connector is 0.74n.m - 0.9n.m. Otherwise the connectors may be damaged or get fire.
3.
3.Please comply with the rated specification. Otherwise it may cause electric shock or fire, and damage the product.
4.Do not use water or oil base cleaner to clean the product. Otherwise it may cause electric shock or fire and damage the product.
5.This product should be avoid working under the circumstance that is flammable, explosive, moist, under sunshine, heat radiation and vibration.
Otherwise it may cause explosion.
6.In this unit it must not have dust or deposit, otherwise it may cause fire or mechanical malfunction.
7.Do not use gasoline, chemical solvent to clean the cover of the product because such solvent can damage it. Please use some soft cloth with water
7.
or alcohol to clean the plastic cover.
I. Code Illustration
DL8A - B Version code
Range
A:AC/DC current V:AC/DC voltage
10:No RS485 18:With RS485
B:One alarm C:Two alarms
A:No alarm R:Relay alarm
Blank: No analogue output I:4~20mA analogue output
DL8A series voltage/ampere meter
Model Input channel and Range Alarm Analog output Communication Default channel and range
DL8A-RC10V600 IN1:0~10V;IN2:0~100V;IN3:0~600V 2 alarm NO NO
DL8A-IRC10V600 IN1:0~10V;IN2:0~100V;IN3:0~600V 2 alarm 4-20mA NO IN3:600V
DL8A-IRC18V600 IN1:0~10V;IN2:0~100V;IN3:0~600V 2 alarm 4-20mA RS485
DL8A-RC10A1000 IN1:AC 0~5A IN2:DC 0~75mV 2 alarm NO NO
DL8A-IRC10A1000 IN1:AC 0~5A IN2:DC 0~75mV 2 alarm 4-20mA NO IN1:5A
DL8A-IRC18A1000 IN1:AC 0~5A IN2:DC 0~75mV 2 alarm 4-20mA RS485
DL8A-RC10A1 IN1:0~100mA、0~10mA IN2:0~1000mA 2 alarm NO NO
DL8A-IRC10A1 IN1:0~100mA、0~10mA IN2:0~1000mA 2 alarm 4-20mA NO IN2:1000mA
DL8A-IRC18A1 IN1:0~100mA、0~10mA IN2:0~1000mA 2 alarm 4-20mA RS485
△ ①When you use the meter, please pay attention that input channel should correspond to range, otherwise, the meter will be malfunction.
②Input signal < 1.2 times of range.
③When measuring AC signal, aviliable for 0~200Hz. When frequency is higher than 100Hz, the measuring accuracy is ±1%FS.

Psge 01 KKDL8AE01A-A/0-20170822
II. Technical Specification
Power Supply AC/DC 100~240V 50Hz/60Hz DC 24V(Need to be ordered)
Display range 0.001-9999 float decimal point display
Accuracy ±0.5%F.S ±2digits(For AC signal frequency under 100Hz)
Analog output 4~20mA load capacity≤600Ω, accuracy:±0.5%F.S
Communication RS485 communication interface,Modbus RTU Protocol
Relay capacity AC 250V/3A or DC 30V/5A
Between power supply connector and other connectors, relay output connectors and other connectors, AC 1800V leakage
Dielectric Strength current 0.5mA,60S;Between input signal connectors and low voltage signal output connectors, DC 600V leakage current
0.5mA,60S
Insulation Impedance ≥100MΩ/500V DC
Working environment Temperature:0-50℃ Humidity:≤85%RH
Sampling rate 5 times/S
Dimension 96W*48H*100L

III. Panel Illustration


Displaying measuring value/parameter code

AL1:Indicating lamp for alarm 11#


V: Voltage indication lamp
AL2:Indicating lamp for alarm 12#
A(mA): Current indication lamp

Decrease key

Increase key
Shift key
Displaying setting value SET: Parameter select/confirm key
or parameter setting

IV. Connection drawing


B- A+ COM 4~20mA
- AL2 B- A+ COM 4~20mA
- AL2
+←
+←






20 19 18 17 16 15 14 13 12 11 20 19 18 17 16 15 14 13 12 11

10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1









AC/DC AL1 IN3 IN2 IN1 GND AC/DC AL1 COM2 COM1
100~240V 100~240V
Voltage input Current input

Note:please subject to the diagram on the product if any changes.

V. Operations
①The second row LED is defaulted to display range and input channel alternately after power on, press ( ) to display range only, press ( ) to returns

to default display
②In the measuring status, press SET >3S to enter setting menu.
③When modifying setting value, press△/ to change value; press ( ) key to shift decimal point; after modifying, press SET key to confirm and enter


next menu. After setting, press SET key more than 3S to exit menu; if there is no operation for a long time, it will exit menu automatically.

No. Paremeter code Setting range Factory value Indication

1 INP IN1~IN3 For range A1000, the default one is IN1;for range A1,the default one is IN2;
for range V600,the default one is IN3
2 Ad1 H or L H
3 AL1 -1999~9999 90% of measuring range
4 Hy1 -1999~9999 1.000
5 Ad2 H or L L
6 AL2 -1999~9999 10% of measuring range AL,HY,Ct,PS,rH,rL
have the sameunit as
7 Hy2 -1999~9999 1.000 the Range.
8 Ct 0~9999 1.000
9 PS -1999~9999 0.000
10 rH -1999~9999 maximum of the range
11 rL -1999~9999 minimum of the range
12 Add 0~255 001
13 bAd 4.8 or 9.6 9.6
14 LCK 0~255 000

Psge 02
Measuring status operation setting
Power On


SET SET


Current Transforming: it is only for


Power supply 5A range or 75mV spliter current input.
Input Channel Selection:
ON If its value is set as the the ratio of external
Chosen from "IN1~IN3"
CT or spliter, the actual range should be CT*5.

SET


SET


All LED For other situation, CT is set as 1.
are on The first alarm mode: Amendment value,displaying value =
H:High;L:Low measured value +PS,factory setting:

Measuring SET
PS=0


SET


Status
The first alarm value setting Analog output high limit setting:
when measured value = rH set value,
the corresponding analogue output is 20mA
SET


SET
→ The first alarm hysteresis. For
example, if Ad1 is H, AL1=50,HY1=5,
Analog output low limit setting:
when measuring value≥50(AL1), alarm
when measured value = rL set value,
is active; when it is≤45(AL1-HY1),
the corresponding analogue output is 4mA
SET

SET


alarm is not active.

The second alarm mode: Add:Meter communication address


It is similar to Ad1.
SET

SET


The second alarm value setting: Communic:ation baud rate:


It is similar to AL1 4.8kbps、9.6kbps for option.
SET SET


Lock key
The second alarm hysteresis: Lock=000,read and write
It is similar to HY1. Lock=010,read only
SET

 VI. Mounting dimension


Front Side Mounting
100 ←
96 ← 91+0.5 30


← -0

← ←
← ←
88.5


45+0.5
-0

48

← ←
44
25←

VII. Notice for use and storage


1、It is suggested that the meter gets on power for 15 minutes before measuring.
2、Working environment is 0~50℃,humidity below 85%RH.
3、The calibration interval for this meter is one year.
4、Please keep the meter from shaking and shocking. Don’t place the meter in the environment full of excess dust and hazard chemicals and gas.
5、If the meter is not used for long time, please get on power every 3 months, each time not less than 4 hours.
6、To be stored in the environment at 0~50℃, humidity below 60%RH, no direct sunshine. The meter should not contact with organic solvent or oil.

VIII. Communication
This meter using Modbus RTU communication protocol, and it can run RS485 half-duplex communication. Read function code is 0x03, write function
code is 0x10, 16-bit CRC checking is applied. The meter don’t feedback error message. The communication data type is 32 bit integer data, true code stands
for positive number, complemental code stands for negative number, data rate is 0.001;for example, if the meter data received by host is 5000, then meter
data * rate = original data (5000*0.001=5.000). Therefore, when host writes meter, the data should multiply by rate 1000 before it is sent to the meter.
Data Frame format:
Start bit Data bit Stop bit Check bit
1 8 1 NO
Handling of abnormal communication:

If there is abnormal response put the function code on the top position 1. For example: Host request the function code 0x03,and the response function
code from slave should be 0x83.
Error type code:
0x02---Data location error:the request data location from host computer exceeds the range of the meter.
0x03---Data value error:the data value sent by host computer exceeds the data range of the meter.
CRC check error, function code error, don’t return value.
1. Read Multiple Registers
For example: The host computer read AL1(1st alarm value 5.0)
Address code of AL1 is 0x0000,32bit(4 byte),seizes 2 data registers; hexadecimal memory code of 5.0*1000=5000 is 0x00001388.
Host request(read multi-register)
1 2 3 4 5 6 7 8
Meter Add Function Code Startbit
address high Start address low Data bytelength high Data byte length low CRC code low bit CRC code high bit
bit bit bit
0x01 0x03 0x00 0x00 0x00 0x02 0xC4 0x0B

Slave normal answer(Read multi-register)


1 2 3 4 5 6 7 8 9
Meter Add Function Code Data byte number Data 1 high bit Data 1low bit Data 2 high bit Data 2 low bit CRC code low bit CRC code high bit
0x01 0x03 0x04 0x00 0x00 0x13 0x88 0xF7 0x65

Psge 03
Abnormal answer: (For example: host request function code 0x03)
Slave abnormal answer(Read multi-register)
1 2 3 4 5
Meter ADD Function code Error code CRC code low bit CRC code high bit
0x01 0x83 0x02 0xC2 0xC1
2. Write multi-register
For example: Host write HY1 (1st alarm value hysteresis 1.0)
ADD code of HY1 is 0x0001, because HY1(4 byte), seizes 2 data registers. The hexadecimal memory code of decimal floating point number
1.0 *1000=1000 is 0x000003E8.
Host request (write multi-register)
1 2 3 4 5 6 7 8 9 10 11 12 13
Function Start ADD Start ADD Data byte Data byte Data byte Data 1 Data 1 Data 2 Data 2 CRC code CRC code
Meter ADD Length Length
code High bit Low bit high bit low bit Length high bit low bit high bit low bit low bit high bit
0x01 0x10 0x00 0x01 0x00 0x02 0x04 0x00 0x00 0x03 0xE8 0x32 0xDD
Slave normal answer (write multi-register)
1 2 3 4 5 6 7 8
Meter ADD Function code Start ADD Start ADD Data byte Length Data byte Length CRC code low CRC code high
high 8 bit low 8 bit high bit low bit bit bit
0x01 0x10 0x00 0x01 0x00 0x02 0x10 0x08
Data location error response: (For example:Host request the ADD index is 0x0050)
Slave abnormal answer (write multi-register)
1 2 3 4 5
Meter ADD Function code Error code CRC code low bit CRC code high bit
0x01 0x90 0x02 0xCD 0xC1
Address Mapping Table of Meter Parameters
No ADD Variable name Data Range Rate Read/write Remark
mapping Length
0 0x0000 1st loop alarm value AL1 2 -1999~9999 0.001 R/W
2 0x0002 1st loop alarm hysteresis HY1 2 -1999~9999 0.001 R/W
4 0x0004 2nd loop alarm value AL2 2 -1999~9999 0.001 R/W

6 0x0006 2nd loop alarm hysteresis HY2 2 -1999~9999 0.001 R/W
8 0x0008 Coefficient Ct 2 0~9999 0.001 R/W
10 0x000A Analog output high limit value rH 2 -1999~9999 0.001 R/W
12 0x000C Analog output low limit value rL 2 -1999~9999 0.001 R/W
14 0x000E Amendment value PS 2 -1999~9999 0.001 R/W
16 0x0010 Read measured value 2 0~9999 0.001 R
Reserve
29 0x001D INP measure channel 1 0~2 1 R/W
30 0x001E 1st loop alarm type Ad1 1 0~1 1 R/W Note ①
31 0x001F 2nd loop alarm type Ad2 1 0~1 1 R/W Note ①
32 0x0020 Alarm status indication 1 0~3 1 R Note ③
33 0x0021 Baud rate 1 0~1 1 R Note ②
34 0x0022 Meter address Add 1 0x255 1 R
35 0x0023 Meter name 1 0xD1 1 R
Reserve
R: read only; R/W: read/write.
Note ①:alarm type Note ②: baud rate Note ③: alarm status indiction
High limit alarm H
Communication D7 D6 D5 D4 D3 D2 D1 D0
0 1
Communication value 1 value AL2 AL1
Low limit alarm L Menu display 4.8 9.6
Communication value 0

16 digits CRC check code acquisition program


unsigned int Get_CRC(uchar *pBuf, uchar num)
{
unsigned i,j;
unsigned int wCrc = 0xFFFF;
for(i=0; i<num; i++)
{
wCrc ^= (unsigned int)(pBuf[i]);
for(j=0; j<8; j++)
{
if(wCrc & 1){wCrc >>= 1; wCrc ^= 0xA001; }
else
wCrc >>= 1;
}
}
return wCrc;
}