Osram Led Power Factor Guide
Osram Led Power Factor Guide
Z = (R2 + XL2)1/2
= 1200Ω2 + 1206.37Ω2
= 1.701KΩ
How to improve PF
As noted above, real power is what actually
Figure 4. Improved PF circuit.
performs work. Therefore, it is important to have a
reduced amount of total reactive power, in order to
As can be seen from the waveform, the voltage and
have an efficient system. In other words, the power
current are now in phase with each other and they
factor of a system or circuit should be improved
have similar shape with the same frequency. The
when possible. If we consider the circuit in Figure 3,
waveform also looks very similar to that of a
it has a PF of only 70.5% and there is room to
resistive load, even though the circuit has resistive,
improve the PF up to 99%. Since the circuit has an
capacitive, and inductive loads. This clearly
inductive reactance component, there needs to be
indicates that the PF is well improved.
a capacitive component added to the circuit to
First, the value of capacitance is calculated as As expected, because the above calculations are
follows: ideal cases per the concept, the PF is improved to
be 100%. In real cases, it is almost impossible to
Q = E2 / X have a PF of 100%, especially with passive
X = E2 / Q components. However, the PF can be well
= 1202/6.0 = 2.4KΩ improved to be within an acceptable level, if proper
design technique is used.
Xc = 1 / 2¶fC
C = 1 / Xc2¶
= 1 / (2*2.4K*¶*60) PF in non-linear loads
= 1.105uF So far, all the example circuits considered have
linear loads, meaning the current wave form
A standard 1.1 uF capacitor is chosen for this matches that of the voltage. Non-linear loads create
purpose. Calculation of PF: harmonic current on top of the original AC current
and the current wave form is no longer a sine wave.
Xc = 1 / (2*¶*60*1.1*10-6) The total harmonic distortion, known as THD,
= 2.411KΩ should be taken into consideration when dealing
with non-linear loads. Also, harmonics cannot be
XL = 2*¶*60*3.2 improved or cancelled by adding linear
= 1.206KΩ components, such as capacitors or inductors. In the
case of non-linear loads, different, yet more
R + XL = 1.206KΩ <90˚+1.2KΩ complex, methods need to be considered to
= 1.701 KΩ <45.14˚ improve PF correction and minimize THD. In many
cases, the method used is active power factor
IL = 120V / 1.701KΩ correction utilizing a dedicated Integrated Circuit,
= 70.55mA known as IC, which is much more complex than a
passive power factor correction method.
Ztotal = Zc // (ZL + ZR)
= 2.411KΩ <-90˚ // PF in non-linear loads
(1.2KΩ <0˚ + 1.206KΩ <90˚) So far, all the example circuits considered have
= 2.412KΩ <0.262˚ linear loads, meaning the current wave form
matches that of the voltage. Non-linear loads create
Itotal = 120 / 2.412 harmonic current on top of the original AC current
= 49.75mA and the current wave form is no longer a sine wave.
The total harmonic distortion, known as THD,
P = True power = (70.55mA)2*1.2 KΩ should be taken into consideration when dealing
= 5.97W with non-linear loads. Also, harmonics cannot be
improved or cancelled by adding linear
S = Apparent power = (49.75mA)2*2.412 KΩ components, such as capacitors or inductors. In the
= 5.97VA case of non-linear loads, different, yet more
Figure 5. Simple rectifier circuit. Figure 6. Active PFC circuit and current
waveform.
A typical non-linear load of a power system can be
rectifiers. Figure 5 shows a simple circuit that can The idea is to turn the switch (S1) on and off at a
be found in AC-DC power supplies. It can be seen different rates during the cycle, such that the