Ba Scalance XC 200 76
Ba Scalance XC 200 76
Safety notices 2
Security recommendations 3
SIMATIC NET
Description of the device 4
Industrial Ethernet switches
SCALANCE XC-200 5
Assembly and disassembly
Connecting up 6
Operating Instructions
Troubleshooting 8
Technical specifications 9
Dimension drawings 10
02/2023
C79000-G8976-C442-14
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance
are required to ensure that the products operate safely and without any problems. The permissible ambient
conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
1 Introduction ........................................................................................................................................... 7
2 Safety notices ...................................................................................................................................... 13
3 Security recommendations.................................................................................................................. 15
4 Description of the device ..................................................................................................................... 23
4.1 Product overview ............................................................................................................... 23
4.2 Device views ...................................................................................................................... 29
4.2.1 SCALANCE XC206-2 (ST/BFOC) ........................................................................................... 29
4.2.2 SCALANCE XC206-2 (SC).................................................................................................... 30
4.2.3 SCALANCE XC206-2G PoE .................................................................................................. 31
4.2.4 SCALANCE XC206-2SFP...................................................................................................... 32
4.2.5 SCALANCE XC208 .............................................................................................................. 32
4.2.6 SCALANCE XC208G PoE ..................................................................................................... 34
4.2.7 SCALANCE XC216 .............................................................................................................. 35
4.2.8 SCALANCE XC216-3G PoE .................................................................................................. 36
4.2.9 SCALANCE XC216-4C ......................................................................................................... 36
4.2.10 SCALANCE XC224 .............................................................................................................. 38
4.2.11 SCALANCE XC224-4C ......................................................................................................... 39
4.3 Accessories ........................................................................................................................ 39
4.4 SELECT / SET button ........................................................................................................... 44
4.5 LED display ........................................................................................................................ 46
4.5.1 Overview ........................................................................................................................... 46
4.5.2 "RM" LED............................................................................................................................ 47
4.5.3 "SB" LED............................................................................................................................. 47
4.5.4 "F" LED............................................................................................................................... 47
4.5.5 LEDs "DM1" and "DM2"....................................................................................................... 47
4.5.6 LEDs "L1" and "L2" .............................................................................................................. 48
4.5.7 Port LEDs ........................................................................................................................... 49
4.6 C-PLUG .............................................................................................................................. 50
4.6.1 Function of the C-PLUG ...................................................................................................... 50
4.6.2 Replacing the C-PLUG......................................................................................................... 52
4.7 Combo ports...................................................................................................................... 53
4.8 Power over Ethernet (PoE).................................................................................................. 54
4.8.1 Power and voltage range according to the standard............................................................ 54
4.8.2 PoE properties of the devices ............................................................................................. 54
4.8.3 Power transfer and pin assignment (30 W) ......................................................................... 56
4.8.4 Power transfer and pin assignment (60 W) ......................................................................... 56
4.8.5 Configuration..................................................................................................................... 57
5 Assembly and disassembly .................................................................................................................. 59
5.1 Safety notices for installation ............................................................................................. 59
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 3
Table of contents
SCALANCE XC-200
4 Operating Instructions, 02/2023, C79000-G8976-C442-14
Table of contents
9.5 Technical specifications of SCALANCE XC206-2G PoE EEC (54 V) ....................................... 104
9.6 Technical specifications SCALANCE XC206-2SFP ............................................................... 107
9.7 Technical specifications of SCALANCE XC206-2SFP G ........................................................ 109
9.8 Technical specifications of SCALANCE XC206-2SFP EEC ..................................................... 111
9.9 Technical specifications of SCALANCE XC206-2SFP G EEC.................................................. 114
9.10 Technical specifications of the SCALANCE XC208 .............................................................. 117
9.11 Technical specifications of SCALANCE XC208G.................................................................. 119
9.12 Technical specifications of SCALANCE XC208G PoE ........................................................... 121
9.13 Technical specifications of SCALANCE XC208G PoE (54 V) ................................................. 123
9.14 Technical specifications of SCALANCE XC208EEC .............................................................. 125
9.15 Technical specifications of SCALANCE XC208G EEC ........................................................... 127
9.16 Technical specifications of the SCALANCE XC216 .............................................................. 129
9.17 Technical specifications of SCALANCE XC216EEC .............................................................. 131
9.18 Technical specifications of SCALANCE XC216-3G PoE ........................................................ 132
9.19 Technical specifications of SCALANCE XC216-3G PoE (54 V).............................................. 134
9.20 Technical specifications of SCALANCE XC216-4C............................................................... 137
9.21 Technical specifications of SCALANCE XC216-4C G............................................................ 139
9.22 Technical specifications of SCALANCE XC216-4C G EEC ..................................................... 141
9.23 Technical specifications of the SCALANCE XC224 .............................................................. 144
9.24 Technical specifications of SCALANCE XC224-4C G............................................................ 146
9.25 Technical specifications of SCALANCE XC224-4C G EEC ..................................................... 148
9.26 Mechanical stability (in operation) ................................................................................... 151
9.27 RF radiation according to NAMUR NE21............................................................................ 151
9.28 Cable lengths................................................................................................................... 151
9.29 Switching properties ........................................................................................................ 152
10 Dimension drawings .......................................................................................................................... 153
11 Certifications and approvals .............................................................................................................. 161
Index .................................................................................................................................................. 169
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 5
Table of contents
SCALANCE XC-200
6 Operating Instructions, 02/2023, C79000-G8976-C442-14
Introduction 1
Purpose of the Operating Instructions
These operating instructions support you when installing and connecting up devices of the
SCALANCE XC-200 product group.
The configuration and the integration of the devices in a network are not described in these
operating instructions.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 7
Introduction
• SCALANCE XC224-4C G
• SCALANCE XC224-4C G EEC
Unless mentioned otherwise, the descriptions in these operating instructions refer to all
devices of the SCALANCE XC-200 product group named above in the section on validity.
Designations used
Additional documentation
In addition, note the Operating Instructions of the pluggable transceivers.
You will find the supplementary documentation here:
• On the data medium that ships with some products:
– Product CD / product DVD
– SIMATIC NET Manual Collection
• On the Internet pages of Siemens Industry Online Support (https://
support.industry.siemens.com/cs/ww/en/ps/15247)
SCALANCE XC-200
8 Operating Instructions, 02/2023, C79000-G8976-C442-14
Introduction
Documentation on configuration
You will find detailed information on configuring the devices in the following configuration
manuals:
• SCALANCE XB-200/XC-200/XF-200BA/XF-200G/XP-200/XR-300WG Web Based Management
• SCALANCE XB-200/XC-200/XF-200BA/XF-200G/XP-200/XR-300WG Command Line Interface
You will find the configuration manuals here:
• on the data medium that ships with some products:
– Product CD / product DVD
– SIMATIC NET Manual Collection
• On the Internet pages of Siemens Industry Online Support (https://
support.industry.siemens.com/cs/ww/en/ps/24185/man).
Further documentation
In the system manuals "Industrial Ethernet / PROFINET Industrial Ethernet" and "Industrial
Ethernet / PROFINET passive network components", you will find information on other SIMATIC
NET products that you can operate along with the devices of this product line in an Industrial
Ethernet network.
There, you will find among other things optical performance data of the communications
partner that you require for the installation.
You will find the system manuals here:
• On the data medium that ships with some products:
– Product CD / product DVD
– SIMATIC NET Manual Collection
• On the Internet pages of Siemens Industry Online Support:
– Industrial Ethernet / PROFINET Industrial Ethernet System Manual (https://
support.industry.siemens.com/cs/ww/en/view/27069465)
– Industrial Ethernet / PROFINET Passive Network Components System Manual (https://
support.industry.siemens.com/cs/ww/en/view/84922825)
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 9
Introduction
Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is necessary
and only when appropriate security measures (e.g. firewalls and/or network segmentation)
are in place.
For additional information on industrial security measures that may be implemented, please
visit
https://www.siemens.com/industrialsecurity (https://www.siemens.com/industrialsecurity).
Siemens’ products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends that product updates are applied as soon as they are
available and that the latest product versions are used. Use of product versions that are no
longer supported, and failure to apply the latest updates may increase customer’s exposure
to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed under
https://www.siemens.com/cert (https://www.siemens.com/cert).
Catalogs
You will find the article numbers for the Siemens products of relevance here in the following
catalogs:
• SIMATIC NET Industrial Communication / Industrial Identification, catalog IK PI
• SIMATIC Products for Totally Integrated Automation and Micro Automation, catalog ST 70
• Industry Mall - catalog and ordering system for automation and drive technology, Online
catalog (https://mall.industry.siemens.com/goos/WelcomePage.aspx?regionUrl=/
de&language=en)
You can request the catalogs and additional information from your Siemens representative.
SCALANCE XC-200
10 Operating Instructions, 02/2023, C79000-G8976-C442-14
Introduction
Device defective
If a fault develops, send the device to your SIEMENS representative for repair. Repairs on-site are
not possible.
Decommissioning
Shut down the device properly to prevent unauthorized persons from accessing confidential
data in the device memory.
To do this, restore the factory settings on the device.
Also restore the factory settings on the storage medium.
Trademarks
The following and possibly other names not identified by the registered trademark sign ® are
registered trademarks of Siemens AG:
SCALANCE, C-PLUG, OLM
Electrostatic discharge
NOTICE
Electrostatic sensitive devices (ESD)
Electronic modules contain electrostatic sensitive components
These components can easily be destroyed if handled incorrectly.
Note the following instructions to avoid damage.
• Touch electronic modules only when you absolutely need to work on them.
• If electronic modules need to be touched, the body of the person involved must first be
electrostatically discharged and grounded.
• Do not bring electronic modules in contact with electrically isolating materials such as
plastic film, isolating table top pads or clothing made of synthetic fibers.
• Place the modules only on conductive surfaces.
• Pack, store and transport electronic modules and components only in conductive packaging
such as metalized plastic or metal containers, conductive foam or household aluminum foil.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 11
Introduction
SCALANCE XC-200
12 Operating Instructions, 02/2023, C79000-G8976-C442-14
Safety notices 2
Read the safety notices
Note the following safety notices. These relate to the entire working life of the device.
You should also read the safety notices relating to handling in the individual sections,
particularly in the sections "Installation" and "Connecting up".
CAUTION
To prevent injury and damage, read the manual before using the device.
WARNING
EXPLOSION HAZARD
Do not open the device when the supply voltage is turned on.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 13
Safety notices
SCALANCE XC-200
14 Operating Instructions, 02/2023, C79000-G8976-C442-14
Security recommendations 3
NOTICE
Information security
Connect to the device and change the standard password for the user set in the factory "admin"
and "" before you operate the device.
To prevent unauthorized access to the device and/or network, observe the following security
recommendations.
General
• Check the device regularly to ensure that these recommendations and/or other internal
security policies are complied with.
• Evaluate the security of your location and use a cell protection concept with suitable products
(https://www.industry.siemens.com/topics/global/en/industrial-security/pages/
default.aspx).
• When the internal and external network are disconnected, an attacker cannot access internal
data from the outside. Therefore operate the device only within a protected network area.
• No product liability will be accepted for operation in a non-secure infrastructure.
• Use VPN to encrypt and authenticate communication from and to the devices.
• For data transmission via a non-secure network, use an encrypted VPN tunnel (IPsec,
OpenVPN).
• Separate connections correctly (WBM, SSH etc.).
• Check the user documentation of other Siemens products that are used together with the
device for additional security recommendations.
• Using remote logging, ensure that the system protocols are forwarded to a central logging
server. Make sure that the server is within the protected network and check the protocols
regularly for potential security violations or vulnerabilities.
Physical access
• Restrict physical access to the device to qualified personnel because the plug-in data medium
can contain sensitive data.
• Lock unused physical interfaces on the device. Unused interfaces can be used to gain access
to the plant without permission.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 15
Security recommendations
Authentication
Note
Accessibility risk - Risk of data loss
Do not lose the passwords for the device. Access to the device can only be restored by resetting
the device to factory settings which completely removes all configuration data.
• Replace the default passwords for all user accounts, access modes and applications (if
applicable) before you use the device.
• Define rules for the assignment of passwords.
• Use passwords with a high password strength. Avoid weak passwords, (e.g. password1,
123456789, abcdefgh) or recurring characters (e.g. abcabc).
This recommendation also applies to symmetrical passwords/keys configured on the device.
• Make sure that passwords are protected and only disclosed to authorized personnel.
• Do not use the same passwords for multiple user names and systems.
• Store the passwords in a safe location (not online) to have them available if they are lost.
• Regularly change your passwords to increase security.
• A password must be changed if it is known or suspected to be known by unauthorized
persons.
• When user authentication is performed via RADIUS, make sure that all communication takes
place within the security environment or is protected by a secure channel.
• Watch out for link layer protocols that do not offer their own authentication between
endpoints, such as ARP or IPv4. An attacker could use vulnerabilities in these protocols to
attack hosts, switches and routers connected to your layer 2 network, for example, through
manipulation (poisoning) of the ARP caches of systems in the subnet and subsequent
interception of the data traffic. Appropriate security measures must be taken for non-secure
layer 2 protocols to prevent unauthorized access to the network. Physical access to the local
network can be secured or secure, higher layer protocols can be used, among other things.
SCALANCE XC-200
16 Operating Instructions, 02/2023, C79000-G8976-C442-14
Security recommendations
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 17
Security recommendations
Interfaces security
• Disable unused interfaces.
• Use IEEE 802.1X for interface authentication.
• Use the function "Locked Ports" to block interfaces for unknown nodes.
• Use the configuration options of the interfaces, e.g. the "Edge Type".
• Configure the receive ports so that they discard all untagged frames ("Tagged Frames Only").
Available protocols
The following list provides you with an overview of the open protocol ports.
The table includes the following columns:
• Protocol
• Port
• Default port status
– Open
The factory setting of the port is "Open".
– Closed
The factory setting of the port is "Closed".
SCALANCE XC-200
18 Operating Instructions, 02/2023, C79000-G8976-C442-14
Security recommendations
• Configurable port
– ✓
The port status can be changed.
– --
The port status cannot be changed.
• Authentication
Specifies whether the communication partner is authenticated.
• Encryption
Specifies whether or not the transfer is encrypted.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 19
Security recommendations
The following is a list of all available Layer 2 services through which the device can be
accessed.
The table includes the following columns:
• Layer 2 service
The Layer 2 services that the device supports.
• Default status
The default status of the service (open or closed).
• Service configurable
Indicates whether the service can be configured via WBM / CLI.
SCALANCE XC-200
20 Operating Instructions, 02/2023, C79000-G8976-C442-14
Security recommendations
RSTP Closed ✓
MSTP Open ✓
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 21
Security recommendations
SCALANCE XC-200
22 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device 4
4.1 Product overview
Article numbers
There are two variants of some devices with different article numbers. The two variants differ
only in their factory settings. All other properties are identical.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 23
Description of the device
4.1 Product overview
SCALANCE XC-200
24 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.1 Product overview
Factory settings
EtherNet/IP variants
• Industrial Ethernet protocol: EtherNet/IP
• Base Bridge Mode: 802.1Q VLAN Bridge
• Redundancy mode: RSTP
• Trust mode: Trust CoS-DSCP
• IGMP Snooping/IGMP Querier: On
• IPv4 Address Collision Detection: Attempt to defend
PROFINET variants
• Industrial Ethernet protocol: PROFINET
• Base Bridge Mode: 802.1D transparent bridge
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 25
Description of the device
4.1 Product overview
Type designation
The type designation of a SCALANCE XC-200 is made up of several parts that have the following
meaning:
XC2 -
[-]
C
EEC
G
PoE
SFP
Number of optical connectors
Number of electrical connectors
SCALANCE XC-200
26 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.1 Product overview
Interface Property
C Combo port
EEC Enhanced Environment Conditions (coated PCB)
G Gigabit
PoE Power over Ethernet
SFP Pluggable transceiver slot
WARNING
Do not use any parts that show evidence of damage
If you use damaged parts, there is no guarantee that the device will function according to the
specification.
If you use damaged parts, this can lead to the following problems:
• Injury to persons
• Loss of the approvals
• Violation of the EMC regulations
• Damage to the device and other components
Use only undamaged parts.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 27
Description of the device
4.1 Product overview
Spare parts
The following spare parts are available for SCALANCE XC-200:
SCALANCE XC-200
28 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.2 Device views
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 29
Description of the device
4.2 Device views
SCALANCE XC-200
30 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.2 Device views
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 31
Description of the device
4.2 Device views
SCALANCE XC-200
32 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.2 Device views
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 33
Description of the device
4.2 Device views
D D
E E
SCALANCE XC-200
34 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.2 Device views
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 35
Description of the device
4.2 Device views
D D
E E
E E
SCALANCE XC-200
36 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.2 Device views
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 37
Description of the device
4.2 Device views
SCALANCE XC-200
38 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.3 Accessories
4.3 Accessories
The following accessories are available for SCALANCE XC-200:
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 39
Description of the device
4.3 Accessories
C-PLUG
Cable
The SFP plug-in transceiver (100 Mbps) cannot be operated in SFP+ slots.
Pluggable transceivers with the supplement (C) in the type name have varnished printed circuit boards
(conformal coating).
Note
Restriction for pluggable transceivers
The maximum ambient temperature changes if you use pluggable transceivers.
You can find the corresponding values for the ambient temperature in the section "Technical
specifications (Page 95)".
SCALANCE XC-200
40 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.3 Accessories
Note
You cannot use the pluggable transceiver SFP (100 Mbps) with the following devices:
• Gigabit versions (suffix "G" in the type designation)
• Devices with combo ports (suffix "C" in the type designation)
Use active pluggable transceivers to connect these devices via optical 100 Mbps connections.
Note
Restriction for pluggable transceivers
The maximum ambient temperature changes if you use pluggable transceivers.
You can find the corresponding values for the ambient temperature in the section "Technical
specifications (Page 95)".
Note
Active plug-in transceivers can be used with the following devices:
• SCALANCE XC206-2G PoE
• SCALANCE XC206-2G PoE (54 V)
• SCALANCE XC206-2G PoE EEC (54 V)
• SCALANCE XC-206-2SFP G
• SCALANCE XC-206-2SFP G EEC
• SCALANCE XC208G PoE
• SCALANCE XC208G PoE (54 V)
• SCALANCE XC216-3G PoE
• SCALANCE XC216-3G PoE (54 V)
• SCALANCE XC-216-4C
• SCALANCE XC-216-4C G
• SCALANCE XC-216-4C G EEC
• SCALANCE XC-224-4C G
• SCALANCE XC-224-4C G EEC
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 41
Description of the device
4.3 Accessories
Pluggable transceivers with the supplement (C) in the type name have varnished printed circuit boards
(conformal coating).
Note
Restriction for pluggable transceivers
The maximum ambient temperature changes if you use pluggable transceivers.
You can find the corresponding values for the ambient temperature in the section "Technical
specifications (Page 95)".
SCALANCE XC-200
42 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.3 Accessories
Note
Restriction for pluggable transceivers
The maximum ambient temperature changes if you use pluggable transceivers.
You can find the corresponding values for the ambient temperature in the section "Technical
specifications (Page 95)".
SFP+ transceiver
Note
Restriction for pluggable transceivers
The maximum ambient temperature changes if you use pluggable transceivers.
You can find the corresponding values for the ambient temperature in the section "Technical
specifications (Page 95)".
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 43
Description of the device
4.4 SELECT / SET button
Position
The "SELECT/SET" button is located on the front of the device.
6(/(&7
6(7
Figure 4-1 Position of the "SELECT/SET" button, for example on the SCALANCE XC-200 with 8 ports
NOTICE
Previous settings
If you reset, all the settings you have made will be overwritten by factory defaults.
NOTICE
Inadvertent reset
An inadvertent reset can cause disturbances and failures in the configured network.
SCALANCE XC-200
44 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.4 SELECT / SET button
Requirement
• The device is in operation.
• The function "Reset to Factory Defaults" is enabled for the "SELECT / SET" button.
Note
Reset despite disabled "SELECT/SET" button
If you have disabled the "Restore Factory Defaults" function for the "SELECT/SET" button in the
configuration, this does not apply during the startup phase, see section "Restoring the
factory settings (Page 94)".
If the function has been disabled in the configuration, it is only disabled on completion of the
startup phase.
Procedure
To reset the device to the factory defaults during operation, follow the steps below:
1. Switch to display mode A.
Display mode A is active if the LEDS "DM1" and "DM2" are unlit.
If the "DM1" and "DM2" LEDs are lit or flashing, you will need to press the "SET/SELECT"
repeatedly until the "DM1" and "DM2" LEDs go off.
If you do not press the "SELECT/SET" button for longer than 1 minute, the device
automatically changes to display mode A.
2. Hold down the "SELECT/SET" button for 12 seconds.
After 9 seconds,the "DM1" and "DM2" LEDs start to flash for 3 seconds. At the same time, the
port LEDs go on one after the other.
After you have held down the button for 12 seconds, the device restarts and the factory
defaults are restored.
If you release the button before the 12 seconds have elapsed, the reset is canceled.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 45
Description of the device
4.5 LED display
4.5.1 Overview
The following figure shows the arrangement of the LEDs based on the example of a SCALANCE
XC-200 with 8 ports.
) 3
50 3
6% 3
'0 3
'0 3
3
/ 3
/ 3
SCALANCE XC-200
46 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.5 LED display
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 47
Description of the device
4.5 LED display
There are 5 display modes (A, B, C, D, and E). Display mode A is the default mode.
Depending on the set display mode, the "L1", "L2" LEDs and the port LEDs show different
information.
SCALANCE XC-200
48 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.5 LED display
If there is a connection problem and the type of transmission is fixed (auto negotiation
off), the desired status, in other words the set transmission speed (10 Gbps, 1000 Mbps,
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 49
Description of the device
4.6 C-PLUG
100 Mbps, 10 Mbps) continues to be displayed. If there is a connection problem and auto
negotiation is active, the port LED goes off.
4.6 C-PLUG
NOTICE
Do not remove or insert a C-PLUG during operation
A C-PLUG may only be removed or inserted when the device is turned off.
SCALANCE XC-200
50 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.6 C-PLUG
Note
The device can also be operated without a C-PLUG.
How it works
Operating mode
In terms of the C-PLUG, there are three modes for the device:
• Without C-PLUG
The device stores the configuration in internal memory.
This mode is active if no C-PLUG is inserted.
• With unwritten C-PLUG
If an unwritten C-PLUG (factory status or deleted with Clean function) is used, the local
configuration already existing on the device is automatically stored on the inserted C-PLUG
during startup.
This mode is active as soon as an unwritten C-PLUG is inserted.
• With written C-PLUG
A device with a written and accepted C-PLUG uses the configuration data of the C-PLUG
automatically when it starts up. The requirement for acceptance is that the data was written
by a compatible device type.
If there is configuration data in the internal memory of the device this is overwritten.
This mode is active as soon as a written C-PLUG is inserted.
Response to errors
Inserting a C-PLUG that does not contain the configuration of a compatible device type and
inadvertently removing the C-PLUG, or general malfunctions of the C-PLUG are indicated by the
diagnostic mechanisms of the device.
• Fault LED
• Web Based Management (WBM)
• SNMP
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 51
Description of the device
4.6 C-PLUG
NOTICE
Do not remove or insert a C-PLUG during operation
The C-PLUG may only be removed or inserted when the device is turned off.
Replacing a C-PLUG.
Removing a C-PLUG
A
1. Turn off the power to the device.
2. Insert a screwdriver between the front edge of the C-PLUG (A) and the slot and release the C-
PLUG.
3. Remove the C-PLUG.
SCALANCE XC-200
52 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.7 Combo ports
Inserting a C-PLUG
Characteristics
Combo port is the name for two communication ports. A combo port has the two following jacks:
• a fixed RJ-45 port
• an SFP transceiver slot that can be equipped individually
Of these two ports, only one can ever be active. Using the mode, you can decide how the
ports are prioritized.
The port name is the same on both jacks of the combo port, for example "PxC".
There is an LED for each combo port. The LEDs for the combo ports can be identified by a vertical
line and the word "COMBO". The labeling of the combo port LEDs does not differ from that of the
other LEDs, e.g. "P3".
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 53
Description of the device
4.8 Power over Ethernet (PoE)
Function
The "Power over Ethernet" function supplies connected devices with power via the Ethernet
cable. Devices supplied with power via an Ethernet cable do not require a separate voltage
source.
PoE-compliant devices can be divided into the following groups:
• Power source (PSE - Power Sourcing Equipment)
These inject power onto the Ethernet cable.
• Power consumer (PD - Powered Device)
These are supplied with power via the Ethernet cable.
PoE class Power supplied by the pow‐ Available power at the pow‐ Type Standard Designation
er source ered device
0 15.4 W 12.95 W 1 IEEE802.3af PoE
1 4 3.84 W
2 7 6.49 W
3 15.4 W 12.95 W
4 30 25.5 W 2 IEEE802.3at PoE+
5 45 40 W 3 IEEE802.3bt 4-pair PoE
6 60 51 W
7 75 62 W 4
8 90 73 W
Note
Turn off the power source before you disconnect the PoE cable of a power consumer.
SCALANCE XC-200
54 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.8 Power over Ethernet (PoE)
Power source
• The device can supply energy consumers of the standards IEEE802.af Type 1, IEEE802.at
Type 2 or IEEE802.3bt Type 3.
• In total, a power source can make the following PoE power available (incl. line losses):
– PoE variants with 24 V DC: 120 W
– SCALANCE XC206-2G PoE with 54 V DC: 240 W
– SCALANCE XC216-3G PoE with 54 V DC: 300 W
The power can be distributed to the ports as desired.
Note that the PoE power is reduced for installation positions other than horizontal; see
sections "Technical specifications (Page 95)" and "Types of installation (Page 62)".
PoE ports
• The PoE ports are not isolated from each other. This means that they meet the conditions
named in Environment A (IEEE 802.3): Power supply over Ethernet within a power supply
system.
• The electrical isolation of the ports from functional grounding is designed for 1500 Vrms (1
minute) (according to Section 5.2.2 of IEC 60950-1:2001).
• The following ports support PoE classes 0 to 4:
Device Port
SCALANCE XC206-2G PoE Port 1 to port 4
SCALANCE XC206-2G PoE (54 V)
SCALANCE XC206-2G PoE EEC (54 V)
SCALANCE XC208G PoE Port 3 to port 6
SCALANCE XC208G PoE (54 V)
SCALANCE XC216-3G PoE Port 8 to port 19
SCALANCE XC216-3G PoE (54 V)
The ports supply connected devices with up to 30 W per port (according to IEEE802.3af and
IEEE802.3at).
• The following ports support PoE classes 0 to 6:
Device Port
SCALANCE XC206-2G PoE Port 5 and port 6
SCALANCE XC206-2G PoE (54 V)
SCALANCE XC206-2G PoE EEC (54 V)
SCALANCE XC208G PoE Port 7 and port 8
SCALANCE XC208G PoE (54 V)
SCALANCE XC216-3G PoE Port 6 and port 7
SCALANCE XC216-3G PoE (54 V)
They supply connected devices with up to 60 W per port (according to IEEE802.3af,
IEEE802.3at and IEEE802.3bt).
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 55
Description of the device
4.8 Power over Ethernet (PoE)
Device Port
SCALANCE XC206-2G PoE Port 1 to port 4
SCALANCE XC206-2G PoE (54 V)
SCALANCE XC206-2G PoE EEC (54 V)
SCALANCE XC208G PoE Port 3 to port 6
SCALANCE XC208G PoE (54 V)
SCALANCE XC216-3G PoE Port 8 to port 19
SCALANCE XC216-3G PoE (54 V)
Device Port
SCALANCE XC206-2G PoE Port 5 and port 6
SCALANCE XC206-2G PoE (54 V)
SCALANCE XC206-2G PoE EEC (54 V)
SCALANCE XC208G PoE Port 7 and port 8
SCALANCE XC208G PoE (54 V)
SCALANCE XC216-3G PoE Port 6 and port 7
SCALANCE XC216-3G PoE (54 V)
SCALANCE XC-200
56 Operating Instructions, 02/2023, C79000-G8976-C442-14
Description of the device
4.8 Power over Ethernet (PoE)
4.8.5 Configuration
How you activate and configure PoE is described in the configuration manuals, see section
"Introduction", section "Documentation on configuration".
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 57
Description of the device
4.8 Power over Ethernet (PoE)
SCALANCE XC-200
58 Operating Instructions, 02/2023, C79000-G8976-C442-14
Assembly and disassembly 5
5.1 Safety notices for installation
Safety notices
When installing the device, keep to the safety notices listed below.
WARNING
If a device is operated in an ambient temperature of more than 55 °C, the temperature of the
device enclosure may be higher than 70 °C. The device must therefore be installed so that it is
only accessible to service personnel or users that are aware of the reason for restricted access
and of the required safety measures at an ambient temperature higher than 55 to 70 °C.
WARNING
If the device is installed in a cabinet, the inner temperature of the cabinet corresponds to the
ambient temperature of the device.
WARNING
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors exceeds
80 °C, special precautions must be taken. If the equipment is operated in an air ambient in
excess of 60 ℃, only use cables with admitted maximum operating temperature of at least 80
℃.
NOTICE
Improper mounting
Improper mounting may damage the device or impair its operation.
• Before mounting the device, always ensure that there is no visible damage to the device.
• Mount the device using suitable tools. Observe the information in the respective section
about mounting.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 59
Assembly and disassembly
5.1 Safety notices for installation
WARNING
EXPLOSION HAZARD
Replacing components may impair suitability for Class 1, Division 2 or Zone 2.
WARNING
The device is intended for indoor use only.
WARNING
The device may only be operated in an environment of contamination class 1 or 2 (see EN/IEC
60664-1, GB/T 16935.1).
WARNING
When used in hazardous environments corresponding to Class I, Division 2 or Class I, Zone 2,
the device must be installed in a cabinet or a suitable enclosure.
Notes for use in hazardous locations according to ATEX, IECEx, UKEX and CCC Ex
If you use the device under ATEX, IECEx, UKEX or CCC Ex conditions you must also keep to
the following safety instructions in addition to the general safety instructions for protection
against explosion:
WARNING
To comply with EU Directive 2014/34 EU (ATEX 114), UK-Regulation SI 2016/1107 or the
conditions of IECEx or CCC-Ex, the housing or cabinet must meet the requirements of at least
IP54 (according to EN/IEC 60529, GB/T 4208) in compliance with EN IEC/IEC 60079‑7, GB
3836.3.
WARNING
If the temperature of the cable or housing socket exceeds 60 °C or the temperature at the
branching point of the cables exceeds 80 °C, special precautions must be taken. If the
equipment is operated in an air ambient in excess of 60 ℃, only use cables with admitted
maximum operating temperature of at least 80 ℃.
SCALANCE XC-200
60 Operating Instructions, 02/2023, C79000-G8976-C442-14
Assembly and disassembly
5.1 Safety notices for installation
WARNING
EXPLOSION HAZARD
For operation the device is intended to be installed within an enclosure/control cabinet. The
inner temperature of the enclosure/control cabinet corresponds to the ambient temperature of
the device. Use installation wiring connections with admitted maximum operating
temperature of at least 30 °C higher than maximum ambient temperature.
The following instructions for wall mounting apply only to devices with a mounting latch:
WARNING
Wall mounting outside of the control cabinet or housing does not fulfill the requirements of the
FM approval.
WARNING
Wall mounting is only permitted if the requirements for the housing, the installation
regulations, the clearance and separating regulations for the control cabinets or housings are
adhered to. The control cabinet cover or housing must be secured so that it can only be opened
with a tool. An appropriate strain-relief assembly for the cable must be used.
Safety notices when using the device as industrial control equipment according to UL
61010-2-201
If you use the device under UL 61010-2-201 conditions you must also keep to the following
safety notices in addition to the general safety notices for protection against explosion:
WARNING
Open equipment
The devices are "open equipment" according to the standard IEC 61010-2-201 or UL
61010-2-201 / CSA C22.2 No. 61010-2-201. To fulfill requirements for safe operation with
regard to mechanical stability, flame retardation, stability, and protection against contact, the
following alternative types of installation are specified:
• Installation in a suitable cabinet.
• Installation in a suitable enclosure.
• Installation in a suitably equipped, enclosed control room.
WARNING
If the temperature at the cable or housing socket or at the branching points of the cables
exceeds 60 °C, special precautions must be taken. If the equipment is operated at ambient
temperatures in excess of 40 °C, only use cables with permitted operating temperature of at
least 80 ℃.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 61
Assembly and disassembly
5.3 Types of installation
Further notes
NOTICE
Warming and premature aging of the network component due to direct sunlight
Direct sunlight can heat up the device and can lead to premature aging of the network
component and its cabling.
Provide suitable shade to protect the network component against direct sunlight.
WARNING
Use only approved SFP transceivers
If you use SFP transceivers that have not been approved by Siemens AG, there is no guarantee
that the device will function according to its specifications.
If you use unapproved SFP transceivers, this can lead to the following problems:
• Damage to the device
• Loss of the approvals
• Violation of the EMC regulations
Use only approved pluggable transceivers.
Note
Plugging and pulling during operation
You can plug and pull pluggable transceivers with the device in operation.
Note
Devices with or without fastening plate
During installation, check whether the device has a fastening plate or not. Refer to section
"Device views (Page 29)" to learn which devices have a fastening plate.
SCALANCE XC-200
62 Operating Instructions, 02/2023, C79000-G8976-C442-14
Assembly and disassembly
5.4 Installation on a DIN rail
Installation clearance
Keep to the minimum clearances so that the convection ventilation of the device is not
blocked.
• Below at least 10 cm
• Above at least 10 cm
Installation position
The following installation position is recommended:
Horizontal
Horizontal installation of the rack (DIN rail)
Note that different values for temperature and PoE power may apply to installation positions
other than horizontal; see section "Technical specifications (Page 95)".
Installation
Note
Note the position of the securing bar, see also section “Dimension drawings (Page 153)“.
When supplied, the securing bar is in the wall mounting position. To change the position of the
securing bar, refer to the section “Changing the position of the securing bar (Page 71)“.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 63
Assembly and disassembly
5.4 Installation on a DIN rail
Figure 5-1 DIN rail mounting with securing bar in the wall mounting position.
Removal
To remove the device from a DIN rail, follow the steps below:
1. Disconnect all connected cables.
2. If necessary, loosen the knurled screw with your hand or a screwdriver.
3. Lever the securing bar down using a screwdriver as far as it will go.
4. Pull the device away from the bottom of the DIN rail with the bar pulled.
SCALANCE XC-200
64 Operating Instructions, 02/2023, C79000-G8976-C442-14
Assembly and disassembly
5.4 Installation on a DIN rail
Installation
WARNING
Danger of injury by falling objects
The 35 mm DIN rail does not provide adequate support in shipping or when there is severe
vibration (> 10 g). When used under these conditions, the device can detach itself and may
cause injury to persons.
When used in shipbuilding or when extreme vibration can be expected, mount the device on
a S7 standard rail.
To install the device on a 35 mm DIN rail complying with DIN EN 60715, follow the steps
below:
1. Place the third housing guide of the device on the top edge of the DIN rail ①.
2. Press the device down against the DIN rail until the spring catch locks in place ②.
3. Connect the electrical connecting cables; refer to the section "Connecting up (Page 73)".
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 65
Assembly and disassembly
5.5 Installation on a standard S7-300 rail
Removal
To remove the device from a DIN rail, follow the steps below:
1. Disconnect all connected cables.
2. Release the DIN rail catch on the bottom of the device using a screwdriver.
3. Pull lower part of the device away from the DIN rail.
Note
Note the position of the securing bar, see also section “Dimension drawings (Page 153)“.
When supplied, the securing bar is in the wall mounting position. To change the position of the
securing bar, refer to the section “Changing the position of the securing bar (Page 71)“.
Figure 5-3 S7-300 mounting rail installation with the securing bar in the wall mounting position.
SCALANCE XC-200
66 Operating Instructions, 02/2023, C79000-G8976-C442-14
Assembly and disassembly
5.5 Installation on a standard S7-300 rail
4. When you tighten the knurled screw. you cannot release the securing bar (torque 0.5 Nm).
The device is additionally fixed.
5. Connect the electrical connecting cables, refer to the section "Connecting up (Page 73)".
Removal
To remove the device from a standard rail, follow the steps below:
1. Disconnect all connected cables.
2. If necessary, loosen the knurled screw with your hand or a screwdriver.
3. Lever the securing bar down using a screwdriver as far as it will go.
4. Remove the device from the mounting rail with the bar pulled.
To screw the device to an S7-300 standard rail, you require a securing screw with the
following properties:
• Self-tapping screw 4 x 45 mm
• Screw head diameter: max. 7 mm
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 67
Assembly and disassembly
5.6 Installation on a standard rail S7-1500
To install the device on an S7-300 standard rail, follow the steps below:
1. Place the second housing guide of the device on the top edge of the standard rail ①.
2. Screw the device to the lower part of the standard rail with the supplied securing screw ②
(tightening torque 1.5 Nm), see also "Device views (Page 29)".
3. Connect the electrical connecting cables; refer to the section "Connecting up (Page 73)".
Removal
To remove the device from a standard rail, follow the steps below:
1. Disconnect all connected cables.
2. Release the screw on the underside of the standard rail.
3. Remove the device from the standard rail.
Note
Note the position of the securing bar, see also section “Dimension drawings (Page 153)“.
When supplied, the securing bar is in the wall mounting position. To change the position of the
securing bar, refer to the section “Changing the position of the securing bar (Page 71)“.
Figure 5-5 S7-1500 mounting rail installation with the securing bar in the wall mounting position.
SCALANCE XC-200
68 Operating Instructions, 02/2023, C79000-G8976-C442-14
Assembly and disassembly
5.6 Installation on a standard rail S7-1500
Removal
To remove the device from a standard rail, follow the steps below:
1. Disconnect all connected cables.
2. If necessary, loosen the knurled screw with your hand or a screwdriver.
3. Lever the securing bar down using a screwdriver as far as it will go.
4. Remove the device from the mounting rail with the bar pulled.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 69
Assembly and disassembly
5.7 Wall mounting with fastening plate
To screw the device to an S7-1500 standard rail, you require a securing screw with the
following properties:
• Self-tapping screw 4 x 45 mm
• Screw head diameter: max. 7 mm
To install the device on an S7-1500 standard rail, follow the steps below:
1. Place the first housing guide of the device on the top edge of the standard rail ①.
2. Screw the device to the lower part of the standard rail with the supplied securing screw ②
(tightening torque 1.5 Nm), see also "Device views (Page 29)".
3. Connect the electrical connecting cables; refer to the section "Connecting up (Page 73)".
Removal
To remove the device from a standard rail, follow the steps below:
1. Disconnect all connected cables.
2. Release the screw on the underside of the standard rail.
3. Remove the device from the standard rail.
Preparation
Note the position of the securing bar, see also section “Dimension drawings (Page 153)“.
When supplied, the securing bar is in the wall mounting position. You do not need to prepare
the device any further.
If the securing bar is in the rail mounting position, note the section “Changing the position of
the securing bar (Page 71)“.
Tools
To mount the device on a wall, you require the following:
• 2 wall plugs with a diameter of 6 mm and a minimum length of 35 mm.
• 2 oval-head screws with a diameter of 3.5 mm to 4 mm and a minimum length of 50 mm.
Note
Use suitable fitting material depending on the mounting surface.
SCALANCE XC-200
70 Operating Instructions, 02/2023, C79000-G8976-C442-14
Assembly and disassembly
5.8 Changing the position of the securing bar
Base Concrete
Drill hole Depth Min. 45 mm
Diameter 6 mm
Fastening material Plugs 6 x 35
Oval-head screws 4 x 50
Assembly
Note
The wall mounting must be capable of supporting at least four times the weight of the device.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 71
Assembly and disassembly
5.9 Disassembly
To change the securing bar from the rail mounting position to the wall mounting position
follow the steps below:
1. If necessary, loosen the knurled screw with your hand or a screwdriver.
2. Move the securing bar down as far as it will go.
– Use the levering aid and level the securing bar down using a screwdriver into this position.
– Push the securing bar down using your hand.
3. Hold the securing bar in this position.
– Hold the securing bar with the screwdriver.
– Use the gap on the rear of the device and fix the securing bar briefly with a pin.
4. Tighten the knurled screw (torque 0.5 Nm).
The securing bar is fixed in the wall mounting position.
5. Remove the pin.
5.9 Disassembly
WARNING
Improper disassembly
Improper disassembly may result in a risk of explosion in hazardous areas.
For proper disassembly, observe the following:
• Before starting work, ensure that the electricity is switched off.
• Secure remaining connections so that no damage can occur as a result of disassembly if the
system is accidentally started up.
SCALANCE XC-200
72 Operating Instructions, 02/2023, C79000-G8976-C442-14
Connecting up 6
6.1 Safety notices for devices without PoE
Operate the device with a power supply according to NEC Class 2. When connecting up the
device, keep to the safety notices listed below.
For devices that must be operated with a NEC Class 2 power supply, you can also connect a fuse
in front of the power supply that meets the following requirements. The power supply must then
meet the requirements for operation with Limited Energy/LPS, see "Safety notices for PoE
devices (Page 75)".
WARNING
Power supply
The device is designed for operation with a directly connectable safety extra low voltage (SELV)
from a limited power source (LPS).
The power supply therefore needs to meet at least one of the following conditions:
• Only safety extra low voltage (SELV) with limited power source (LPS) complying with IEC
60950‑1 / EN 60950‑1 / VDE 0805‑1 or IEC 62368-1 / EN 62368-1 / VDE 62368-1 may be
connected to the power supply terminals.
• The power supply unit for the device must meet NEC Class 2 according to the National
Electrical Code (r) (ANSI / NFPA 70).
If the device is connected to a redundant power supply (two separate power supplies), the
combination of the two power supplies must meet these requirements.
WARNING
Safety extra low voltage
The device is designed for operation with a directly connectable power supply whose output
power corresponds to "Limited Energy" according to UL/IEC 61010-1.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 73
Connecting up
6.1 Safety notices for devices without PoE
WARNING
Requirements for operation with limited power or safety extra low voltage
1. If the device is supplied by a power supply with limited power (Limited Power Source, LPS)
that complies with National Electrical Code (r) (ANSI / NFPA 70), then no additional power
limitation is required.
If the device is connected to a redundant power supply (two separate power supplies), the
combination of the two power supplies must meet these requirements.
To comply with EU Directive 2014/34/EU (ATEX 114), UK Regulation SI 2016/1107 or the
conditions of IECEx or CCC-Ex, the housing or cabinet must meet the requirements of at
least IP54 (according to EN/IEC 60529, GB/T 4208) in compliance with EN IEC/IEC 60079‑7,
GB 3836.3.
2. If the device is operated with a power supply for safety extra low voltage (SELV) without
limited power and the entire power requirement does not exceed 100 W, a fuse must be
installed between the power supply and each supply input of the device to meet the
requirements for limited power (Limited Power Source, LPS). For more information, see
"Suitable fusing for the power supply cables" below.
To comply with EU Directive 2014/34/EU (ATEX 114), UK Regulation SI 2016/1107 or the
conditions of IECEx or CCC-Ex, the housing or cabinet must meet the requirements of at
least IP54 (according to EN/IEC 60529, GB/T 4208) in compliance with EN IEC/IEC 60079‑7,
GB 3836.3.
SCALANCE XC-200
74 Operating Instructions, 02/2023, C79000-G8976-C442-14
Connecting up
6.2 Safety notices for PoE devices
NOTICE
Suitable fuse for the power supply cables (corresponds to "Limited Energy")
The current on the terminal may not exceed 3 A. Use a fuse for the power supply that is suitable
for protection of AC/DC power supply circuits *) and protects against currents > 3 A.
• In areas subject to the NEC or CEC, the fuse must meet the following requirements:
– Suitable for AC/DC *) (min. 60 V / 3 A)
– Breaking current at least 10 kA
– Approval according to ANSI/UL 248-14 (suppl. fuses), ANSI/UL 248-4 (Class CC), ANSI/UL
248-8 (J), ANSI/UL 248-15 (T), or CSA C22.2-4 No. 248.14 (suppl. fuses), No. 248-4
(Class CC), No. 248-8 (J), No. 248-15 (T)
• In other areas, the fuse must meet the following requirements:
– Suitable for AC/DC *) (min. 60 V / 3 A)
– Breaking current at least 10 kA
– Approval according to IEC/EN 60947‑1/2/3 or IEC/EN 60898-1/2 for circuit breakers
– Breaking characteristics: B or C
– Approval according to IEC/EN 60127-1 for fuses
– Breaking characteristics: max. 120 s at 2 x In (corresponds to melting integral I2t < 4320)
If the properties of the supplying current source are known, the following fuse is also possible:
• In areas subject to the NEC or CEC, the fuse must meet the following requirements:
– Suitable for AC/DC *) (min. 60 V / 3 A)
– Breaking current > highest possible current of the current source (incl. short circuit
current and fault)
– Approval according to UL 1077 or CSA C22.2 No. 235
• In other areas, the fuse must meet the following requirements:
– Suitable for AC/DC *) (min. 60 V / 3 A)
– Breaking current > highest possible current of the current source (incl. short circuit
current and fault)
– Approval according to IEC/EN 60934
– Breaking characteristics: max. 120s at 2 x In
*) AC or DC depending on availability
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 75
Connecting up
6.2 Safety notices for PoE devices
WARNING
Safety notices for operation with a power supply according to "Limited Energy"
1. If the device is supplied by a power supply with limited power (Limited Energy) that
complies with IEC/UL61010-1 or VDE 0805-1, no additional power limitation is required
according to National Electrical Code (r) (ANSI/NFPA 70).
If the device is connected to a redundant power supply (two separate power supplies), the
combination of the two power supplies must meet these requirements.
To comply with EU Directive 2014/34/EU (ATEX 114), UK Regulation SI 2016/1107 or the
conditions of IECEx or CCC-Ex, the housing or cabinet must meet the requirements of at
least IP54 (according to EN/IEC 60529, GB/T 4208) in compliance with EN IEC/IEC 60079‑7,
GB 3836.3.
2. If the device is operated with a power supply for without power limitation and the entire
power requirement does not exceed 100 W, a fuse must be installed between the power
supply and each supply input of the device to meet the requirements for limited power
(Limited Energy) according to IEC/UL61010-1 or VDE 0805-1. For more information, see
"Suitable fusing for the power supply cables" below.
To comply with EU Directive 2014/34/EU (ATEX 114), UK Regulation SI 2016/1107 or the
conditions of IECEx or CCC-Ex, the housing or cabinet must meet the requirements of at
least IP54 (according to EN/IEC 60529, GB/T 4208) in compliance with EN IEC/IEC 60079‑7,
GB 3836.3.
3. If the device is operated with a power supply without power limitation and the entire power
requirement exceeds 100 W, the device must be installed in a fire protection housing
according to ANSI/UL-61010-1:2018, paragraph 9.3.
SCALANCE XC-200
76 Operating Instructions, 02/2023, C79000-G8976-C442-14
Connecting up
6.2 Safety notices for PoE devices
NOTICE
Suitable fuse for the power supply cables (corresponds to "Limited Energy")
The current on the terminal may not exceed 3 A. Use a fuse for the power supply that is suitable
for protection of AC/DC power supply circuits *) and protects against currents > 3 A.
• In areas subject to the NEC or CEC, the fuse must meet the following requirements:
– Suitable for AC/DC *) (min. 60 V / 3 A)
– Breaking current at least 10 kA
– Approval according to ANSI/UL 248-14 (suppl. fuses), ANSI/UL 248-4 (Class CC), ANSI/UL
248-8 (J), ANSI/UL 248-15 (T), or CSA C22.2-4 No. 248.14 (suppl. fuses), No. 248-4
(Class CC), No. 248-8 (J), No. 248-15 (T)
• In other areas, the fuse must meet the following requirements:
– Suitable for AC/DC *) (min. 60 V / 3 A)
– Breaking current at least 10 kA
– Approval according to IEC/EN 60947‑1/2/3 or IEC/EN 60898-1/2 for circuit breakers
– Breaking characteristics: B or C
– Approval according to IEC/EN 60127-1 for fuses
– Breaking characteristics: max. 120 s at 2 x In (corresponds to melting integral I2t < 4320)
If the properties of the supplying current source are known, the following fuse is also possible:
• In areas subject to the NEC or CEC, the fuse must meet the following requirements:
– Suitable for AC/DC *) (min. 60 V / 3 A)
– Breaking current > highest possible current of the current source (incl. short circuit
current and fault)
– Approval according to UL 1077 or CSA C22.2 No. 235
• In other areas, the fuse must meet the following requirements:
– Suitable for AC/DC *) (min. 60 V / 3 A)
– Breaking current > highest possible current of the current source (incl. short circuit
current and fault)
– Approval according to IEC/EN 60934
– Breaking characteristics: max. 120s at 2 x In
*) AC or DC depending on availability
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 77
Connecting up
6.3 Safety notices on use in hazardous areas
WARNING
EXPLOSION HAZARD
Do not connect or disconnect cables to or from the device when a flammable or combustible
atmosphere is present.
WARNING
EXPLOSION HAZARD
Do not press the SELECT/SET button when there is an explosive atmosphere.
WARNING
Unsuitable cables or connectors
Risk of explosion in hazardous areas
• Only use connectors that meet the requirements of the relevant type of protection.
• If necessary, tighten the connector screw connections, device fastening screws, grounding
screws, etc. according to the specified torques.
• Close unused cable openings for electrical connections.
• Check the cables for a tight fit after installation.
WARNING
Lack of equipotential bonding
If there is no equipotential bonding in hazardous areas, there is a risk of explosion due to
equalizing current or ignition sparks.
• Ensure that equipotential bonding is available for the device.
WARNING
Unprotected cable ends
There is a risk of explosion due to unprotected cable ends in hazardous areas.
• Protect unused cable ends according to IEC/EN 60079-14.
SCALANCE XC-200
78 Operating Instructions, 02/2023, C79000-G8976-C442-14
Connecting up
6.3 Safety notices on use in hazardous areas
WARNING
Improper installation of shielded cables
There is a risk of explosion due to equalizing currents between the hazardous area and the non-
hazardous area.
• Ground shielded cables that cross hazardous areas at one end only.
• Lay a potential equalization conductor when grounding at both ends.
WARNING
Insufficient isolation of intrinsically safe and non-intrinsically safe circuits
Risk of explosion in hazardous areas
• When connecting intrinsically safe and non-intrinsically safe circuits, ensure that the
galvanic isolation is performed properly in compliance with local regulations (e.g. IEC
60079-14).
• Observe the device approvals applicable for your country.
Notes for use in hazardous locations according to ATEX, IECEx, UKEX and CCC Ex
If you use the device under ATEX, IECEx, UKEX or CCC Ex conditions you must also keep to
the following safety instructions in addition to the general safety instructions for protection
against explosion:
WARNING
Transient overvoltages
Take measures to prevent transient overvoltages of more than 40% of the rated voltage (or
more than 119 V). This is the case if you only operate devices with SELV (safety extra-low
voltage).
WARNING
Suitable cables at high ambient temperatures in hazardous area
At an ambient temperature of ≥ 60 °C, use heat-resistant cables designed for an ambient
temperature at least 20 °C higher. The cable entries used on the enclosure must comply with
the IP degree of protection required by EN IEC / IEC 60079-0, GB 3836.1.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 79
Connecting up
6.4 Further notes
WARNING
EXPLOSION HAZARD
You may only connect or disconnect cables carrying electricity when the power supply is
switched off or when the device is in an area without inflammable gas concentrations.
WARNING
EXPLOSION HAZARD
Do not disconnect while circuit is live unless area is known to be non-hazardous.
WARNING
Insulation of external power supplies
Ext. circuits intended to be connected to this device shall be galv. separated from hazardous live
voltage by reinforced or double insulation.
WARNING
Safety notice for connecting with a LAN ID (Local Area Network)
A LAN or LAN segment with all the interconnected devices should be contained completely in
a single low voltage power distribution in a building. The LAN is designed either for
“Environment A” according to IEEE802.3 or "Environment 0" according to IEC TR 62102.
Do not connect any electrical connectors directly to the telephone network (telephone network
voltage) or a WAN (Wide Area Network).
The following table shows which ports fulfill the conditions of Environment A or B:
SCALANCE XC-200
80 Operating Instructions, 02/2023, C79000-G8976-C442-14
Connecting up
6.5 Wiring rules
Note
Protective ground
A PELV circuit contains a connection to protective ground. Without a connection to protective
ground, or in case there is a fault in the connection to the protective ground, the voltage for the
circuit is not stabilized.
Note
Minimum temperature rating of the cable to be connected to the field wiring terminals, 90 °C.
Note
Wire end ferrules
Use crimp shapes with smooth surfaces, such as provided by square and trapeze shaped crimp
cross sections.
Crimp shapes with wave-shaped profile are unsuitable.
Note
Wiring with PoE variants
PoE variants have a high current consumption. Design the cable cross-section based on the
maximum current consumption.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 81
Connecting up
6.6 24 V DC power supply
WARNING
Incorrect power supply
If the power supply is designed redundantly (two separate power supplies), the combination
of the two power supplies must meet these requirements.
Never operate the device with AC voltage or DC voltage higher than 32 V DC.
CAUTION
Damage to the device due to overvoltage
The connector of the external power supply is not protected against strong electromagnetic
pulses that can, for example, result from lightning strikes or switching large loads.
One of the tests used to attest the immunity of devices of the IE switches SCALANCE XC-200 to
electromagnetic interference was the "surge immunity test" according to EN61000-4-5. This
test requires overvoltage protection for the power supply lines. A suitable device is, for
example, the Dehn Blitzductor BVT AVD 24, article number 918 422 or a comparable protective
element.
Manufacturer: DEHN+SOEHNE GmbH+Co. KG, Hans-Dehn-Str.1, Postfach 1640, D92306
Neumarkt, Germany
Operate the SCALANCE XC-200 with suitable overvoltage protection.
Note
The device can be disconnected from the power supply by pulling off the terminal block.
SCALANCE XC-200
82 Operating Instructions, 02/2023, C79000-G8976-C442-14
Connecting up
6.7 54 V DC power supply
/
0
0
/
Figure 6-1 Position of the power supply based, for example on the SCALANCE XC-200 with 8 ports
and assignment of the terminal block
Contact Assignment
L1+ 24 VDC
M1 Ground
M2 Ground
L2+ 24 VDC
WARNING
Incorrect power supply
When the device is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
Never operate the device with AC voltage or DC voltage higher than 57 V DC.
CAUTION
Damage to the device due to overvoltage
The connector of the external power supply is not protected against strong electromagnetic
pulses that can, for example, result from lightning strikes or switching large loads.
One of the tests used to attest the immunity of devices of the IE switches SCALANCE XC-200 to
electromagnetic interference was the "surge immunity test" according to EN61000-4-5.
Note
The device can be disconnected from the power supply by pulling off the terminal block.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 83
Connecting up
6.7 54 V DC power supply
/
0
0
/
Figure 6-2 Position of the power supply based, for example on the SCALANCE XC-200 with 8 ports
and assignment of the terminal block
Contact Assignment
L1+ 54 V DC
M1 Ground
M2 Ground
L2+ 54 V DC
SCALANCE XC-200
84 Operating Instructions, 02/2023, C79000-G8976-C442-14
Connecting up
6.8 Signaling contact
NOTICE
Damage due to voltage being too high
You can load the signaling contact with the operating voltage of the device and a maximum of
100 mA.
Higher voltages or currents can damage the device.
)
)
Figure 6-3 Position of the signaling contact based, for example on the SCALANCE XC-200 with 8
ports and assignment of the terminal block
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 85
Connecting up
6.9 Functional ground
Contact Assignment
F1 Fault contact 1
F2 Fault contact 2
Signaling faults
• The signaling of errors by the signaling contact is synchronized with the fault LED "F", see
section ""F" LED (Page 47)".
All errors that the fault LED "F" indicates (freely configurable) are also signaled by the
signaling contact.
• If an internal fault occurs, the fault LED "F" lights up and the signaling contact opens.
• If you connect a communications node to an unmonitored port or disconnect it, this does not
cause an error message.
• The signaling contact remains open until one of the following events occurs:
– The problem is eliminated.
– The current status is entered in the fault mask as the new desired status.
SCALANCE XC-200
86 Operating Instructions, 02/2023, C79000-G8976-C442-14
Connecting up
6.10 Serial interface
Protective/functional ground
The connection of the reference potential surface with the protective ground system is normally
in the cabinet close to the power feed-in. This ground conducts fault currents to ground safely
and according DIN/VDE 0100 is a protective ground to protect people, animals and property from
too high contact voltages.
Apart from the protective ground, there is functional grounding in the cabinet. According
to EN60204-1 (DIN/VDE 0113 T1) electrical circuits must be grounded. The chassis (0 V) is
grounded at one defined point. Here, once again the grounding is implemented with the
lowest leakage resistance to ground in the vicinity of the power feed-in.
With automation components, functional ground also ensures interference-free operation of
a controller. Via the functional ground, interference currents coupled in via the connecting
cables are discharged to ground.
5 4 3 2 1
&2162/(
6
5
4
3
2
1
9 8 7 6
Figure 6-4 Position and pin assignment of the serial interface (RJ-11 jack), based for example on the
XC-200 with 8 ports as well as the pin assignment of the D-sub socket.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 87
Connecting up
6.11 Industrial Ethernet
Contact Pin assignment of the RJ-11 plug Pin assignment of the D-sub female con‐
nector
1 - -
2 - TD (Transmit Data)
3 TD (Transmit Data) RD (Receive Data)
4 SG (Signal Ground) -
5 RD (Receive Data) SG (Signal Ground)
6 - -
7 -
8 -
9 -
Note
Pin assignment of the RJ-11 jack on the device
The RJ-11 jack on the device has a pinout to match the RJ-11 plug of the connecting cable.
6.11.1 Electrical
Note
Strain relief for the Ethernet cables
In order to avoid mechanical stress on the Ethernet cables and resulting interruption of the
contact, fasten the cables at a short distance from the connector using a cable guide or busbar.
Note
Unlocking the plug with a screwdriver
If installation space is limited, you can unlock the connectors using a screwdriver, see also
"SIMATIC NET: IE FC RJ45 Plug 4x2 CAT 6A (https://support.industry.siemens.com/cs/ww/en/
view/102047916)".
SCALANCE XC-200
88 Operating Instructions, 02/2023, C79000-G8976-C442-14
Connecting up
6.11 Industrial Ethernet
Pin assignment
The following table shows the pin assignment of the R-45 connectors.
Note
Formation of loops
Please note that the direct connection of two ports on the IE switch or accidental connection
over several IE switches causes an illegal loop. Such a loop can lead to network overload and
network failures.
Autonegotiation
Autonegotiation means the automatic detection/negotiation of the transmission rate and the
operating mode of ports at the opposite end. This makes it possible to configure different devices
automatically.
Two components connected to a link segment can exchange information about the transfer
and can adapt their settings to each other. The mode with the highest possible speed is set.
Note
• If a port is set permanently to full duplex, the connected partner port must also be set to full
duplex.
• If a port operating in the "Auto negotiation" mode is connected to a partner port that is not
operating in the"Auto negotiation" mode, the partner port setting must be fixed at 100 Mbps
or 10 Mbps half duplex mode.
• If you disable the "Auto negotiation" function, the "MDI/MDI-X autocrossover" function is also
turned off. Then use a crossover cable.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 89
Connecting up
6.11 Industrial Ethernet
6.11.2 Optical
NOTICE
Failure of the data traffic due to contamination of optical plug-in connections
Optical sockets and plugs are sensitive to contamination of the end face. Contamination can
lead to the failure of the optical transmission network. Take the following precautions to avoid
functional impairments:
• Clean the end face of field-assembled connectors carefully before connecting. No residues
of processing may remain on the connector.
• Only remove the dust caps of optical transceivers and pre-configured cables shortly before
connecting the cables.
• Close unused optical sockets and plugs as well as pluggable transceivers and slots with the
supplied protective caps.
Note
No light power measurement (PROFINET diagnostics)
The devices do not support diagnostics with light power measurement.
SC connectors
ST/BFOC connectors
LC connector technology
SCALANCE XC-200
90 Operating Instructions, 02/2023, C79000-G8976-C442-14
Maintenance and cleaning 7
WARNING
Unauthorized repair of devices in explosion-proof design
Risk of explosion in hazardous areas
• Repair work may only be performed by personnel authorized by Siemens.
WARNING
Impermissible accessories and spare parts
Risk of explosion in hazardous areas
• Only use original accessories (Page 39) and original spare parts (Page 23).
• Observe all relevant installation and safety instructions described in the manuals for the
device or supplied with the accessories or spare parts.
CAUTION
Hot surfaces
Risk of burns during maintenance work on parts with a surface temperature above 70 °C
(158 °F).
• Take appropriate protective measures, for example, wear protective gloves.
• Once maintenance work is complete, restore the touch protection measures.
NOTICE
Cleaning the housing
If the device is not in a hazardous area, only clean the outer parts of the housing with a dry cloth.
If the device is in a hazardous area, use a slightly damp cloth for cleaning.
Do not use solvents.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 91
Maintenance and cleaning
SCALANCE XC-200
92 Operating Instructions, 02/2023, C79000-G8976-C442-14
Troubleshooting 8
8.1 Downloading new firmware using TFTP without WBM and CLI
Firmware
The firmware is signed and encrypted. This ensures that only firmware created by Siemens can
be downloaded to the device.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 93
Troubleshooting
8.2 Restoring the factory settings
NOTICE
Previous settings
If you reset, all the settings you have made will be overwritten by factory defaults.
NOTICE
Inadvertent reset
An inadvertent reset can cause disturbances and failures in the configured network.
NOTICE
Reset despite disabled "SELECT/SET" button
Using the "SELECT/SET" button, you can always reset the device parameters to the factory
defaults during the startup phase of the device. This applies also if the "Reset to Factory
Defaults" function was disabled in the configuration. This allows you to reset the device to the
factory defaults in an emergency.
If the function has been disabled in the configuration, it is only disabled on completion of the
startup phase.
To reset the device to the factory defaults during the startup phase, follow the steps below:
1. Turn off the power to the device.
2. Now press the "SELECT/SET" button and reconnect the power to the device while holding
down the button.
3. Hold down the button until the red error LED "F" stops flashing and is permanently lit.
4. Now release the button and wait until the fault LED "F" goes off again.
5. The device starts automatically with the factory defaults.
SCALANCE XC-200
94 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications 9
9.1 Technical specifications SCALANCE XC206-2 (ST/BFOC)
The following technical specifications apply to the SCALANCE XC206-2 (ST/BFOC).
Technical specifications
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC 500 mA
24 VDC 250 mA
Effective power loss 6W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature With operation up to 2000 m above During operation in horizontal installation po‐
sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +60 °C
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 95
Technical specifications
9.1 Technical specifications SCALANCE XC206-2 (ST/BFOC)
Technical specifications
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 540 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 46 years
1)
Note the wiring rules (Page 81).
Electrical connectors
Properties
Quantity 6
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 Mbps
Optical connectors
Optical connectors
Quantity 2
Connectors
Properties
Transmission mode 100Base-FX complying with IEEE 802.3
Transmission rate 100 Mbps (Fast Ethernet)
Transmission medium Multimode fiber-optic cable
Light source LED/Class1-LASER "Eye safe"
Wavelength 1300 nm
Cable length (max.) * )
At 50 µm fiber core diameter 3 km
At 62.5 µm fiber core diameter 3 km
SCALANCE XC-200
96 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.2 Technical specifications SCALANCE XC206-2 (SC)
Properties
Transmitter output (optical) Minimum At 50 μm -24 dBm
At 62.5 μm -20 dBm
Maximum -14 dBm
Receiver input Sensitivity min. -31 dBm
Input power max. -12 dBm
Technical specifications
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC 500 mA
24 VDC 250 mA
Effective power loss 6W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1) Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 97
Technical specifications
9.2 Technical specifications SCALANCE XC206-2 (SC)
Technical specifications
Ambient temperature With operation up to 2000 m above During operation in horizontal installation po‐
sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +60 °C
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 540 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 46 years
1)
Note the wiring rules (Page 81).
Electrical connectors
Properties
Quantity 6
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 Mbps
SCALANCE XC-200
98 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.2 Technical specifications SCALANCE XC206-2 (SC)
Optical connectors
Optical connectors
Quantity 2
Connectors
Properties
Transmission mode 100Base-FX complying with IEEE 802.3
Transmission rate 100 Mbps (Fast Ethernet)
Transmission medium Multimode fiber-optic cable
Light source LED/Class1-LASER "Eye safe"
Wavelength 1300 nm
Cable length (max.) * )
At 50 µm fiber core diameter 3 km
At 62.5 µm fiber core diameter 3 km
Transmitter output (optical) Minimum At 50 μm -24 dBm
At 62.5 μm -20 dBm
Maximum -14 dBm
Receiver input Sensitivity min. -31 dBm
Input power max. -12 dBm
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 99
Technical specifications
9.3 Technical specifications of SCALANCE XC206-2G PoE
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 6
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable transceivers Quantity 2
Connector SFP transceivers (LC port)
Transmission speed 1000 / 10000 Mbps
100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 24 V DC
Voltage range (incl. tolerance) 19.2 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly
Current consumption At 19.2 V DC Max. 7.5 A
Effective Power At max PoE load Max. 144 W
Thermal Design Power Max. 18 W
Overvoltage category CAT II
Fusing Basic device 2.5 A / 125 V
PoE consumers 15 A / 125 V
PoE power per device At 24 V DC With horizontal mounting position and opera‐
tion without pluggable transceiver:
• 120 W
In other installation position:
• 90 W
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 V DC
Load capability Max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
100 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.3 Technical specifications of SCALANCE XC206-2G PoE
Technical specifications
Ambient temperature 2) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector with max. PoE load up to sition:
2000 m above sea level • -40 °C to +60 °C
During operation in a different installation po‐
sition:
• -40 °C to +50 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• [-] Standard version • -40 °C to +60 °C
• LD • Max. PoE power: 90 W
Up to 2000 m above sea level During operation in a different installation po‐
sition:
• -40 °C to +50 °C
• Max. PoE power: 60 W
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• LH • -40 °C to +55 °C
• LH+ • Max. PoE power: 90 W
• ELH Other mounting positions are not permitted.
• SFP992-1+
Up to 2000 m above sea level
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design Compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 100 x 147 x 125 mm
Weight 955 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 37 years
1)
Note the wiring rules (Page 81).
2)
Depending on which pluggable transceiver you use, the maximum ambient temperature
can change, see section "Accessories", "SFP transceiver (Page 39)".
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 101
Technical specifications
9.4 Technical specifications of SCALANCE XC206-2G PoE (54 V)
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 6
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable transceivers Quantity 2
Connector SFP transceivers (LC port)
Transmission speed 1000 / 10000 Mbps
100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 54 V DC
Voltage range (incl. tolerance) 52 to 57 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly
Current consumption At 52 V DC Max. 5 A
Effective Power At max PoE load Max. 260 W
Thermal Design Power Max. 10 W
Overvoltage category CAT II
Fusing Basic device 2.5 A / 125 V
PoE consumers 15 A / 125 V
PoE power per device At 54 V 240 W
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 54 V DC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
102 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.4 Technical specifications of SCALANCE XC206-2G PoE (54 V)
Technical specifications
Ambient temperature 2) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector with max. PoE load up to sition:
2000 m above sea level -40 °C to +60 °C
During operation in a different installation po‐
sition:
-40 °C to +50 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• [-] Standard version -40 °C to +60 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +50 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• LH -40 °C to +55 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +50 °C
• SFP992-1+
Up to 2000 m above sea level
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 540 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 42.8 years
1)
Note the wiring rules (Page 81).
2)
Depending on which pluggable transceiver you use, the maximum ambient temperature
can change, see section "Accessories", "SFP transceiver (Page 39)".
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 103
Technical specifications
9.5 Technical specifications of SCALANCE XC206-2G PoE EEC (54 V)
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 6
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable transceivers Quantity 2
Connector SFP transceivers (LC port)
Transmission speed 1000 / 10000 Mbps
100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 54 V DC
Voltage range (incl. tolerance) 52 to 57 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly
Current consumption At 52 V DC Max. 5 A
Effective Power At max PoE load Max. 260 W
Thermal Design Power Max. 10 W
Overvoltage category CAT II
Fusing Basic device 2.5 A / 125 V
PoE consumers 15 A / 125 V
PoE power per device At 54 V 240 W
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 54 V DC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
104 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.5 Technical specifications of SCALANCE XC206-2G PoE EEC (54 V)
Technical specifications
Ambient temperature 2) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector with max. PoE load up to sition:
2000 m above sea level -40 °C to +60 °C
During operation in a different installation po‐
sition:
-40 °C to +50 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• [-] Standard version -40 °C to +60 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +50 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• LH -40 °C to +55 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +50 °C
• SFP992-1+
Up to 2000 m above sea level
With operation between 2000 m and The maximum ambient temperature is re‐
3000 m above sea level duced by 5 °C 3)
With operation between 3000 m and The maximum ambient temperature is re‐
4000 m above sea level duced by 10 °C 3)
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Properties Coated printed circuit board (conformal coating)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 540 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 42.8 years
1)
Wiring rules
Observe the wiring rules (Page 81).
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 105
Technical specifications
9.5 Technical specifications of SCALANCE XC206-2G PoE EEC (54 V)
2)
Ambient temperature with SFP
The maximum ambient temperature during operation depends on the operating elevation
and the installed pluggable transceivers, see also the section "SFP transceiver (Page 39)" in
the "Accessories" section.
3)
Derating
The derating values depend on the maximum ambient temperatures during operation up to
2000 m.
SCALANCE XC-200
106 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.6 Technical specifications SCALANCE XC206-2SFP
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 6
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 Mbps
Slots for pluggable transceivers Quantity 2
Connector SFP transceivers (LC port)
Transmission speed 100 / 1000 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC Without SFP 400 mA
With SFP 2) 500 mA
24 VDC Without SFP 200 mA
With SFP 2)
250 mA
Effective power loss Without SFP 4.8 W
With SFP 2) 6W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1) Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 107
Technical specifications
9.6 Technical specifications SCALANCE XC206-2SFP
Technical specifications
Ambient temperature 3) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector up to 2000 m above sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• [-] Standard version -40 °C to +70 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +60 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• LH -40 °C to +65 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +60 °C
• ELH200
• SFP992-1+
Up to 2000 m above sea level
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 520 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 47 years
1)
Note the wiring rules (Page 81).
2)
Detected with the SFP992-1ELH. You will find the precise values in the operating
instructions of the pluggable transceivers, see the section "Introduction", Additional
documentation (Page 7).
3)
Depending on which pluggable transceiver you use, the maximum ambient temperature
can change, see section "Accessories", "SFP transceiver (Page 39)".
SCALANCE XC-200
108 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.7 Technical specifications of SCALANCE XC206-2SFP G
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 6
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable transceivers Quantity 2
Connector SFP transceivers (LC port)
Transmission speed 1000 Mbps
100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC Without SFP 400 mA
With SFP 2)
500 mA
24 V DC Without SFP 200 mA
With SFP 2) 250 mA
Effective power loss Without SFP 4.8 W
With SFP 2)
6W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 V DC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 109
Technical specifications
9.7 Technical specifications of SCALANCE XC206-2SFP G
Technical specifications
Ambient temperature 3) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector up to 2000 m above sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• [-] Standard version -40 °C to +65 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +60 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• LH -40 °C to +60 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +60 °C
• SFP992-1+
Up to 2000 m above sea level
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 520 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 55 years
1)
Note the wiring rules (Page 81).
2)
Detected with the SFP992-1ELH. You will find the precise values in the operating
instructions of the pluggable transceivers, see the section "Introduction", Additional
documentation (Page 7).
3)
Depending on which pluggable transceiver you use, the maximum ambient temperature
can change, see section "Accessories", "SFP transceiver (Page 39)".
SCALANCE XC-200
110 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.8 Technical specifications of SCALANCE XC206-2SFP EEC
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 6
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 Mbps
Slots for pluggable transceivers Quantity 2
Connector SFP transceivers (LC port)
Transmission speed 100 / 1000 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC Without SFP 400 mA
With SFP 2) 500 mA
24 VDC Without SFP 200 mA
With SFP 2)
250 mA
Effective power loss Without SFP 4.8 W
With SFP 2) 6W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1) Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 111
Technical specifications
9.8 Technical specifications of SCALANCE XC206-2SFP EEC
Technical specifications
Ambient temperature 3) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector up to 2000 m above sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• [-] Standard version -40 °C to +70 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +60 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• LH -40 °C to +65 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +60 °C
• ELH200
• SFP992-1+
Up to 2000 m above sea level
With operation between 2000 m and The maximum ambient temperature is re‐
3000 m above sea level duced by 5 °C 4)
With operation between 3000 m and The maximum ambient temperature is re‐
4000 m above sea level duced by 10 °C 4)
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Properties Coated printed circuit board (conformal coating)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 520 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 47 years
SCALANCE XC-200
112 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.8 Technical specifications of SCALANCE XC206-2SFP EEC
1)
Wiring rules
Observe the wiring rules (Page 81).
2)
Pluggable transceiver
Detected with the SFP992-1ELH. You will find the precise values in the operating instructions
of the pluggable transceivers, see the section "Introduction", Additional documentation
(Page 7).
3)
Ambient temperature with SFP
The maximum ambient temperature during operation depends on the operating elevation
and the installed pluggable transceivers, see also the section "SFP transceiver (Page 39)" in
the "Accessories" section.
4)
Derating
The derating values depend on the maximum ambient temperatures during operation up to
2000 m.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 113
Technical specifications
9.9 Technical specifications of SCALANCE XC206-2SFP G EEC
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 6
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable transceivers Quantity 2
Connector SFP transceivers (LC port)
Transmission speed 1000 Mbps
100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC Without SFP 400 mA
With SFP 2)
500 mA
24 V DC Without SFP 200 mA
With SFP 2) 250 mA
Effective power loss Without SFP 4.8 W
With SFP 2)
6W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 V DC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
114 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.9 Technical specifications of SCALANCE XC206-2SFP G EEC
Technical specifications
Ambient temperature 3) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector up to 2000 m above sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• [-] Standard version -40 °C to +65 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +60 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• LH -40 °C to +60 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +60 °C
• SFP992-1+
Up to 2000 m above sea level
With operation between 2000 m and The maximum ambient temperature is re‐
3000 m above sea level duced by 5 °C 4)
With operation between 3000 m and The maximum ambient temperature is re‐
4000 m above sea level duced by 10 °C 4)
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Properties Coated printed circuit board (conformal coating)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 520 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 55 years
1)
Wiring rules
Observe the wiring rules (Page 81).
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 115
Technical specifications
9.9 Technical specifications of SCALANCE XC206-2SFP G EEC
2)
Pluggable transceiver
Detected with the SFP992-1ELH. You will find the precise values in the operating instructions
of the pluggable transceivers, see the section "Introduction", Additional documentation
(Page 7).
3)
Ambient temperature with SFP
The maximum ambient temperature during operation depends on the operating elevation
and the installed pluggable transceivers, see also the section "SFP transceiver (Page 39)" in
the "Accessories" section.
4)
Derating
The derating values depend on the maximum ambient temperatures during operation up to
2000 m.
SCALANCE XC-200
116 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.10 Technical specifications of the SCALANCE XC208
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 8
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Property Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC 350 mA
24 VDC 175 mA
Effective power loss 4.2 W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature With operation up to 2000 m above During operation in horizontal installation po‐
sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 117
Technical specifications
9.10 Technical specifications of the SCALANCE XC208
Technical specifications
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 520 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 48 years
1)
Note the wiring rules (Page 81).
SCALANCE XC-200
118 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.11 Technical specifications of SCALANCE XC208G
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 8
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Property Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC 400 mA
24 VDC 200 mA
Effective power loss 4.3 W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature With operation up to 2000 m above During operation in horizontal installation po‐
sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 119
Technical specifications
9.11 Technical specifications of SCALANCE XC208G
Technical specifications
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 520 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 54 years
1)
Note the wiring rules (Page 81).
SCALANCE XC-200
120 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.12 Technical specifications of SCALANCE XC208G PoE
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 8
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 24 V DC
Voltage range (incl. tolerance) 19.2 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Property Implemented redundantly
Current consumption At 19.2 V DC Max. 7.5 A
Effective Power At max PoE load Max. 144 W
Thermal Design Power Max. 18 W
Overvoltage category CAT II
Fusing Basic device 2.5 A / 125 V
PoE consumers 15 A / 125 V
PoE power per device At 24 V DC In horizontal installation position:
120 W
In other installation position:
90 W
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability Max. 100 mA
Permitted ambient conditions
Ambient temperature With operation with max. PoE load up During operation in horizontal installation po‐
to 2000 m above sea level sition:
-40 °C to +60 °C
During operation in a different installation po‐
sition:
-40 °C to +50 °C
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design Compact
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 121
Technical specifications
9.12 Technical specifications of SCALANCE XC208G PoE
Technical specifications
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 100 x 147 x 125 mm
Weight 955 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 37.3 years
1)
Note the wiring rules (Page 81).
SCALANCE XC-200
122 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.13 Technical specifications of SCALANCE XC208G PoE (54 V)
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 8
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 54 V DC
Voltage range (incl. tolerance) 52 to 57 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Property Implemented redundantly
Current consumption At 52 V DC Max. 5 A
Effective Power At max PoE load Max. 260 W
Thermal Design Power Max. 10 W
Overvoltage category CAT II
Fusing Basic device 2.5 A / 125 V
PoE consumers 15 A / 125 V
PoE power per device At 54 V 240 W
Signaling contact 1) Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 54 V DC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature With operation with max. PoE load up During operation in horizontal installation po‐
to 2000 m above sea level sition:
-40 °C to +60 °C
During operation in a different installation po‐
sition:
-40 °C to +50 °C
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 123
Technical specifications
9.13 Technical specifications of SCALANCE XC208G PoE (54 V)
Technical specifications
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 540 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 42.6 years
1)
Note the wiring rules (Page 81).
SCALANCE XC-200
124 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.14 Technical specifications of SCALANCE XC208EEC
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 8
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Property Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC 350 mA
24 VDC 175 mA
Effective power loss 4.2 W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature With operation up to 2000 m above During operation in horizontal installation po‐
sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
With operation between 2000 m and The maximum ambient temperature is re‐
3000 m above sea level duced by 5 °C 2)
With operation between 3000 m and The maximum ambient temperature is re‐
4000 m above sea level duced by 10 °C 2)
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 125
Technical specifications
9.14 Technical specifications of SCALANCE XC208EEC
Technical specifications
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Properties Coated printed circuit board (conformal coating)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 520 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 48 years
1)
Note the wiring rules (Page 81).
2)
The derating values depend on the maximum ambient temperatures during operation up
to 2000 m.
SCALANCE XC-200
126 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.15 Technical specifications of SCALANCE XC208G EEC
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 8
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Property Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC 400 mA
24 VDC 200 mA
Effective power loss 4.3 W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature With operation up to 2000 m above During operation in horizontal installation po‐
sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
With operation between 2000 m and The maximum ambient temperature is re‐
3000 m above sea level duced by 5 °C 2)
With operation between 3000 m and The maximum ambient temperature is re‐
4000 m above sea level duced by 10 °C 2)
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 127
Technical specifications
9.15 Technical specifications of SCALANCE XC208G EEC
Technical specifications
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Properties Coated printed circuit board (conformal coating)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 520 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 54 years
1)
Note the wiring rules (Page 81).
2)
The derating values depend on the maximum ambient temperatures during operation up
to 2000 m.
SCALANCE XC-200
128 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.16 Technical specifications of the SCALANCE XC216
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 16
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC 550 mA
24 VDC 275 mA
Effective power loss 6.6 W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature With operation up to 2000 m above During operation in horizontal installation po‐
sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 129
Technical specifications
9.16 Technical specifications of the SCALANCE XC216
Technical specifications
Dimensions (W x H x D) 120 x 147 x 125 mm
Weight 800 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 48 years
1)
Note the wiring rules (Page 81).
SCALANCE XC-200
130 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.17 Technical specifications of SCALANCE XC216EEC
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 16
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC 550 mA
24 VDC 275 mA
Effective power loss 6.6 W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature With operation up to 2000 m above During operation in horizontal installation po‐
sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
With operation between 2000 m and The maximum ambient temperature is re‐
3000 m above sea level duced by 5 °C 2)
With operation between 3000 m and The maximum ambient temperature is re‐
4000 m above sea level duced by 10 °C 2)
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 131
Technical specifications
9.18 Technical specifications of SCALANCE XC216-3G PoE
Technical specifications
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Properties Coated printed circuit board (conformal coating)
Degree of protection IP20
Dimensions (W x H x D) 120 x 147 x 125 mm
Weight 800 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 48 years
1)
Note the wiring rules (Page 81).
2)
The derating values depend on the maximum ambient temperatures during operation up
to 2000 m.
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 16
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable transceivers Quantity 3
Connector SFP transceivers (LC port)
Transmission speed Port P1 1000 Mbps
100 Mbps also possible via active SFPs
Port P2 and 1000 / 10000 Mbps
P2 100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 24 V DC
Voltage range (incl. tolerance) 19.2 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly
Current consumption At 19.2 V DC Max. 7.8 A
SCALANCE XC-200
132 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.18 Technical specifications of SCALANCE XC216-3G PoE
Technical specifications
Effective Power At max PoE load Max. 150 W
Thermal Design Power Max. 28 W
Overvoltage category CAT II
Fusing Basic device 2.5 A / 125 V
PoE consumers 15 A / 125 V
PoE power per device At 24 V DC With horizontal mounting position and opera‐
tion without pluggable transceiver:
• 120 W
In other installation position:
• 90 W
Signaling contact 1) Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 V DC
Load capability Max. 100 mA
Permitted ambient conditions
Ambient temperature 2) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector with max. PoE load up to sition:
2000 m above sea level • -40 °C to +60 °C
During operation in a different installation po‐
sition:
• -40 °C to +50 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• [-] Standard version • -40 °C to +60 °C
• LD • Max. PoE power: 90 W
Up to 2000 m above sea level During operation in a different installation po‐
sition:
• -40 °C to +50 °C
• Max. PoE power: 60 W
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• LH • -40 °C to +55 °C
• LH+ • Max. PoE power: 90 W
• ELH Other mounting positions are not permitted.
• SFP992-1+
Up to 2000 m above sea level
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design Compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 133
Technical specifications
9.19 Technical specifications of SCALANCE XC216-3G PoE (54 V)
Technical specifications
Degree of protection IP20
Dimensions (W x H x D) 180 x 147 x 125 mm
Weight 1560 g
Installation options • Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 24.6 years
1)
Note the wiring rules (Page 81).
2)
Depending on which pluggable transceiver you use, the maximum ambient temperature
can change, see section "Accessories", "SFP transceiver (Page 39)".
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 16
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable transceivers Quantity 3
Connector SFP transceivers (LC port)
Transmission speed Port P1 1000 Mbps
100 Mbps also possible via active SFPs
Port P2 and 1000 / 10000 Mbps
P2 100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 54 V DC
Voltage range (incl. tolerance) 52 to 57 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly
Current consumption At 52 V DC Max. 6.5 A
Effective Power At max PoE load Max. 338 W
Thermal Design Power Max. 28 W
Overvoltage category CAT II
SCALANCE XC-200
134 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.19 Technical specifications of SCALANCE XC216-3G PoE (54 V)
Technical specifications
Fusing Basic device 2.5 A / 125 V
PoE consumers 15 A / 125 V
PoE power per device At 54 V 300 W
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 54 V DC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature 2) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector with max. PoE load up to sition:
2000 m above sea level -40 °C to +60 °C
During operation in a different installation po‐
sition:
-40 °C to +50 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• [-] Standard version -40 °C to +60 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +50 °C
When operating with pluggable trans‐ During operation in horizontal installation po‐
ceivers of the types: sition:
• LH -40 °C to +55 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +50 °C
• SFP992-1+
Up to 2000 m above sea level
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 140 x 147 x 125 mm
Weight 1140 g
Installation options • Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 23 years
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 135
Technical specifications
9.19 Technical specifications of SCALANCE XC216-3G PoE (54 V)
1)
Note the wiring rules (Page 81).
2)
Depending on which pluggable transceiver you use, the maximum ambient temperature
can change, see section "Accessories", "SFP transceiver (Page 39)".
SCALANCE XC-200
136 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.20 Technical specifications of SCALANCE XC216-4C
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 12
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 Mbps
Combo ports Quantity 4
Electrical connec‐ Quantity 4
tors Connector RJ45 jack
Properties Half/full duplex, MDI-X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable Quantity 4
transceivers Connector SFP transceivers (LC port)
Transmission speed 1000 Mbps
100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 24 V DC
Voltage range (incl. tolerance) 19.2 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 24 V DC Without SFP 450 mA
With SFP 2) 550 mA
Effective power loss Without SFP 10.8 W
With SFP 2)
13.2 W
Overvoltage category CAT II
Fusing 3.15 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 V DC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 137
Technical specifications
9.20 Technical specifications of SCALANCE XC216-4C
Technical specifications
Ambient temperature 3) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector up to 2000 m above sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
When operating with pluggable During operation in horizontal installation po‐
transceivers of the types: sition:
• [-] Standard version -40 °C to +65 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +60 °C
When operating with pluggable During operation in horizontal installation po‐
transceivers of the types: sition:
• LH -40 °C to +60 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +60 °C
• SFP992-1+
Up to 2000 m above sea level
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 140 x 147 x 125 mm
Weight 1200 g
Installation options • Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 46 years
1)
Note the wiring rules (Page 81).
2)
Detected with the SFP992-1ELH. You will find the precise values in the operating
instructions of the pluggable transceivers, see the section "Introduction", Additional
documentation (Page 7).
3)
Depending on which pluggable transceiver you use, the maximum ambient temperature
can change, see section "Accessories", "SFP transceiver (Page 39)".
SCALANCE XC-200
138 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.21 Technical specifications of SCALANCE XC216-4C G
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 12
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Combo ports Quantity 4
Electrical connec‐ Quantity 4
tors Connector RJ45 jack
Properties Half/full duplex, MDI-X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable Quantity 4
transceivers Connector SFP transceivers (LC port)
Transmission speed 1000 Mbps
100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 24 V DC
Voltage range (incl. tolerance) 19.2 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 24 V DC Without SFP 450 mA
With SFP 2) 550 mA
Effective power loss Without SFP 10.8 W
With SFP 2)
13.2 W
Overvoltage category CAT II
Fusing 3.15 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 V DC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 139
Technical specifications
9.21 Technical specifications of SCALANCE XC216-4C G
Technical specifications
Ambient temperature 3) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector up to 2000 m above sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
When operating with pluggable During operation in horizontal installation po‐
transceivers of the types: sition:
• [-] Standard version -40 °C to +65 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +60 °C
When operating with pluggable During operation in horizontal installation po‐
transceivers of the types: sition:
• LH -40 °C to +60 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +60 °C
• SFP992-1+
Up to 2000 m above sea level
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 140 x 147 x 125 mm
Weight 1200 g
Installation options • Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 46 years
1)
Note the wiring rules (Page 81).
2)
Detected with the SFP992-1ELH. You will find the precise values in the operating
instructions of the pluggable transceivers, see the section "Introduction", Additional
documentation (Page 7).
3)
Depending on which pluggable transceiver you use, the maximum ambient temperature
can change, see section "Accessories", "SFP transceiver (Page 39)".
SCALANCE XC-200
140 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.22 Technical specifications of SCALANCE XC216-4C G EEC
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 12
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Combo ports Quantity 4
Electrical connec‐ Quantity 4
tors Connector RJ45 jack
Properties Half/full duplex, MDI-X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable Quantity 4
transceivers Connector SFP transceivers (LC port)
Transmission speed 1000 Mbps
100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 24 V DC
Voltage range (incl. tolerance) 19.2 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 24 V DC Without SFP 450 mA
With SFP 2) 550 mA
Effective power loss Without SFP 10.8 W
With SFP 2)
13.2 W
Overvoltage category CAT II
Fusing 3.15 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 V DC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 141
Technical specifications
9.22 Technical specifications of SCALANCE XC216-4C G EEC
Technical specifications
Ambient temperature 3) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector up to 2000 m above sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
When operating with pluggable During operation in horizontal installation po‐
transceivers of the types: sition:
• [-] Standard version -40 °C to +65 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +60 °C
When operating with pluggable During operation in horizontal installation po‐
transceivers of the types: sition:
• LH -40 °C to +60 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +60 °C
• SFP992-1+
Up to 2000 m above sea level
With operation between 2000 m and The maximum ambient temperature is re‐
3000 m above sea level duced by 5 °C 4)
With operation between 3000 m and The maximum ambient temperature is re‐
4000 m above sea level duced by 10 °C 4)
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Properties Coated printed circuit board (conformal coating)
Degree of protection IP20
Dimensions (W x H x D) 140 x 147 x 125 mm
Weight 1200 g
Installation options • Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 46 years
1)
Wiring rules
Observe the wiring rules (Page 81).
SCALANCE XC-200
142 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.22 Technical specifications of SCALANCE XC216-4C G EEC
2)
Pluggable transceiver
Detected with the SFP992-1ELH. You will find the precise values in the operating instructions
of the pluggable transceivers, see the section "Introduction", Additional documentation
(Page 7).
3)
Ambient temperature with SFP
The maximum ambient temperature during operation depends on the operating elevation
and the installed pluggable transceivers, see also the section "SFP transceiver (Page 39)" in
the "Accessories" section.
4)
Derating
The derating values depend on the maximum ambient temperatures during operation up to
2000 m.
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 143
Technical specifications
9.23 Technical specifications of the SCALANCE XC224
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 24
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 V DC
Voltage range (incl. tolerance) 9.6 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Property Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 12 VDC 750 mA
24 VDC 375 mA
Effective power loss 9W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature With operation up to 2000 m above During operation in horizontal installation po‐
sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
SCALANCE XC-200
144 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.23 Technical specifications of the SCALANCE XC224
Technical specifications
Dimensions (W x H x D) 120 x 147 x 125 mm
Weight 880 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 41 years
1)
Note the wiring rules (Page 81).
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 145
Technical specifications
9.24 Technical specifications of SCALANCE XC224-4C G
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 20
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Combo ports Quantity 4
Electrical connec‐ Quantity 4
tors Connector RJ45 jack
Properties Half/full duplex, MDI-X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable Quantity 4
transceivers Connector SFP transceivers (LC port)
Transmission speed 1000 Mbps
100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 24 V DC
Voltage range (incl. tolerance) 19.2 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 24 V DC Without SFP 600 mA
With SFP 2) 700 mA
Effective power loss Without SFP 14.4 W
With SFP 2)
16.8 W
Overvoltage category CAT II
Fusing 3.15 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 V DC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
146 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.24 Technical specifications of SCALANCE XC224-4C G
Technical specifications
Ambient temperature 3) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector up to 2000 m above sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
When operating with pluggable During operation in horizontal installation po‐
transceivers of the types: sition:
• [-] Standard version -40 °C to +65 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +60 °C
When operating with pluggable During operation in horizontal installation po‐
transceivers of the types: sition:
• LH -40 °C to +60 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +60 °C
• SFP992-1+
Up to 2000 m above sea level
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 140 x 147 x 125 mm
Weight 1300 g
Installation options • Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 20 years
1)
Note the wiring rules (Page 81).
2)
Detected with the SFP992-1ELH. You will find the precise values in the operating
instructions of the pluggable transceivers, see the section "Introduction", Additional
documentation (Page 7).
3)
Depending on which pluggable transceiver you use, the maximum ambient temperature
can change, see section "Accessories", "SFP transceiver (Page 39)".
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 147
Technical specifications
9.25 Technical specifications of SCALANCE XC224-4C G EEC
Technical specifications
Connection to Industrial Ethernet
Electrical connectors Quantity 20
Connector RJ45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 / 1000 Mbps
Combo ports Quantity 4
Electrical connec‐ Quantity 4
tors Connector RJ45 jack
Properties Half/full duplex, MDI-X pinning
Transmission speed 10 / 100 / 1000 Mbps
Slots for pluggable Quantity 4
transceivers Connector SFP transceivers (LC port)
Transmission speed 1000 Mbps
100 Mbps also possible via active SFPs
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 24 V DC
Voltage range (incl. tolerance) 19.2 to 31.2 V DC Safe Extra Low Voltage (SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly;
The connected power supply must meet the
requirements of NEC Class 2.
Current consumption 24 V DC Without SFP 600 mA
With SFP 2) 700 mA
Effective power loss Without SFP 14.4 W
With SFP 2)
16.8 W
Overvoltage category CAT II
Fusing 3.15 A / 125 V
Signaling contact 1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 V DC
Load capability max. 100 mA
Permitted ambient conditions
SCALANCE XC-200
148 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.25 Technical specifications of SCALANCE XC224-4C G EEC
Technical specifications
Ambient temperature 3) During LAN operation with RJ45 con‐ During operation in horizontal installation po‐
nector up to 2000 m above sea level sition:
-40 °C to +70 °C
During operation in a different installation po‐
sition:
-40 °C to +70 °C
When operating with pluggable During operation in horizontal installation po‐
transceivers of the types: sition:
• [-] Standard version -40 °C to +65 °C
• LD During operation in a different installation po‐
sition:
Up to 2000 m above sea level
-40 °C to +60 °C
When operating with pluggable During operation in horizontal installation po‐
transceivers of the types: sition:
• LH -40 °C to +60 °C
• LH+ During operation in a different installation po‐
sition:
• ELH
-40 °C to +60 °C
• SFP992-1+
Up to 2000 m above sea level
With operation between 2000 m and The maximum ambient temperature is reduced
3000 m above sea level by 5 °C 4)
With operation between 3000 m and The maximum ambient temperature is reduced
4000 m above sea level by 10 °C 4)
During storage -40 °C to +85 °C
During transportation -40 °C to +85 °C
Relative humidity During operation at 25 ℃ ≤ 95% without condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Properties Coated printed circuit board (conformal coating)
Degree of protection IP20
Dimensions (W x H x D) 140 x 147 x 125 mm
Weight 1300 g
Installation options • Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 20 years
1)
Wiring rules
Observe the wiring rules (Page 81).
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 149
Technical specifications
9.25 Technical specifications of SCALANCE XC224-4C G EEC
2)
Pluggable transceiver
Detected with the SFP992-1ELH. You will find the precise values in the operating instructions
of the pluggable transceivers, see the section "Introduction", Additional documentation
(Page 7).
3)
Ambient temperature with SFP
The maximum ambient temperature during operation depends on the operating elevation
and the installed pluggable transceivers, see also the section "SFP transceiver (Page 39)" in
the "Accessories" section.
4)
Derating
The derating values depend on the maximum ambient temperatures during operation up to
2000 m.
SCALANCE XC-200
150 Operating Instructions, 02/2023, C79000-G8976-C442-14
Technical specifications
9.28 Cable lengths
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 151
Technical specifications
9.29 Switching properties
Note
The number of SCALANCE XC-200 modules connected in a line influences the entire frame
delay. When a frame passes through the IE switch, this is delayed by the store-and-forward
function of the SCALANCE XC-200 by 10-130 microseconds (at 100 Mbps).
SCALANCE XC-200
152 Operating Instructions, 02/2023, C79000-G8976-C442-14
Dimension drawings 10
Note
Dimensions are specified in mm.
Front view
This front view applies to the following devices:
• SCALANCE XC206-2 (ST/BFOC)
• SCALANCE XC206-2 (SC)
• SCALANCE XC206-2G PoE (54 V)
• SCALANCE XC206-2G PoE EEC (54 V)
• SCALANCE XC206-2SFP
• SCALANCE XC206-2SFP G
• SCALANCE XC206-2SFP EEC
• SCALANCE XC206-2SFP G EEC
• SCALANCE XC208
• SCALANCE XC208G
• SCALANCE XC208G PoE (54 V)
• SCALANCE XC208EEC
• SCALANCE XC208G EEC
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 153
Dimension drawings
Front view
This front view applies to the following devices:
• SCALANCE XC206-2G PoE
• SCALANCE XC208G PoE
SCALANCE XC-200
154 Operating Instructions, 02/2023, C79000-G8976-C442-14
Dimension drawings
Front view
This front view applies to the following devices:
• SCALANCE XC216
• SCALANCE XC216EEC
• SCALANCE XC224
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 155
Dimension drawings
Front view
This front view applies to the following devices:
• SCALANCE XC216-3G PoE (54 V)
• SCALANCE XC216-4C
• SCALANCE XC216-4C G
• SCALANCE XC216-4C G EEC
• SCALANCE XC224-4C G
• SCALANCE XC224-4C G EEC
SCALANCE XC-200
156 Operating Instructions, 02/2023, C79000-G8976-C442-14
Dimension drawings
140
147
Front view
This front view applies to the following devices:
• SCALANCE XC216-3G PoE
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 157
Dimension drawings
180
140
147
SCALANCE XC-200
158 Operating Instructions, 02/2023, C79000-G8976-C442-14
Dimension drawings
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 159
Dimension drawings
Figure 10-7 Drilling template with securing bar in the wall mounting position (as supplied)
SCALANCE XC-200
160 Operating Instructions, 02/2023, C79000-G8976-C442-14
Certifications and approvals 11
The SIMATIC NET products described in these Operating Instructions have the approvals listed
below.
Note
Issued approvals on the type plate of the device
The specified approvals apply only when the corresponding mark is printed on the product. You
can check which of the following approvals have been granted for your product by the markings
on the type plate.
Machinery directive
The product is a component in compliance with the EC Machinery Directive 2006/42/EEC and the
Supply of Machinery (Safety) Regulations 2008 (UK).
According to the Machinery Directive respectively the Supply of Machinery (Safety)
Regulations (UK), we are obliged to point out that the product described is intended solely
for installation in a machine.
Before the final product can be put into operation, it must be tested to ensure that it
conforms with the Machinery Directive 2006/42/EEC and the Supply of Machinery (Safety)
Regulations 2008 (UK).
EC declaration of conformity
The SIMATIC NET products described in these operating instructions meet the requirements
and safety objectives of the following EC directives and comply with the harmonized
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 161
Certifications and approvals
European standards (EN) which are published in the official documentation of the European
Union and here.
• 2014/34/EU (ATEX explosion protection directive)
Directive of the European Parliament and the Council of 26 February 2014 on the
approximation of the laws of the member states concerning equipment and protective
systems intended for use in potentially explosive atmospheres, official journal of the EU L96,
29/03/2014, pages. 309-356
• 2014/30/EU (EMC)
EMC directive of the European Parliament and of the Council of February 26, 2014 on the
approximation of the laws of the member states relating to electromagnetic compatibility;
official journal of the EU L96, 29/03/2014, pages. 79-106
• 2011/65/EU (RoHS)
Directive of the European Parliament and of the Council of 8 June 2011 on the restriction of
the use of certain hazardous substances in electrical and electronic equipment, official
journal of the EC L174, 01/07/2011, pages 88-110
You will find the EC declaration of conformity for these products on the Internet pages of
Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/15273/
cert).
The EC Declaration of Conformity is available for all responsible authorities at:
Siemens Aktiengesellschaft
Digital Industries
DE-76181 Karlsruhe
Germany
UK Declaration of Conformity
The UK declaration of conformity is available to all responsible authorities at:
Siemens Aktiengesellschaft
Digital Industries
Process Automation
DE-76181 Karlsruhe
Germany
Importer UK:
Siemens plc,
Manchester M20 2UR
You can find the current UK Declaration of Conformity for these products
on the Internet pages under Siemens Industry Online Support (https://
support.industry.siemens.com/cs/ww/en/ps/15273/cert).
SCALANCE XC-200
162 Operating Instructions, 02/2023, C79000-G8976-C442-14
Certifications and approvals
The SIMATIC NET products described in this document meet the requirements of the
following directives:
• UK-Regulation
SI 2016/1107 Equipment and Protective Systems Intended for use in Potentially Explosive
Atmospheres Regulations 2016, and related amendments
• EMC Regulation
SI 2016/1091 Electromagnetic Compatibility Regulations 2016, and related amendments
• RoHS Regulation
SI 2012/3032 Restriction of the Use of Certain Hazardous Substances in Electrical and
Electronic Equipment Regulations 2012, and related amendments
WARNING
Risk of explosion in hazardous areas
When using SIMATIC NET products in hazardous area zone 2, make absolutely sure that the
associated conditions in the following document are adhered to:
"SIMATIC NET Product Information Use of subassemblies/modules in a Zone 2 Hazardous Area".
You will find this document
• on the data medium that ships with some devices.
• on the Internet pages under Siemens Industry Online Support (https://
support.industry.siemens.com/cs/ww/en/view/78381013).
Enter the document identification number "C234" as the search term.
II 3 G Ex ec IIC T4 Gc
DEKRA 18ATEX0025 X
DEKRA 21UKEX0001 X
IECEx DEK 18.0017X
Importer UK:
Siemens plc,
Manchester
M20 2UR
(Ex ec IIC T4 Gc, not on the nameplate)
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 163
Certifications and approvals
Note
CLASS 1 LASER
The device contains optical radiation sources which comply with the limits of Class 1 according
to IEC 60825-1. Fiber-optic cables connected to these optical radiation sources may therefore be
routed either to or through hazardous areas requiring Category 2G, 3G, 2D or 3D equipment.
RoHS
The SIMATIC NET products described in these operating instructions meet the requirements on
the restriction of the use of certain hazardous substances in electrical and electronic equipment
according to the EU Directive 2011/65/EU as well as the UK-Regulation SI 2012/3032 and their
associated amendments.
SCALANCE XC-200
164 Operating Instructions, 02/2023, C79000-G8976-C442-14
Certifications and approvals
Applied standard:
• EN IEC 63000
FM
The product meets the requirements of the standards:
• Factory Mutual Approval Standard Class Number 3611
• FM Hazardous (Classified) Location Electrical Equipment:
Non Incendive / Class I / Division 2 / Groups A,B,C,D / T4 and
Non Incendive / Class I / Zone 2 / Group IIC / T4
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 165
Certifications and approvals
SCALANCE XC-200
166 Operating Instructions, 02/2023, C79000-G8976-C442-14
Certifications and approvals
* In modular devices, you can find the marking on the pluggable transceiver used or in the relevant
operating instructions.
FDA IEC
CAUTION
Use of controls or adjustments or performance of procedures other than those specified herein
may result in hazardous radiation exposure.
Installation guidelines
The devices meet the requirements if you adhere to the installation and safety instructions
contained in this documentation and in the following documentation when installing and
operating the devices.
• "Industrial Ethernet / PROFINET Industrial Ethernet" System Manual (https://
support.industry.siemens.com/cs/ww/en/view/27069465)
• "Industrial Ethernet / PROFINET - Passive Network Components" System Manual (https://
support.industry.siemens.com/cs/ww/en/view/84922825)
• "EMC Installation Guidelines" configuration manual (https://
support.industry.siemens.com/cs/ww/en/view/60612658)
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 167
Certifications and approvals
WARNING
Personal injury and property damage can occur
The installation of expansions that are not approved for SIMATIC NET products or their target
systems may violate the requirements and regulations for safety and electromagnetic
compatibility.
Only use expansions that are approved for the system.
Note
The test was performed with a device and a connected communications partner that also meets
the requirements of the standards listed above.
When operating the device with a communications partner that does not comply with these
standards, adherence to the corresponding values cannot be guaranteed.
SCALANCE XC-200
168 Operating Instructions, 02/2023, C79000-G8976-C442-14
Index
Fault/error status, 47
Firmware, 47
A
Approvals, 161
Article numbers, 23
G
Autonegotiation, 89 Glossary, 9
Grounding, 29, 30, 31, 32, 33, 34, 35, 36, 37, 38, 39,
86
C Grounding screw, 29, 30, 31, 32, 33, 34, 35, 36, 37,
38, 39
CE mark, 161
Combo port, 53
Command Line Interface (CLI), 52, 87, 93
Components of the product, 27
H
Configuration, 45 Housing, 95, 98, 101, 103, 105, 108, 110, 112, 115,
Connecting cable, 87 117, 119, 121, 123, 125, 127, 129, 131, 133, 135,
Connecting up 138, 140, 142, 144, 147, 149
Grounding, 86
Connection to Industrial Ethernet, 100, 102, 104, 107,
109, 111, 114, 117, 119, 121, 123, 125, 127, 129, I
131, 132, 134, 137, 139, 141, 144, 146, 148
Installation, 95, 98, 101, 103, 105, 108, 110, 112,
C-PLUG
115, 117, 119, 121, 123, 125, 127, 129, 131, 133,
Configuration, 51
135, 138, 140, 142, 144, 147, 149
Installation on a DIN rail, 64, 65
Installation on a standard rail, 66, 68, 69, 70
D Wall mounting, 70
Dimensions, 95, 98, 101, 103, 105, 108, 110, 112, Installation on a DIN rail, 64, 65
115, 117, 119, 121, 123, 125, 127, 129, 131, 133, Installation on a standard rail, 66, 68, 69, 70
135, 138, 140, 142, 144, 147, 149
Display mode, 44, 47
K
Knurled screw, 29, 30, 31, 32, 33, 34, 35, 38, 64, 66,
E 69
Electrical data, 95, 97, 100, 102, 104, 107, 109, 111,
114, 117, 119, 121, 123, 125, 127, 129, 131, 132,
134, 137, 139, 141, 144, 146, 148 L
Environmental conditions, 40, 41, 42, 43, 95, 97, 100,
LED display, 29, 30, 31, 32, 33, 34, 35, 36, 37, 38, 39,
102, 104, 107, 109, 111, 114, 117, 119, 121, 123,
46
125, 127, 129, 131, 133, 135, 137, 139, 141, 144,
Levering aid, 29, 30, 31, 32, 33, 34, 35, 38, 72
146, 148
ESD directives, 11
M
F MDI / MDI-X autocrossover, 89
MTBF, 96, 98, 101, 103, 105, 108, 110, 112, 115, 118,
Factory defaults, 44, 94
120, 122, 124, 126, 128, 130, 132, 134, 135, 138,
Factory setting, 94
140, 142, 145, 147, 149
Factory settings, 44, 94
Fault mask, 45
SCALANCE XC-200
Operating Instructions, 02/2023, C79000-G8976-C442-14 169
Index
P W
Permitted ambient conditions, 40, 41, 42, 43, 95, 97, Web Based Management (WBM), 52, 93
100, 102, 104, 107, 109, 111, 114, 117, 119, 121, Weight, 95, 98, 101, 103, 105, 108, 110, 112, 115,
123, 125, 127, 129, 131, 133, 135, 137, 139, 141, 117, 119, 121, 123, 125, 127, 129, 131, 133, 135,
144, 146, 148 138, 140, 142, 144, 147, 149
Pin assignment, 89 Wiring rules, 82, 84, 85
PLUG, 51
Pluggable transceiver
SFP, 8, 40, 41, 42, 43
SFP active, 41
Plug-in transceiver
SFP bidirectional, 42
PoE, 54
Power over Ethernet, 54
Power supply, 27, 29, 30, 31, 32, 33, 34, 35, 36, 37,
38, 39, 82, 84
R
Reset device, 44, 94
Reset to Factory Defaults, 45, 94
S
S7-1500, 69, 70
S7-300, 66, 68
Safety notices
for installation, 59
general, 13
Use in hazardous areas, 13, 59
Securing bar, 29, 30, 31, 32, 33, 34, 35, 38, 64, 66, 69,
154, 155, 156, 159
Securing location, 68, 70
Securing screw, 68, 70
SELECT/SET button, 29, 30, 31, 32, 33, 34, 35, 36, 37,
38, 39, 44, 48, 93, 94
Serial interface, 87
SFP transceiver, 8, 40, 41, 42, 43
SFP+ transceiver, 43
Signaling contact, 27, 29, 30, 31, 32, 33, 34, 35, 36,
37, 38, 39, 47, 85
SIMATIC NET glossary, 9
SIMATIC NET manual, 9
Spare parts, 28
Spring-loaded terminal, 27, 82, 84, 85
Startup phase, 45, 47, 94
System manual, 9, 167
SCALANCE XC-200
170 Operating Instructions, 02/2023, C79000-G8976-C442-14