Smoke Calculation Based on 6 - ACPH in GIS BUILDING

Sum of the areas of all rooms Ar 2100 Sqm

Average height of room Hr 11.0 m

Volume of all rooms Sv = Ar x Hr 23100.0 m3


Air Changes per hour for smoke exhaust
ACPHelectrical 6
in case of fire
Required Air flow rate V1 = ( ACPHelectrical x Sv ) 138600 cmh
Reference
No. of smoke exhaust fans Fn 6 nos.
7.6
Capacity of each fan Fcap = V1 / Fn 23100 cmh
Selected Capacity (with 10% safety
Feach = Fcap x 1.10 25410 cmh 7058.33 L/s 1X100%
factor)
Smoke Calculation Based on 6 - ACPH in Fire Water Pump House

Sum of the areas of all rooms Ar 370 Sqm

Average height of room Hr 7.3 m

Volume of all rooms Sv = Ar x Hr 2701.0 m3


Air Changes per hour for smoke exhaust
ACPH 6
in case of fire
Required Air flow rate V1 = ( ACPH x Sv ) 16206 cmh

No. of smoke exhaust fans Fn 2 nos.

Capacity of each fan Fcap = V1 / Fn 8103 cmh

Selected Capacity (with 10% safety CFM


Feach = Fcap x 1.10 8913 cmh 2475.92 L/s 5248.9433
factor)

By Comparison Heat Release Method and 6 ACPH Method We Selected The Higher Capacity.
Smoke Calculation Based on 6 - ACPH in Chiller Plant Room

Sum of the areas of all rooms Ar 680 Sqm

Average height of room Hr 9.8 m

Volume of all rooms Sv = Ar x Hr 6664.0 m3


Air Changes per hour for smoke exhaust
ACPH 6
in case of fire
Required Air flow rate V1 = ( ACPH x Sv ) 39984 cmh

No. of smoke exhaust fans Fn 2 nos.

Capacity of each fan Fcap = V1 / Fn 19992 cmh

Selected Capacity of Each Smoke CFM


Feach = Fcap x 1.10 21991 cmh 6108.67 L/s 12950.373
Exhaust Fan (with 10% safety factor)

By Comparison Heat Release Method and 6 ACPH Method We Selected The Higher Capacity.
Smoke Calculation Based on 6 - ACPH in Air Compressor Room (GAB)
Sum of the areas of all rooms Ar 445 Sqm

Average height of room Hr 10.7 m

Volume of all rooms Sv = Ar x Hr 4761.5 m3


Air Changes per hour for smoke exhaust
ACPH 6
in case of fire
Required Air flow rate V1 = ( ACPH x Sv ) 28569 cmh

No. of smoke exhaust fans Fn 2 nos.

Capacity of each fan Fcap = V1 / Fn 14285 cmh

Selected Capacity of Each Smoke CFM


Feach = Fcap x 1.10 15713 cmh 4364.71 L/s 9253.18167
Exhaust Fan (with 10% safety factor)

By Comparison Heat Release Method and 6 ACPH Method We Selected The Higher Capacity.
Smoke Calculation Based on 6 - ACPH in DM Plant (GAB)
Sum of the areas of all rooms Ar 830 Sqm

Average height of room Hr 10.7 m

Volume of all rooms Sv = Ar x Hr 8881.0 m3


Air Changes per hour for smoke exhaust
ACPH 6
in case of fire
Required Air flow rate V1 = ( ACPH x Sv ) 53286 cmh

No. of smoke exhaust fans Fn 2 nos.

Capacity of each fan Fcap = V1 / Fn 26643 cmh


Selected Capacity of Each Smoke CFM
Feach = Fcap x 1.10 29307 cmh 8140.92 L/s 17258.743
Exhaust Fan (with 10% safety factor)

By Comparison Heat Release Method and 6 ACPH Method We Selected The Higher Capacity.
Smoke Calculation Based on 6 - ACPH in Chemical Storage Area (GAB)
Sum of the areas of all rooms Ar 370 Sqm

Average height of room Hr 7.0 m

Volume of all rooms Sv = Ar x Hr 2590.0 m3


Air Changes per hour for smoke exhaust
ACPH 6
in case of fire
Required Air flow rate V1 = ( ACPH x Sv ) 15540 cmh

No. of smoke exhaust fans Fn 2 nos.

Capacity of each fan Fcap = V1 / Fn 7770 cmh

Selected Capacity of Each Smoke CFM


Feach = Fcap x 1.10 8547 cmh 2374.17 L/s 5033.2333
Exhaust Fan (with 10% safety factor)

By Comparison Heat Release Method and 6 ACPH Method We Selected The Higher Capacity.
Smoke Calculation Based on 6 - ACPH in Store-1 BUILDING
Sum of the areas of all rooms Ar 1168 Sqm

Average height of room Hr 10.3 m

Volume of all rooms Sv = Ar x Hr 12030.4 m3


Air Changes per hour for smoke exhaust
ACPH 6
in case of fire
Required Air flow rate V1 = ( ACPH x Sv ) 72182 cmh
Reference
No. of smoke exhaust fans Fn 2 nos.
7.6
Capacity of each fan Fcap = V1 / Fn 36091 cmh
Selected Capacity (with 10% safety
Feach = Fcap x 1.10 39700 cmh 11027.87 L/s 1X100%
factor)
Smoke Calculation Based on 6 - ACPH in Gas Oil Treat
Sum of the areas of all rooms Ar 435 Sqm

Average height of room Hr 8.0 m

Volume of all rooms Sv = Ar x Hr 3480.0 m3


Air Changes per hour for smoke exhaust
ACPH 10
in case of fire
Required Air flow rate V1 = ( ACPH x Sv ) 34800 cmh
Reference
No. of smoke exhaust fans Fn 2 nos.
7.6
Capacity of each fan Fcap = V1 / Fn 17400 cmh
Selected Capacity (with 10% safety
Feach = Fcap x 1.10 19140 cmh 5316.67 L/s 1X100%
factor)