Ivem LV 1

This document provides specifications for the IVEM-LV Series 3KVA and 5KVA inverters. It includes key details like: - Output voltage ranges from 80-140VAC depending on the load type. - Battery voltage is 48V for both models. - The 3KVA model can connect up to 6 batteries in parallel while the 5KVA can connect up to 12. - Additional details are provided on LCD screens, settings, data logging, ratings and dimensions. Intelligent fan control helps reduce noise.

Uploaded by

logicgates2002
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
99 views

Ivem LV 1

This document provides specifications for the IVEM-LV Series 3KVA and 5KVA inverters. It includes key details like: - Output voltage ranges from 80-140VAC depending on the load type. - Battery voltage is 48V for both models. - The 3KVA model can connect up to 6 batteries in parallel while the 5KVA can connect up to 12. - Additional details are provided on LCD screens, settings, data logging, ratings and dimensions. Intelligent fan control helps reduce noise.

Uploaded by

logicgates2002
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

IVEM-LV Series(3KVA~5KVA)

358-010278-00
LCD operation flow chart 19
Base information Page 19
Setting Page 21
Energy stored data Page 26
BMS information Page 27
Rated information Page 27
Lithium Battery Communication 29
30
30
30
33
33
35
35
36
Parallel connection quantity up to 12units for 5KVA model(Battery must be connected)
Intelligent fan control greatly reduces fan noise
IVEM3048-LV IVEM5048-LV

3000VA 5000VA

3000W 5000W

48V 48V

110Vac

80.5Vac±3V (For Home Appliances)90Vac±3V (For Computers)

85.5Vac±3V (For Home Appliances)95Vac±3V (For Computers)

140Vac±3V

134.5Vac±3V

140Vac±3V

IVEM3048-LV IVEM5048-LV

40A 63A

30A/3000W 50A/5000W
IVEM3048-LV IVEM5048-LV

IVEM3048-LV IVEM5048-LV 3000VA 5000VA

110Vac
3000W 5000W

65-140Vac
48V 48V

60A 100A 110Vac±5%

50+0.3Hz/60Hz±0.3Hz(Adjustable)

Parallel capability No Yes,up to 12 units

93%
500V
5.5s@≥150%load;[email protected]%~150%load
PV voltage range 90V-500V

60A 100A

60A 100A

30A

100V

Power Limitation
When battery voltage is lower than 48Vdc,
output power will be derated If 100%
connected load is higher than this
derated power the AC output voltage will
80%
decrease until the output power reduces
to this derated power. The minimum AC
56.4V output voltage is 90V.

58.4V

11.9KG 13.1KG

14.2KG 15KG

440x328x130MM 550x431.5x213MM

542x400x224MM 562x443.5x231MM
Current sharing cable x 1 U-shaped terminal x 2 RJ45 Terminal x 1 Expansion bolt x 2

Wall Hangers x 2 and


Screws x 4 Parallel Manual x 1

Parallel communication
Inevter unit x 1 Manual x 1 RS-232 cable x 1 cable x 1
two 6

40 63

1*4AWG 25

35
6

10

Recommended air switch or circuit breaker type for AC input:

Maximum bypass Recommended air switch


Models
input current or circuit breaker type

3KVA 40A 2P-40A

5KVA 63A 2P-63A


4

10 AWG 6 1.2 Nm

2.Max. power voltage (Vmp) should be during PV array MPPT voltage range.

500V
PV panels
Wiring System for Inverter

L
L
N
N
PE
PE

Utility
Load

Battery pack
four

To previous page

To confirm the selection or go to next page


LCD operation flow chart

Setting Page

Indicates Lithium battery type.

Energy stored data page


Indicates communication is built between inverter and battery.

Base information Page

Keep press "ENTER" for 3 sec

BMS information
Rated informationpage
page

Rated information page

On base information page, pressing and holding "ENTER" key for 3 sec, the unit will enter parameters page.
Press "UP" or "DOWN" key to switch the selection and press "ENTER" key to enter selected page. Press "ESC" key
to back to previous page.

Base information Page


The base information

110V 110V 110V


Date
110V 110V 2022-01-01

Time
110V 110V 09: 58: 55

Setting Page

110V

120V
Output voltage
01 Output voltage configuration
setting

127V

02

20 21
Setting range is from 10A to 60A.
Increment of each click is 1A(3KVA).

Setting range is from 10A to 100A.


Increment of each click is 1A(5KVA).

Setting range is from 10A to 60A.


Increment of each click is 1A(3KVA).

Setting range is from 10A to 100A.


Increment of each click is 1A(5KVA).
If selected, inverter is not allowed to
feed exceeding solar power to grid.
Feeding power
to grid
If selected, inverter is allowed to feed
exceeding solar power to grid.

If selected, inverter will esase all historical


data of PV and Load energy, and stop
record historical data for PV and Load
energy.
Energy stored
21 data for PV If selected, inverter will record
and Load historical data for PV and Load energy.
NOTE: Before selected, please double
check if date and time is correct, if
incorrect, please set date and time in
program 22~27.

Year
22 Time Setting rage is from 22 to 99.
setting- Year

Month
Time
23 Setting rage is from 1 to 12
setting- Month

Day
Time
24 Setting rage is from 1 to 31
setting- Day

Hour
25 Time Setting rage is from 0 to 23
setting- Hour

Minute
Time
26 Setting rage is from 0 to 59
setting- Minute

Second
Time
27 Setting rage is from 0 to 59
setting- Second

24 25
Energy stored data Page BMS information Page
The energy stored data

PV generated energy today PV generated energy this month Mean SOC/ Battery pack number / BMS status PV generated energy this month
99 kWh 99 kWh Mean SOC is 97%, Connected Battery pack number is 4, BMS status is 51 (Check detail in warning
code table). If BMS status occurred, it will be rolled with battery pack number automatically.

PV generated energy this year PV generated energy current in total


99 kWh 340 kWh
BMS version / SOC BMS voltage / current
BMS version is 100, SOC is 99% on battery pack BMS voltage is 54.0V, current is 1A on battery
of address 1 pack of address 1

Load consumed energy today Load consumed energy this month


79 kWh 79 kWh

BMS highest temerpature / lowest temerpature BMS fault code / flag


BMS highest temerpature is 25℃ , lowest BMS fault code is 0, flag is 000 on battery pack
temerpature is -10℃ on battery pack of address 1 of address 1

Load consumed energy this year Load consumed energy in total


80 kWh 272 kWh

Rated information Page


The rated information

26 27
Rated VA / WATT Rated battery voltage / Max. charge current Lithium Battery Communication
Rated VA is 5KVA, WATT is 5KW Rated battery voltage is 48V, Max. charge current is 100A
It’s allowed to connect lithium battery and build communication only which it has been configured.
Please follow bellow steps to configure communication between lithium battery and inverter.
1. Connect power cables between lithium battery and inverter. Please pay attention to the terminals of positive
and negative. Make sure the positive terminal of battery is connected to the positive terminal of inverter, and
the negative terminal of battery is connected to the negative terminal of inverter.
2. The communication cable is bundled with lithium battery. Both sides are RJ45 port. One port is connected to
the BMS port of inverter and another one is connected to the COMM port of lithium battery.

Firmware version
Firmware version is 1400

BMS BAT+ BAT-

3. Configure battery type to “Lib” in LCD setting No. 08.

And then LCD will show you “Li” icon.

28 29
4. Power up lithium battery and inverter. Wait a moment, if the communication is built between them, LCD will
show you “C” icon as below.

5. Roll LCD real time information pages by pressing “UP” or “DOWN” button, as below page, you can see
the parameters of SOC and battery pack units in the communication system.

This page means SOC is 88% and battery pack units are 6.

NOTE 1:

NOTE 2: Under parallel operation modes, battery must be connected with inverters.
NOTE 3: Before starting up inverters, please connect all negative(-) wires of battery together.

NOTE:Before starting up inverters, please connect all N wires of AC output together.

30 31
Before starting up inverters, please connect
all N wires of AC output together.

32 33
Fan is locked(left)

04 Fan is locked(right)

50 UpgradethefirmwareofBMS.

BMSdoesn’tallow Inverterwillstopchargingbattery
51
invertertochargebattery. automatically.
BMS doesn’t allow inverter Inverter will stop discharging battery
52
to discharge battery. automatically.
BMS require inverter to Inverterwillchargebattery
53
charge battery. automatically.
BMSdetectsomething If the code is keeping for long time,
54~65
wrongshappened. please contact with your installer.

AC Surge or internal components failed.


Bus voltage is too high Restart the unit, if the error happens again, please return to
repair center.

Restart the unit, if the error happens again, please return to


Bus voltage is too low
repair center.
Internal components failed.
Bus soft start fail Restart the unit, if the error happens again, please return to
repair center.
Internal components failed.
Inverter soft start fail Restart the unit, if the error happens again, please return to
repair center.

Over current or surge Restart the unit, if the error happens again, please return to
detected by Software repair center.
Over current or surge Restart the unit, if the error happens again, please return to
detected by hardware repair center.

34 35
Reduce the connected load. 1. Please check AC input and output wires are connected correctly.
Output voltage is too low Restart the unit, if the error happens again, please return to 2. If this error happens during parallel installation, please check
The AC input and output wires
repair center. wires connection. If they are connected correctly, please funish
27 are inversely connected
Restart the unit, if the error happens again, please return to parallel installation first, and then restart inverters.
Output voltage is too high
repair center. 3. If the problem remains, please contact your installer.

1. Please check if single unit is installed to parallel system.


Output short circuited Check if wiring is connected well and remove abnormal load.
2. If this error happens during parallel installation, please check
Overload time out Reduce the connected load by switching off some equipment. Single unit is installed to parallel wires connectiotn. If they are connected correctly, please funish
28
system parallel installation first, and then restart inverters.
Battery voltage is too high Check if spec and quantity of batteries are meet requirements. 3. If the problem remains, please contact your installer.
Over current happen at Restart the unit, if the error happens again, please return to
29 DC/DC soft start fail. Restarttheunit,iftheerrorhappensagain,pleasereturntorepaircenter.
DC/DC circuit repair center.
The temperature of internal convert H component is over the
PV voltage is too high Reduce the number of PV modules in series.
Over temperature happen limitation.
Short circuited happen at 31 at convert H circuit Check whether the air flow of the unit is blocked or whether the
Check if wiring is connected well.
PV port ambient temperature is too high.

PV power is abnormal Reduce the number of PV modules. The temperature of internal DC/DC TX is over the limitation.
Over temperature happen
32 Check whether the air flow of the unit is blocked or whether the
Over current happen at PV Restart the unit, if the error happens again, please return to at LLC TX
ambient temperature is too high.
port repair center.

Check if wiring is connected well. Over current happen at Restart the unit, if the error happens again, please return to repair
Fan is locked 33
Replace the fan. LLC circuit center

The temperature of internal PV component is over the limitation. 40 CAN data loss
1. Check if communication cables are connected well and restart
Over temperature happen at
18 Check whether the air flow of the unit is blocked or whether the Host data loss
41 the inverter.
PV circuit
ambient temperature is too high.
2. If the problem remains, please contact your installer.
42 Synchronization data loss
The temperature of Convert L battery converter component is over
Over temperature happen at the limitation. 1. Restart the inverter.

Convert L circuit Check whether the air flow of the unit is blocked or whether the 2. Check if L/N cables are not connected reversely in all inverters.
ambient temperature is too high. 3. For parallel system in single phase, make sure the sharing cables
Current feedback into the are connected in all inverters. For supporting three-phase system,
43
The temperature of internal INV component is over the limitation. inverter is detected. make sure the sharing cables are connected in the inverters in the
Over temperature happen at same phase, and disconnected in the inverters in different phases.
Check whether the air flow of the unit is blocked or whether the
INV circuit 4. If the problem remains, please contact your installer.
ambient temperature is too high.

1. Update all inverter firmware to the same version.


The inner temperature is over the limitation.
2. Check the version of each inverter via LCD setting and make sure
The inner temperature over Check whether the air flow of the unit is blocked or whether the
The firmware version of each the CPU versions are same. If not, please contact your installer to
ambient temperature is too high.
44 provide the firmware to update.
inverter is not the same.
Restart the unit, if the error happens again, please return to
DCDC current sensor failed 3. After updating, if the problem still remains, please contact your
repair center.
installer.
No.2 DCDC current sensor Restart the unit, if the error happens again, please return to
failed repair center. The output current of each 1. Check if sharing cables are connected well and restart the inverter.
45
inverter is different. 2. If the problem remains, please contact your installer.
Restart the unit, if the error happens again, please return to
Inverter current sensor failed 1. Switch off the inverter and check LCD setting program 28.
repair center.
2. For parallel system in single phase, make sure no 3P1, 3P2 or
Restart the unit, if the error happens again, please return to AC output mode
OP current sensor failed 46 3P3 is set on program 28. For supporting three-phase system, make
repair center. setting is different.
sure no “PAL” is set on program 28.
Restart the unit, if the error happens again, please return to
Sharing current sensor failed 3. If the problem remains, please contact your installer.
repair center.